COMMSCOPE FACT NG4 Chassis for Modules and Adapter Packs Instruction Manual
- June 10, 2024
- CommScope
Table of Contents
- CommScope FACT NG4 Chassis for Modules and Adapter Packs
- Installation Instructions
- General product information
- General product information
- Product image
- Kit content
- Mounting FACT chassis in the rack
- Installation of the modules
- Installation of the Adapter Packs
- Trademarks
- Contact information
- Documents / Resources
CommScope FACT NG4 Chassis for Modules and Adapter Packs
Installation Instructions
FACT NG4 CHASSIS FOR MODULES & ADAPTER PACKS
TC-40161-IP-EN Rev A, March 2019
General product information
The universal FACT NG4 chassis (FACT-xENG4) for modules & adapter packs supports the NG4-access connectivity packs and modules that easily snap in the chassis. It accommodates SC, LC and MPO adapter packs, MPO-modules (MPO to LC, or MPO to SC), Cabled modules (CMOD) and Value-added modules (VAM).
Warnings and caution
860648849 Rev. A
Product image
Refer to the user manual for a product image.
Kit content
- FACT NG4 chassis
- Modules
- Adapter packs
Mounting FACT chassis in rack
Mounting FACT chassis
- Prepare the rack with the brackets on the position where you want to install the FACT chassis (by sliding them in).
- Take the FACT chassis with both hands and align with the brackets on both sides.
- Slide the FACT chassis into the fingers until you hear a clicking noise.
Dismounting FACT chassis
-
Open upper drawer (releasable).
-
Pull the blue puller locks (make sure both sides -left &
right- are in the unlocked position). -
Slowly slide the FACT chassis out (pull simultaneously on both sides, with both hands).
Installation of the modules
- FACT element is provided with 2 trays (1 module per tray) per drawer.
- Use the latch to detach the insert on the desired side.
- Remove the insert.
- Align the module in on the side where the insert was removed, by placing it on top.
- Align the module as illustrated. Don’t push it in yet.
- Align the module as illustrated. Don’t push it in yet.
- Align the module as illustrated. Don’t push it in yet.
- Push in snapping feature number 1.
- Push in snapping feature number 2.
- Push in snapping feature number 3.
- Push in snapping feature number 4.
- Push in snapping feature number 5.
- Routing the patch cords (modules)
- Refer to the user manual for instructions on routing patch cords for modules.
- Installation of the adapter packs
- Refer to the user manual for instructions on installing adapter packs.
- Routing the patch cords (adapter packs)
- Refer to the user manual for instructions on routing patch cords for adapter packs.
- Trademarks
- All trademarks are the property of their respective owners.
- Contact Information
- For additional information, please contact Commscope technical support at 1-800-866-0046 or visit www.commscope.com.
General product information
The universal FACT NG4 chassis (FACT-xENG4) for modules & adapter packs supports the NG4-access connectivity packs and modules that easily snap in the chassis. It accommodates SC, LC and MPO adapter packs, MPO-modules (MPO to LC, or MPO to SC), Cabled modules (CMOD) and Value-added modules (VAM).
Warnings and caution
- Fiber optic cables may be damaged if bent or curved to a radius that is less than the recommended minimum bend radius. Always observe the recommended bend radius limit when installing fiber optic cables and patch cords.
- Exposure to laser radiation can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not assume the laser power is turned off or that the fiber is disconnected at the other end.
- Pay attention to the routing of the patch cords. These should move/hang freely, where they leave the bend control. If you see that there is tension occuring on the patch cords, please reroute these.
Product image
Note: FACT chassis with LC-Adapters shown as an example.
Kit content
- FACT element NG4
- Brackets
- Color coding labels
- Transparent pockets with labels
Mounting FACT chassis in the rack
Mounting FACT chassis
- Prepare the rack with the brackets on the position where you want to install the FACT chassis (by sliding them in ).
- Take the FACT chassis with both hands and align with the brackets on both sides.
- Slide the FACT chassis into the fingers until you hear a “clicking noise”.
Dismounting FACT chassis
- Open the upper drawer (releasable).
- Note: the empty drawer is shown. This one is marked at the front (blue marking at the bend control).
- Pull the blue puller locks (make sure both sides -left & right- are in the unlocked position).
- Slowly slide the FACT chassis out (pull simultaneously on both sides, with both hands).
- Note: empty drawer is shown.
Installation of the modules
- FACT element is provided with 2 trays (1 module per tray) per drawer.
- To access the bottom tray, remove the velcro and rotate the top tray to a 90° position.
- Use the latch to detach the insert on the desired side.
- Remove the insert.
- Align the module in on the side where the insert was removed, by placing it on top.
- Align the module as illustrated. Don’t push it in yet.
- Align the module as illustrated. Don’t push it in yet.
- Push in snapping feature number 1.
- Push in snapping feature number 2.
- Push in snapping feature number 3.
- Push in snapping feature number 4.
- Push in snapping feature number 5.
- SC-MPO Module installed.
- VA Module installed.
- LC-MPO Module installed
- Cabled Module installed.
Routing the patch cords (modules)
- Open the bend control cover. Unlatch the snapping feature (on the backside of the bend control) as shown.
- The retaining feature can be opened (hinged back) if additional space is needed (optional).
- Open the back lid by pushing the snap feature to the inside and then lifting the lid.
- Route the patch cords through the first bend as illustrated. Use 3 patch cords per bend control for the SC-MPO Module. Clean the connectors before installing!
- Route the patch cords through the first bendµ as illustrated. Use 6 patch cords per bend control for the VA Module. Clean the connectors before installing them!
- Route the patch cords through the first bend as illustrated. Use 6 patch cords per bend control for the LC-MPO Module. Clean the connectors before installing them!
- Route the patch cords through the first bend as illustrated. Use 6 patch cords per bend control for the Cabled Module. Clean the connectors before installing them!
- Route the patch cords to the back side of the FACT element.
- When you route both trays, it should look as illustrated.
- Carefully close the back lid.
- Close the bend control cover (retaining feature down).
- Route the patch cords through the trumpet.
- Before closing the drawer, pay attention to the patch cord routing.
Installation of the Adapter Packs
- FACT element is provided with 2 trays (2 adapter packs per tray) per drawer.
- To access the bottom tray, remove the velcro and rotate the top tray to a 90° position.
- Align the Adapter Packs.
- Make sure that features 1, 2 & 3 are aligned correct.
- Align feature number 1 and push it in (flush with edge).
- Align snapping feature number 2 and push it in.
- Align snapping feature number 3 and push it in.
- SC-SC Adapter Packs installed.
- MPO-MPO Adapter Packs installed.
Routing of the patch cords (Adapter Packs)
- Open the bend control cover. Unlatch the snapping feature (on the backside of the bend control) as shown.
- The retaining feature can be opened (hinged back) if additional space is needed (optional).
- Open the back lid by pushing the snap feature to the inside and then lifting the lid.
- Route the patch cords through the first bend as illustrated. Use 3 patch cords per bend control for the SC-SC Adapter Packs. Clean the connectors before installing them!
- Route the pach cords through the first bend as illutrated. Use 6 patch cords per bend control for the LC-LC Adapter Packs. Clean the connectors before installing!
- Route the patch cords through the first bend as illustrated. Use 2 patch cords per bend control for the MPO-MPO Adapter Packs. Clean the connectors before installing!
- Route the patch cords to the back side of the FACT element.
- When you route both trays, it should look as illustrated.
- Carefully close the back lid.
- Close the bend control cover (retaining feature down).
- Route the patch cords through the trumpet.
- Before closing the drawer, pay attention to the patch cord routing.
Trademarks
- All trademarks identified by ® or ™ are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services. CommScope is committed to the highest standards of business integrity and environmental sustainability, with a number of CommScope facilities across the globe certified in accordance with international standards, including ISO 9001, TL 9000, and ISO 14001.
- Further information regarding CommScope’s commitment can be found at www.commscope.com/About-Us/Corporate-Responsibility-and-Sustainability.
Contact information
- Visit our website or contact your local CommScope representative for more information.
- For technical assistance, customer service, or to report any missing/damaged parts, visit us at: http://www.commscope.com/SupportCenter
- This product may be covered by one or more U.S. patents or their foreign equivalents.
- For patents, see www.cs-pat.com
- © 2018 CommScope, Inc. All Rights Reserved
Documents / Resources
|
COMMSCOPE FACT NG4 Chassis for Modules and Adapter
Packs
[pdf] Instruction Manual
TC-40161-IP, FACT-2ENG4, FACT NG4 Chassis for Modules and Adapter Packs, FACT
NG4 Chassis, Modules Chassis, Adapter Packs Chassis, Chassis
---|---