Danfoss 20MT Gas Cooler Replacement for Optyma iCO2 User Guide

October 30, 2023
Danfoss

Danfoss 20MT Gas Cooler Replacement for Optyma iCO2

Step 1 : Preparation

  • Condensing unit should still have a small blanket charge of nitrogen to keep the system dry, please check and release nitrogen through service valves

  • To be manipulate deep switches and set the unit, ensure Power supply is turned OFF.

  • Turn ON dip SW5-7 (Up) and turn ON power. All electronically operated valves and electronic expansion valves will be fully open, this will ensure of nitrogen released from the unit and help with the re-works

  • Remove the fan motors from the top panel and connecting cables from the PCB

  • Remove the top panel from the unit,(fig. 1) show a little caution as this top panel gives the unit some structure and the gas coolers will move a little

  • De-braze the inlet / outlet piping connections(fig 2 and fig.3) of the gas coolers working in parallel and lift out the gas coolers

  • Connect the nitrogen cylinder at HP service valve via regulator and gauge manifold for brazing work and airtightness test.

Please use appropriate PPE kit while removing and replacing gas coolers.

Step 2 : Heat exchanger replacement

  • Lift the new gas cooler into position and re-braze the piping connections
  • Make sure to purge with nitrogen to avoid oxidisation during the brazing process
  • In addition to this, please make sure to fill the piping connection with a sufficient amount of brazing rod
  • In the image below you can see some examples

Design and practice the piping work as instructed below.

  • Sufficiently clean the inside of low pressure device, pipes, etc., to remove dirt or moisture, and dry them before use. Use always a pipe cutter to cut refrigerant pipes, and blow off dirt with nitrogen, or air, before connection. (Avoid to use a saw, or grinder, because it could produce a lot of Swarf.)
  • Use the nitrogen gas blow when brazing pipes to prevent oxide scale

Step 3 : Airtightness test for heat exchanger high pressure tubing

  • Power off the unit, then dip SW5-7, Turn ON dip SW5-8 (UP) and turn on power. All electronically operated valves and electronic expansion valves will be fully closed (see fig. 6)
  • In this case of Heat exchanger replacement, please make sure to apply 140bar (14Mpa) from the HP service port
  • When you applying nitrogen to the system, charge the nitrogen in steady increments and stop for 5 minutes at each incremental increase
  • As shown in the presentation material, start at 10bar (1Mpa), 30bar (3Mpa), 70bar (7Mpa), 100bar (10Mpa), 130bar (14Mpa)
  • Finally charge the nitrogen to 140bar (14Mpa) and hold for 10 minutes to check for any pressure drop, visible tube deformation
  1. Two stage compressor (scroll-rotary)
  2. Suction line Accumulator
  3. Oil Separator
  4. DC Fan assembly
  5. Micro Channel Heat Exchanger with Fan
  6. Strainer
  7. Liquid Receiver
  8. EEV for liquid bypass
  9. EEV for Middle pressure receiver inlet
  10. EEV for Sub cooling coll
  11. Sub cooling coil
  12. Check Valve
  13.  Oil pod
  14. Solenoid Valve
  15. Middle Pressure sensor
  16. Service Valve
  17. Shut off Valve
  18. Pressure Relief valve
  19. Capillary
  20.  Sight glass
  21. Under dome temperature sensor
  22.  Injection inlet temperature sensor
  23. Discharge pipe temperature sensor
  24. Subcooling coil temperature sensor
  25. Middle pressure receiver inlet temperature sensor
  26. Gas cooler temperature sensor
  27. High pressure sensor
  28. High Pressure switch
  29. Low pressure sensor
  30. Gas cooler temperature sensor
  31. Liquid feed pipe temperature sensor
  32. Crankcose Heater
  33. Outside air temperature sensor
  34. Suction pipe temperature sensor
  35. Filter Drier (Accessory)

High Pressure Circuit
Low Pressure Circuit
Medium Pressure Circuit

Yellow highlight should be pressurised with N2 140bar (14MPa) after replacement of the gas cooler

Maintenance

If the components located in medium and low-pressure area (Yellow and blue colour) are replaced

  • Same manner with Air tightness test at installation phase Usage pressure : 80.0bar

Step 4 : Vacuuming

  • Never use the compressor to evacuate the system.
  • Connect a vacuum pump to both the LP & HP sides for quicker and efficient evacuation.
  • Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) absolute.
  • Do not use a megohmmeter or apply power to the compressor while it is under vacuum as this may cause internal damage.
  • After the airtight test, connect the vacuum pump to the low pressure side service port and high pressure side service port, and evacuate.
  • Use always a vacuum pump to the equipment.
  • Check the low pressure with the gauge manifold or vacuum gauge.
  • When their is no power supply to the unit, remove the coil from the medium pressure suction solenoid valve, and open it forcibly using a special magnet.
  • When there is a power supply to the unit, ensure this is turn OFF and then turn the dip switch SW5-7 to ON (Up) to turn on the unit’s power supply. The electronic expansion valve and solenoid valve in the unit open. The vacuum pump is connected to the low pressure side only at that time.

Step 5 : Nitrogen (N2, oxygen free) /CO2 charge

  • When the unit is not installed, for storage purposes, please charge small amount of N2 (0.1bar) to the Condensing unit and ensure piping caps are fitted, ensure the Condensing unit is keep dry
  • When you are doing that on site, please charge according to the previous commissioning or use the Danfoss calculation charge tool to ensure the right amount of refrigerant and oil charge.

Note:
Ensure that the airtight test report and pressure test report are captured with possible evidences to further Pressure equipment regulations.

DanfossA/S
Climate Solutions•
danfoss.com
+45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/5 or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All rights reserve
BC451938732076en-000101
© Danfoss | Climate Solutions | 2023.05

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals