PANDUIT T-PMPI-62-PC Copper Compression Connectors Instruction Manual

June 10, 2024
PANDUIT

PANDUIT Logo COPPER COMPRESSION CONNECTORS
C Panduit Corp. 2021
INSTALLATION INSTRUCTIONS
T-PMPI-62-PC
PANDUIT T PMPI 62 PC Copper Compression Connectors

COPPER COMPRESSION CONNECTOR INSTALLATION

  1. Use a connector marked for the wire size and wire material to be used. NEVER use a copper connector on aluminum wire.
  2. Strip wire insulation to approximate length shown on tool chart. DO NOT nick or ring the conductor
  3. Clean the wire.
  4. Insert stripped wire into connector until the wire stops.
  5. Using installation tooling shown on other side, insert connector in die and crimp between color bands or knurl markings. REQUIRED NUMBER OF COMPRESSIONS SHOWN IN ( ).
  6. After crimping, inspect for sharp edges, flash or burrs and remove if present.

HEAT SHRINK INSULATION INSTRUCTION

  1. Refer to Panduit catalog or www.panduit.com for heat shrink material information, tubing size, voltage rating, and shrink temperature.
  2. Cut tubing to length allowing insulation coverage as desired. Allow a minimum of 1-1/2″ inch overlap on wire insulation.
  3. Shrink with a standard propane torch or heat gun. MOVING FROM CRIMPED PORTION OF CONNECTOR TOWARD INSULATED WIRE. Adhesive flow at ends indicate shrinkage complete.

*Heat shrink insulation, blank tongues, & non-plated lugs not tested by TELCORDIA.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Tool Chart for Compression Connectors Type LCB, LCC, LCP, and SCL with Copper Cable

PANDUIT T-PMPI-62-PC Copper Compression Connectors

Panduit Part NumberL=Lug S=Splice| Std. Wire Size AWG| Wire trip Length in.)| CT-720| CT-2600/L CT-0/LINT CT-0/LUK CT-0/LAUS CT-600/TO| A See Tool List Below| B See Tool List Below| CT-2920/CCP CT-2920/CCPINT CT-2920/CCPUK CT-2920/CCPAUS CT-2920/CCPTO CT-920CH/CCP with UA12IDIndenterDie| C See Uni-ie™Dieless Tools Below| ****

CT-3980 CT-3980/INT CT-3980/UK CT-3980/AUS CT-3980/TOUni-Die™DielessTool

---|---|---|---|---|---|---|---|---|---
LCB300 LCBN300 LCC300 LCCN300| 300 kcmil| 2-5/16| CD-720-4White P66 (4)| KC4-300White (2)| CD-2001-300White P66 (3)| CD-920-300White P66 (3)| STD (1)| 2/0 AWG –300 kcmil(3)| STD (1)
SCL300| 2
LCB350 LCBN350 LCC350 LCCN350| 350 kcmil| 2-5/16| CD-720-5Red P714)| —| CD-2001-350Red P71 (3)| CD-920-350Red P71 (3)| STD (1)| 3/0 AWG –350 kcmil(3)| STD (1)
SCL350| 2
LCB400 LCBN400 LCC400 LCCN400| 400 kcmil| 2-3/8| CD-720-6Blue P76 (4)|


| CD-2001-400Blue P76 (4)| CD-920-400Blue P76 (3)| STD (1)| * 4/0 AWG –400 kcmil(3)| STD (1)
SCL400| 2-1/8
LCB500 LCBN500 LCC500 LCCN500 LCP500| 500 kcmil| 2-9/16| CD-720-7Brown P87 (4)| —| CD-2001-500Brown P87 (4)| CD-920-500Brown P87 (3)| STD (1)| 4/0 AWG –500 kcmil(3)| STD (1)
SCL500| 2-1/4
LCB600 LCBN600 LCC600 LCCN600| 600 kcmil| 2-3/4| —| —|
KC22-600BGreen (4)| CD-920-600Green P94 (4)| STD (1)| 250 –600kcmil (3)| STD (1)
SCL600|
LCB750 LCBN750 LCC750 LCCN750 LCP750| 750kcmil| 2-15/16| —| —| —| CD-920-750 CD-940-750 4Black P106 (4)| STD (1)| 500 – 750kcmil (3)| —
SCL750| 2-7/8
LCB800 LCBN800 LCC800 LCCN800| 800 kcmil| 3| —| —| —| CD-940-800 4Orange P107 (4)| —| —| —
LCB1000 LCBN1000 LCC1000 LCCN1000 LCP1000| 1000 kcmil| 3-1/16| —| —| —| CD-940-1000 4White P125 (4)| —| —| —
SCL1000| 3
LCB1250 LCC1250 LCP1250| ****

1250 kcmil

| 3-3/8| —| —| —| CD-940-1250 4Yellow P140 (4)| —| —| —
Panduit Part Number L=Lug S=Splice| Std. Wire Size AWG| Wire Strip Length (in.)| B See Tool List Below| Burndy Tool Y60B
---|---|---|---|---
LCB1500| | | CD-940-1500 4| Burndy Die
LCC1500| 1500 kcmil| 3-3/8| Green P150| L46RT
LCP1500| | | (4)| (3)
LCB2000| | | | Burndy Die
LCC2000| 2000 kcmil| 3-5/8| —| L48RT
LCP2000| | | | (4)

  1. The crimp die pockets are integrated into the tool frame.
  2. CD-920 dies can be used with CT-940CH and CT-2940 tools with die adapter
  3. CD-940 dies to be used exclusively with CT-940CH series and CT-2940 series tools
  4. Maximum size: 500 kcmil lugs and 250 kcmil splices.
  5. Maximum size: 250 kcmil lugs and splices. No extended wire range.
  6.  Rotate gauge selector to the indicated gauge setting
  7. Maximum size: 600 kcmil lugs and splices.
  • LCC8-12 wire strip length is 7/8″
    *** KC22-600B crimp die for used with CT-3001/ST and CT-3001/CCP series tools.

A CT-2001, CT-2001/L, CT-2001/LE, CT-2002, CT-2002/L, CT-3001, CT-3001/E, CT-3001/ST, CT-3001/STINT, CT-3001/STUK, CT3001/STAUS, CT-3001/TO, CT-3001/CCP, CT-3001/CCPINT, CT-3001/CCPUK, CT-3001/CCPAUS,
CT-3001/CCPTO
B CT-920, CT-920/CV, CT-920CH, CT-920CH/CV, CT-920CH/CCP, CT-930, CT- 930CH, CT-930LPCH 9 , CT-940CH/BJO 3 , CT-2920, CT-2920/CCP, CT-2920/CCPINT, CT-2920/CCPUK, CT-2920/CCPAUS, CT-2920/CCPTO, CT-2930, CT-2930/L, CT2930/LE, CT-2931, CT-2931/ST, CT-2931/STINT, CT-2931/STUK, CT-2931/STAUS, CT-2931/TO, CT-2931/STCV, CT-2931/STCVINT, CT-2931/STCVUK, CT-2931/STCVAUS, CT-2931/CVTO, CT-2940 3 , CT-2940/L 3 , CT-2940/LE 3
C CT-980, CT-980CH, CT-980LPCH 6 , CT-2950 5 , CT-2980, CT-2980/L, CT-2980/LE, CT-2980/ST, CT-2980/STINT, CT-2980/STUK, CT2980/STAUS, CT-2980/TO, CT-2981, Extended Wire Range

For Instructions in Local Languages and Technical Support:
www.panduit.com/resources/install_maintain.asp
PANDUIT Logo www.panduit.com
E-mail:cs@panduit.com
Phone:800-777-3300

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals