Altronix 6062 Multi-Purpose Timer Instructions

June 4, 2024
Altronix

Altronix 6062 Multi-Purpose Timer

Altronix-6062-Multi-Purpose-Timer

Overview:

Model 6062 programmable timer is suitable for many functions that require a timed operation e.g. Access Control Applications, Siren/Bell Cut Off Module, Dialer Delay, Guard Tour Supervisory Timer, etc. Some optional functions include: One Shot, Delayed Release, Delayed Operate, Delayed Pulse and Pulser/Flasher. A new feature has been added which provides a momentary relay acti-vation at the end of a desired timing cycle. This feature eliminates the need for having to use two (2) timers to achieve this function.

Specifications:

  • Input: 12VDC or 24VDC operation is selectable.
  • Current Draw:   Stand-by: 3mA, Relay energized: 40mA.
  • Relay:
    • Selectable relay activation at the start or end of the timing cycle.
    • One (1) second momentary relay activation at the end of the timing cycle (eliminates the need to use two (2) timers for this function).
  • Visual Indicators: LED indicates relay is energized.
  • Electrical:
    Operating temperature: -20º C to 49º C ambient.

Features:

  • Triggers via positive DC (+) voltage, dry contact closure, or removal of contact closure.
  • Quick and extremely accurate time range adjustment from 1 second to 60 minutes.
  • Built-in reset feature that cancels timing cycle.
  • Repeat (flasher/pulse) mode.

Mechanical:

  • Snap Trac compatible (order Altronix model #ST3).
  • Board Dimensions (L x W x H approx.): 3” x 2.5” x 0.75” (76.2mm x 63.5mm x 19.05mm).
  • Product weight (approx.): 0.1 lb. (0.05 kg).
  • Shipping weight (approx.): 0.15 lb. (0.07 kg).

Installation Instructions:

  1. Mount 6062 in desired location/enclosure.
  2. Set proper DC Input Voltage DIP Switch 3: 12VDC ON, 24VDC OFF.
  3. Refer to DIP Switch Selection and Jumper Selection Tables for desired functions (e.g.: Timing, Trigger, Pulse)
  4. Measure DC input voltage before powering device to ensure proper operation.
  5. Refer to Terminal Identification Table and Typical Applications fig. 1 through fig. 8. for desired wiring connections. Note: When triggering via a N.O. (normally open), momentary or maintained trigger, connect the dry contact trigger to Pos (+) and TRG terminals. When triggering via a N.C. (normally closed), momentary or maintained trigger, connect the trigger to Neg. (–) and TRG terminals and install a resistor [for 12VDC – 2K (2,000 ohm) or for 24VDC – 4.7K (4,700 ohm)] between the Pos (+) and TRG terminals (Fig. 8).
  6. Enable the reset features:
    Cut J3 when power is removed the timer will reset and not re-trigger when power is restored unless a new trigger is applied. Note: The closed trigger and delayed pulse options will not operate if the reset feature is desired.

DIP Switch Selection Table:

DIP # Off On
1 Relay energizes at the start of timing cycle.* Relay energizes at the end

of timing cycle.*
2| 1-60 Minutes timing range (trimpot adjustable).| 1-60 Seconds timing range (trimpot adjustable).
3| 24VDC operating voltage.| 12VDC operating voltage.
4| Timing begins immediately upon trigger input.| Timing starts after removal of trigger input.

Jumper Selection Table:

Number Function/Description
J1 Cutting J1 selects the pulser/flasher mode.

Relay will flip ON and OFF continuously in equally set timed intervals when timer is powered up.

J2| Cutting J2 puts timer in delayed output mode.

Relay will pulse for 1 second at the end of a preset timing cycle. *DIP Switch 1 must be ON for this function.

J3| 6062 will go through an initial timing cycle when first powered up unless J3 is cut. If J3 is cut, timing can only be initiated via TRG terminal.

Terminal Identification:

Terminal Legend Function/Description
TRG Applying a positive voltage will activate timing cycle.

Trigger voltage range: 7-12VDC at 12 volt setting, 15-24VDC at 24 volt setting.

– , +| Connect 12 or 24VDC filtered and regulated voltage. Refer to DIP Switch Selection Table for voltage setting.
N.O., C, N.C.| Dry form “C” relay contacts are rated 8A at 120VAC/28VDC.

6062 Typical Applications:

Fig. 1 – Timed Door Annunciator:

For this application Switch #1 and Switch #4 should be in the OFF position.

Fig. 2 – Guard Tour Supervisory Timer:

For this application Switch #1 and Switch #4 should be in the OFF position.

Fig. 3 – Swinger Eliminator:

For this application Switch #1 should be in the OFF position and Switch #4 should be in the ON position.

Fig. 4 – Delay Timer:
Use for Door Ajar Alarm, Delayed Activation of Digital Dialer, Defrost Cycle Timer, etc…

For this application Switch #1 should be in the ON position and Switch #4 is not used in this application.
Altronix is not responsible for any typographical errors.

Fig. 5 – Timed Door Strike:

For this application Switch #1 should be in the OFF position and Switch #4 should be in the ON position.

Fig. 6 – Timed Shunt for a Door: Use to bypass alarm contacts.

For this application Switch #1 should be in the OFF position and Switch #4 should be in the ON position.

Fig. 7 – Bell Cut Off Timer:

For this application Switch #1 should be in the ON position and Switch #4 is not used in this application.

Fig. 8 – Closed Circuit Trigger Option:

For this application a resistor [for 12VDC – 2K (2,000 Ohm) or for 24VDC – 4.7K (4,700 Ohm)] must be installed as shown (resistor not supplied).

Contact US

140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com
e-mail: info@altronix.com
Lifetime Warranty
II6062 – Rev. 032211

Read User Manual Online (PDF format)