GE APPLIANCES RAK150VF2 Digital Wall Thermostat Instruction Manual

June 10, 2024
GE Appliances


Digital

THERMOST AT

INSTALLATION INSTRUCTIONS

RAK150VF2

31-5000604   Rev. 1   02-22   GEA

IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING

WARNING
FIRE AND SHOCK HAZARD

  • Always turn off power at the main power supply before installing, cleaning or removing the thermostat. Failure to do so could result in electrical shock hazard.
  • Do not use on voltages over 30 VAC. Higher voltages will damage the thermostat and could cause shock or fire hazard.

NOTICE

  • All wiring must conform to local and national electrical and building codes.
  • Use this thermostat only as described in this manual.
Specifications

Electrical rating:

  • 24 VAC (18-­30 VAC)
  • 1 amp maximum per terminal
  • 4 amp maximum total load

Operating temperature range: 40°F-­99°F (4°C-­37°C)
Temperature set range: 60°F-­85°F (15°C­-29°C)
Accuracy: ± 1°F (± 0.5°C)
System configurations:

  • Factory Setting: 3-stage heat (heat pump low, heat pump high, resistance heat), 2-stage cool (cool low, cool high), 2-speed fan
  • Alternate Setting: 2-stage heat (heat pump/resistance heat), 1-stage cool, 2-speed fan
  • Alternate Setting: 1-stage heat (resistance heat), 1-stage cool, 2-speed fan

Terminations: R, C, B, Y1, W, Y2, GL, GH
Wiring: Maximum wiring length is 66ft (20 meters) for AWG18. Maximum wiring length is 60ft (18 meters) for AWG20

INTRODUCTION OVERVIEW

THERMOSTAT CONTROLS

  1. Display
  2. Up/Down Buttons

THERMOSTAT BASE LAYOUT

  1. Display
  2. Up/Down Buttons
  3. Wiring Channel
  4. Mounting Hole
  5. Fan
  6. Mode
  7. Reset Button
  8. Configuration Button
INSTALLATION INSTRUCTIONS

WARNING

ELECTRICAL SHOCK HAZARD — Turn off power by unplugging the unit or by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat. Failure to do so could result in risk of electric shock.

PACKAGE CONTENTS/TOOLS REQUIRED:

Package includes:

  • Thermostat base
  • Thermostat cover
  • Wiring labels
  • Screws
  • Wall anchors

Tools needed:

  • Drill with 3/16″ bit
  • Hammer
  • Screwdriver
  • Putty
TO REMOVE EXISTING THERMOSTAT
  1. Turn off power to heating and cooling system by removing the fuse or switching off the appropriate circuit breaker.
  2. Remove cover of old thermostat. This should expose the wires.
  3. Label the existing wires with the enclosed wire labels before removing wires.
  4. After labeling wires, remove wires from wire terminals.
  5. Remove existing thermostat base from wall.
  6. Refer to the following section for instructions on how to install this thermostat.
TO INSTALL THERMOSTAT

IMPORTANT: Thermostat installation must conform to local and national building and electrical codes and ordinances.
NOTE:
Mount the thermostat about five feet above the floor. Do not mount the thermostat on an outside wall, in direct sunlight, behind a door or in an area affected by a vent or duct.

  1. Turn off power to the heating and cooling system by removing the fuse or switching off the appropriate circuit breaker.

  2. Remove the cover by inserting and twisting a coin or screwdriver in the slots on the top of the thermostat.

  3. Put thermostat base against the wall where you plan to mount it. Make sure wires will feed through the wire opening in the base of the thermostat.

  4. With the base level, mark the placement of the mounting holes.

  5. Set thermostat base and cover away from working area.

  6. Using a 3/16″ drill bit, drill holes in the locations you have marked for mounting.

  7. Use a hammer to tap supplied anchors in mounting holes.

  8. Align thermostat base with mounting holes and feed the control wires through the wire opening.

  9. Seal hole for wires behind thermostat with nonflammable insulation or putty, or use a wall plate obtainable from a local hardware or home building store.

  10. Use supplied screws to mount thermostat base to wall.

  11. Insert stripped, labeled wires in matching wire terminals by pressing on the corresponding terminal contact. See the “Wiring Diagrams” section of this manual.
    NOTICE
    Make sure exposed portion of wires do not touch other wires.

  12. Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper terminal.

  13. Replace cover on thermostat by snapping it in place.

  14. Plug the unit in or turn on power to the system at the main service panel.

  15. Test thermostat operation.

WIRING DIAGRAMS

Table 1: Terminals for eight wires. 3-stage heat/2-stage cool system

GE APPLIANCES RAK150VF2 Digital Wall Thermostat A3

Table 2: Terminals for seven wires. 2-stage heat/1-stage cool system

GE APPLIANCES RAK150VF2 Digital Wall Thermostat A4

Table 3: Terminals for six wires. 1-stage heat/1-stage cool system

GE APPLIANCES RAK150VF2 Digital Wall Thermostat A5

CONFIGURATION MODE

The configuration mode is used to set the RAK150VF2 to match the heating/cooling system. The default setting of this thermostat is for 2-stage cooling with a 3-stage heat pump system. For an alternate configuration, see

7 in the Configuration Mode Settings below.

To configure the RAK150VF2, perform the following steps:

1. Ensure thermostat is in OFF mode.
2. Remove the thermostat’s front cover.
3. To enter the configuration mode, hold CONFIG for ~ 2 seconds.
4. Once in the configuration mode, press the ∨ or ∧ button to change settings within each screen.

– Press the FAN (right) button to advance to the next screen.
– Press the MODE (left) button to return to the previous screen.
NOTE: Hold CONFIG button for ~2 seconds to save changes and exit configuration menu.

Configuration Mode Settings

The setup screens for Configuration Mode are as follows:

1. Temperature Scale (°F or °C) –Choose Fahrenheit or Celsius.

– Press the ∨ or ∧ button to select.
– Press the FAN (right) button to advance to the next screen. NOTE: Default factory setting is Fahrenheit.

2. Temperature Differential–Stage 1–(1­-9°F) (.5-4.5°C)
Set the number of degrees between the “setpoint” temperature and the “turn on” temperature for first stage.

– Press the ∨ or ∧ button to set differential value.
– Press the FAN (right) button to advance to the next screen.
– Note: Default factory setting is 1ºF /.5ºC.

3. Temperature Differential–Stage 2 (1­-9°F) (.5-4.5°C)
Set the number of degrees between when stage 1 turns on and stage 2 turns on.

– Press the ∨ or ∧ button to set differential value.
– Press the FAN (right) button to advance to the next screen.
Note: Default factory setting is 1°F/.5°C.

4. Temperature Differential–Stage 3 (1­-9°F) (.5-4.5°C)
Set the number of degrees between when stage 2 turns on and stage 3 turns on

– Press the ∨ or ∧ button to set differential value.
– Press the FAN (right) button to advance to the next screen.
Note: Default factory setting is 1°F/.5ºC.

5. System – Select appropriate cooling/heating system based on model selection

– HP b2: two stage cooling / two stage (B type) heat pump with a backup 3rd stage of resistance heat.
Use for AZ9V models.
– HP b1: single stage cooling / single stage (B type) heat pump with a backup 2nd stage of resistance heat.
Use for AZ95H and AZ65H models.
– ELC: single stage cooling / single stage resistance heating.
Use for AZ95E and AZ45E Models.
– Press the ∨ or ∧ button to change selection.
– Press the FAN (right) button to advance to the next screen.
– Note: Default factory setting is HP b2.

6. Minimum Cool Setpoint (60, 64, 66, 68, 70, 72, 74, 76°F) (15, 17, 19, 20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set temperature allowed.

– Press the ∨ or ∧ button to select.
– Press the FAN (right) button to advance to the next screen.
Note: Default factory setting is 60°F/15°C.

7. Maximum Heat Setpoint (65, 70, 72, 74, 76, 78, 80, 85°F) (18, 21, 22, 23, 24, 26, 27, 29°C)
Adjust to control the maximum Heat set temperature allowed.

– Press the ∨ or ∧ button to select.
– Press the FAN (right) button to advance to the next screen.
Note: Default factory setting is 85°F/29°C.

8. Room Temperature Offset (+9°F to ­-9°F) (+5°C to -­5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.

– Press the ∨ or ∧ button to select.
– Press the FAN (right) button to advance to the next screen.
Note: Default factory setting is 0°F/0°C.

9. Continuous Fan
This setting controls the availability of the continuous fan options available for selection by the thermostat user. Continuous fan options allow for the fan to be operated all the time if selected.

– Press the ∨ or ∧ button to change selection.
Note: Default factory setting is ON (1). 1=ON, 0=OFF

OPERATING FUNCTIONS

Off

  • In this mode, the thermostat will not turn on the heating or cooling devices (manual fan can operate if Continuous Fan mode is enabled).
  • Off is also used to access Configuration mode.

Heat

  • In this mode, the thermostat controls the heating system.
  • Press the ∨ or ∧ button to set the desired temperature.
  1. Heating Setpoint
  2. Room Temp
  3. Heating Indicator

Cool

  • In this mode, the thermostat controls the cooling system.
  • Press the ∨ or ∧ button to set the desired temperature.
  1. Cooling Setpoint
  2. Cooling Indicator
  3. Room Temp

Fan

  • Fan operation is available in either low or high speed.
  • Press the ∨ or ∧ button to select a fan option. Selection will be locked in after 8 seconds.
  • “Auto” options operate the fan only during a cooling or heating cycle.
  • Continuous (“On”) options operate the fan all the time including while in “OFF” mode. These options can be disabled in the thermostat configuration (Config #9).

Auto, Low Speed:

Auto, High Speed:

Continuous, Low Speed:

Continuous, High Speed:

TROUBLESHOOTING TIPS

Problem Solution
No Display Check for 24 VAC; display is blank when 24 VAC is not

present
System fan does not come on properly| Verify that wiring is correct.
All thermostat buttons are inoperative| Verify that 24 VAC is present; unit will not operate when 24 VAC is not present.
Thermostat turns on and off too frequently| Adjust temperature differential (see Configuration Mode – Setting Temperature Differential, Stage 1, Stage 2, and Stage 3 section).
Fan runs continuously| Check fan selection. If set to ON, fan will run.
Room temperature is not correct| Verify that wall hole is plugged with putty or insulation to prevent airflow from the wall cavity. Adjust Temperature Offset (see Configuration Mode – Room temperature offset section).
Compressor doesn’t run or turn off immediately when changing function or setting| There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off.
Fan doesn’t run or turn off immediately when changing function or setting| This is normal. On some models, the fan may have a minimum run time/off time delay.
Problem not listed above| Press the Reset button once to reset the thermostat microprocessor.

THERMOSTAT WARRANTY

Staple your receipt here. Proof of the original purchase date is needed to validate the warranty.

For The Period Of: GE Appliances Will Replace:

One Year

From the date of the original purchase

| Full Replacement of the thermostat which fails due to a defect in materials or workmanship.

For Warranty replacement, contact your distributor.

What GE Appliances Will Not Cover:

  • Service trips to your location.
  • Improper installation. If you have an installation problem, contact your installer. You are responsible for providing adequate electrical connections to the product.
  • Failure of the product resulting from modifications to the product or due to unreasonable use, including failure to provide reasonable and necessary maintenance.
  • In commercial locations, labor necessary to move the unit, after it has been initially installed, to a location where it is accessible for service by an individual technician; or, if the instructions included in this manual have been disregarded.
  • Replacement of location fuses or the resetting of circuit breakers.
  • Damage to the product caused by improper power supply voltage, accident, fire, floods or acts of God.
  • Incidental or consequential damage caused by possible defects with this thermostat.

EXCLUSION OF IMPLIED WARRANTIES–Your sole and exclusive remedy is product exchange as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.

This warranty is extended to the original purchaser and any succeeding owner for products purchased for use within the USA and Canada. In Alaska, the warranty excludes the cost of shipping or service calls to your site.

Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state’s Attorney General.

Warrantor: GE Appliances, a Haier company
Louisville, KY 40225

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

GE Appliances User Manuals

Related Manuals