The nVent RAYCHEM E-150 is a low profile end seal kit used with nVent RAYCHEM BTV-, QTVR-, XTV-, and KTV-heating cables. It is rated for a voltage of 277V and a current of 40A. The maximum surface temperature depends on the configuration of the Trace Heating system, determined in accordance with IEC/IEEE 60079-30-1. The product has hazardous location certifications from DEKRA and IECEx DEK, and is suitable for use in Class I Zone 2 AEx e IIC T*, Class I, Div. 2, Groups A, B, C, D, Class II, Div. 2, Groups F, G, and Class III hazardous locations.

Product Usage Instructions: nVent RAYCHEM E-150

Before installation, it is important to make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to.

During installation of the nVent RAYCHEM E-150 kit, it is important to prevent water ingress. The maximum surface temperature depends on the configuration of the Trace Heating system, determined in accordance with IEC/IEEE 60079-30-1. The installation instructions for the low profile end seal kit should be followed carefully for use with all nVent RAYCHEM BTV-, QTVR-, XTV-, and KTV- heating cables. The product is rated for a voltage of 277V and a current of 40A.

For further information on installation and limitations of the nVent RAYCHEM E-150, refer to the product manual at nVent.com/RAYCHEM.

Hazardous Locations

nVent RAYCHEM E-150 Low Profile-End-Seal-Kit-
Instruction-Manual-fig-2

For system Temperature Code, see heating cable or design documentation.

TOOLS REQUIRED

nVent RAYCHEM E-150 Low Profile-End-Seal-Kit-Instruction-
Manual-fig-1

Hazardous Locations

Ex-Bereiche

WARNING: The purchaser should make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to.
WARNING: To prevent electrical shock or fire, this product must be installed correctly. Water ingress must be avoided before and during the installation. De-energise circuits before installation or servicing. Maximum nominal current rating of over-current protection: 40 A. Persons involved in the installation and testing of elec-tric trace heating systems shall be suitably trained in all special techniques required. Installation shall be carried out under the supervision of a qualified person Ground fault equipment protection must be used on each heating cable circuit as arcing may not be stopped by conventional circuit breakers. Before installing this product, read the instructions com plete ly. Keep ends of trace heaters and kit components dry before and during installation The electrically conductive covering (braid) of the heating cable shall be connected to a suitable earthing terminal. The presence of the heating cables shall be made evident by the posting of caution signs or markings at appropriate locations and/or at frequent intervals along the circuit The insulation resistance of the heating cable shall be measured and recorded after installation and shall not be less than 20 MOhm (or a higher value if specified by the manufacturer). Avoid skin and eye contact with sealing grease. Consult nVent RAYCHEM safety datasheet VEN 0058, (INSTALL-027).

Schedule of limitations

The maximum surface temperature depends on the configuration of the Trace Heating system, determined in accordance with IEC/IEEE 60079-30-1.

  • Minimum ambient temperature: –55°C
  • Maximum ambient temperature: +55°C
  • Maximum operating temperature, power “on”: +150°C
  • Maximum exposure temperature, power “off”: +200°C

Installation instruction for low profile end seal kit E-150. For use with all nVent RAYCHEM BTV-, QTVR-, XTV- and KTV-heating cables.

  • Rated Volt age: 277 V
  • Rated Current: 40A

INSTALLATION INSTRUCTION 

nVent RAYCHEM E-150 Low Profile-End-Seal-Kit-
Instruction-Manual-fig-3 nVent RAYCHEM E-150 Low Profile-End-Seal-Kit-Instruction-Manual-
fig-4

Avoid skin and eye contact with sealing grease. Consult nVent RAYCHEM safety datasheet VEN 0058, (INSTALL-027).nVent RAYCHEM E-150 Low Profile-End-Seal-
Kit-Instruction-Manual-fig-6

Tel. 0800 969 013
Fax 0800 968 624
salesthermalUK@nVent.com

©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice. RAYCHEM-IM-INSTALL045-E150-ML-2111

nVent.com/RAYCHEM

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

nVent RAYCHEM User Manuals

Related Manuals