Operating

AB-QM 4.0 ChangeOver6 Flexo DN 15, PN16

 MAINTENANCE FREE WARTUNGSFREI

 0 … 90°C

 PN 16

Recommended installing position

The recommended installing position is as shown in the picture. Hairpins from factory setting are inserted based on this position.

In any installed position of the set, assure that hairpins must be inserted sideways or from top to bottom (do not insert the hairpins from bottom side of click fits).

All the connections, fittings and hairpins must be re-tightened after transportation.

For the 18mm straight pipe variant, deburring must be done by customer before installation and it must be ensured that metal chips do not get into the pipe system.

The AB-QM 4.0 CO6 Flexo Set valve must be properly supported. The holes with M5 thread at ChangeOver6 valve can be used for fixing/hanging.

Installation

 Ensure the system can compensate for thermal expansion in the pipes without deformation or twisting of the set.

  • Installation

  • Shut-off / Absperrung

  • SHUT OFF ABSPERRUNG

  • Setting / Einstellung

The 6 ports of the ChangeOver6 valve allow the following flow directions.

| Control Signal from NovoCon: Cooling
---|---
Port 1 to port 2 and port 3 to port 4
| Control Signal from NovoCon: Heating
Port 5 to port 2 and port 3 to port 6
| Heating or cooling distribution pipes
Ports 1, 4, 5 and 6
| Terminal unit pipes
Ports 2 and 3

Sizing

Setting Einstellung DN15 LF DN15
L/h L/s GPM
10% 20 0.006
15% 30 0.008
20% 40 0.011
25% so 0.014
30% 60 0.017
35°/4 70 0.019
40% 80 0.022
45°/4 90 0.025
50% 100 0.028
55°/4 110 0.031
60°/4 120 0.033
65°/4 130 0.036
70% 140 0.039
75°/4 150 0.042
80% 160 0.044
85% 170 0.047
90% 180 0.050
95% 190 0.053
100% 200 0.056

NovoCon® S

When using NovoCon S – no presetting of AB-QM 4.0 valve is needed.

Any Information, including, but not limi ted to Information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data In product manual s, catalogues descriptions, advertisements, etc. and whether made available in writ ing, orally, electronic.ally, online or via download. shall be considered informative, and is only binding if and to the extent. explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Oanfoss reserves the right to al ter its products without notice. This also appl ies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/Sor Danfoss group companies. Danfoss and t he Danfoss logo are t rademarks of Danfoss A/S. All rights reserved.

Customer Support

Danfoss A/S
Climate Solutions
danfoss.com
+45 7488 2222

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals