Jean Muller T500113002 NH Fuse Switch Disconnector Size 00 3 Pole Design Baseplate Mounting User Manual
- June 15, 2024
- Jean Muller
Table of Contents
Jean Muller T500113002 NH Fuse Switch Disconnector Size 00 3 Pole Design
Baseplate Mounting
Product Information
- The NH-fuse-switch-disconnector is a 3-pole design device that is used for disconnecting power and protecting against hazardous voltage.
- It is designed for baseplate mounting and is categorized as Size 00.
- The product should only be installed and operated by electrotechnically qualified personnel.
- Laymen should not attempt to install or operate the device due to the potential risks involved.
Product Usage Instructions
- Before proceeding:
- Before proceeding with any work on the equipment, make sure to disconnect the power to avoid electrical shock and burns.
- Only apply fuse links with silver-plated contacts or silver-plated solid links.
- Assembling:
- Insert the fuse-link into the device.
- Switch on the device to activate it.
- Disassembling:
- Switch off the device.
- Remove the fuse link from the device.
- Place the device in the parking position.
- Accessory:
- The device can be fixed to a DIN rail using the provided accessory (A).
- Note: For more detailed instructions and safety precautions, please refer to the complete user manual.
Warning
- Hazardous voltage! Can cause electrical shock and burns.
- Disconnect power before proceeding with any work on this equipment.
Advice
- The product described in this operating manual may be installed only by electrotechnically qualified personnel.
- “Laymen” must not install or operate because they cannot foresee the possible consequences of their actions.
ASSEMBLING
Disassembling
Attention!
Only apply fuse-links with silver-plated contacts or silver-plated solid
links.
CONNECTING
- Switch-off (1): Removal of fuse-link (2), parking position (3)
- Accessory (C): Micro-switch for indication of switch-position
- Accessory (D): Micro-switch for mechanical fuse-monitorung
- Voltage test
- Accessory (E): Locking device Sealing (1)
Power theft protection
Connection: Connection of aluminum conductors: Mechanically remove the oxide coating at the conductor ends immediately before connection and treat with acid- and alkali-free grease.
Accessory
Further accessories and installation instructions you will find on our website www.jeanmueller.de. or in our catalog „Current distribution components for NH-systems“
DIMENSION
SPECIFICATION
Type | NH00 |
---|---|
According to standard | DIN EN 60947-3 |
For NH fuse-links acc. to DIN VDE 0636-2 | Größe Size |
Rated operational voltage | Ue |
Rated operational current 1)
| Ie| A| 160
free air thermal current with fuse-links1)| Ith| A| 160
Rated insulation voltage| Ui| V| AC800
Rated impulse withstand voltage| Uimp| kV| 8
Utilization category|
–
|
–
| AC-23B (400V/160A) AC-22B (500V/160A) AC-21B (690V/160A) DC-22B (250V/160A)
Rated short-time withstand current| Icw| kA| 5/1s
Max. permits. power loss per fuse-link| Pa| W| 12
Rated conditional short-cirquit current| Iq| kA| 120 (500V)
100 (690V)
61439 zu beachten/In case of mounting several units in low voltage switchgear combinations, please consider rated diversity factors acc. to EN 61439.