KERBL 223582 Heating Cable 230V 1m,16W Instruction Manual

June 11, 2024
KERBL

KERBL logo 223582 Heating Cable 230V 1m,16W
Instruction Manual
KERBL 223582 Heating Cable 230V
1m,16W

Frost protection heating cable for pipelines

223582 Heating Cable 230V 1m,16W

KERBL 223582 Heating Cable 230V 1m,16W - figDo not cross overKERBL 223582 Heating Cable 230V 1m,16W - fig
1Do not insert the heating cable rolled up!KERBL 223582
Heating Cable 230V 1m,16W - fig 2Plastic pipeKERBL 223582 Heating Cable 230V 1m,16W - fig
3Do not wind too tightly!KERBL 223582 Heating Cable 230V
1m,16W - fig 3

Installation instructions frost protection heating cable for pipelines
Please read these instructions carefully before installation and use.
Damage caused by not following the instructions is excluded from any liability and warranty.

Safety instructions

Caution!
Risk of physical injury to people and animals and material damage if used incorrectly!

  • Proper connection and installation should only be carried out by a qualified electrician! Please note the relevant VDE (Association of German Electrical Engineers) regulations!

Fig. 1 – symbol on product

  • Fire hazard! To prevent fires, the heating cable should be kept at least 13 mm away from all flammable materials.

  • Fire hazard! Only non-flammable pipe insulation must be used. (Fig. 11)

  • The heating cable connection must be at a 230 V socket with protective contact. This must be protected with a B10 A or B16 A MCB.
    A separate 30 mA RCD circuit breaker should also be provided. A combined RCD/MCB with adequate tripping characteristic may be used. The RCD circuit breaker must only supply the circuits intended for the heating cable.

  • The RCD in the distribution board, in sub-distribution boards and the socket or junction box must also each be labelled with a sticker bearing warning signs and indicating the precise mounting location of the heating cable.

  • The circuits used to operate a heating cable must be clearly marked in the schematic and the fuse list.

  • Regularly check the functioning of the RCD using the function key.

  • Never form kinks in the heating cable. If the minimum bending radius of Rmin = 20 mm is undercut, the heating cable may no longer be installed and must be disposed of. (Fig. 1)

  • This device can be used by children 8 years of age and older and by individuals with impaired physical, sensory or mental abilities or those with insufficient experience and knowledge to do so, if they are being supervised or have been trained on the safe use of the device and understand the underlying hazards. Children may not play with the device. Cleaning and user maintenance may not be performed by children without supervision.

  • The frost protection heating cable jacket is only designed for contact with water and may not come into contact with chemicals, acids and alkalis.

  • Before laying, the heating cable should be checked for any transit damage, general damage, cracks or discolourations in the heating cable jacket and across the entire device.

  • Damaged heating cables may no longer be installed or connected to the mains.

  • Check the voltage and performance of the heating cable on the type plate.

  • The plug (230 V) may not be connected to the mains during installation.

  • The heating cable must not be shortened and is ready to operate as supplied. It must also not be otherwise altered. (Fig. 2)

  • The selected heating cable must not be 600 mm shorter or longer than the tube section to be heated. Excess length should be wrapped around the pipe at the end section with a minimum distance of 50 mm. (Fig. 8)

  • Any attempt to change the heating cable physically will invalidate the warranty. If the heating cable is cut, it can no longer be repaired.

  • No extension cord can be used in conjunction with the device.

  • The heating cable must not be in contact with itself or second heating cable at any point. (Fig. 3)

  • The thermostat should be placed at the coldest point and out of direct sunlight. The thermostat should not be permanently in water. The access line must not be in water or in direct sunlight. Do not affix the heating cable with adhesive tape where the adhesive has an aggressive effect.

  • Avoid damaging the heating cable through sharp edges. (Use edge protectors.)

  • The mains plug must only be used in dry spaces.

  • Do not lay the heating cable twisted.

  • Do not lay the heating cable along building parts that are heated, hot or separately heated (e.g. chimneys, hot pipes).

  • Never install the heating cable in walls, floors or ceilings.

  • The cable and its connections to the thermostat and power cord must not be exposed to tensile, compressive or torsional stresses.
    Never separate, open or damage the system by force, as this can compromise the device’s functioning and invalidate the warranty.
    The IP X7 (waterproof) protection class would also no longer be guaranteed.

  • For safety reasons, metal pipes, protective tubes and sheathing must be earthed before installation. Ensure every metal part is  earthed before beginning installation. The entire system must be checked for consistency and any necessary additional earthing connection must be created.

  • Do not install the same heating cable simultaneously on different pipes. This could cause the heating cable to overheat and lead to fire or electric shock.

  • Never install the heating cable on a plastic pipe unless it is ensured that the pipe is always filled with water.

  • If the heating cable is to be used to keep a plastic water pipe free from frost, the plastic water pipe must be completely wrapped with an aluminium adhesive tape (Kerbl item no.: 222809) before installation and must only be used on temperature resistant water pipes approved for hot water. (Fig. 5)

  • The heating cable and the entire unit are maintenance-free but should still be regularly visually checked, at least once a year. In the case of visible damage or wear (cracks, cuts, deformation, fragility, charred spots or discolouration) to the insulation, the entire heating cable must be replaced.

  • Disconnect the heating cable from the mains before starting a visual check.

  • If the fuse (RCD) of the heating cable has tripped, the fuse must not be reset until the cause has been identified and the entire device and the installation checked for potential damage or wear by a qualified electrician.

  • The heating cable must not be installed at outside temperatures of < +5 °C.

  • If the heating cable becomes stiff (due to cold), then it should be unwound and connected for a few minutes until it becomes warm and pliable, before it can be installed.

  • Never connect the heating cable to the power supply when it is still wound up. (Fig. 4)

  • The heating cable and the power cable must be protected from damage and wear, e.g. through nibbling animals, ice, icicles, mechanical stress etc..

  • Do not staple, nail or otherwise affix the cable using unsuitable materials.

  • The heating cable must not be connected outside of the heating cable (unplug it).

  • The insulation must be no thicker than 13 mm. Inordinate insulation of the heating cable leads to overheating. You must ensure that the insulation is not flammable. (Fig. 9 and 11)

  • The power supply cord of this device cannot be replaced. The device must be discarded if the power supply cord becomes damaged.

  • Please observe these safety notes and warnings. Retain the safety notes and warnings for later extension or monitoring of the cable installation and give the instructions to the person responsible for the regular visual inspections.

Description

2.1 Construction
This frost protection heating cable consists of a resistance heating element (heating cable), thermostat and power cable. The metallic jacket provides additional mechanical strength and the connection to the earthing.
A thermostat, built-in to regulate temperature, is between the thermistor and heating cable.
2.2 Correct use
The frost protection heating cable must only be used to keep metal cold water pipes and temperature-resistance plastic up to a diameter of 40 mm free from frost. The heating cable should be installed flat to the underside of the pipe.
The regulations and safety instructions set out in these operating instructions must be complied with. Use of the cable in any other area shall be deemed incorrect use. The manufacturer accepts no liability for any resulting physical and/or material damage.
This user guide is also available to download on www.kerbl.com.
2.3 Technical data

Article number / type designation DCHK-001 — DCHK-049
Voltage 230 VAC / 50 Hz
Power 16 W/m
Protection class
Protection class IPX7
Connector cable length 2 meters
Heating cable outer diameter Approx. 0 5.0 mm (width 12.5 mm)
Shield Two parallel heating conductors, each individually shielded by a bare

copper braid
Coat| PVC
Heating cable mechanical strength class as per IEC 60800| M1
Minimum bending radius| Rin = 20 mm
Minimum installation temperature| >= +5 °C

2.4 Function
The heating cable has an automatic thermostat that switches the heating cable on when it detects a temperature of approx. +3 °C and switches it off again when it detects a temperature of approx. +13 °C. (Fig. 12)

Installation and commissioning

Prepare the pipe and heating cable:

  1. ensure that the area around the pipeline is easily accessible and there are no sharp edges or flammable materials.
    Danger!
    • Fire hazard! To prevent fires, the heating cable should be kept at least 13 mm away from all flammable materials.

  2. If the heating cable is to be used to keep a plastic water pipe free from frost, the plastic water pipe must be completely wrappedith an aluminium adhesive tape (Kerl item no.: 222809).
    The aluminium adhesive tape improves heat transfer, evenly distributes the heat around the pipe and prevents localized heating, as aluminium is a better heat conductor than plastic. (Fig. 5)
    Danger!
    • The heating cable must only be used on temperature resistant water pipes approved for hot water.
    • Never install the heating cable on a plastic pipe unless it is ensured that the pipe is always filled with water.

  3. Electrically earth all installation metal parts.
    Danger!
    • For safety reasons, metal pipes, guttering, protective tubes and sheathing must be earthed before installation. Ensure every metal part is earthed before beginning installation. The entire system must be checked for consistency and any necessary additional earthing connection must be created.
    • Do not install the same heating cable simultaneously on different pipes. This could cause the heating cable to overheat and lead to fire or electric shock.

  4. Allow the heating cable to warm up to room temperature before beginning the installation.
    Danger!
    • The heating cable must not be installed at outside temperatures of < +5 °C.

  5. The heating cable’s continuity, resistance and insulation resistance must be checked before beginning installation and also after installation, but always before connecting the power cord.
    Important! The resistance value before and after installation must match the value on the product label. A tolerance of + -5 % to +10 % is allowed. The insulation resistance must be more than 10 MOhm. (See: Table 1.) Table 1: Frost protection heating cable — power 16 W / m at 230 VAC

    Type| Length (m)| Watts (W)| Resistance (0) at +20 ° C, (-5 %, +10%)| Current (Amp)
    DCHK-001| 1| 16| 3306| 0.07
    DCHK-002| 2| 32| 1653| 0.14
    DCHK-004| 4| 64| 827| 0.28
    DCHK-005| 5| 80| 662| 0.35
    DCHK-008| 8| 128| 413| 0.56
    DCHK-012| 12| 192| 276| 0.83
    DCHK-014| 14| 224| 236| 0.97
    DCHK-018| 18| 288| 184| 1.25
    DCHK-024| 24| 384| 138| 1.67
    DCHK-036| 36| 576| 91.3| 2.52
    DCHK-037| 37| 592| 89.4| 2.57
    DCHK-049| 49| 784| 68.5| 3.41

  6. Roll out the heating cable and place it on the ground in the way it will be mounted on the pipe later.
    • The heating cable must not be 600 mm shorter or longer than the pipe.
    • Do not lay the heating cable twisted.
    Preparing the power supply:

  7. mount the socket in a protected (indoor) area.
    Danger!
    • The heating cable connection must be at a 230 V socket with protective contact. This must be protected with a B10 A or B16 A MCB. A separate 30 mA RCD circuit breaker should also be provided. A combined RCD/MCB with adequate tripping characteristic may be used. The RCD circuit breaker must only supply the circuits intended for the heating cable.

  8. Form a drip loop with the power cord after the mains socket in order to avoid condensate entering the socket.
    Mount the heating cable and thermostat:

  9. attach the thermostat at the coldest end of the pipe, place the heating cable on the underside of the pipe and affix the heating cable to the pipe in intervals of max. 200 mm using PVC insulating tape. (Fig. 7). The thermostat and the entire heating cable must be in contact with the pipe and fit tightly. The heating cable may not be wound around the pipe. Only any leftover length may be wound around the pipe at the end area.
    Danger!
    • Do not use any straps or metal connectors to fix the heating cable in place.
    • Always use good quality insulation tape (PVC tape) with a temperature resistance of at least 80 °C for mounting. Other adhesive tapes can be deformed by normal cable operating temperatures, potentially leading to overheating, fire or electric shock.
    • If laying the end of the heating cable wrapped around the pipe, the distance between the loops must be at least 50 mm. (Fig. 8)
    • The heating cable must not be in contact with itself or a second heating cable at any point. (Fig. 3)

  10. In order to secure the frost protection in extremely cold weather conditions or to minimize energy consumption, the pipe and the heating cable should be insulated. The pipe / heating cable can be insulated using non-combustible mineral wool or foam insulation (fig. 9). Danger!
    • Fire hazard! Only non-flammable pipe insulation must be used. (Fig. 11)
    • The insulation must be no thicker than 13 mm. Inordinate insulation of the heating cable leads to overheating.
    The insulation mounted on the pipe/heating cable must also be placed over the thermostat in the same thickness. This ensures that the same temperature is maintained in all pipe sections. (Fig. 10)

  11. The insulation must be protected with an additional water-tight sheath which is laid helically over the insulation to prevent moisture ingress.

Operation

Connect the plug to the socket to start operation. Remove the plug from the socket to end operation.

Maintenance and repairs

The heating cable must be checked before every use. The heating cable and the connection to the socket must be inspected for signs of damage and the power supply checked for proper operation. If the heating cable is cut, damaged, has been immersed in water, shows signs of charring or cracking or is damaged in any way, it must no longer be used and should be removed. The heating cable should also be checked for animal bites and invading foreign bodies such as splinters.
The heating cable contains no serviceable parts.
CE-conformity declaration
Albert KERBL GmbH hereby declares that the product / device described in these instructions complies with the fundamental requirements and other relevant stipulations and regulations. The CE mark confirms compliance with the Directives of the European Union. The declaration of conformity can be viewed by visiting www.kerbl.com/artikel/345760
Electronic scrap
Disposing of this device after its service life is the responsibility of the operator. Please consult the valid national regulations. The device must not be disposed of in household waste. In accordance with the stipulations of the EU Directive on the Disposal of Electrical and Electronic Devices, the device can be disposed of free of charge at the local waste collection or recycling centre. Alternatively, it can be returned to retailers who offer a collection service. The proper disposal helps to ensure environmental protection and prevents any adverse effects on human health and the environment.
Control card

Serial number| Check| Before installation| After installation but before connection to the power supply
---|---|---|---
| Perfect working order| |
| Cable resistance in ohms| |
| Insulation resistance in MOhms| |
Installation location (address + description)|
Installation date
Name, address and signature of the installation specialist (stamp and signature)
Ensure that this card is filled out and signed by an authorised electrician and keep it in a safe place.

Kerbl Austria Handels GmbH
Wirtschaftspark 1
9130 Poggersdorf, Austria
Tel.: +43 4224 81555 – 0
Fax: +43 4224 81555 – 629
order@kerbl-austria.at
www.kerbl-austria.at
223582=223585=223586=223587=223588=223590=223589=
223591=223592=223593=BA_Frostschutzkabel_112x160mm

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals