COPPER COMPRESSION CONNECTORS
C Panduit Corp. 2021
INSTALLATION INSTRUCTIONS
T-PMPI-62-PC
COPPER COMPRESSION CONNECTOR INSTALLATION
- Use a connector marked for the wire size and wire material to be used. NEVER use a copper connector on aluminum wire.
- Strip wire insulation to approximate length shown on tool chart. DO NOT nick or ring the conductor
- Clean the wire.
- Insert stripped wire into connector until the wire stops.
- Using installation tooling shown on other side, insert connector in die and crimp between color bands or knurl markings. REQUIRED NUMBER OF COMPRESSIONS SHOWN IN ( ).
- After crimping, inspect for sharp edges, flash or burrs and remove if present.
HEAT SHRINK INSULATION INSTRUCTION
- Refer to Panduit catalog or www.panduit.com for heat shrink material information, tubing size, voltage rating, and shrink temperature.
- Cut tubing to length allowing insulation coverage as desired. Allow a minimum of 1-1/2″ inch overlap on wire insulation.
- Shrink with a standard propane torch or heat gun. MOVING FROM CRIMPED PORTION OF CONNECTOR TOWARD INSULATED WIRE. Adhesive flow at ends indicate shrinkage complete.
*Heat shrink insulation, blank tongues, & non-plated lugs not tested by TELCORDIA.
For Technical Support:
www.panduit.com/resources/install_maintain.asp
Tool Chart for Compression Connectors Type LCB, LCC, LCP, and SCL with
Copper Cable
Panduit Part NumberL=Lug S=Splice| Std. Wire Size AWG| Wire trip Length in.)| CT-720| CT-2600/L CT-0/LINT CT-0/LUK CT-0/LAUS CT-600/TO| A See Tool List Below| B See Tool List Below| CT-2920/CCP CT-2920/CCPINT CT-2920/CCPUK CT-2920/CCPAUS CT-2920/CCPTO CT-920CH/CCP with UA12IDIndenterDie| C See Uni-ie™Dieless Tools Below| ****
CT-3980 CT-3980/INT CT-3980/UK CT-3980/AUS CT-3980/TOUni-Die™DielessTool
---|---|---|---|---|---|---|---|---|---
LCB300 LCBN300 LCC300 LCCN300| 300 kcmil| 2-5/16| CD-720-4White P66 (4)|
KC4-300White (2)| CD-2001-300White P66 (3)| CD-920-300White P66 (3)| STD (1)|
2/0 AWG –300 kcmil(3)| STD (1)
SCL300| 2
LCB350 LCBN350 LCC350 LCCN350| 350 kcmil| 2-5/16| CD-720-5Red P714)| —|
CD-2001-350Red P71 (3)| CD-920-350Red P71 (3)| STD (1)| 3/0 AWG –350 kcmil(3)|
STD (1)
SCL350| 2
LCB400 LCBN400 LCC400 LCCN400| 400 kcmil| 2-3/8| CD-720-6Blue P76 (4)|
—
| CD-2001-400Blue P76 (4)| CD-920-400Blue P76 (3)| STD (1)| * 4/0 AWG –400
kcmil(3)| STD (1)
SCL400| 2-1/8
LCB500 LCBN500 LCC500 LCCN500 LCP500| 500 kcmil| 2-9/16| CD-720-7Brown P87
(4)| —| CD-2001-500Brown P87 (4)| CD-920-500Brown P87 (3)| STD (1)| 4/0 AWG
–500 kcmil(3)| STD (1)
SCL500| 2-1/4
LCB600 LCBN600 LCC600 LCCN600| 600 kcmil| 2-3/4| —| —| KC22-600BGreen (4)|
CD-920-600Green P94 (4)| STD (1)| 250 –600kcmil (3)| STD (1)
SCL600|
LCB750 LCBN750 LCC750 LCCN750 LCP750| 750kcmil| 2-15/16| —| —| —| CD-920-750
CD-940-750 4Black P106 (4)| STD (1)| 500 – 750kcmil (3)| —
SCL750| 2-7/8
LCB800 LCBN800 LCC800 LCCN800| 800 kcmil| 3| —| —| —| CD-940-800 4Orange P107
(4)| —| —| —
LCB1000 LCBN1000 LCC1000 LCCN1000 LCP1000| 1000 kcmil| 3-1/16| —| —| —|
CD-940-1000 4White P125 (4)| —| —| —
SCL1000| 3
LCB1250 LCC1250 LCP1250| ****
1250 kcmil
| 3-3/8| —| —| —| CD-940-1250 4Yellow P140 (4)| —| —| —
Panduit Part Number L=Lug S=Splice| Std. Wire Size AWG| Wire Strip Length
(in.)| B See Tool List Below| Burndy Tool Y60B
---|---|---|---|---
LCB1500| | | CD-940-1500 4| Burndy Die
LCC1500| 1500 kcmil| 3-3/8| Green P150| L46RT
LCP1500| | | (4)| (3)
LCB2000| | | | Burndy Die
LCC2000| 2000 kcmil| 3-5/8| —| L48RT
LCP2000| | | | (4)
- The crimp die pockets are integrated into the tool frame.
- CD-920 dies can be used with CT-940CH and CT-2940 tools with die adapter
- CD-940 dies to be used exclusively with CT-940CH series and CT-2940 series tools
- Maximum size: 500 kcmil lugs and 250 kcmil splices.
- Maximum size: 250 kcmil lugs and splices. No extended wire range.
- Rotate gauge selector to the indicated gauge setting
- Maximum size: 600 kcmil lugs and splices.
- LCC8-12 wire strip length is 7/8″
*** KC22-600B crimp die for used with CT-3001/ST and CT-3001/CCP series tools.
A CT-2001, CT-2001/L, CT-2001/LE, CT-2002, CT-2002/L, CT-3001, CT-3001/E,
CT-3001/ST, CT-3001/STINT, CT-3001/STUK, CT3001/STAUS, CT-3001/TO,
CT-3001/CCP, CT-3001/CCPINT, CT-3001/CCPUK, CT-3001/CCPAUS,
CT-3001/CCPTO
B CT-920, CT-920/CV, CT-920CH, CT-920CH/CV, CT-920CH/CCP, CT-930, CT-
930CH, CT-930LPCH 9 , CT-940CH/BJO 3 , CT-2920, CT-2920/CCP, CT-2920/CCPINT,
CT-2920/CCPUK, CT-2920/CCPAUS, CT-2920/CCPTO, CT-2930, CT-2930/L, CT2930/LE,
CT-2931, CT-2931/ST, CT-2931/STINT, CT-2931/STUK, CT-2931/STAUS, CT-2931/TO,
CT-2931/STCV, CT-2931/STCVINT, CT-2931/STCVUK, CT-2931/STCVAUS, CT-2931/CVTO,
CT-2940 3 , CT-2940/L 3 , CT-2940/LE 3
C CT-980, CT-980CH, CT-980LPCH 6 , CT-2950 5 , CT-2980, CT-2980/L,
CT-2980/LE, CT-2980/ST, CT-2980/STINT, CT-2980/STUK, CT2980/STAUS, CT-2980/TO,
CT-2981, Extended Wire Range
For Instructions in Local Languages and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
E-mail:cs@panduit.com
Phone:800-777-3300
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>