HOLOPHANE HLDMPS Pendant Stem Mount Cylinder Instruction Manual
- June 11, 2024
- HOLOPHANE
Table of Contents
IMPORTANT SAFETY INSTRUCTIONS
HLDMPS – Pendant Stem Mount Cylinders
OCCUPIED SPACES DIRECT IRRADIATION UV EQUIPMENT
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
When using electrical equipment, basic safety precautions should always be
followed including the following:
-
To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
-
Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
-
Installation and service of this equipment should be performed by a qualified licensed electrician.
-
This equipment is designed for use with germicidal UV radiation sources and must be installed in compliance with competent technical directions to prevent risk of personal injury from UV radiation.
-
UV radiation can pose a risk of personal injury. Overexposure can result in damage to eyes and bare skin. To reduce the risk of overexposure this equipment must be installed in accordance with the manufacturer’s site planning recommendations. This may include instructions on the relative location of each germicidal system component, the minimum distances between UV-generating devices and other objects or surfaces, and protection from line-of-sight exposure to UV radiation in occupied spaces located above the equipment mounting area (e. g. upper floor balconies, open staircases, etc.)
-
UV and optical radiation can be reflected by surrounding surfaces such as ceilings and walls. Since the reflective properties of surfaces can vary widely, it should be considered as part of site planning. Follow the manufacturer’s recommendations for selecting appropriate ceiling and wall finishes.
-
IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT PERSONS WILL NOT BE EXPOSED TO EXCESSIVE UV OR OPTICAL RADIATION DURING EQUIPMENT OPERATION. THIS WILL REQUIRE THE INSTALLER TO CONDUCT AN ASSESSMENT OF IRRADIANCE OR ILLUMINANCE LEVELS IN THE SURROUNDING OCCUPIED SPACES PRIOR TO OCCUPANCY.
-
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
-
Maintenance and servicing of this UV generating equipment shall be performed by authorized personnel. Service personnel must wear appropriate Personal Protective Equipment (PPE) if the equipment will be in operation during the maintenance or servicing work. Contact the equipment manufacturer for PPE recommendations and guidance.
-
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
-
Do not use this equipment for other than intended use.
-
Take precautions to ensure that the concentration of ozone in the installation is limited to a value that is within applicable permissible exposure limits.
Verify acceptable ozone concentrations in the installation taking into account the number of products in a given volume of space, the characteristics of the ventilation system, access, and other factors. Permissible exposure limits vary based on the place of ozone application, the length of exposure, and other factors and are publicly available. For reference, the EPA National Ambient Air Quality Standard is 0.070 ppm maximum concentration averaged over 8 hours and current OSHA regulations set an eight-hour time-weighted average permissible exposure limit of 0.10 ppm. The amount of ozone emitted by this equipment does not exceed a concentration of 0.001 ppm over an 8-hour period, as tested in accordance with UL 867. -
Not intended for use with wall switches. Connect to an unswitched circuit intended for 24/7/365 continuous operation.
-
All references to “disinfection” are referring generally to the reduction of pathogenic bioburden and are not intended to refer to any specific definition of the term as may be used for other purposes by the U.S. Food and Drug Administration or the U.S. Environmental Protection Agency. The disinfection technology as incorporated in Acuity Brands products is not for use as a medical device or for the disinfection of medical devices.
-
It is the obligation of the end-user to consult with appropriately qualified Professional Engineer(s), Certified Infection Control professionals, and Certified Industrial Hygienists, as applicable, to determine whether this equipment and its installation meets the applicable requirements for system performance, code compliance, safety, suitability and effectiveness for use in a particular application design. In no event will Acuity Brands Lighting be responsible for any loss resulting from any use of this equipment in an application design.
-
DO NOT INSTALL DAMAGED PRODUCT! This equipment has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after installation should be replaced. Contact the manufacturer for replacement.
-
Follow all disposal laws when replacing or disposing. Excimer lamps do not contain hazardous materials and can be recycled by standard electronics recyclers.
-
Do not install below the minimum height specified in these installation instructions.
-
This equipment, including the lamp modules, must be stored in a dust-free environment and be handled while wearing clean gloves. Since Far-UVC radiation is absorbed by proteins and other organic compounds, accumulation of dust particles or touching of the optical radiation surface will negatively impact the output of the UV radiation source and its germicidal power.
-
Replacement lamp modules must be purchased through Acuity Brands Lighting. Contact Acuity Brands Lighting when module reaches end of life.
-
These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired, or should problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, please contact the Holophane Field Service Department at 740-345-9631.
PRECAUTIONARY STATEMENTS HAZARDS TO HUMANS AND DOMESTIC ANIMALS
WARNING
RISK OF ELECTRIC SHOCK
Disconnect or turn off power before installation or servicing.
Verify that supply voltage is correct by comparing it with the equipment label
information.
Make all electrical and grounded connections in accordance with the National
Electrical Code (NEC) and any applicable local code requirements.
All wiring connections should be capped with UL approved recognized wire
connectors.
CAUTION
RISK OF INJURY
Wear gloves and safety glasses at all times when removing equipment from
carton, installing, servicing or performing maintenance.
Avoid direct eye exposure to the light source while it is on.
CAUTION
OZONE EXPOSURE RISK
This equipment emits UV radiation at wavelengths less than 250 nm which can
generate ozone. Take precautions to ensure that ozone concentration stays
within applicable permissible exposure limits.
WARNING
RISK OF BURN
Allow lamp/fixture to cool before handling. Do not touch hot lens, lamp,
guard, or enclosure.
Follow all lamp manufacturer’s warnings, recommendations and restrictions on
lamp operation including but not limited to: ballast type, burning position,
replacement, and recycling.
CAUTION
RISK OF FIRE
Keep combustible and other materials that can burn away from lamp/lens.
Do not operate in close proximity to persons, combustible materials or
substances affected by heat or drying.
CAUTION
UV EXPOSURE RISKS
Disconnect or turn off power to equipment before performing maintenance or
servicing other elements in the ceiling or space that require closer proximity
than normal standing height away from the equipment.
Skin or eye injury may result from overexposure to the light produced by the
lamp in this equipment at distances less than 24 in. from the emitter.
Emitters used in this equipment are in the EXEMPT RISK GROUP for actinic UV
(200-400nm), near UV (315-400nm), and blue light (300-700nm) hazards, as
described in IEC 62471, when installed and used according to instructions in
this document.
This equipment emits UV radiation which can cause degradation of many
materials. Remove or protect these materials prior to operation of the unit.
Failure to follow any of these instructions could void product warranties
available at
www.acuitybrands.com/support/warranty.
For technical assistance, call
740-345-9631.
Introduction
1.1 Product Description. HLDMPS – Pendant Stem Mount Fixtures
1.2 Mounting Types.
CJB – Canopy over Recessed or Surface Junction Box
CJBSC – Canopy over Surface Junction Box w Conduit Connectors
1.3 Mounting configurations
Figure 1.3
1.4 Parts Identification
Figure 1.4.1: Stem Cylinder Assembly
Figure 1.4.2: Cord Hardware
Figure 1.4.3: Canopy Assembly
Figure 1.4.4: Conduit Keys (CJBSC Only)
1.5 Stems
1.5.1 External and internal threaded ends:
STMHLDMPS internal threads: 1/4-18 NPSM
STMHLDMPS external threads: 3/8-18 NPSM
Figure 1.5.1
1.5.2 External and internal threaded ends: STMHLDMPS internal threads: 1/8-27
NPSM STMHLDMPS internal threads: 1/4-18 NPSM
Figure 1.5.2
1.5.3 Threaded Nipple
Figure 1.5.3
1.6 Stem Assembly
1.6.1 Stem Length Calculation: Calculate the necessary stem length per the
equations below.
1.6.2 If there are multiple sections of stem, assemble them together using the
threaded nipples provided.
Figure 1.6.1
Figure 1.6.2
1.6.3 Cut the assembled stem to the calculated length per Step 2.1.
Figure 1.6.3
1.7 Alternate Information Sources:
Holophane
Field Service Department
P.O. Box 3004
Newark, OH 43058-3004
740-345-9631
Operation
2.1 When line voltage is applied to the luminaire, the Status Indicator LED
should appear as a green solid light. The UV lamp module will remain inactive
for between 11 and 12 minutes. Complete any mechanical adjustments to the
luminaire before applying line voltage, or else ensure that any work on or
near the luminaire that would require any part of the installer to be more
than 7ft off the floor is complete within the first 11 minutes after line
voltage is applied to prevent the installer from receiving a UV dose that is
larger than the recommended amount.
2.2 The UV lamp module will operate on 12-minute cycles, activating for a
duration between 10 and 50 seconds each cycle. The duration will depend on the
Programming Option value in each luminaire’s order nomenclature (e.g.
HLDMPS…D108). Refer to the product spec sheet for guidance in selecting the
correct Programming Option value for each application.
2.3 When activated, the UV module will illuminate with a faint purple glow
(see image below). The Status Indicator LED will remain green whether the UV
module is active or inactive if all self-diagnostics report proper function.
2.4 The Status Indicator LED may reflect additional states throughout the
lifetime of the luminaire. The possible states are as shown below.
2.5 The UV lamp modules are rated for approximately 5 years of life (3000
activated hours). The Status Indicator
LED will change to yellow solid when six months of projected life are left in
the lamp module – order replacement parts and schedule labor accordingly to
ensure continuous operation.
Figure 2
UV Emitter Information
3.1 HIGHEST IRRADIANCE AT 500 mm: 0.51 W/m2
3.2 Use only replacement lamp modules provided by Acuity Brands Lighting. Each
unit has a label listing the correct replacement part to order.
3.3 Minimum height of bottom face of luminaire when installed:
- HLDMPS…D108 = 108 Inch (min) to 113 Inch (max) height from floor to module face
- HLDMPS…D114 = 114 Inch (min) to 119 Inch (max) height from floor to module face
- HLDMPS…D120 = 120 Inch (min) to 125 Inch (max) height from floor to module face
- HLDMPS…D126 = 126 Inch (min) to 131 Inch (max) height from floor to module face
- HLDMPS…D132 = 132 Inch (min) or greater height from floor to module face
Tools and Materials Required
Table 1. Installation Tools and Materials
DESCRIPTION | USE |
---|---|
5/64” Allen Key* | Conduit Key Set Screws |
T-15 Torx Driver | Faceplate & Module Screws |
Phillips Screwdriver | Cover Screws |
3/16” Drill Bit | Stem End Hole |
Conduit Canopy Assembly (CJBSC)
Note: CJBSC mounting type requires a 1.5” depth, 4” octagonal junction
box.
5.1 For CJB option go to Fixture Install (Section 6).
Select the appropriate keys and insert them into the correct canopy slots for
each specific junction box configuration. Adjust set screws in the keys to
allow the keys to slide in completely. Tighten the set screws to secure the
keys in place.
Note: CJBSC mounting type requires a 1.5” depth, 4” octagonal junction
box.
Figure 3
*All measurements in μW/cm² measured at plane 7 ft above floor – 1x1ft grid
**All measurements in mJ/cm² per 8 hours, measured at plane 7 ft above floor –
1x1ft grid. ACGIH guideline for maximum dose is 22.87 mJ/cm² per 8 hours.
Consult Acuity Brands UV Lighting Specialist for layout of multiple-luminaire
installations.
Figure 5.1.1
Figure 5.1.2
5.2 Loosen screws securing the plate to the canopy so the screws can slide
within the slots.
Figure 5.2
5.3 Bring canopy up to junction box (J-box) and insert Jbox screws into key
slots. Rotate the plate attached to the canopy to allow the J-box screws to
slide into the key slots. Tighten the screws that secure the plate to the
canopy. This will secure the canopy to the ceiling for fixture install. Leave
J-box screws loose for fixture install.
Figure 5.3
Fixture Install
6.1 Stem End Hole Drilling for Swivel Ball
6.1.1 Locate the swivel ball and stem that has already been assembled and cut
to length.
Figure 6.1.1
6.1.2 Place swivel ball on the stem end opposite of the external threads.
Figure 6.1.2
6.1.3 Make sure ball is seated on the top of the stem.
Thread screws into each side of the swivel ball to secure it in place before
drilling.
Figure 6.1.3
6.1.4 Using the guide holes in the ball and a drill with a 3/16” drill bit,
drill through both sides of the stem.
Figure 6.1.4
6.1.5 Loosen screws and remove swivel ball from stem for later assembly steps.
Note: Swivel Ball will be secured to the stem in a later step by
tightening screws and engaging them into the holes that were drilled in the
end of the stem.
Figure 6.1.5
6.2 Stem Cylinder Assembly
6.2.1 Unscrew cap from cylinder. Align stem with the cylinder so the external
threads of the stem are closest to the top of the cylinder. Pull the wires
through the stem, then thread it into the cylinder. Leave at least 6” of
wires coming out of the end of the stem.
Note: Set screw may need to be loosened to allow threading in the stem.
Figure 6.2.1
6.2.2 Once the stem has been threaded in fully, tighten the set screw to lock the stem in the cylinder. Then screw on and hand tighten the cap.
Figure 6.2.2
Note:
- CJB mounting type fixtures require a 1.5” minimum depth, 4” octagonal junction box.
- Order Square Junction Box Adapter option (HJBA) if square junction box will be used.
- See step 7 for installation details for HJBA.
- CJBSC mounting type fixtures require a 1.5” depth, 4” octagonal junction box.
- Recessed junction boxes cannot be more than 1/8” proud of the ceiling surface.
6.3 Slide Canopy (1), Mounting Bracket (2), and Swivel Ball (3) onto the end
of the cord in below order.
Note: Rest the Canopy and Mounting Bracket on the top of the cylinder.
Figure 6.3
6.4 Thread screws into swivel ball and align with drilled holes in stem.
Tighten screws so they are engaged through the holes in the stem.
Figure 6.4 6.5 Align swivel ball groove with mounting plate tab as it is
brought up to secure to ceiling.
Figure 6.5
6.6 Bring the fixture up to junction box with the swivel ball seated in the
mounting plate.
Figure 6.6
6.7 Pull stem wires through the multiple triangular cutouts in the mounting
plate. Also pull the corresponding supply wires through each respective
cutout.
Figure 6.7
6.8 Use the keyholes in the mounting bracket to secure it with the junction
box screws. Align screws with the indication marks on the bracket. Adjust as
necessary for fixture alignment. Tighten screws.
Figure 6.8
6.9 After securing mounting plate, make branch circuit connections per below
diagram and push them through the mounting bracket cutouts into the junction
box.
Figure 6.9
6.10 Bring the canopy up to the ceiling and align the spring clips on the canopy with the rectangular cutouts on the bracket. Push the canopy up to the ceiling to snap the clips into the cutouts to secure the canopy.
Figure 6.10.1
Figure 6.10.2
6.11 Once the fixture is installed, remove the protective face cover and
inspect the module glass for cracks or dust and fingerprints, etc. If cracks
are present, DO NOT APPLY POWER, but return the fixture to Acuity Brands
Lighting for a replacement.
6.12 Remove the HLDM Info Label (the lower rectangular portion of the Face
Protector Label) and affix it in a location that will be visible after
installation in a location likely to be discovered by future maintenance
personnel. Suggested locations include: a cover plate near the entrance to the
room containing the HLDM fixture, the electrical panel supplying the
luminaire branch circuit, or a clean, smooth wall near the room entrance.
Figure 6.11
Square Junction Box Adapter (HJBA) Details
7.1 Remove existing junction box screws, then position adapter plate onto
junction box and fasten in place with provided undercut flat head screws.
Figure 7.1
7.2 Install provided pan head screws. Position screw heads approximately 1/4”
off from adapter plate surface.
Figure 7.2
CAUTION: DO NOT USE ABRASIVE
CLEANERS ON THE LENS. THEIR USE MAY RESULT IN DAMAGE.
8.3 If dust or fingerprints are present, clean the glass with a non-abrasive
cleaner. It is recommended that the glass be cleaned periodically to retain
intended UV-C transmission.
Holophane | 3825 Columbus Rd., Granville, OH 43023 | Phone: 866-HOLOPHANE |
www.holophane.com
© 2021 Acuity Brands Lighting, Inc. All rights reserved.
References
- Warranty
- Holophane | Lighting solutions for commercial, industrial, emergency and outdoor applications.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>