Schneider Electric VC1GUN TeSys Vario Enclosed Emergency Switch Disconnector Instruction Manual
- June 10, 2024
- Schneider Electric
Table of Contents
VC1GUN TeSys Vario Enclosed
Emergency Switch Disconnector
Instruction Manual
VC1GUN TeSys Vario Enclosed Emergency Switch Disconnector
DANGER
HAZARD OF ELECTRIC SHOCK, 0 EXPLOSION, OR ARC FLASH
- Disconnect all power before servicing equipment.
- Close securely the enclosure before reapplying power.
Failure to follow these instructions will result in death or serious injury.
The product’s manufacture date is coded as
PP-YY-WW, where:
- PP: plant code
- YY: year of manufacture
- WW: week of manufacture
Eg: 2F1429 means the product manufactured at plant 2F on week 29 2014.
| a| b| c| c1| d
---|---|---|---|---|---
Vpp01GE / Vpp02GE /| 90| 146| 85| 131| 130
Vpp0GE / Vpp1GE /| 3.54| 5.75| 3.35| 5.16| 5.12
Vpp2GE / Vpp01GEGP/| | | | |
Vpp02GEGP /| | | | |
Vpp0GEGP / Vpp1GEGP| | | | |
Vpp3GE / Vpp4GE| 150| 170| 106| 152| 164
5.91| 6.69| 4.17| 5.98| 6.46
| | | | UL| UL
---|---|---|---|---|---
Wire gauge| Torque
mm²| mm²| N.m| AWG| lb-in
V01 / V02 / V0 / V1 / V2 VZ01 / VZ02 / VZ0 VZ1 / VZ2 / VZ11 / VZ14| 1×2,5…6
2×2,5…4| 1×2,5…10 2×2,5…4| 2,1| 14…8| 20
V3 / V4 / VZ3 / VZ4 VZ12 / VZ15| 1×4…16 2×4…10| 1×4…25 2×4…10| 4| 10*| 35
8| 40
2…4| 50
VZ7 / VZ20| 1×4 2×1…2,5| 1×4 2×1…2,5| 0.7| 14…12| 7
-
Use flexible wire only
-
Recommended wire
≤ 4 mm² (12 AWG) for VpppGEGP / Fil recommend
≤ 4 mm² (12 AWG) pour VpppGEGP
| a| b| c| c1| d| d1| e
---|---|---|---|---|---|---|---
VC1GUN VC2GUN| 121 4.76| 164 6.46| 87 3.43| 132,1 5.20| 50 1.97| 141 5.55| 98
3.86
VC3GUN VC4GUN| 164 6.46| 193 7.60| 87 3.43| 132,1 5.20| 100 3.94| 170 6.69|
141 5.55
* Use flexible wire only
| | | | UL| UL
---|---|---|---|---|---
Wire gauge| Torque
mm²| mm²| N.m| AWG| lb-in
V1 / V2 VZ11| 1×2,5…6 2×2.5…4| 1×2,5…10 2×2,5…4| 2,1| 14…8| 20
V3 / V4 VZ12| 1×4…16 2×4…10| 1×4…25 2×4…10| 4| 10*| 35
8| 40
2…4| 50
VZ7 / VZ20| 1×4 2×1…2,5| 1×4 2×1…2,5| 0.7| 14…12| 7
AB1VVN1035U| 2,5…10| 6…16| 4| 16…6| 35
AB1VVN3535U| 10…35| 10…50| 5,6| 10…2| 50
| (1)
---|---
I| II
V1 / V2| 25| 50
V3 / V4| 60| 125
SHORT- CIRCUIT PROTECTION
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 600 Volts maximum.
Main Circuit- Short-circuit protective device rating must comply with
applicable electrical codes.
Do not exceed rating (1) for the applicable protective devices :
I – Class RK1 (CSA HRC1-R) time delay fuse
II – Class J (CSA HRC1-J) or Class T (CS A HRC1-T) fuse
Control and Auxiliary Circuits – Electrical codes may require additional
overcurrent protection.
| | | | UL| UL
---|---|---|---|---|---
Wire gauge| Torque
mm²| mm²| N.m| AWG| lb-in
V5 / V6 VZ13 / VZ16| 1×10…70 2×10…35,| 1×10…95 2×10…35,| 22,6| 8…2| 200
VZ7 / VZ20| 1×4 2×1…2,5| 1×4 2×1…2,5| 0.7| 14…12| 7
| (1)
---|---
I| II
V5 V6| 125| 250
SHORT- CIRCUIT PROTECTION
Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 600 Volts maximum.
Main Circuit- Short-circuit protective device rating must comply with
applicable electrical codes.
Do not exceed rating (1) for the applicable protective devices :
I – Class RK1 (CSA HRC1-R) time delay fuse II – Class J (CSA HRC1-J) or Class
T (CSA HRC1-T) fuse
Control and Auxiliary Circuits – Electrical codes may require additional
overcurrent protection.
Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F-92506 Rueil Malmaison cedex
www.se.com
Printed on recycled paper.
BBV28752-09
recycled paper.
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom
www.se.com/uk
© 2021 Schneider Electric – All rights reserved.
Documents / Resources
|
Schneider Electric VC1GUN TeSys Vario Enclosed Emergency Switch
Disconnector
[pdf] Instruction Manual
VC1GUN, TeSys Vario Enclosed Emergency Switch Disconnector, VC1GUN TeSys Vario
Enclosed Emergency Switch Disconnector, VC2GUN, VC3GUN, VC4GUN
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>