nVent RAYCHEM S-40 Heat Shrinkable Splice Kit Instruction Manual

June 10, 2024
nVent RAYCHEM

nVent RAYCHEM S-40 Heat Shrinkable Splice Kit

WHAT IN BOX

nVent-RAYCHEM S-40-Heat-Shrinkable-Splice-Kit-fig-
\(1\)

TOOLS REQUIREDnVent-RAYCHEM S-40-Heat-Shrinkable-Splice-Kit-fig-
\(2\)

WIRING

nVent-RAYCHEM S-40-Heat-Shrinkable-Splice-Kit-fig-
\(19\)

Product Information

The S-40 Heat-Shrinkable Splice Kit is designed for use with all nVent RAYCHEM XTV, KTV, HTV, and VPL heating cable types. It is available in ATEX/UKEX, IECEX, and cCSAus certifications. The kit includes an easy-to-install heat- shrinkable sleeve that provides a watertight seal and ensures high-quality performance.

Certifications

  • ATEX/UKEX: II 2 G Ex 60079-30-1 eb IIC T* Gb, II 2 D Ex 60079-30-1 tb IIIC
  • IECEX: Ex 60079-30-1 IIC T Gb, Ex 60079-30-1 IIIC T Db
  • cCSAus: Class I Division 2 Group A, B, C, D; Class II/III Division 2 Group E, F, G Ex 60079-30-1 IIC T Gb, Ex 60079-30-1 IIIC T Db

Specific Conditions of Use

  • Installation must be carried out in clean, dry conditions, and all cable ends must be protected from moisture.
  • The purchaser must inform the manufacturer of any external effects or aggressive substances that the equipment may be exposed to.

Product Usage Instructions

Before starting the installation process, please ensure that you have read and understood the product manual provided with your S-40 Heat-Shrinkable Splice Kit.

Step-by-Step Installation Guide

  1. Ensure that the installation area is clean and dry.
  2. Cut the heating cables to the required length, and strip the ends of the insulation to expose the conductors.
  3. Insert the conductors into the S-40 splice kit sleeve, ensuring that they are properly aligned and secured.
  4. Heat the sleeve using a heat gun or other appropriate heating tool until it shrinks around the conductors and forms a watertight seal.
  5. Allow the splice to cool and inspect it to ensure that there are no gaps or voids in the seal.
  6. If required, apply a layer of sealant or tape over the splice to provide additional protection against moisture and other external factors.
  7. Connect the heating cables to the power supply and test the system to ensure that it is operating correctly.

By following these instructions carefully, you can ensure that your S-40 Heat- Shrinkable Splice Kit is installed properly and will provide reliable and efficient performance for years to come.
By design with TraceCalc Pro® Engineering Software and as shown in the approval

WARNING : Please make sure the installation is carried out in clean, dry conditions and all cable ends are protected from moisture. Follow instructions carefully.
WARNING : The purchaser should make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to. Installation instructions for nVent RAYCHEM S-40 heat-shrinkable splice kit. For use with all nVent RAYCHEM XTV, KTV, HTV and VPL heating cable types.

INSTALLATION INSTRUCTION

nVent-RAYCHEM S-40-Heat-Shrinkable-Splice-Kit-
fig- \(3\) nVent-RAYCHEM S-40-Heat-Shrinkable-
Splice-Kit-fig- \(5\) nVent-RAYCHEM S-40-Heat-
Shrinkable-Splice-Kit-fig- \(7\) nVent-RAYCHEM S-40-Heat-Shrinkable-Splice-Kit-fig-
\(9\) nVent-RAYCHEM S-40-Heat-Shrinkable-
Splice-Kit-fig- \(11\) nVent-RAYCHEM S-40-Heat-
Shrinkable-Splice-Kit-fig- \(13\) nVent-RAYCHEM S-40-Heat-Shrinkable-Splice-Kit-fig-
\(15\)nVent-RAYCHEM S-40-Heat-Shrinkable-
Splice-Kit-fig- \(16\) nVent-RAYCHEM S-40-Heat-
Shrinkable-Splice-Kit-fig- \(18\)

Specific conditions of use

  • Maximum exposure temperature: 260°C (500°F)
  • Minimum installation temperature: –60°C (–76°F)
  1. Earth fault equipment protection is required for each circuit.
  2. De-energise circuits before installation or servicing.
  3. Keep ends of Trace heaters and kit components dry before and during installation.
  4. The electrically conductive covering of this trace heater shall be connected to a suitable earthing terminal.
  5. The presence of the trace heaters shall be made evident by the posting of caution signs or markings at appropriate locations and/or at frequent intervals along the circuit.
  6. The insulation resistance of the trace heater shall be measured and recorded after installation and shall not less than 20 Mohm.
  7. Persons involved in the installation and testing of electric trace heating systems shall be suitably trained in all special techniques required.
  8. Installation shall be carried out under the supervision of a qualified person.
  9. Refer to installation manual. A ground fault circuit interrupter shall be used with this device.

Important note: Heat shrink technique for S-40 kits Steps 18 and 21

Heat gun power for optimal shrinking time – 3000 W or greater is recommended. Lower power heat guns may work, but may require more time.
Recommended heat gun temperature: 600-650°C

  1. Set heat gun at recommended temperature, or as close as possible, and maximum air flow.
  2. Starting in the centre, hold heat gun in one position over the translucent heat shrink tubing until it turns clear (+/– 1 min). Then slowly move the heat gun around all sides until the heat shrink turns clear in this segment.
  3. Slowly move to an adjacent translucent position on one half of the splice and repeat for this next segment.
  4. Slowly continue along the length of heat shrink, rotating the heat gun at each segment until both halves are complete. Installation can take several minutes per piece of heat shrink tubing.
  5. Keep heat gun as close as possible to heat shrink (5 mm) but do not allow it to touch cable or heat shrink (to avoid burning and damaging materials). DE, FR, NL, NO, SV, DA, FI, IT, ES, PL, RU, CZ, HU, CRO: page 22-27

Bulgaria
Tel. +359 5686 6886 Fax +359 5686 6886 salesee@nVent.com
Česká Republika
Tel. +420 602 232 969 czechinfo@nVent.com
Denmark
Tel. +45 70 11 04 00 salesdk@nVent.com
Deutschland
Tel. 0800 1818205 Fax 0800 1818204 salesde@nVent.com
Españal
Tel. +34 911 59 30 60 Fax +34 900 98 32 64 ntm-sales-es@nVent.com
France
Tél. 0800 906045
Fax 0800 906003 salesfr@nVent.com
Hrvatska
Tel. +385 1 605 01 88 Fax +385 1 605 01 88 salesee@nVent.com
Italia
Tel. +39 02 577 61 51 Fax +39 02 577 61 55 28 salesit@nVent.com
Lietuva/Latvija/Eesti
Tel. +370 5 2136633 Fax +370 5 2330084 info.baltic@nVent.com
Magyarország
Tel. +36 1 253 7617 Fax +36 1 253 7618 saleshu@nVent.com
Nederland
Tel. 0800 0224978 Fax 0800 0224993 salesnl@nVent.com

nVent.com/RAYCHEM
©2022 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.
RAYCHEM-IM-EU1602-S40-ML-2205