SPACEPAK SSIC2-0119 System Interface Control Instruction Manual
- June 10, 2024
- SPACEPAK
Table of Contents
SPACEPAK SSIC2-0119 System Interface Control
Introduction
Unit Description
The SpacePak System Interface Control (SSIC) takes inputs from up to five Air
Handlers and sends control signals to the chiller, chiller reversing valve,
boiler, and system pump based on installed options. Air Handlers receive their
calls from their respective thermostats and output a heating or cooling call
to the SSIC. Based on these demands the SSIC determines how to operate the
system.
Standard Equipment
- SSIC Control Box
- Outdoor Air Temperature Sensor (OAT)
- Buffer Tank Temperature Sensor
Optional Equipment
- Buffer Tank
- Bypass Valves
Operation
The base system has two modes of operation; Auto and Master.
- Auto: The first zone to call is treated as the master zone and the system mode will reflect the type of call (heat/cool) coming from that zone. Any calls from other zones of the opposing type will be ignored until all calls of the original type are satisfied.
- Master: The user can define a master zone that will always determine the system mode if it is calling. When the master zone is not calling, calls are treated as in Auto mode.
Any zone that is calling will be shown on the controller’s LCD, showing the corresponding zone number and call type. If the call matches the current system mode there will be a capital H or C next to the zone number. If not, the letter will be lowercase.
S| Y| S| T| E| M| | M| O| D| E| :| H| E| A| T| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Z| O| N| E| :| 1| H| | 2| c| | 5| H| | | | | | |
O| U| T| P| U| T| S| :| B| | | | | | | | | | |
O| A| :| | 4| 6| °| F| | | T| A| N| K| :| 1| 0| 5| °| F
Table 1: Example screen shot
Buffer Tank
An available option to the SpacePak Control is buffer tank control that can
provide hot or cold water to the zones faster than a system without the buffer
tank. Depending on the outside air temperature, the controller maintains a
water temperature in the tank that can provide fast cooling or heating to any
of the system’s zones. An available bypass valve option can also be installed
for even more control on days when zone demands do not match the predicted
temperature demands based on the outside temperatures.
Buffer Tank Operation
If the buffer tank is installed and enabled in the firmware, it is treated as
the master zone for the system. Any calls for hot or cold water by the buffer
tank are serviced before opposite calls from the zones. Buffer tank demand is
determined by:
Outside Air
Temperature
|
System Mode
---|---
≤ 50°F| Heating
5| Cooling
50°F > OAT > 65°F| Idle
Table 2: Temperatures shown are default values and are adjustable
If the system mode is IDLE, any calls from zones are serviced on a first come
first served basis.
When in either BUFFER HEATING or BUFFER COOLING mode, the control will
continue to call until the water temperature in the tank reaches the setpoint
for that mode. Once the temperature in the buffer tank has reached its
setpoint, the buffer mode switches to SATISFIED and the temperature is allowed
to change by an amount determined by the DIFF (Differential) settings (default
10° for heating, 6° for cooling), after which point the heating/cooling will
again work to satisfy the buffer demand.
There are 2 potential sources for heating depending on how each system is set up (boiler or chiller) so there are 2 different set points for heating (160°F and 120°F). Because chillers generally cannot get water as hot as a boiler that setpoint is lower. Either setpoint can be adjusted in the buffer tank setpoints menu as shown later on in this document.
System Mode
| Buffer Tank
Temperature
|
Buffer Mode
---|---|---
Heating| ≤160°F| Heating
| >160°F| Satisfied
Cooling| ≥48°F| Cooling
| <48°F| Satisfied
Table 3: Temperatures shown are default boiler values and are adjustable
Buffer Bypass
The buffer tank may be bypassed with the installation of two bypass valves. If
conditions allow the buffer tank demand to remain IDLE there is no need to
maintain a temperature in the tank. Calls would be serviced directly from the
chiller or boiler instead, saving energy by not having to heat up the water in
the tank.
Buffer Override
Buffer override allows the buffer tank demand to be overridden if the right
conditions are met. If the buffer tank’s temperature demand has been satisfied
and there is a call for the opposite mode from the system and there are no
other zone calls, the buffer tank can be overridden so the zone may be
satisfied directly from the sources. For the buffer override feature to work
the system must have 2 bypass valves installed (shown in plumbing diagram) and
the Buffer Bypass and Buffer Override must be enabled on the controller.
Note: If bypass valves are not installed and enabled the system will never service calls from zones that oppose the buffer tank’s calls even if the buffer tank is satisfied. For example, if the OAT is below 50°F (default) any cool calls from zones will not be serviced.
ThinWall Control
If a SpacePak ThinWall unit is installed in a zone, the control needs to be
configured to accommodate it. The ThinWall fan coil unit has one control
output and uses the OAT to predict if the zone needs heating or cooling. Each
zone with a ThinWall unit must have ThinWall control enabled from the ThinWall
menu on the SSIC to properly set the heating or cooling mode as necessary. In
addition to an enable for each zone, the user can set the OAT switchover,
hysteresis, and a control timeout for systems with a mix of ThinWall and non-
ThinWall units.
ThinWall inputs must be connected to the W terminal of the appropriate zone to
operate. The control will not recognize anything connected to Y if ThinWall is
enabled for that zone.
Installation
Mounting
SSIC Mount the control box in a dry indoor location that has easy wiring
access from the air handler(s), and the outside chiller.
There are three hole locations for mounting the SSIC (see below).
- Use a #8 wood screw and corresponding wall anchor to mount the SSIC. Secure wood screw into anchor leaving 3/16″ (5mm) between screw head and the wall. Hook the unit and slide into place.
- Remove lower front panel. Use two #5 wood screws in the bottom hole locations to secure the unit to the wall.
Wiring
warning
Electrical shock hazard – Disconnect all electrical power before wiring the
unit.
- Remove the lower access panel to gain access to the wire terminals.
- Pass the wires from the Air Handlers, Pump, Chiller, etc. through the grommets at the bottom of the unit and plug into their corresponding connector (see below or for more detailed information see the wire diagram on page 6)
- When all wiring between the air handlers, pumps, and chillers is completed, connect the power.
- When connecting 115V, connect the line (hot) wire to L; connect the neutral wire to N, and connect the ground wire (bare copper or green) to G.
Outdoor Air Temperature Sensor
- Avoid areas subject to excessive vibration, electrical noise, direct sunlight, or the effects of radiant heat.
- Keep electrical wiring as short as possible to minimize temperature error.
Buffer Tank Temperature Sensor
- Coat sensing bulb liberally with heat transfer paste.
- Insert sensor into well of the buffer tank.
- Slide plastic locknut over the lead and hand tighten only onto the threads of the bulb well.
- Route lead back to the chiller and connect to terminals X+Y (as indicated in the chiller IOM).
SSIC Terminal Blocks
__
OA
| __
Outdoor Air Temperature Sensor (included)
| __
ZONE X
| __
Connection from Zone X (1-5) Air Handler
---|---|---|---
__
WATER
| __
Buffer Tank Temperature Sensor (included)
| __
XW
| __
24VAC Heating Signal from Air Handler
__
RETURN
| __
Return Temperature Sensor (N/A*)
| __
XY
| __
24VAC Cooling Signal from Air Handler
__
SENSE
| __
Connections for Future Models (N/A*)
| __
XC
| __
Ground from Air Handler
__
R
| __
24VAC
| __
COM X
| __
Connections for Future Models (N/A*)
__
RELAY
| Dry Contact Relay to activate Bypass Valves| __
C
| __
24VAC Return
__
PUMP
| __
Dry Contact Relay to activate the Pump
|
__
BOILER
| __
Dry Contact Relay to activate the Boiler
|
__
CHILLER
| Dry Contact Relay to activate the Chiller’s enable|
__
RV
| Dry Contact Relay to activate Chiller’s Reversing Valve|
Wiring diagram
SPACEPAK SYSTEM INTERFACE CONTROL FIELD WIRING
Buffer Tank Bypass
Buffer Tank Bypass is a function available within the SSIC that allows a
hydronic system to store thermal energy in the form of heated or chilled
water. The Heat Pump simultaneously reverses cycle to satisfy a temporary
demand that is the opposite of the prevailing operating mode (i.e., a cooling
call when the system is operating in heating mode, or a heating call when the
system is operating in cooling mode)
There three basic configurations, each with its own advantages. The installer
is free to employ any configuration that best fits the installation.
Four Pipe Buffer Tank
This is the most common buffer tank installation. The primary loop is routed
through one side of the buffer tank, the secondary loop through the other.
When the Bypass feature is engaged, each of the four three-way valves
transfers, isolating the buffer tank and creating two runaround paths linking
the Heat Pump directly to the emitters.
Two Pipe Buffer Tank
The choice between a two-pipe or four-pipe plumbing configuration is based
upon operation during normal conditions. Once the bypass is engaged, they
operate essentially the same. The advantage of two-pipe in bypass application
is that it requires only two, rather than four valves.
Hybrid Piped Buffer Tank
This configuration is unique in that it is the only arrangement that can
deliver heating and cooling simultaneously (for a limited duration). The zone
(Zone 1 as shown) that is plumbed directly to the Buffer Tank will always
provide conditioning consistent with the prevailing mode (heating or cooling)
The capacity of this zone during bypass operation is limited to the amount of
energy stored within the buffer tank, as it is isolated from the heat pump and
not replenished. Zone 2 is isolated from the buffer tank, and Zone 1, so it
can deliver heating or cooling operation whenever called for. The bypass is
accomplished by two three-way valves.
Operation
Control Logic (Firmware V1.5)
The following sections outline how the SSIC can be configured using the menus
that appear on its display. Menus are navigated using the UP, DOWN, BACK, and
SELECT keys on the keypad. The user navigates to the setting they want to
change by using the UP and DOWN keys. Pressing SELECT will move the cursor in
front of the selectable options. Pressing the UP and DOWN keys will change the
state from disabled to enabled or vice versa. Pressing the SELECT key saves
the setting and pressing BACK will revert to its original setting.
Main Screen – No Buffer Tank
This is the display screen that shows the status of the system.
S| Y| S| T| E| M| | M| O| D| E| :| H| E| A| T| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Z| O| N| E| :| 1| H| | 2| c| | 5| H| | | | | | |
O| U| T| P| U| T| S| :| B| | | | | | | | | | |
O| A| :| | 4| 6| °| F| | | T| A| N| K| :| N| /| A| |
Figure 6: Main screen when the buffer tank option is disabled. Zone 2’s call is being ignored by the system.
SYSTEM MODE: The general operation of the entire system. If the system is
sending no outputs, then the system mode will display ‘IDLE’. If the system is
cooling then the system mode will display ‘COOL’, and if it is heating, then
‘HEAT’ will be displayed.
ZONE CALLS: All zone calls are displayed here with their corresponding
call type. Calls that match the current system mode show as a capital letter,
conflicting calls show a lower case letter.
OUTPUTS: The systems outputs to the boiler, chiller, and pump are here.
Each output is represented by the following:
- B: Boiler
- C: Chiller
- RV: Chiller Reversing Valve P: Pump
- BY: Bypass valves
TEMPERATURES: Shows the outside air and water temperatures. The forth line will also show if there is a sensor error detected.
Main Screen – Buffer Tank
When the buffer tank is enabled, the main screen also shows the buffer mode
and the tank’s temperature.
S | Y | S | : | H | E | A | T | T | A | N | K | : | H | E | A | T | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Z | O | N | E | : | 1 | H | 2 | c | 5 | H | |||||||||
O | U | T | P | U | T | S | : | B | |||||||||||
O | A | : | 4 | 6 | ° | F | T | A | N | K | : | 1 | 0 | 5 | ° | F |
Figure 7: Main screen when the buffer tank is enabled
Settings Menu
The following sections will explain in detail each of the configuration
settings.
→| M| a| s| t| e| r| | Z| o| n| e| | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| B| o| i| l| e| r| /| C| h| i| l| l| e| r| | O| P| |
| B| u| f| f| e| r| | T| a| n| k| | | | | | | |
| T| h| i| n| W| a| l| l| | | | | | | | | |
Figure 8: Settings Page 1
→| S| y| s| t| e| m| | S| e| t| t| i| n| g| s| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| T| e| m| p| e| r| a| t| u| r| e| | U| n| i| t| s| |
| R| e| s| t| o| r| e| | D| e| f| a| u| l| t| s| | |
| L| o| a| d| | F| i| r| m| w| a| r| e| | | | | |
figure 9: Settings Page 2
Master Zone
- Setting the master zone determines what zone call takes priority.
- Auto: First zone to call governs the mode of the system (heating or cooling). It stays in this mode until all zones making the same call have been satisfied.
- Zones 1 – 5: The chosen zone acts as the master and governs the mode of the system. If the master zone is not calling then the other zones can have their calls satisfied.
- The master zone is only settable by the user if the buffer tank is disabled. See the description in the introduction for more details.
M| a| s| t| e| r| | Z| o| n| e| :| | Z| o| n| e| | 1|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 10: Master Zone
Boiler/Chiller OP
This menu allows the user to configure the system’s heating operation.
→| C| h| i| l| l| e| r| | H| e| a| t| | M| o| d| e| :|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | C| h| i| l| l| e| r| | O| n| l| y| | | | | |
| | | | | | | | | | | | | | | | | | |
| C| h| i| l| l| e| r| | R| V| :| | 0| (| C| o| o| l| )
Figure 11: Boiler/Chiller OP Menu
Chiller Only Mode
The boiler is not used and only the chiller is used to supply heating and
cooling. The chiller’s heating and cooling operation is governed by how the RV
is energized which is user configured.
Required Sensors: None
Boiler Only Mode
The chiller is never used for heating, and only the boiler supplies the heat.
The chiller’s cooling outputs are based on the RV configuration.
Required Sensors: None
Boiler Help
Boiler Help uses both the Boiler and the Chiller to provide heat. When heat is
called for the chiller kicks in to provide the hot water. If the water
temperature has not risen to the low temperature setpoint (80°F default)
within the defined time period (2 minutes default), the boiler is turned on to
assist and remains on until the heat call is satisfied.
A | d | j | u | s | t | M | o | d | e | S | e | t | t | i | n | g | s | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
L | o | w | T | e | m | p | : | 8 | 0 | ° | F | ||||||||
T | i | m | e | : | 2 | m | i | n | s | ||||||||||
Figure 12: Boiler Help settings
Required Sensors: Buffer
Outdoor Air (OA) Switch Over
OA switchover will change the heat source between the chiller and boiler
depending on the outside air temperature. If the OAT is below or equal to the
setpoint (40°F default) the boiler will provide the hot water, above the
setpoint the chiller will provide the heat.
Required Sensors: OA
S| e| t| | O| A| | S| w| i| t| c| h| o| v| e| r| | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
T| e| m| p| e| r| a| t| u| r| e| | | | | | | | |
| | | | | | | | | | →| 4| 0| °| F| | | |
| | | | | | | | | | | | | | | | | | |
Figure 13: OA Switchover Settings
Separate Boiler
If the system has a boiler feeding directly into the serviced loop and
bypassing a buffer tank the Separate Boiler option can be enabled. The system
will maintain a buffer tank as explained in the buffer tank sections of this
document using the chiller as the source until the OAT drops to or below the
setpoint (40°F default). Once below that SP the boiler services any calls for
heat, while the chiller would still service any calls for cool. Zones are
serviced on a first come first served basis. Buffer override and buffer bypass
are disabled until the OAT rises above the SP. When the OAT is below the
setpoint and there is a call for heat, the system pump is disabled regardless
of the pump setting.
S| e| t| | O| A| | S| w| i| t| c| h| o| v| e| r| | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
T| e| m| p| e| r| a| t| u| r| e| | | | | | | | |
| | | | | | | | | | →| 4| 0| °| F| | | |
| | | | | | | | | | | | | | | | | | |
Figure 14: Separate Boiler Settings
Required Sensors: OA
Chiller RV
The user can change the chiller’s reversing valve to be energized in either
Cooling (O) or Heating (B) operation depending on system requirements.
Buffer Tank
All buffer tank options can be found here, including enables, disables, and
temperature settings.
When the buffer tank option is disabled, no other menu options appear on the
buffer tank menu.
→| B| u| f| f| e| r| :| | D| i| s| a| b| l| e| d| | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 15: Buffer disabled
Once the buffer option has been enabled, the Bypass option is shown. Default is enabled. In this case the buffer tank can be used but there are no bypass or override functions available. The buffer tank is always treated as the master and conflicting calls are never serviced.
→| B| u| f| f| e| r| :| | E| n| a| b| l| e| d| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| B| y| p| a| s| s| :| | D| i| s| a| b| l| e| d| | |
| O| v| e| r| r| i| d| e| :| | D| i| s| a| b| l| e| d|
| T| a| n| k| | S| e| t| p| o| i| n| t| s| | | | |
Figure 16: Buffer enabled, bypass disabled (Default)
If the bypass is enabled but override is disabled, the energy saving features of the buffer tank bypass will function but the buffer tank is always treated as the master and conflicting calls are never serviced.
→| B| u| f| f| e| r| :| | E| n| a| b| l| e| d| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| B| y| p| a| s| s| :| | E| n| a| b| l| e| d| | | |
| O| v| e| r| r| i| d| e| :| | D| i| s| a| b| l| e| d|
| T| a| n| k| | S| e| t| p| o| i| n| t| s| | | | |
Figure 17: Buffer and bypass enabled, override disabled
Enabling the bypass and the override opens all options for the buffer tank.
→| B| u| f| f| e| r| :| | E| n| a| b| l| e| d| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| B| y| p| a| s| s| :| | E| n| a| b| l| e| d| | | |
| O| v| e| r| r| i| d| e| :| | E| n| a| b| l| e| d| |
| T| a| n| k| | S| e| t| p| o| i| n| t| s| | | | |
Figure 18: All buffer tank options enabled
Using a buffer tank requires the use of a buffer tank sensor and OA sensor at all times regardless of Boiler/Chiller OP settings.
Tank Setpoints
Temperature setpoints for the buffer tank can be found here. Pressing the UP
or DOWN arrow off the page will scroll to the next page.
→ | H | e | a | t | O | A | S | P | : | 5 | 0 | ° | F | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
H | e | a | t | ( | B | ) | S | P | : | 1 | 6 | 0 | ° | F | |||||
H | e | a | t | ( | C | ) | S | P | : | 1 | 2 | 0 | ° | F | |||||
H | e | a | t | D | i | f | f | : | 1 | 0 | ° | F |
Figure 19: Tank setpoints page 1. Default values shown.
→ | C | o | o | l | O | A | S | P | : | 6 | 5 | ° | F | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
C | o | o | l | T | a | n | k | S | P | : | 4 | 8 | ° | F | |||||
C | o | o | l | D | i | f | f | : | 6 | ° | F | ||||||||
Figure 20: Tank setpoints page 2. Default values shown.
ThinWall
ThinWall unit settings can be found here. Enable any zone that has a ThinWall
fan coil unit. Set the desired OAT switchover temperature and the hysteresis.
Then set the timer.
→| Z| o| n| e| 1| :| | D| i| s| a| b| l| e| d| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| Z| o| n| e| 2| :| | D| i| s| a| b| l| e| d| | | |
| Z| o| n| e| 3| :| | D| i| s| a| b| l| e| d| | | |
| Z| o| n| e| 4| :| | D| i| s| a| b| l| e| d| | | |
→| Z| o| n| e| 5| :| | D| i| s| a| b| l| e| d| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| T| W| | S| e| t| p| o| i| n| t| :| | | | 5| 0| °| F
| T| W| | +| /| –| | | | | | | | | | | 5| °| F
| T| W| | T| i| m| e| r| | | | | | | 1| 5| m| i| n
When the ThinWall unit’s internal thermostat sends a call to the SSIC, the SSIC checks the OAT. If the OAT is above the setpoint, the system will call for cool; below the setpoint, it will call for heat. Once the OAT reaches the setpoint +/- the hysteresis setpoint, the call will switch to the opposite type.
Example using default settings: OAT is 40° when the zone calls. Heat is
provided. OAT rises to 55°, system switches to cooling.
The timer is provided for installations that have 1 or more zones with a
ThinWall unit and 1 or more standard fan control units. If all zones are idle
and a TW zone calls first, the TW zone will set the system mode. If a standard
zone calls for the opposite mode while the TW zone is actively calling, the
timer will start. The TW mode will continue to be serviced until the timer
expires. The system then switches over to service the standard zone. Normal
operation resumes from this point. The timer can be disabled by setting the
value to 0 minutes. If all zones are TW zones, this setting can be ignored.
System Settings
The user can enable or disable any of the following
settings outlined below.
→| P| u| m| p| :| | D| i| s| a| b| l| e| d| | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| H| e| a| t| :| | E| n| a| b| l| e| d| | | | | |
| C| o| o| l| :| | E| n| a| b| l| e| d| | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 21: System settings. Defaults shown.
Pump: Disable or enable the system pump. If enabled, the system pump will
activate alongside any chiller or boiler outputs.
Heat: Disable or enable heating operations. When disabled, all heating calls
are ignored and no heating outputs are generated. When enabled, all heating
operations function as normal.
Cool: Disable or enable cooling operations. When disabled, all cooling calls
are ignored and no cooling outputs are generated. When enabled, all cooling
operations function as normal.
Temperature Units
Select the units in which the temperature is displayed. Pressing the SELECT
key will move the cursor in front the units. The user can use the UP or DOWN
keys to select either Fahrenheit or Celsius. Pressing SELECT will save the
setting, and pressing BACK will restore it to its previous value.
→| T| e| m| p| | U| n| i| t| s| :| | °| F| | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 22: Temperature unit selection
Restore Defaults
This setting allows the user to restore all settings to the factory defaults.
R| E| S| T| O| R| E| | D| E| F| A| U| L| T| S| ?| N| O|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 23: Restore defaults menu
Load Firmware
This setting walks the user through the process of updating new firmware into
the control via a USB drive. USB drives must contain a directory called
“firmware” and have the .hex file in this directory.
- The user will be prompted to insert their USB into the USB terminal.
I| N| S| E| R| T| | U| S| B| | D| R| I| V| E| | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
S| E| L| E| C| T| | T| O| | C| O| N| T| I| N| U| E| |
Figure 24: Update firmware first screen.
- Once the USB drive is in place and the user hits the SELECT key, a brief “PLEASE WAIT…” response will be displayed. After a brief wait, the user will be prompted to select the firmware .hex file they wish to load. Use the UP and DOWN keys to navigate to the file, the SELECT key to select the file, and the BACK key to abort.
F| I| L| E| N| A| M| E| .| H| E| X| | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
B| A| C| K| | S| E| L| | U| P| /| D| O| W| N| | | |
Figure 25: Update firmware second screen.
If no USB drive is inserted the following will be displayed:
N| O| | D| R| I| V| E| | | | | | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
B| A| C| K| | S| E| L| | U| P| /| D| O| W| N| | | |
Figure 26: Update firmware no drive.
If no firmware is found or there is no “firmware” directory, the following will be displayed:
N| O| | F| I| R| M| W| A| R| E| | | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
B| A| C| K| | S| E| L| | U| P| /| D| O| W| N| | | |
Figure 27: Update firmware no firmware.
-
After selecting the file, the user may be asked to select the storage location. If prompted, select storage location
-
This screen is skipped when updating from version 1.2 or later.
S| T| O| R| A| G| E| | L| O| C| A| T| I| O| N| →| 1| |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | -
A loading screen will appear with a number that increases quickly, indicating the process of the file data transfer. After it is complete, a “SAVING FILE” message will appear.
L| O| A| D| I| N| G| :| 0| 1| 2| 3| 4| 5| 6| | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 28: Loading screen
- The “UPDATE ON REBOOT” screen asks the user if they would like to commit to the firmware they just loaded. Pressing the UP or DOWN keys will cycle between the ‘Yes’ and ‘No’ options. If ‘YES’ is selected then the firmware will be loaded into flash and the control will reboot with the new firmware. If ‘NO’ is selected then the new firmware will not be loaded and the user will be returned to the menu screen. This screen is skipped when updating from version 1.2 or later.
U| P| D| A| T| E| | O| N| | R| E| B| O| O| T| ?| N| O|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 29: Reboot option
- A flash screen will appear with a loading bar indicating the progress of the flash process.
F| L| A| S| H| :| F| I| L| E| N| A| M| E| .| H| E| X| |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
█| █| █| █| █| | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Figure 30: Flashing
- After the flash process completes a message will appear indicating that the new firmware has been loaded. The control will then reboot itself with the new firmware. All the settings will return to their defaults.
N| E| W| | F| I| R| M| W| A| R| E| | L| O| A| D| E| D|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | | | | | | |
L| O| A| D| I| N| G| | D| E| F| A| U| L| T| S| | | |
| | | | | | | | | | | | | | | | | | |
Figure 31: Firmware loaded
Variable Descriptions and Defaults
Section| Name| Description| Default Value| Max Value|
Min Value
---|---|---|---|---|---
Boiler Help| Low Temp| Boiler will help the chiller provide heat if the
chiller has not been able to raise the temperature above this value| 80°F|
140°F| 40°F
| Time| Time limit for the boiler to start assisting the chiller provide
heat| 2 min| 100 min| 0 min
OA Switchover| Temp| Outside air temperature value where the system will
switch the heat source| 40°F| 200°F| -10°F
OA Switchover – Separate Boiler| Temp| Outside air temperature value
where the system will switch the heat source| 40°F| 200°F| -10°F
Buffer Tank| Buffer Enable| Enables/disables the buffer tank option|
Enabled| N/A| N/A
| Bypass Enable| Enables/disables the bypass valves| Disabled| N/A| N/A
| Override Enable| Enables/disables the override function| Disabled| N/A| N/A
| Heat OA SP| Buffer tank starts calling for heat if the outside air is below
this value| 50°F| 60°F| 20°F
| Heat (B) SP| Water temperature target for the buffer tank when the boiler
is the heat source| 160°F| 180°F| 50°F
| Heat (C) SP| Water temperature target for the buffer tank when the chiller
is the heat source| 120°F| 140°F| 50°F
| Heat Diff| After reaching the SP the system will allow the temperature to
drop by this value before heating begins again| 10°| 20°| 0°
| Cool OA SP| Buffer tank starts calling for cool if the outside air is above
this value| 65°F| 80°F| -20°F
| Cool Tank SP| Water temperature target for the buffer tank in cooling
mode.| 48°F| 65°F| 35°F
| Cool Diff| After reaching the SP the system will allow the temperature to
rise by this value before cooling begins again| 6°F| 20°F| 0°F
Thin Wall| Zone 1-5 Enables| Enables Thin Wall control for each zone|
Disabled| N/A| N/A
| TW Setpoint| OAT setting that determines if the system will be heating or
cooling when a Thin Wall enabled zone calls| 50°F| 100°F| 0°F
| TW +/-| Hysteresis setting. System will not switch heating/cooling modes
until an OAT of SP+/- is reached| 5°F| 10°F| 1°F
---|---|---|---|---|---
| TW Timer| Timer for preventing the system from potentially getting stuck in
one mode based on TW calls and OAT| 15min| 30min| 1min (0min to
disable timer)
System Settings| Pump Enable| Enables/disables the system pump output|
Disabled| N/A| N/A
| Heat Enable| Enables/disables the heat output| Enabled| N/A| N/A
| Cool Enable| Enables/disables the cool output| Enabled| N/A| N/A
Temperature Units| Temp Units| Switch between F and C| F| N/A| N/A
Condition | Possible cause | Solution |
---|---|---|
Chiller, Boiler or Pump does not respond to call for conditioning. | ||
Disconnected or broken wire. | Physically inspect the condition of the wires |
between the thermostat, air handler and the interface module, and between the interface module and the chiller,
boiler, or pump.
Chiller gives a call for cooling when called upon for heating, or heating when
called upon for cooling.| Reversing Valve Mode is set to the wrong mode.|
Check the Chiller RV and make sure it is set to the right mode Cooling (O) or
Heating (B).
Unit is not working correctly| Settings or wiring could have been installed
incorrectly.| Review all system settings and make sure module is wired
properly.
Sensor error is showing on the LCD| Sensor input is either shorted or open.|
Check sensor wiring and connections
N/A is showing for a temperature| Sensor input is either shorted or open but
the sensor is not required for the current mode.
| Check wiring if the sensor is supposed to be connected, or disregard otherwise.
IN UNITED STATES: 260 NORTH ELM ST. WESTFIELD, MA 01085
800-465-8558 / FAX
413-564-5815
IN CANADA: 7555 TRANMERE DRIVE, MISSISSAUGA, ONTARIO, L5S 1LR
905-670-5888 / FAX
905-670-5782
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>