FLARE FIREPLACES 50 Front Facing Framing Guidevent Free Wood Framing
Product Information
The Front Facing Framing GuideVent Free- Wood Framing is an outdoor-rated fireplace from the Flare Fireplaces Vent Free line that uses stainless steel, corrosion-resistant materials. It requires a 110V AC (15 AMP dedicated recommended but not required) power source and gas supplied from the right side of the unit. The appliance must be installed on a non-combustible material floor and requires clearances to combustible finishing materials such as ground or another combustible surface, side walls, ceiling, alcove width, and non-combustible board above the opening. The manual gas shut-off is required on all outdoor unit installations.
Product Usage Instructions
- Ensure that the fireplace is installed on a non-combustible material floor with at least an 11-inch clearance from any combustible flooring.
- Provide a 110V AC (15 AMP dedicated recommended but not required) power source to run the fireplace. The electrical connection needs to be provided to the right of the unit and utilize a Ground Fault Circuit Interrupter (GFCI/GFI) outlet required. Ensure a switch is installed to control power to an outlet for control over the fireplace.
- Gas should be run into the right side of the unit. Flex pipe will be provided within the unit, but hard piping should be done into the fireplace box.
- Install a manual gas shut-off that must be visible (after finishing) and remain accessible in the event of an emergency. Consult city, state, and other local codes to confirm additional requirements as needed.
- Maintain Framing clearances to combustible framing from firebox: 2 Sides, 2 Back, 4 Top, and 0 below (Re-enforced Base).
- Ensure that the fireplace has the required clearances from combustible finishing materials such as ground or another combustible surface, side walls, ceiling, alcove width, and the non-combustible board above the opening.
- Plan for drainage to run outside of the cavity away from other fixed buildings and objects.
- Refer to the Installation Manual for all clearances and requirements. Type-X is not acceptable for use in Vent-Free applications.
Unit Dimensions
Model | 50 | 60 | 70 | 80 | 100 |
---|---|---|---|---|---|
A- Inch | 56 13/16 | 65 8/16 | 73 6/16 | 83 10/16 | 101 12/16 |
B- Inch | 52 14/16 | 61 9/16 | 69 7/16 | 79 11/16 | 97 13/16 |
C- Inch | 27 6/16 | 27 6/16 | 27 6/16 | 27 6/16 | 27 6/16 |
D- Inch | 16 | 16 | 16 | 16 | 16 |
Cavity Dimensions and Framing Clearances
Maintain Framing clearances to combustible framing from the firebox:
- 2” Sides 2” Back
- 4” Top 0” below (Re-enforced Base)
X | Y | Z | |
---|---|---|---|
50 | Inch | 60 13/16 | 31 6/16 |
mm | 1545 | 797 | 422 |
60 | Inch | 69 8/16 | 31 6/16 |
mm | 1765 | 797 | 422 |
70 | Inch | 77 6/16 | 31 6/16 |
mm | 1965 | 797 | 422 |
80 | Inch | 87 10/16 | 31 6/16 |
mm | 2226 | 797 | 422 |
100 | Inch | 105 12/16 | 31 6/16 |
mm | 2686 | 797 | 422 |
Appliance Considerations
- Drainage- Flare Fireplaces Vent Free lines are outdoor rated using Stainless Steel, corrosion-resistant materials. However, care should be taken to ensure rain and other moisture cannot collect between the unit and the mounting platform. Plan for drainage to run outside of the cavity away from other fixed buildings and objects.
- Electrical Connection – 110V AC (15 AMP dedicated recommended but not required) power source must be provided to run the fireplace. An electrical connection needs to be provided to the right of the unit and utilize a Ground Fault Circuit Interrupter (GFCI/GFI) outlet is required. Ensure a switch is installed to control power to an outlet for control over the fireplace.
- Gas Supply – Gas should run into the right side of the unit. Flex pipe will be provided within the unit, but hard piping should be done into the fireplace box.
- Manual Gas Shut Off – Required on all outdoor unit installations. The manual Gas Shut off must be visible (after finishing) and remain accessible in the event of an emergency. Consult city, state, and other local codes to confirm additional requirements as needed.
- Clearance to Floor – Flare Ventless line must maintain box opening at least 11” above any combustible flooring. For fireplaces that are considering being mounted lower, flooring must be non-combustible material (i.e. stone, tile, cement, etc.)
Clearance from Combustible Finishing Materials
Index
|
Description
|
Dimension From Opening
---|---|---
A| From the ground or another combustible surface| 11”
B| From side-walls| 6”
C| From ceiling (minimum)| 36”
D| Alcove width (minimum)| Fireplace width plus 12”
E| The non-Combustible board above the opening| 8”
See the Installation Manual for all clearances and requirements. Type-X is not acceptable for use in Vent-Free applications.