INSPECTUSA 50215 4-In-1 Multi Function Detector Instruction Manual

June 9, 2024
INSPECTUSA

INSPECTUSA 50215 4-In-1 Multi Function Detector Instruction Manual

SONIN INC.
© 2006 SONIN Inc. All Rights Reserved
Printed in China

INTRODUCTION

Thank you for choosing a SONIN 4-IN-I Multi Function Detector.
Your detector is recommended for INDOOR use only. To ensure proper use of this product and to obtain optimum performance, be sure to read this manual carefully before use.

INTRODUCTION
The Sonin 4-IN-I Multi Function Detector is a microprocessor based instrument. The functions include moisture measurement for hard or soft wood, plaster, carpet and more to determine the extent of moisture. Detects and locates studs, live AC voltage and metal behind walls.

PRODUCT FEATURES

  • Measure moisture levels present in wood, sheetrock, carpet & more from 8 to 22%.
  • Detects and locates studs, voltage and metal from behind walls.
  • Automatic calibration to ensure the accuracy for the measuring object.
  • Fast, accurate and easy to read LED display with buzzer sound.
  • Low Battery warning.

Important Note: The sensitivity of Stud, Voltage and Meta/ detection in this product is designed for use on dry interior walls only (wood or plaster board); it is not suitable for use with  concrete.

DESCRIPTION OF PRODUCT

FIG 1 DESCRIPTION OF PRODUCT

BATTERY INSTALLATION

  1. Open the battery compartment door on the rear of unit.
  2. Install a fresh 9V alkaline battery and push the clip firmly  in place.
  3. Put battery back into the battery compartment then close the battery door.

DETECTING MOISTURE

  1. Set the function switch to LMoistureJ mode.

  2. Remove the protective cover on the end of unit.  L Caution: probes are sharp and could cause injury if mishandled – do not attempt to plug probes into electrical  outlets I

  3. Insert the test probes about 1/8″ into the target object (such
    as wood or plasterboard) to be tested.

  4. Then, press and hold the LTESTI button, the green LPOWERJ  indicator will light up and the LED display will show the measuring result between 8-22%.

WARNING AND SAFETY NOTICE:
DO NOT plug the moisture test probes into any electrical  receptacle. The test probes are for moisture measurement as  indicated above only.

Helpful Hints:

  1. If only the IPOWERI indicator lights up when taking a  1  moisture reading, this indicates that the moisture level is  lower than 8%. If the result is in the green area (8-12%)  means that is safe, in yellow (14-16%) it may need attention,  in red (18-22% or over) you may need to take action.
  2. You can use your hand, wet cloth or any conductive material  to touch the test probes to check the detector before use.
  3. It may affect the reading if the measuring surface is covered by paint, waterproof coating or any insulating materials etc.

IMPCRTANT: Abnormally high readings may be caused by  surface salts on newly plastered walls or by contact with metal  or steel reinforcing bars, etc. behind a particular surface. (Note:  the moisture measurement is based on the impedance of an  object, any conductive body or metallic materials will affect  the measurement result).

DETECTING STUDS

  1. Set the function switch to LStudl mode.
  2. Hold the detector on the surface (wall) where you want to locate a stud.
  3. Press and hold the LTESTJ button. The green IPOWERI indicator and the tStudJ indicator light up for one second and the unit will click. This indicates the detector is ready for use.
  4. While holding down the LTESTI button, move the detector, fabric side down, slowly across the surface in a straight line. When a stud is detected, the tStudl indicator will light  up and a “beep” sounds.
  5. Slowly move the detector in same direction until over the  stud, and then move back again to find out the center line  of stud.

Helpful Hints:

  1. Repeat 2-3 times from different positions to ensure the result is correct.
  2. The detector may not respond when you start detection at a stud, if so, you can move to another position then try again.
  3. When using the Sonin 4-IN-I Multi Function Detector to  locate a wood or metal stud, it is recommended to be used  at 30-60% relative humidity.
  4. You can also use the metal detection to locate metal studs.

IMPORTANT: The detection may fail or indicate a wrong  result in the following cases:

  1. Relative humidity is greater than 80% or the surface is too  wet.
  2. The maximum depth is greater than 2″ (50mm).
  3. Some metals or high density objects disturb the detection, such as pipes, cables or screws etc.

DETECTING VOLTAGE

  1. Set the function switch to LVoltageJ mode.
  2. Press and hold the LTESTJ button away from the wall or any electrical equipments, the green LPOWERI indicator and the Voltagel indicator will light up for one second and the unit will click. This indicates that the detector is ready for use.
  3. Hold the detector, fabric side on the surface (wall, receptacle, or switch, etc.) where you want to locate live AC wire.
  4. While holding down the ETESTJ button, slowly move the detector across the surface, the LVoItageJ indicator will light up and the unit will beep when in proximity of a live wire.

WARNING AND SAFETY NOTICE:
Shielded, dead or non-powered wires or live wires in metal conduits or casings, thick or concrete walls, will not be detected.

To avoid electric shock and damage of wires, remember always turn off the AC power and be careful when working near electrical wiring.

Some factors could affect your readings, such as the maximum measuring range (depth), the thickness of wall, the wall’s material and conditions, and the interferential environment etc, causing incorrect results or scanned position for wire. Therefore, you should always be careful and turn off the AC power before drilling, nailing or cutting in walls, ceilings and floors.

DO NOT plug the moisture test probes into any electrical receptacle. The test probes are for moisture measurement only.

DETECTING METAL

  1. Set the function switch to LMetalJ mode.
  2. Press and hold the LTESTI button away from any metallic objects, the green LPOWERI indicator and the MetalJ indicator will light up and the unit will click. This indicates that the detector is ready for use.
  3. While holding down the LTESTI button, slowly move the detector, fabric side down, across the surface where you want to locate metal pipes or studs.
  4. The Metall indicator will light up and the unit will beep once it locates metal behind the wall.

Note: The metal detection is only to detect metal behind walls, ceilings and floors within 2″ (50 mm); it is not suitable for locating steel reinforcing bar inside concrete walls.

TECHNICAL SPECIFICATIONS

FIG 2 TECHNICAL SPECIFICATIONS

LOW BATTERY WARNING

The POWER indicator will light up in green when you press the [TEST] button in any mode. If the color changes to red, replace the battery.

https://manuals.plus/wp-admin/post.php?post=835416&action=edit&classic- editor#axzz82MkZb6us

Read More About This Manual & Download PDF:

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

INSPECTUSA User Manuals

Related Manuals