RIELLO RS 28 Gas Burners LPG Kit Instruction Manual

June 10, 2024
RIELLO

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual -
Code

1 General warnings

1.1 Guarantee and responsibility

The rights to the guarantee and the responsibility will no longer be valid in the event of damage to things or injury to people, if such damage/injury was due to any of the following causes:

▶ intervention of unqualified personnel;
▶ carrying out of unauthorised modifications on the equipment;
▶ powering of the burner with unsuitable fuels;
▶ faults in the fuel supply system; repairs and/or overhauls incorrectly carried out;
▶ use of non-original components, including spare parts, kits, accessories and optional;
▶ force majeure.

The manufacturer furthermore declines any and every responsibility for the failure to observe the contents of this manual.

– Personnel must always use the personal protective equipment envisaged by legislation and follow the indications given in this manual.
– Personnel must observe all the danger and caution indications shown on the machine.
– Personnel must not carry out, on their own initiative, operations or interventions that are not within their province.
– Personnel must inform their superiors of every problem or dangerous situation that may arise.

1.2 Installation safety notes

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual - Installation safety
notes

2 LPG kit

2.1 Kit description

The kit allows the burners, to operate on LPG. The kit is composed of: Description Gas distributor Disc Self-adhesive label Instructions

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual - Kit
description RIELLO RS 28 Gas
Burners LPG Kit Instruction Manual - Kit description

2.2 Technical features

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual - Technical
features

2.3 Conversion

⚠ DANGER
Disconnect the electrical supply from the burner by means of the main system switch.

⚠ DANGER
Close the fuel interception tap.

Proceed as follows: On the combustion head: replace the gas distributor 1) with that one supplied for LPG 2).

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual - Fig.
1

2.4 Combustion head setting

Air setting: screw 1)(Fig. 2 – A): unchanged
Gas setting: disc 1) (Fig. 2 – B): always set on 0.

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual - Fig.
2

2.5 Combustion chamber pressure

The pressure in the combustion chamber is the same as for natural gas operation.

⚠ WARNING
For pressure levels different from those indicated above, please contact the Technical Office.

2.6 Gas pressure – output

Pressure measured at the coupling with combustion chamber at 0 “WC (Tab. C).
If the combustion chamber is pressurized, the required gas-pressure is that shown on the table plus the pressurization value.

RIELLO RS 28 Gas Burners LPG Kit Instruction Manual - Gas pressure -
output

2.7 Gas train

The gas trains for LPG operation are the same as those used for natural gas.

2.8 Electrical wiring

For the electrical wiring to the burner, refer to the burner instruction manual.