Emergency Lights Co NYC-EX-COMBO New York Combination Emergency Exit Light Instruction Manual
- June 4, 2024
- Emergency Lights Co
Table of Contents
Emergency Lights Co NYC-EX-COMBO New York Combination Emergency Exit
Light
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
- Do not use outdoors.
- Do not et power supply cords touch hot surfaces.
- Do not mount near gas Or electric eaters
- Equipment should be mounted securely in locations and at heights where it will not be readily
- SuDectea to tampering Dy unauthorized personnel.
- The use of accessory equipment and replacement parts not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment tor other than its intended purpose.
- The AC voltage rating of this equipment is specified on the product label. Do naot connect equipment to ay other voltage
IMPORTANT:
When re-lamping use only lamps specified by the manufacturer. Using other lamp
types may result in transformer damage or cause unsafe conditions.
Battery in this unit may not be fully charged. After electriaty is hooked up
to the unit, let the battery charge up for at least 24 hours. Ihen normal
operation of this unit should then take effect.
INSTALLATION
Back Mounting
- Slide out the front exit panel face plate and lens/ filter by removing the screw on the bottom of the unit.
- Remove internal metal reflector plate by removing the (2) screws.
- Determine which mounting holes will be used to mount the fixture to J-BOX and then punch out proper K/Os from the K/0 pattern on the back panel of the housing.
- There are two additional KEY HOLE sots located on the top of the unit. These holes must be used when the unit is mounted to the wal.
- Connect AC supply wires to fixture input wires. Black is for 120V; Red is for 277V; White is for Neutral.
- Connect the Red and Blue leads coming from the Circuit board to the battery terminals. Red lead would be connected to the positive terminal and Blue lead to the negative terminal.
- Replace the internal metal reflector and secure unit with the (2) screws.
- Reinsert the front exíit panel and red lens/ filter and secure with screw.
OPTION:
The package includes an ADDITIONAL 3rd LIGHTING HEAD. IF required this head could be mounted in between the two existing heads on the unit. This could be done before, during or after the unit’s installation. The procedure is described in the following steps.
- Punch out the square mounting hole on the top of the unit.
- Mount the head securely with the included nut (Fig. 1).
- Connect the yellow and violet wires coming from the circuit board (labeled ‘remote wires’) to the yellow and violet wires on the lamp head using wire nuts or any other prescribed method.
OPERATION
- To test the equipment, depress the TEST switch and the emergency lights will illuminate.
- Once you release the TEST switch the emergency lights will turn OFF.
- The automatic charger will return into action, charging the battery and trying to maintain it in a fully charged state. NOTE:
- Allow the battery to charge for a minimum of 24 hrs after installation or after a power failure before conducting a 90-minute test (see TESTING section).
CAUTION: This equipment is furnished with a sophisticated solid state transfer switch which will automatically disconnect the emergency lights from the battery if the battery has been discharged to the end of its useful output.
MAINTENANCE:
CAUTION: Always turn OFF AC power to the equipment before servicing. Servicing should be performed only by a qualified service technician. Only manufacturer SUPPLIED or APPROVED replacement parts must be used.
- BATTERY: The battery supplied with this unit requires ZERO maintenance. However it should be tested periodically (see TESTING section) and replaced when it no longer operates the connected fixtures for the complete duration of a 30-second or 90-minute test. It has a lfe expectancy of 5-7 yrs when used in a normal ambient temperature of 72° E
- OTHER: Clean lenses and replace lamps as and when required.
TESTING:
Paragraph 31-1.3.7 of NFPA 101-1985, Life Safety Code requires that all emergency lighting equipment be functionally tested every 30 days for a minimum of 30 seconds and tested annually for full 90-minute duration. Written records of the testing are to be kept for examination by the authority having jurisdiction.
TROUBLESHOOTING
-
The emergency lights DO NOT operate and:
- lf the charge indicator light is OFF- Check that the circuit breaker for AC supply is ON.
- If the charge indicator light is ON:
-
Check that the battery is properly connected.
-
If remote lamps are connected to the equipment, then turn OFF the AC supply and disconnect the remote circuit wires from the equipment. Turn ON the AC supply and depress the test switch. If the local lamps (mounted on the equipment itself) come ON, then check the remote circuit for short or overload condition and correct as required. Reconnect the circuit wires and restore AC power.
If the local lamps don’t turn ON after disconnecting the remote circuit wires, then replace battery -
Emergency lights are dim – Impies battery might not be fully charged. Allow battery to recharge for 24 hours and then re-test.
-
Remote lights are dim
-
Remote wire size is too small causing excessive voltage drop (more than the permitted 5%) and thus causing the lamps to illuminate with less intensity Refer to STEP 4 of the INSTALLATION section for more information.
NOTE:
Please contact factory for help with other types of issues.
LAMP HEAD INSTALLATION INSTRUCTION
Documents / Resources
|
Emergency Lights Co NYC-EX-COMBO New York Combination Emergency Exit
Light
[pdf] Instruction Manual