INSTALLATION R747 W3K
Installation Directions
-
Switch off mains power supply
-
Connect Dimmable Driver to mains voltage cable (L, N) Do not connect downlight to driver if driver is live.
Inrush current from live driver will cause instant downlight failure. Do not switch secondary side. -
Carefully install downlight into Precut 80-90mm hole.
-
Turn on mains power and switch on lighting circuit.
Approved Clearances
Note: 0mm required but 25mm always recommended for optimum product lifespan through effective heat dissipation.
Example 1:
0mm Approved Height Clearance. Building element abutting rear, insulation
abutting sides of fitting.
Example 2:
0mm Approved Side Clearance. Building element abutting gide of fitting,
insulation abutting and covering fitting.
Driver is designed to be covered and abutted with IC / IC-F approved insulation.
CLASSIFICATION SHEET/IC
Manufacturer / Supplier | Halcyon Lighting Ltd |
---|---|
Product Code | R747 W3K |
Product Type | LED Recessed Luminaire |
Primary Voltage | 220-240V~50/60Hz |
Secondary Voltage | 2600mA 36VDC Constant Current |
Wattage | 9.5W |
Ingress Protection Rating | IP44 |
Classification |
exposed to 90°C allowed to abut and cover the luminaire.
---|---|---
In the vicinity of the recessed luminaire, use an insulation product that:
(a) Maintains its dimensions and structural integrity when exposed to a
temperature of 90°C; and (b) Withstands a 30-second needle flame test carried
out in accordance with AS/NZS 60695.11.5 with the flame applied to all
surfaces of the sample.
Rear of fitting may abut structural members and building elements.
Do not install through o r directly into joist, beam, rafter or ceiling
batten.
Side Clearance from heatsink to building element ( e . g . timber, joist o r
batten)| SCB: 0mm
---|---
Height Clearance from heatsink to building element ( e . g . timber, joist o
r batten)| HCB: 0mm
Minimum insulation clearance to building element| MIC: Omm
Recessed luminaires and their associated equipment may pose a risk of fire or
damage to property if not installed and maintained correctly. Halcyon
recommends a clearance of 25mm to building elements for optimum lifespan.
Halcyon IC rated luminaires are completely safe to install in sarked timber
ceiling linings.
Halcyon accepts no responsibility if the timber used is not treated correctly
and dries out , crack or warps over time due to the constant low heat from the
aforementioned “IC Rated” LED recessed lighting.
This data sheet contains information necessary to ensure compliance with the
New Zealand Electrical Code of Practice for Installation and Maintenance of
Recessed Luminaires and Associated Equipment AS/NZS 60598.2.2:2001
Cutting of holes prior to receiving goods is entirely at the risk o f the
installer.
10 Basalt Place, East Tamaki, Auckland, PO Box 58-501, Botany, Manukau 2163,
Auckland, New Zealand
Ph (0064 9 ) 273-9177 Fax (0064 9 ) 2739155
Email: sales@halcyon.co.nz Web:
www.halcyonlights.co.nz
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>