JUNG 230061SR Switch Actuator Instruction Manual

June 11, 2024
JUNG

JUNG 230061SR Switch Actuator Instruction Manual
JUNG 230061SR Switch Actuator

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire or property damage possible. Please read and follow manual fully. Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains voltage and SELV/PELV together to the device. For parallel connection of several motors to an output it is essential to observe the corresponding instructions of the manufacturers, and to use a cut- off relay if necessary. The motors may be destroyed. Use only Venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct adjustment. Observe the specifications of the motor manufacturers. Device can be damaged. Do not connect any three-phase motors. Device can be damaged. This manual is an integral part of the product, and must remain with the end customer.

Device components

OVERVIEW

  1. Button field for manual operation
  2. Programming button and LED
  3. KNX connection
  4. Status LEDs for outputs
  5. Load connections (relay outputs)

Function

System information
This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite to proper understanding. The function of this device depends upon the software. Detailed information on loadable software and attainable functionality as well as the software itself can be obtained from the manufacturer´s product database. The device can be updated. Firmware can be easily updated with the Jung ETSService App (additional software). The device is KNX Data Secure capable. KNX Data Secure offers protection against manipulation in building automation and can be configured in the ETS project. Detailed specialist knowledge is required. A device certificate, which is attached to the device, is required for safe commissioning. During mounting, the device certificate must be removed from the device and stored securely. Planning, installation and commissioning of the device are carried out with the aid of the ETS, version 5.7.3 and above.

Intended use

  • Switching of electrical loads with potential-free contacts
  • Switching of electrically-driven Venetian blinds, roller shutters, awnings and similar hangings
  • Installation in sub-distribution unit on DIN rail according to DIN EN 60715

Product characteristics

  • Outputs can be operated manually, construction site mode
  • Manual switching between Venetian blind operation and switching operation without commissioning
  • Feedback in manual mode and in bus mode
  • Disabling of individual outputs manually or by bus
  • Status feedback (e. g. wind alarm)
  • KNX Data Secure compatible
  • Updatable with Jung ETS Service App

Characteristics switch operation

  • Operation as NO or NC contacts
  • Feedback function
  • Logic and restraint function
  • Central switching functions with collective feedback
  • Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
  • Scene function
  • Operating hours counter

Characteristics blinds operation

  • Suitable for AC motors 110…230 V
  • Operating modes “Venetian blind with slats”, “Roller shutter/awning”, “Venting louvre/roof window”
  • Blind/shutter position directly controllable
  • Slat position directly controllable
  • Feedback of movement status, blind/shutter position and slat position
  • Forced position through higher-level controller
  • Safety function: 3 independent wind alarms, rain alarm, frost alarm
  • Sun protection function with heating/cooling operation
  • Disabling function (lock-out protection)
  • Scene function

Logic function characteristics

  • Logic gate
  • Transformer (conversion)
  • Disabling element
  • Comparator
  • Limit value switch

Operation

OVERVIEW

  1. Status LEDs for outputs
    ON: Relay output closed
    OFF: Relay output opened
    Flashes slowly: Output in manual mode selected
    Flashes quickly: Output disabled via continuous manual mode

  2. Button ǃ Manual operation

  3. LED ǃ ON: Continuous manual mode active/Flashing: Temporary manual mode active

  4. LED DŽ ON: Relay outputs closed, manual mode active

  5. Button DŽ Short: Switch on, adjust slats or stop Long: Move hanging upwards

  6. Button Short: Switch off, adjust slats or stop Dž Long: Move hanging downwards

  7. LED ON: Relay outputs opened, manual mode active Dž

  8. Button ALL OFF Open all relay outputs, stop driv

In operation with the button field the device distinguishes between a short and a long press.

  • Short: Pressing for less than 1 s
  • Long: Pressing for between 1 and 5 s

In switching operation, the device distinguishes between the “NO contact” and “NC contact” operating modes. The buttons (9 + 10) switch the switching state when actuated: NO contact: Switch on = close relay, Switch off = open relay NC contact: Switch on = open relay, Switch off = close relay The LED (4 + 8 + 11) always indicate the relay state. The LEDs (4) optionally indicate the states of the outputs only temporarily (parameter-dependent)

Operating modes
Bus operation: operation via push-button sensors or other bus devices

  • Temporary manual control: manual control locally with keypad, automatic return to bus control
  • Continuous manual mode: Exclusively manual operation on the device
    No bus operation is possible in manual mode.
    After a bus failure and restoration the device switches to bus operation.
    The manual mode can be disabled in ongoing operation via a bus telegram.

Switching on temporary manual operation mode
Operation is not disabled.

  • Press button ǃ (6) briefly.
    LED ǃ (7) flashes, LEDs A1… (4) of the first configured output or output pair flash. Short-time manual operation is switched on. After 5 s without a button actuation, the actuator returns automatically to bus operation.

Switching off temporary manual operation mode
The device is in short-term manual mode.

  • No button-press for 5 s.
    – or –

  • Press ǃ (6) button briefly as many time as necessary until the actuator leaves the short-time manual mode. Status LEDs A1… (4) no longer flash, but rather indicate the relay status. Short-time manual operation is switched off. Switching outputs: depending on the programming, the output relays switch to the position that is active after the manual mode is switched off, e.g. logic function. Blind/shutter outputs: depending on the programming, the hangings move to the position that is active after the manual mode is switched off, e.g. to safety or sun protection position.

Switching on permanent manual operation mode
Operation is not disabled.

  • Press the ǃ (6) button for at least 5 s. LED ǃ (7) lights up, LEDs A1… (4) of the first configured output or output pair flash. Continuous manual mode is switched on.

Switching off permanent manual operation mode
The device is in continuous manual mode.

  • Press the ǃ (6) button for at least 5 s. LED ǃ (7) is off.

Continuous manual mode is switched off. Bus operation is switched on. Switching outputs: depending on the programming, the output relays switch to the position that is active after the manual mode is switched off, e.g. logic function. Blind/shutter outputs: depending on the programming, the hangings move to the position that is active after the manual mode is switched off, e.g. to safety or sun protection position.

Operating an output in manual mode

  • Activate short-term or permanent manual operation.
  • Press button ǃ (1) repeatedly until LED A1… (4) of the desired output or output pair flashes.
  • Press button DŽ (9) or Dž (10). Short: Switch on/off, drive stop. Long: Move blind/shutter upwards/downwards.
    LED (3) ON: Relay output closed
    LED (6) OFF: Relay output opened
    Short-term manual mode: After running through all of the outputs the device exits manual mode after another brief actuation.

Switching off all outputs / Stopping all hangings
The device is in permanent manual operation mode.

  • Press the ALL OFF button (7). Switching outputs: All outputs switch off (NO operating mode: relay output opened/NC operating mode: relay output closed). Venetian blind outputs: All blinds/shutters stop.

Disabling outputs
The device is in continuous manual mode. The bus control can be disabled (ETS parameter).

  • Press button ǃ (6) repeatedly until LED A1… (4) of the desired output or output pair flashes.
  • Press the DŽ (9) and Dž (10) buttons simultaneously for approx. 5 s. Selected output is disabled. The status LED A1… (4) of the selected output or output pair flashes quickly

Re-enabling outputs
The device is in continuous manual mode. One or more outputs were disabled in manual mode.

  • Press button ǃ (6) repeatedly until the output to be unlocked or the output pair is selected.
  • Press the DŽ (9) and Dž (10) buttons simultaneously for approx. 5 s.

Switching between Venetian blind and switching operation

Device is not in operation

  • Activate permanent manual operation.
  • Press button ǃ (1) repeatedly until LED A1… (8) of the desired output or output pair flashes.
  • Press the ǃ (1) and DŽ (4) and Dž (5) buttons simultaneously for approx. 5 s. Switching operation: Both status LEDs A1… (8) of the output pair light up. Venetian blind operation: Both status LEDs A1… (8) of the output pair flash alternately.
  • Press the DŽ (4) and Dž (5) buttons simultaneously. Outputs switch between switching operation and Venetian blind operation. Both status LEDs A1… (8) indicate the current operating mode.
  • Press the ǃ (1) and DŽ (4) and Dž (5) buttons simultaneously for approx. 5 s. Operating mode switchover is terminated, permanent manual operation mode is activated.
  • Press the ǃ button (1) for approx. 5 s. Operating mode switchover is terminated, permanent manual operation mode is deactivated.

Information for electrically skilled persons

DANGER!
Mortal danger of electric shock. Disconnect the device. Cover up live parts.

Mounting and electrical connection Mounting the device In secure operation (preconditions):

  • Secure commissioning is activated in the ETS.
  • Device certificate entered/scanned or added to the ETS project. A high resolution camera should be used to scan the QR code.

Observe ambient temperature. Ensure adequate cooling.

  • Mount device on DIN rail.
  • In secure operation: The device certificate must be removed from the device and stored securely.

Connecting the device

Connecting the device

  • Connect bus line with KNX device connection terminal observing the correct polarity.
  • Attach the cover cap to the KNX connection as protection against hazardous voltages.
  • Connect load as shown in the connection example. Two adjacent relay outputs form a Venetian blind output.
    The total current capacity of neighbouring outputs is a maximum of 20 A

Current capacity
Image 4: Total current capacity of neighbouring outputs

Commissioning

NOTICE!
Incorrect load control due to undefined relay state at delivery. Risk of destruction of connected drive motors. During commissioning, before switching on the load, ensure that all relay contacts are open by applying the KNX bus voltage. Observe commissioning sequence!

  • Switch on the KNX bus voltage.
  • Wait about 10 s.
  • Switch on load circuits.
    Delivery state: The outputs can be operated with manual control. Outputs are set as Venetian blind outputs

Device label

Load physical address and application program

  • For switched loads, configure the outputs as a switching output.
  • For Venetian blind operation, configure the outputs as a Venetian blind output.
  • In Venetian blind operation: measure blind/shutter and slat travel times and enter them in the parameter setting.
  • Press the programming button. The programming LED lights up.
  • Load physical address and application program using the ETS.

Safe-state mode
The safe-state mode stops the execution of the loaded application program. Only the system software of the device is still functional. ETS diagnosis functions and programming of the device are possible. Manual operation is not possible.

Activating safe-state mode

  • Switch off the bus voltage or remove the KNX device connection terminal.
  • Wait about 15 s.
  • Press and hold down the programming button.

Deactivating safe-state mode
Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.

Master reset
The master reset restores the basic device settings (physical address 15.15.255, firmware remains in place). The device must then be recommissioned with the ETS. Manual operation is possible. In secure operation: A master reset deactivates device security. The device can then be recommissioned with the device certificate.

Technical data

Ambient conditions
Ambient temperature -5 … +45 °C
Storage/transport temperature – 25 … +70 °C
KNX
KNX medium TP256
Commissioning mode S-mode
Rated voltage KNX DC 21 … 32 V SELV

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.