HALCYON R693 KWWUDL Recessed Dimmable Downlight Gimbal Instruction Manual
- June 10, 2024
- HALCYON
Table of Contents
R693 KWWUDL Recessed Dimmable Downlight Gimbal
Instruction Manual
Installation Directions
- Switch off mains power supply
- Connect Dimmable Driver to mains voltage cable (L, N) Do not connect downlight to driver if driver is live. Inrush current from live driver will cause instant downlight failure. Do not switch secondary side.
- Carefully install downlight into pre-cut 93mm hole.
- Turn on mains power and switch on lighting circuit.
Approved Clearances
Note: Omm required but 25mm always recommended for optimum product lifespan through effective heat dissipation.
Example 1:
0mm Approved Height Clearance. Building element abutting rear, insulation
abutting sides of fitting.
Example 2:
0mm Approved Side Clearance. Building element abutting side of fitting,
insulation abutting and covering fitting.
Driver is designed to be covered and abutted with IC / IC-F approved insulation.
Cutting of holes prior to receiving goods is entirely at the risk of the
installer.
10 Basalt Place, East Tamaki, Auckland, PO Box 58-501, Botany, Manukau 2163,
Auckland, New Zealand
Ph (0064 9) 273-9177 Fax (0064 9) 2739155
Email: sales@halcyon.co.nz Web:
www.halcyonlights.co.nz
CLASSIFICATION SHEET/IC
Manufacturer / Supplier | Halcyon Lighting Ltd |
---|---|
Product Code | R693 KWWUDL |
Product Type | LED Recessed Luminaire |
Primary Voltage | 220-240V-50/60Hz |
Secondary Voltage | 500mA 15.5VDC Constant Current |
Wattage | 9.5W |
Ingress Protection Rating | IP20 |
Classifcation |
exposed to 90°C allowed to abut and cover the luminaire.
---|---|---
In the vicinity of the recessed luminaire, use an insulation product that:
(a) Maintains its dimensions and structural integrity wnen exposed to a
temperature of 90°C; and
(b) Withstands a 30-second needle flame test carried out in accordance with
AS/NZS 60695.11.5 with the flame applied to all surfaces of the sample.
Rear of fitting may abut structural members and building elements.
Do not install through or directly into joist, beam, rafter or ceiling batten.
Side Clearance from heatsink to building element (e.g. timber, joist or
batten)| SCB: 0mm
---|---
Height Clearance from heatsink to building element (e.g. timber, joist or
batten)| HCB: Omm
Minimum insulation clearance to building element| MIC: Omm
Recessed luminaires and their associated equipment may pose a risk of fire or
damage to property if not installed and maintained correctly. Halcyon
recommends a clearance of 25mm to uilding elements for optimum lifespan.
Halcyon IC rated luminaires are completely safe to install in sarked timber
ceiling linings.
Halcyon accepts no responsibility if the timber used is not treated correctly
and dries out, crack or warps over time due to the constant low heat from the
aforementioned “IC Rated” LED recessed lighting.
This data sheet contains information necessary to ensure compliance with the
New Zealand Electrical Code of Practice for Installation and Maintenance of
Recessed Luminaires and Associated Equipment AS/NZS 60598.2.2:2001