Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors Installation Guide

June 10, 2024
Schneider Electric

XX7V1A1NAM12: NO
NPN output; Sortie NPN
Ultrasonic Sensors
Installation Guide

Mounting

Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors -
Fig1

Operation

Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors -
Fig2

A Deadband: erratic operation within this range
B Sensing range
C Sensing window
D Bicolor LED
D1 Bicolor LED is green when an object is not sensed.
D2 Bicolor LED is amber when an object is sensed.
NO Normally open output

**** WARNING

DETECTION OUTSIDE THE SENSING WINDOW
Do not set up this product to detect an object within the deadband.
Unintended operation can result in death, serious injury, or equipment damage.
Setting the Sensing Window Using Accessory XXZPB100

Manual Setup (without XXZPB100)

Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors -
Fig4

Setting the Sensing Window
NOTE: For manual setup, use the external contact in place of button G.

  1. Install accessory XXZPB100.
  2. Remove all objects from the sensor’s field of detection.
  3. Align the sensor with the object to be detected.
  4. Push and hold the setup button (G) until the bicolor LED (D) rapidly flashes green.
  5. Release the button. The bicolor LED continues to flash green.
  6. Within 30 s, insert an object into position 1, then push and release the setup button. The bicolor LED flashes amber.
  7. Within 30 s, insert an object into position 2, then push and release the setup button. The bicolor LED flashes green, then turns steady amber The device is set up properly if:
    – The LED turns amber when an object is sensed inthe window.
    – The LED turns green when an object is not sensed.

To reset the sensor, repeat Step 4.
When setup is complete, disconnect power and remove accessory XXZPB100.
Reconnect power to the sensor.
Wiring

Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors -
Fig5

BRN Brown
BLK Black/Output
WHT White/ Teach Input
BLU Blue/DC Com
NPN Sinking
PNP Sourcing

Beam Plot

Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors -
Fig6

Cabling Accessories

| | |
---|---|---|---
XZCP1141L2 (2 m / 6.6 ft)
XZCP1141L5 (5 m / 16.4)
XZCP1141L10 (10 m / 32.8)| XZCP1241L2 (2 m / 6.6 ft)
XZCP1241L5 (5 m / 16.4)
XZCP1241L10 (10 m / 32.8)| XZCC12FDM40B
XZCC12FDP40B| XZCC12FCM40B
XZCC12FCP40B

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any  consequences arising out of the use of this material.
© 2004 Schneider Electric All Rights Reserved

30072-450-14

Documents / Resources

| Schneider Electric XX7V1A1.AM12 Ultrasonic Sensors [pdf] Installation Guide
XX7V1A1.AM12 Ultrasonic Sensors, XX7V1A1.AM12, Ultrasonic Sensors, Sensors
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals