Schneider Electric LC2D A Series TeSys Deca Reversing Contactor Instruction Manual
- June 10, 2024
- Schneider Electric
Table of Contents
Electric LC2D A Series TeSys Deca Reversing
Contactor
Instruction Manual
LC1DppApp / LC1DppA3pp / T02DN13pp
LC2DppApp / LC2DppA3pp / T02DN23pp
LC2D A Series TeSys Deca Reversing Contactor
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all power before servicing equipment.
Failure to follow these instructions will result in death or serious
injury.
WARNING
HAZARD OF FIRE OR ELECTRIC SHOCK
On contactors connected to a feeder circuit, it is mandatory to install large
spacing adapters GV3G66 on top and bottom connections of the contactor to
respect UL and CSA requirements in North America.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
AC/DC:
- use of this product in EMC environment B may require mitigation measures to avoid unwanted disturbance.
- full open AC at 10%Us.
WARNING
HAZARD OF FIRE OR ELECTRIC SHOCK (FOR CONTACTOR WITH UL HI-FAULT SHORT CIRCUIT CURRENT RATINGS ONLY)
- The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted.
- To reduce the hazard of fire or electric shock, current-carrying parts and the other components of the controller should be examined and replaced if damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Additional
ratings| Lighting
Tungsten| Lighting
Ballast| DefLill e Purpose ratings, 3Phase,
Load wiring: breaking all lines| Elevator Duty HP ratings
(except .D and .W DC coil)| High-Fault SCCR
Class J Fuse| High-Fault SCCR
with CB
---|---|---|---|---|---|---
Device| 600 V| 600 V| FLA| LRA| 1Ph
120 V| 1Ph
240 V| 3Ph
200 V| 3Ph
230 V| 3Ph
480 V| 3Ph
600 V| 600 V| 480 V| 600 V
240 V| 480 V| 600 V
LC1D40A| 60 A| 60 A| 40 A| 240 A| 200 A| 160 A| –| 5hp| 10hp| 10hp| –| –| 100
kA| 100 kA| 50 kA
LC1D50A| 70 A| 70 A| 50 A| 300 A| 250 A| 200 A| 3hp’| 7.5hp| 15hp| 15hp|
25hp| 30hp| 100 kA| 100 kA| 50 kA
LC1D5OANR,| –| –| –| –| –| –| –| –| –| –| –| –| 100 kA| 100 kA| 50 kA
LC1D65A/80A| 70 A| 80 A| | 390 A| 325 A| 208 A| 3hr| 10hp| 15hp| 20hp’|
25hp| 30hp| 100 kA| 100 1(A| 50 kA
Refer to information on device label when ordering replacement parts.
The product’s manufacture date is coded PPYYWWD, where:
- PP: plant code
- YY: year of manufacture
- WW: week of manufacture
- (D: weekday of manufacture (Monday = 1))
LC1D A6
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all power before servicing equipment.
Failure to follow these instructions will result in death or serious injury.
Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex
www.se.com
References
Read User Manual Online (PDF format)