Dyness Power cube Solar Energy Warehouse User Manual

June 5, 2024
DYNESS

POWERCUBE
User ManualDyness Power cube Solar Energy Warehouse
-

The copyright of this document belongs to Jiangsu Daqin New Energy Technology Co., Ltd.
No part of this documentation may be excerpted, reproduced, translated, annotated, or duplicated in any form or by any means without the prior written permission of Jiangsu Daqin New Energy Technology Co., Ltd. All Rights Reserved.
This product complies with the design requirements of environmental protection and personal safety. The storage, use, and disposal of the products shall be carried out in accordance with the product manual, relevant contract, or relevant laws and regulations.
Customers can check the related information on the website of Jiangsu Daqin New Energy Technology Co., Ltd when the product or technology is updated.
Web URL:http://www.dyness-tech.com/
Please note that the product can be modified without prior notice.
Revision History

Revision NO. Revision Date Revision Reason
1 2019.04.22 First Published
1.1 2019.10.24 Add a new product model

Safety Precautions and maintenance instructions
Warning

  • Please do not put the battery into water or fire, in case of an explosion or any other situation that might endanger your life.
  • Please connect wires properly while installation, do not reverse connect.
  • To avoid short circuits, please do not connect positive and negative poles with a conductor (Wires for instance).
  • Please do not stab, hit, trample or strike the battery in any other way.
  • Please shut off the power completely when removing the device or reconnecting wires during daily use or it could cause the danger of electric shock.
  • Please use a dry powder extinguisher to put out the flame when encountering a fire hazard, liquid extinguisher could result in the risk of secondary disaster.
  • For your safety, please do not arbitrarily dismantle any component in any circumstances unless a specialist or an authorized one from our company, device breakdown due to improper operation will not be covered under warranty.

Caution

  • We have a strict inspection to ensure the quality when products are shipped out, however, please contact us if their case bulging or if another abnormal phenomenon.
  • For your safety, the device shall be ground connected properly before normal use.
  • To assure the proper use please make sure parameters among the relevant device are compatible.
  • Please do not mixed-use batteries from different manufacturers, different types and models, as well as old and new together.
  • Ambient and storage methods could impact the life span and product reliability, please consider the operation environment abundantly to make sure the device works in proper condition.
  • For long-term storage, the battery should be recharged once every 6 months, and the amount of electric charge shall exceed 80% of the rated capacity.
  • Please charge the battery 18 hours after it discharges fully and starts over-discharging protection.
  • The formula of theoretical standby time: T=C/I (T is standby time, C is battery capacity, and I is the total current of all loads).
  • The product is affixed with a torn invalid label before leaving the factory. If anyone needs to open the cover to operate, such as set DIP mode, expand the capacity, or do other operations that won’t harm the product, the customer needs to contact DYNESS and inform the product ID. DRYNESS will record the case, confirm the operation can be operated and will authorize it. After the authorization, only professionals are allowed to operate. Contact the DYNESS authorized distributor or agent to get a new torn invalid label. After the operation, re-attach the new torn invalid label at different locations.

Preface
Manual declaration
Powercube series energy storage system is composed of several B4850 or B4874 energy storage system units connected in parallel to provide users with energy storage power generation.
During the day, the excess power of photovoltaic power generation can be stored in the battery.
At night or when needed, the stored electrical energy can be used to supply power to the electrical equipment, which can improve the efficiency of photovoltaic power generation, peak load shifting, and emergency power backup.
This user manual describes all kinds of Powercube series. It details the basic structure, parameters, installation, and operation and maintenance of the equipment.

Introduction

1.1 Brief Introduction
The B4850 and B3 lithium iron phosphate battery systems are standard battery system units.
Each module can be connected in parallel to obtain a complete system of certain specifications.
Customers can select the appropriate Powercube specifications according to their needs. The product is especially suitable for energy storage applications with high operating temperatures, limited installation space, long power backup time, and long service life.

1.2 Product Properties
Powercube series energy storage product’s anode materials are lithium iron phosphate, battery cells are managed effectively by BMS with better performance, the system feature as below:

  • Comply with European ROHS, Certified SGS, employ non-toxic, non-pollution environment-friendly battery.
  • Anode materials are lithium iron phosphate (LiFePO4), safer with a longer life span.
  • Carries a battery management system with better performance and possesses protection functions like over-discharge, over-charge, over-current, and abnormal temperature.
  • Self-management on charging and discharging, Single core balancing function.
  • Intelligent design configures an integrated inspection module, with 3 remote functions (remote-measuring, remote-communicating, and remote-controlling).
  • Flexible configurations allow parallel of multi-battery for longer standby time.
  • Self-ventilation with lower system noise.
  • Less battery self-discharge, the recharging period can be up to 10 months during the storage.
  • No memory effect so that battery can be charged and discharged shallowly.
  • With a wide range of temperatures for the working environment, -10 ºC ~ +55 ºC, circulation span and discharging performance are well under high temperature.
  • Less volume, lighter weight, and longer system backup time.

1.3 Product identity definition
Figure1-1 Battery Energy Storage System nameplate

| Battery voltage is higher than safe voltage, direct contact with electric shock hazard.
---|---
| Be careful with your actions and be aware of the dangers.
**| Read the user manual before using.
| The scrapped battery cannot be put into the garbage can and must be professionally recycled.
Recycle Icon**| After the battery life is terminated, the battery can continue to be used after it is recycled by the professional recycling organization and
do not discard at will.
| This battery product meets European directive requirements.
| This battery product passed the TUV certification test.

Product Specification

2.1 Size and Weight
Table 2-1 Powercube series Device Model

product Series| Dimension (mm)| Nominal Voltage| Nominal Capacity| Weight| IP Level
---|---|---|---|---|---
Powercube-2B3| 6005201140| DC48V| 150Ah| ≈122.5kg| IP65
Powercube-3B3| DC48V| 225Ah| ≈155kg| IP65
Powercube-4B3| DC48V| 300Ah| ≈187.5kg| IP65
Powercube-5B3| DC48V| 375Ah| ≈220kg| IP65
Powercube-6B3| DC48V| 450Ah| ≈252.5kg| IP65

2.2 Performance Parameter
Table 2-2 Powercube series performance parameter

Product Series| Powercube-2B 3| Powercube- 3B3| Powercube-4 B3| Powercube- 5Box| Powercube- 6Box
---|---|---|---|---|---
Nominal Voltage(V)| 48| 48| 48| 48| 48
Work Voltage Range(V)| 42~54| 42~54| 42~54| 42~54| 42~54
Nominal Capacity(Ah)| 150| 225| 300| 375| 450
Nominal Energy(kWh)| 7.2| 10.8| 14.4| 18.0| 21.6
Nominal Power(kW)| 3.6| 5.4| 7.2| 9.0| 10.8
Max Power(kW)| 7.2| 10.8| 10.8| 10.8| 10.8
Maximum charge/ discharging current
[Ad.c.]| 150| 225| 225| 225| 225
1s Peak Power(kW)| 7.2| 10.8| 14.4| 18| 21.6
1s Peak Current(A)| 150| 225| 300| 375| 450
Charging Current(A)| 75| 112.5| 150| 187.5| 225
Discharge Current(A)| 75| 112.5| 150| 187.5| 225
Operating altitude range [m]| ≤2000m| ≤2000m| ≤2000m| ≤2000m| ≤2000m
Storage temperature

range (°C)

| 10~40| 10~40| 10~40| 10~40| 10~40
Storage humidity range| 5 to 85 % RH| 5 to 85 % RH| 5 to 85 % RH| 5 to 85 % RH| 5 to 85 % RH
Protection class| Class I| Class I| Class I| Class I| Class I
Discharge Depth| 90%| 90%| 90%| 90%| 90%
Over Voltage   Grade| OCV II| OCV II| OCV II| OCV II| OCV II
Ambient operating temperature range (°C)| (-10~55) for discharge (0~55)
for charge non-derating under 50°C| (-10~55) for discharge (0~55) for charge non-derating under 50°C| (-10~55) for discharge 0~55) for charge non-rating
under 50°C| (-10~55) for discharge (0~55) for charge non-derating under 50°C| (-10~55) for discharge (0~55) for charge non-derating under 50°C

2.3 Interface Definition
This section elaborates on the interface functions of the back interface on the Powercube cabinet.
Figure2-1 The sketch of the back interface of Powercube.

Table 2-3 Interface Definition

Item Name Definition
Interface 1 Power cable- negative waterproof connector Reserve
Interface 2 Power cable- negative waterproof connector The battery

DC output negative pole
Interface 3| RJ45 network cable connector| Reserve
Interface 4| RJ45 network cable connector| CAN/RS485 communication interface (Factory default CAN communication mode)
Interface 5| Power cable- positive waterproof connector| The battery DC output positive pole
Interface 6| Power cable- positive waterproof connector| Reserve

The below section elaborates on the interface functions of the front interface of the battery module.

Table 2-4 Interface Definition

Item Name Definition
1 Power switch OFF/ON, remains ‘ON when using
2 Positive socket Battery output or parallel positive line
3 ADD DIP switch
4 SW (battery wake/sleep Switch) When the power switch is in ‘ON’,

long press SW for 3s to enable the battery to switch on, then switch on the DC breaker between the battery with inverter. If you need to shut down the system, firstly switch off the DC breaker between the battery with the inverter, then press SW for 3s and switch the power button to “OFF”.
5| SOC| Greenlight, showing battery capacity
6| ALM| Red lights, flash when warming, always on when Protection. When the condition of triggering protection is removed, the battery can recover automatically

7

|

RUN

| Greenlight, flashing when standby, always on when discharge, flash when charging
8| CAN/485| Communication Port Communication (factory default CAN communication)
9| DRY CONTACT| /
10| Negative socket| Battery output or parallel negative line
11| Grounding| Shell ground connection
12| COM| Communication cascade port, support RS232

2.3.1 DIP switch definition and description
Table 2-5 Interface Definition

DIP switch position (host communication protocol and baud rate selection)

1| #2| #3| #4

spare| Host or slave| Baud rate selection
OFF| OFF: slave| OFF:CAN: 500K,485: 9600
ON: host| ON:CAN: 250K,485: 115200

DIP switch description:
The battery pack is connected in parallel in the Powercube, and the battery module that communicates connected to the inverter is defined as the host. The host can communicate with the slave through the CAN interface. The host summarizes the information of the entire battery system and communicates with the inverter through CAN or 485. The connection mode is divided into the following two cases:

Note:
Before opening the cover to change the DIP mode, contact DYNESS to inform the ID, DYNESS will record the battery ID and authorizes the opening operation. Only authorized by Dyness to operate.
Except for changing the DIP mode, any other operations cannot be done.
Figure2-3 DIP switch mode schematic diagram

  1. If the host is the latest B3 battery with a DIP switch:

  2. The communication cable from the host CAN into the inverter comm port should be the correct one.

  3. When the battery works with GOODWE, Solis, LUX, Sofar, DEYE, VICTRON, IMEON, Infinisolar, Sungrow, SMA, RENAC, DELIOS, SAJ(CAN Comm) , Growatt HVM-ES/WPV(CAN port), before starting the battery, you need put the host DIP switch “# 3” to the “ON” position (to the top), then turn on the batteries.

  4. If the battery communicates with the Expert-king, Expert-VMIII, Growatt SPH/SPA(CAN comm)、GMDE、Saj(485 comm), turn the host DIP switch “#2” to the “ON” position.

  5. If the battery communicates with the Growatt SPF HVM-P/ES/WPV by RS485 port, turn the host DIP switch “#2” and “#3” to “ON”.

  6. If the battery module is in communication with the ICC by 485 communication, turn the host DIP switch “#1” and “#4” to “ON”. the DIP switch of the slaves needs to turn the “#4” to “ON”.

  7. The DIP switch of the slaves does not need to be changed.

  8. If the energy storage system has only one B3, it is the host itself, and still follows the above steps.
    Note: For more information on matching inverter brands, please be subject to the latest document <The list of compatibility between Dyness ESS and Inverters >.

Caution: The DIP switch mode in case (5),1001 is only for ICC(a special communication device of some no-communication inverter), it’s a special firmware in BMS, different from general firmware, so if customers want to use ICC, please contact dryness to confirm.

Note:

  1. After the whole system connection, set the master DIP mode according to the inverter model first, then start the battery.
  2.  The BAT-INV comms cable is from inverter comm port to master CAN IN port, BAT-BAT cable is from master CAN OUT to slave1 CAN IN,slave1 CAN OUT to slave2 CAN IN.

2.4 Battery Management System(BMS)
2.4.1 Voltage Protection
Discharging Low Voltage Protection:
When any battery cell voltage is lower than the protection value during discharging, the over-discharging protection starts and the battery buzzer makes an alarm sound. The battery system stops supplying power to the outside. When the voltage of each cell recovers to the rated return range, the protection is over.

Charging Over Voltage Protection:
When total voltage or any battery cell voltage reaches the protection value during charging, the battery stops charging. When total voltage or a cell recovers to the rated return range, the protection is over.

2.4.2 Current Protection
Over Current Protection in Charging:
When the charging current is greater than the protection value, the battery buzzer alarms and the system stops charging. Protection is released after rated time delaying.
Over Current Protection in Discharging:
When the discharge current is greater than the protection value, the battery buzzer alarms and the system stops discharging. Protection is released after rated time delaying.

Note:
The buzzer sound alarm setting can be manually turned off on the background software, and the factory default is on.

2.4.3 Temperature Protection
Less/Over temperature protection in charging:
When the battery’s temperature is beyond the range of 0 ℃ ~55 ℃ during charging, temperature protection starts, and the device stops charging.
The protection is over when it recovers to the rated return range.
Less/Over temperature protection in discharging:
When the battery’s temperature is beyond the range of -10℃~+55℃ during discharging, temperature protection starts and the device stops supplying power to the outside.
The protection is over when it recovers to the rated return range.

2.4.4 Other Protection
Short Circuit Protection:
When the battery is activated from the shutdown state, if a short circuit occurs, the system starts short-circuit protection for 1 minute.

Self-Shutdown:
When a device connects with no external loads for over 72hours, the device will dormant standby automatically.

Caution
The battery’s maximum discharging current should be more than the load’s maximum working current.

Installation and Configuration

3.1 Ready for installation
Safety Requirement
This system can only be installed by personnel who have been trained in the power supply system and have sufficient knowledge of the power system.
The safety regulations and local safety regulations listed below should always be followed during the installation.

  • All circuits connected to this power system with an external voltage of less than 48V must meet the SELV requirements defined in the IEC60950 standard.
  • If operating within the power system cabinet, make sure the power system is not charged. Battery devices should also be switched off
  • Distribution cable wiring should be reasonable and has protective measures to avoid touching these cables while operating power equipment.
  • when installing the battery system, must wear the protective items below:

3.1.1 Environmental requirements
Working temperature: -10 o C ~ +55 o C

  • The charging temperature range is 0 o o C~55 C,

  • Discharging temperature range is-10 ºC ~ +55 ºC
    Storage temperature: 10 ºC ~ 40 ºC
    Relative humidity: 5% ~ 85%
    RH Elevation: no more than 2000m
    Operating environment: Indoor or outdoor installation, sites avoid direct sunlight, no conductive dust, and corrosive gas.

  • The installation location should be away from the sea to avoid a brine and high humidity environment.

  • The ground is flat and level.

  • There is no flammable explosive near the installation places.

  • The optimal ambient temperature is 15 ºC ~ 30 ºC Keep away from dust and messy zones

3.1.2 Tools and data
Hardware tool
Tools and meters that may be used are shown in table 3-1.

Table 3-1 Tool instrument

Name


Screwdriver (word, cross)| AVO meter
Wrench| Clamp meter
Inclined pliers| Insulating tape
Needle nose pliers| The thermometer
Clip forceps| Wrist strap
Wire stripper| AVO meter
Electric drill| Tape

3.1.3 Technical preparation
Electrical interface check
Devices that can be connected directly to the battery can be user equipment, power supplies, or other power supplies.

  • Confirm whether the user’s PV power generation equipment, power supply, or other power supply equipment has a DC output interface, and measure whether the DC power output voltage meets the voltage range requirements in Table 2-2.
  • Confirm that the maximum discharge current capability of the DC power interface of the user’s photovoltaic power generation equipment, power supply or other power supply equipment should be greater than the maximum charging current of the products used in Table 2-2.
  • If the maximum discharge capacity of the DC power interface of the user’s photovoltaic power generation equipment is less than the maximum charging current of the products used in Table 2-2, the DC power interface of the user’s photovoltaic power generation equipment shall have a current limiting function to ensure the normal operation of the user’s equipment.
  • Verify that the maximum operating current of the battery-powered user equipment (inverter DC input) should be less than the maximum discharge current of the products used in Table 2-2.

The security check

  • Firefighting equipment should be provided near the equipment, such as portable dry powder fire extinguishers.
  • An automatic fire fighting system shall be provided for the case where necessary.
  • No flammable, explosive, or other dangerous articles are placed beside the battery.

3.1.4 Unpacking inspection

  • When the equipment arrives at the installation site, loading and unloading should be carried out according to the rules and regulations, to prevent exposure to sun and rain.
  • Before unpacking, the total number of packages shall be indicated according to the shipping list attached to each package, and the case shall be checked for good condition.
  • In the process of unpacking, handle with care and protect the surface coating of the object.
  • Open the package, the installation personnel should read the technical documents, verify the list, according to the configuration table and packing list, and ensure objects are complete and intact, if the internal packing is damaged, should be examined and recorded in detail.

The packing list is as follows:

Item Specification ( mm) Quantity Figure
2B3 3B3 4B3 5B3
Cabinet 6005201140 1 1
Battery module B3: 48V745h
480*405×132 2 3 4
Parallel cable- positive Red/25mm2/L215 mm 1 2
Parallel cable- negative Black/25mm2/L215 mm 1 2
Power cable- positive1 Red/25mm2/L370 0mm 1 1
Power cable- positive2 Red/25mm2/L270 0mm 1 1
Power cable- negative1 Black/25mm2/L370 0mm 1 1
Power cable- negative2 Black/25mm2/L270 0mm 1 1
Communicate on parallel cable Black/250mm/ Double RJ45 plug 1 1
Communicate on cable-to inverter-1 Yellow/L800mm/ Double RJ45 plug 1 1
1
Communicate on cable-to inverter-2 Black/L2000m m/ Double RJ45 plug 1 1
1
--- --- --- ---
Ground wire L500mm,4mm² 1 1

3.1.5 Engineering coordination
Attention should be paid to the following items before construction:

  • Power line specification.
    The power line specification shall meet the requirements of maximum discharge current for each product in table2-2.

  • Mounting space and bearing capacity.
    Make sure that the battery has enough room to install, and that the battery rack and bracket have enough load capacity.

  • Wiring.
    Make sure the power line and ground wire are reasonable. Not easy to short- circuit, water and corrosion.

  • Circuit breaker.
    Install the circuit breaker between the battery system and the inverter, Select the circuit breaker based on the actual battery system usage and installation suggestions.

3.2 Equipment installation
The wall for battery installation shall be solid brick or cement wall with a strong bearing capacity and wall thickness no less than 100mm.
Mounting space requirements: floor installation

Table 3-2 Installation steps

Step1| Installation Preparation| Confirm that the ON/OFF switch on the front panel of each B3 unit is in the “OFF” state to ensure no live operation.
---|---|---
Step 2| Mechanical installation| 1. Cabinet placement position determination
2. Top cables pre-installed
3. Battery module installation
Step3| Electrical installation| 1. Battery module parallel cable installation
2. Battery module Power cable- positive installation
3. Battery module Power cable- negative installation
4. Communication parallel cable connection
Step4| Battery system self-test| 1. Press the ON/OFF switch to the “ON” state
2. BMS system power-on activation
3. Check the system output voltage
4. Shut down the system
Step5| Connect to the inverter| 1. Wiring the battery system Power cable- positive and Power cable- positive to the circuit breaker between the inverter and battery system.
2. Connect the Communication cable to the inverter

3.2.1 Installation Preparation

  1. Prepare equipment and tools for installation
  2. Check the cabinet and confirm that the ON/OFF switch on the front panel of each battery module is in the “OFF” state to ensure no live operation.

3.2.2 Mechanical installation

  1. Fix the Powercube cabinet to the mounting position and remove the front cover.
    Please refer to 3.2 to place the cabinet on the ground.
    Pass the total positive cable and the total negative cable (Power cable- positive1, Power cable- positive2 and Power cable-negative1,
    Power cable-negative2) through the waterproof connector (Interface1,2,5,6)on the back of the cabinet, and insert the external CAN cable(Communication cable-to inverter2) into the RJ45 network cable connector(Interface 4). Table 3-3 Interface Definition Item| Name| Definition
    ---|---|---
    Interface1| Power cable- negative waterproof connector| Reserve
    Interface 2| Power cable- negative waterproof connector| The battery DC output negative pole
    Interface 3| RJ45 network cable connector| Reserve
    Interface 4| RJ45 network cable connector| CAN/RS485 communication interface  (Factory default CAN communication mode)
    Interface 5| Power cable- positive waterproof connector| The battery DC output positive pole
    Interface 6| Power cable- positive waterproof connector| Reserve
  2. Place the battery unit on the cabinet bracket as shown in the figure and push it into the cabinet to the installation position.
  3. Fix the battery unit in the cabinet with nuts through the top of the mounting holes on the hanging ears of the battery module front panel. The other units are in this order, as shown in Figure3-6.

3.2.3 Electrical installation
Statement: For the Australian market, installations should be conducted in accordance with AS/NZS 3000 and AS/NZS 5139”.
Before connecting the power cables, use a multimeter to measure cable continuity, short circuit, confirm positive and negative, and accurately mark the cable labels.
Measuring method:

  • Cable availability: Select the buzzer and use the probe to measure the ends of the same color cable. If the buzzer calls, it means the cable is available.
  • Short circuit judgment: choose multimeter resistor file, probe the same end of positive and negative pole, if the resistor shows infinity, means that the cable is available.
  • After visual testing of the power line is connected well, the positive and negative poles of the battery shall be connected respectively to the positive and negative poles of the opposite terminal.

It is better to add a circuit breaker between the inverter and the battery system. The selection of the circuit breaker requires: Voltage: U>60V

The circuit breaker is installed between the battery module and the inverter, as shown in Figures 3-8:

Caution
Note: If you have any questions during installation, please contact your dealer to avoid damage to the equipment.

  1. Install the power cable
    Install the Parallel cable- negative and the Parallel cable- positive as shown in Figures 3-8, then connect the positive cable and the total negative cable (use Power cable- positive1, Power cable- positive2 and Power cable- negative1, Power cable- negative2).
    Among them, the Power cable- positive1, Power cable- positive2 are red, and Power cablenegative1, Power cable- negative2 are black.

  2. Install the communication line
    Insert the Communication cable-to inverter 1 into the IN-communication port of the uppermost No. 1 battery module, take a Communication parallel cable, insert one end
    into the OUT-communication port of No. 1 battery module, and the other end into the IN-communication port of No. 2 battery module on the next layer.
    Connect all communication lines in this order. Foot position| Color| Definition
    ---|---|---
    PIN1| Orange/white| 485B
    PIN2| Orange| 485A
    PIN3| Green/white| GND
    PIN4| Blue| CANH
    PIN5| Blue/white| CANAL
    PIN6| Green| Reserve
    PIN7| Brown/white| XIN
    PIN8| Brown| Reserve
    PIN9| Orange/white| Reserve
    PIN10| Orange| Reserve
    PIN11| Green/white| GND
    PIN12| Blue| CANH
    PIN13| Blue/white| CANAL
    PIN14| Green| Reserve
    PIN15| Brown/white| XOUT
    PIN16| Brown| Reserve

The Pin definition of COM port

Foot position Definition
PIN1 Reserve
PIN2 GND
PIN3 TXD
PIN4 RDX
PIN5 GND
PIN6 Reserve

Note: Please pay attention of the communication com definition of the inverter, in order to avoid voltage in the port to affect communication.

  1. Connect to the inverter
    Connect the total positive cable(Power cable- positive1 and Power cable- positive2) and the total negative cable(Power cable- negative1 and Power cable- negative2) that are
    pulled out from the outside of the cabinet to the circuit breaker(the other end of the circuit breaker is connected to the inverter), and the external CAN communication line 2(Communication cable-to-inverter2) is connected to the inverter. Complete as shown in Figures 3-8.
    Batteries and inverters must be installed in accordance with the compatibility list in the “Dryness compatible list-Final-LV&HV-F-2022V2-Y”;
    Dryness compati
    bal list-F-2022V2-Y.pdf

Use, maintenance, and troubleshooting

4.1 Battery system usage and operation instructions
After completing the electrical installation, follow these steps to start the battery system.

  1. Press the ON/OFF button to the ON position, and press and hold the SW button for 3 seconds.
    After the indicator self-test, the RUN indicator will light and the SOC indicator will be on (100% SOC status in Figure 4-1).

Note: If you need to shut down the system, firstly switch off the DC breaker between the battery with the inverter, then press SW for 3s and switch the power button to “OFF”.

Caution:

  1. After pressing the power button, if the battery status indicator on the front panel continues to be red, please refer to the “4.2 Alarm description and processing “. If the failure cannot be eliminated, please contact the dealer timely.
  2. Use a voltmeter to measure whether the voltage of the circuit breaker battery access terminal is higher than 42V and check whether the voltage polarity is consistent with the inverter input polarity. If the circuit breaker battery input terminal has a voltage output that is greater than 42V, then the battery begins to work normally.
  3. After confirming that the battery output voltage and polarity are correct, turn on the inverter, and close the circuit breaker.
  4. Check if the indicator of the inverter and battery connection (communication indicator and battery access status indicator) is normal. If it is normal, successfully complete the connection between the battery and the inverter. If the indicator light is abnormal, please refer to the inverter manual for the cause or contact the dealer.

4.2 Alarm description and processing
When protection mode is activated or system failure occurred, the alarm signal will be given through the working status indicator on the front panel of the B3. The network management can query the specific alarm categories.
If the fault such as single cell overvoltage, charging over-current, under- voltage protection, high-temp protection, and other abnormalities which affect the output, please deal with it according to Table 4-1.
Table 4-1 Main alarm and Protection

Statue Alarm category Alarm indication Processing
Charge state Over-current RED Buzzer start Stop charging and find out the

cause of the trouble
High temp| RED| Stop charging
Discharge state| Over-current| RED Buzzer start| Stop discharging and find out the cause of the trouble
High temp| RED| Stop discharging and find out the cause of the trouble
Total voltage undervoltage| RED Buzzer start| Start charging
Cell voltage undervoltage| RED Buzzer start| Start charging

4.3 Analysis and treatment of common faults
Analysis and treatment of common faults in Table 4-2:
Table 4-2 Analysis and treatment of common faults

No . Fault phenomenon Reason analysis Solution
1 The indicator does not respond after the power on Total voltage lower than
35V Check the total voltage
2

No DC output

| The battery data status is abnormal.
The battery gets into over-discharged protection| Read the battery information on the monitor.
3| The DC power supply time is too short| Battery capacity becomes smaller| Storage battery replacement or add more modules
4| The battery can’t be fully charged to 100%| The charging voltage is too low| Adjust charging voltage at 53.5V or 54V
5| The power cable sparks once power is on and ALM light RED| Power connection short-circuit| Turn off the battery, check the cause of the short circuit
6| Communication fault| The DIP setting of the host is wrong/     the battery type of the inverter is wrong/ Communication cable is used incorrectly/
The communication cable is incorrectly connected at the battery communication port or the inverter communication port/
The battery firmware version is too low to support the inverter| Check these possible causes one by one
---|---|---|---

If you need any technical help or have any questions, please contact the dealer in time.

DAQIN NEW ENERGY TECH(TAIZHOU)Co., LTD
Address: Building 13, Jiangyan Industrial Park, Sanshui Street,
Jiangyan District, Taizhou City, Jiangsu Province,225500
Email: sales@dyness-tech.com
Website: www.dyness-tach.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals