HALCYON LED502 LED IP65 Batten Light Instruction Manual

June 10, 2024
HALCYON

LED502 LED IP65 Batten Light
Instruction Manual

LED502 LED IP65 Batten Light

Product Name: LED IP65 Batten Light
Model #: LED501 W46XPEM, LED502 W46XPEM
Description: 36 Watt LED, Non-dimmable, IP65, 4000K / 6(000K 45 Watt LED, Non-dimmable, IP65, 4000K / 6000K
Rated Voltage: 220-240V~, 50/60Hz

  1. Switch off power.
  2. Install the bracket.
  3. Knock out the hole, fix the waterproof gland.
  4. Connect the power cords as show on the picture.
  5. Fasten the clips and drive the 2pcs screws.
  6. Tighten the waterproof gland.
  7. Install the fixture on ceiling.
  8. Switch luminaire on to test luminaire functions correctly and is electrically safe.

Installation note: Do not install on the same circuits as Metal halide, Fluorescent and other “Low power factor” devices.
When installed on the same circuit it can cause flickering and/or premature failure of the “high power factor” electronic drivers. The harmonic distortion from low power factor devices alters the Waveform of the AC supply which can cause componentry in high power factor electronic drivers to resonate, run over temperature and fail after prolonged exposure.

Wiring for Maintained Mode
Maintained mode = Luminaire is illuminated when switched on, luminaire can be switched on and off like a normal fitting. The battery is charged (maintained) via un-switched active connection. In the case of power failure emergency mode is activated and luminaire turns on with battery backup.

Maintained Mode:
Step 1: SA Switched Supply: Connect mains from on/off switch to Switched Active terminal “SA”. Step 2: UA Non Switched Supply (Maintained):
Connect non switched main supply to un-switched active terminal “UA”.
Note: For 24/7 Operation (no switch in circuit) Connect Un-Switched Mains Supply Active to Un-Switched Active “UA” terminal and loop into Switched Active “SA” terminal.

Wiring for Non Maintained Mode
Non-maintained mode is when the luminaire is not illuminated via switch at all during normal mains supply conditions. In the case of power failure
emergency mode is activated and luminaire turns on with battery backup.

Non Maintained Mode:
Step 1: Connect active mains supply to UA (Un-Switched Active) terminal only.