Product Information:

The Space Logic KNX Flush Mounted Universal Dimming Actuator 1g with 3 binary inputs, model number MTN6003-0013, is an electrical device designed to control the dimming and switching of lighting fixtures. The device can be integrated into a KNX network and has three binary inputs for additional control options. The product comes with safety instructions that must be followed to ensure safe installation and operation.

Safety Instructions:

The product must be installed by skilled professionals who have profound knowledge of connecting to installation networks, connecting several electrical devices, laying electric cables, connecting and establishing KNX networks, safety standards, local wiring rules, and regulations. Failure to follow the safety instructions may result in death or serious injury due to electric shock, explosion, or arc flash. Live parts must be covered, and th device must be disconnected before any work is done on it. When connecting the bus/extensions and mains voltage wires in a shared appliance box, the KNX bus line may come into contact with the mains voltage, which endangers the safety of the entire KNX installation. Therefore, bus/extensions and mains voltage terminals must not be placed in a shared connection compartment. Use an appliance box with a fixed partition wall or separate appliance boxes.

Product Usage:

To use the product, connect it to the installation network and integrate it into the KNX network. The device can then be used to control the dimming and switching of lighting fixtures. The three binary inputs can be used for additional control options. Before any work is done on the product, it must be disconnected and live parts must be covered. Follow the safety instructions provided in the manual for safe operation.

About this document

You can find all the information required for safe installation in this document.
For your safety
DANGER!
HAZARD OF ELECTRIC SHOCK, EXPLO-SION, OR ARC FLASH
Safe electrical installation must be carried out only by skilled professionals. Skilled professionals must prove profound know-ledge in the following areas:

  • Connecting to installation networks
  • Connecting several electrical devices
  • Laying electric cables
  • Connecting and establishing KNX networks
  • Safety standards, local wiring rules and regulations
    Failure to follow these instructions will result in death or serious injury.

Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
The device may not be opened or operated outside the technical specifications.
Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load is not electrically isolated from the mains even when the output is switched off.
Danger of electric shock. Make sure during the installation that there is always sufficient insulation between the mains voltage and the bus. A minimum distance of at least 4 mm must be maintained bet-ween bus conductors and mains voltage cores.
Danger of electric shock on the KNX installation. Do not connect any external voltage to the inputs. The device might be damaged, and the SELV potential on the KNX bus line will no longer be available.
Fire hazard. For operation with inductive transformers, each transformer must be fused on the primary side in accordance with the manufacturer’s instructions. Only safety transformers according to EN 61558-2-6 may be used.
Risk of destruction of the dimmer and load if the set operating mode and load type do not match. Set the correct dimming principle before connecting or ex- changing the load.
These instructions are an integral part of the pro-duct, and must remain with the end customer.

Function

Intended use

  • Operating in KNX systems
  • Switching and dimming of lighting
  • Reading in switching states of installation switches or push-buttons and other potential-free contacts at inputs 1…3
  • Acquisition of temperature values via NTC temperature sensor at input 3 (see accessories)
  • Mounting in appliance boxes according to DIN 49073

Information for electrically skilled persons

DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
DANGER!
When connecting the bus/extensions and mains voltage wires in a shared appliance box, the KNX bus line may come into con-tact with the mains voltage.
This endangers the safety of the entire KNX installation. People at remote devices may also receive an electric shock.

  • Do not place bus/extensions and mains voltage terminals in a shared connection compartment. Use an appliance box with a fixed partition wall or separate applian-ce boxes.

Connecting and fitting the device
In secure operation (preconditions):

  • Secure commissioning is activated in the ETS.
  • Device certificate entered/scanned or added to the ETS project. A high resolution camera should be used to scan the QR code.
  • Document all passwords and keep them safe.

Mounting in suitable appliance box (recommendation: electronic device box with partition). Observe cable routing and spacing

  • (5) Appliance box
  • (6) Partition
  • (7) potential-free contacts (e.g. series push-but- ton)
  • (8) NTC temperature sensor (optional)Schneider Electric MTN6003-0013 KNX Flush Mounted 1

Minimum spacing between the mains voltage and bus/extension wires: 4 mmSchneider Electric MTN6003-0013 KNX Flush Mounted 2Observe ambient temperature. Ensure adequate cooling.

  • Connect the device to KNX with the correct polarity.
  • Connect load as shown in the connection example.Schneider Electric MTN6003-0013 KNX Flush Mounted 3
  • If required, connect potential-free contacts to inputs 1…3, or NTC temperature sensors to in-put 3 .Schneider Electric MTN6003-0013 KNX Flush Mounted 4
  • Install the device in the appliance box.
  • In secure operation: The device certificate must be removed from the device and stored securely.
    The COM reference potential must not be connected together with COM connections of other devices!

Technical data

Ambient conditions

  • Rated voltage                                      AC 230 V~
  • Mains frequency                                 50 / 60 Hz
  • Power loss max.                                  1.5 W
  • Standby power approx.                       0.2 W
  • Ambient temperature                         -5 … +45 °C
  • Storage/transport temperature          -25 … +70 °C
  • Dimensions (W × H × D)                48 x 50 x 28 mm

KNX

  • KNX medium                                TP256
  • Commissioning mode                    S-mode
  • Rated voltage KNX                       DC 21 … 32 V SELV
  • Current consumption KNX          5 … 18 mA
  • Connection mode KNX                Connection terminal on control cable

Output

  • Connection mode                        Screw terminals
  • Rated voltage                              AC 230 / 240 V ~

Connected load depends on the connected lamps and set load type: Schneider
Electric MTN6003-0013 KNX Flush Mounted 5
Schneider Electric MTN6003-0013 KNX Flush Mounted 6UNI
ETS parameter load type universal (with automatic calibration procedure) conv. transformer (inductive / leading edge phase control)
LED
LED (leading edge phase control) electr. transformer (capacitive / trailing edge phase control)
LED (trailing edge phase control)

Power reduction

  • when installed in wooden or dry construction walls      -15%
  • when installed in multiple combinations                        -20%

Clampable conductor cross-section

  • Connection torque screw terminals                          Max. 0.8 Nm

Inputs

  • Control cable (pregerminated)                                   YY6x0.6
  • Input type                                                                  Potential-free
  • Number                                                                     3
  • Total length of extension device cable                      max. 10 m
  • Cable type (preferably)                                              J-Y(St)Y
  • Poll voltage, extension inputs                                    approx. 5 V

Accessories

Remote sensor for room temperature measurement            MTN616790
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Centre in your country.
se.com/contact