GROWATT MAX 80-150KTL3 Inversor On Grid User Manual
- June 10, 2024
- Growatt
Table of Contents
MAX 80-150KTL3 Inversor On Grid
Product Information
The MAX-X Series solar inverters from Shenzhen Growatt New
Energy Co., Ltd are designed to convert the DC power generated by
solar panels into AC power suitable for use in homes or businesses.
The inverters are equipped with AFCI detection function and
anti-PID function to ensure the safety and reliability of the
system. The inverter can also be remotely monitored through a
communication cable connection.
Applicable Personnel
Only qualified electrical technicians should install the MAX-X
series inverter. To ensure proper installation and operation, it is
important to read through the installation and operation manual
carefully and follow all safety precautions. If there are any
problems during installation or operation, contact the
manufacturer’s customer service hotline or log on to their website
for assistance.
Safety Precautions
-
Read through the entire manual before installation to avoid
damage caused by improper installation. -
All operations and connections must be done by a trained and
qualified electrical technician. -
Do not touch any inside part of the inverter except for
terminals during installation. -
All electrical connections must meet local safety
regulations. -
Contact an authorized technician for maintenance and
replacement of parts. -
Get local power supplier’s permit before connecting the
inverter to the grid.
Product Usage Instructions
Installation
Before installation, make sure to read through the entire
installation and operation manual. All operations and connections
must be done by a trained and qualified electrical technician. The
following steps should be taken:
-
Ensure that all electrical connections meet local safety
regulations. -
Connect the AC side and DC side cables as instructed in the
manual. -
Connect the communication cables between the inverter and
monitoring device. -
Connect the ground cables.
-
Install the inverter on a wall or other suitable location,
taking into account the installation environment requirements.
Commissioning
After installation, the inverter needs to be commissioned before
it can start working. The following steps should be taken:
-
Turn on the AC and DC switches on the inverter.
-
The inverter will enter “Standby” mode, and then “Startup”
mode. Check the LED display for any error codes. -
If there are no error codes, the inverter will enter “Normal”
mode and start working.
Monitoring
The MAX-X series inverters can be monitored remotely through a
communication cable connection. The monitoring device should be
installed according to the manufacturer’s instructions. The
following steps should be taken:
-
Install the monitoring device according to the manufacturer’s
instructions. -
Connect the communication cables between the monitoring device
and inverter. -
Use the monitoring device to check the performance of the
inverter and identify any issues that may arise.
Maintenance
To ensure proper operation of the inverter, routine maintenance
should be performed by an authorized technician. The following
steps should be taken:
-
Disconnect the AC and DC switches before performing any
maintenance. -
Check for any damage or wear on the components, and replace as
necessary. -
Clean the inverter and surrounding area regularly to prevent
dust build-up.
Download Manual
Growatt New Energy
Shenzhen Growatt New Energy Co., Ltd 4-13/F,BuildingA,Sino- German(Europe)IndustrialPark, HangchengAve,Bao’anDistrict,Shenzhen,China T:+86 755 27471942 E:service@ginverter.com W:www.ginverter.com
GR-UM-241-A-00
Installation & Operation Manual
1 Overview 2 Safety Precautions 3 Product Introduction 4 Unpacking 5 Installation
List
1.1 Product Overview 1.2 Applicable Personnel
2.1 Safety Overview 2.2 Symbol 2.3 Meaning of Symbol
3.1 Appearance 3.2 Dimensions 3.3 Nameplate 3.4 Working Principle 3.5 Inverter
Storage 3.6 Grid Types 3.7 AFCI Detection Function 3.8 Anti-PID Function
5.1 Basic Installation Requirements 5.2 Installation Environment
Requirements 5.3 Moving Requirements 5.4 Wall Mounted Installation 5.5
Installing the Inverter
6 Connecting Cables 7 System Commissioning 8 Monitoring 9 Maintenance 10 Product Specification
6.1 Connection on AC side 6.2 Connection on DC side 6.3 Connection of
Communication
Cables 6.4 Connecting the Ground Cables
7.1 Inverter Commissioning 7.2 Modes 7.3 LED display
8.1 Remote Data Monitoring 8.2 Local Data Monitoring
9.1 Routine Maintenance 9.2 Trouble Shooting
11 Decommissioning 12 Quality Assurance 13 Contact Us
1 Overview
1.1 Product Overview
This manual is aimed at providing sufficient information and installing
instruction for consumers buying Shenzhen Growatt New Energy Co.,Ltd (short as
Growatt) MAX-X Series solar inverters. Please read this manual carefully
before using the MAX-X series inverters and store the manual in a reachable
place for an authorized technician. No further notice if there is any change
in this manual.
1.2 Applicable Personnel
Only qualified electrical technicians are allowed to install MAX-X series
inverter. With reading through this manual and following all the precautions,
qualified electrical technician can properly install MAX-X serial inverter,
finish trouble shooting and communication settings.
If there is any problem during the installation, the installer can either log
on www.ginverter.com and leave a message or call consumer service hotline +86
755
27471942.
2 Safety Precautions
2.1 Safety Overview
1>Before installation please make sure reading through this manual, any damage
caused by improper installation, Growatt reserve the right to disclaim any
warranty. 2>All the operations and connections must be done by trained
qualified electrical technician. 3>During installation except for terminals,
do not touch any inside part of the inverter. 4>All the electrical connections
must meet local country’s safety regulations.
5>If you need maintenance for this inverter, please contact our local
authorized
installing and maintenance technician. 6>You must get the local power
supplier’s permit before connecting this inverter to the grid.
H a n d l e P r o c e s s
WARNING
·The inverter is heavy,please treat with care while handling,in case of crushing injury.
Installation NOTICE
·Before installation,please read through this manual,any damage cause by improper installation,Growatt reserve the right to disclaim any warranty.
DANGER
·Ensure that the inverter is not connected to a power supply and is not power on before installation.
1
WARNING
·Please follow this installation manual as installation condition environment,space and so on. ·Please install the inverter in a dry and ventilated environment,otherwise may affect the performance of the inverter. ·Please follow the installation procedures in this manual.
Electrical Connections:
DANGER
·Before electrical connection, please ensure the inverter DC switch is
at “OFF” also disconnect AC switch, otherwise the high voltage from
inverter may cause life risk. ·Only trained authorized electrical technician
can do the electric connection also please follow the connection procedures in
this
manual along with local country’s regulations. ·High voltage may cause
electric shocks and serious injury please
do not touch the inverter. ·Please do not store inverter in area with
flammable and explosive material.
WARNING
·Each inverter must install one AC breaker; AC breaker is forbidden to share
with other inverters.
·It is forbidden to add load between inverter and breaker. ·If the cable is
thick, after tightening the cable do not shake it and ensure the cable is
well-connected and then start the inverter.Loose connection may cause
overheat. ·Before connecting between PV panels and inverter please ensure the
positive and negative poles are correct connected.
Maintenance and replacement:
DANGER
·Must be installed by trained and authorized electrical technician and accurately follow this manual. ·Please disconnect the DC and AC switch for at least five minutes, all the operations should be carried after power disconnection. ·If there is PV isolation low alarm, the inverter case may be ungrounded, please do not touch the inverter case. ·High voltage of inverter may result in electric shock.
WARNING
·For better cooling purpose, please regularly clean the fans. ·Do not use air pump to clean the fans, cause it may damage the fans.
2
Other
·After you receiving the inverter please check the packing materials for damage,if there is any damage please contact your supplier.
WARNING
·The Max PV input voltage should not exceed 1100V. ·For the disposed inverter,the consumer should dispose it according to local disposal rules for electrical equipment waste.
2.2 Symbol Conventions
Symbol
Description
DANGER WARNING
Indicates an imminently hazardous situation which,if not avoided, will result in serious injury or death. Indicates potentially hazardous situation which,if not avoided,will result in serious injury or death.
CAUTION
Indicates potentially hazardous situation which,if not avoided,will result in minor or moderate injury.
NOTICE
Indicates certain hazardous situation which,if not avoided,will rusult in property damage.
Reminds operator to read installation manual before operating or installing inverter.
2.3 Lable Description
Symbol
Name
Meaning
High Voltage Electric Shock
Inverter operating with high voltage,any operation regarding inverter need to be done by trained and authorized electrical technician.
Burn Warning
Do not touch a running inverter cause it generates high temperature on the case.
Protective Grounding
Connect inverter to grounding bar.
Delay discharge
Residual voltage exists after the inverter is powered off,it takes 5 minutes for the inverter to discharge to the safe voltage.
Read the installation
manual
Reminds operator to read installation manual before operating or installing inverter.
DC
Means this terminal is for DC side.
AC
Means this terminal is for AC side.
CE Mark
The inverter complies with the requirements of the applicable CE guidelines.
3
4
3 Product Introduction
3.1 Appearance
Front view:
Bottom view(Termial):
Fig 3.1
Side view:
Fig 3.2
Fig 3.3 5
Mark A B C D E F G
Description Front panel LED PV terminal DC switch
Breathing valve External fans USB interface
3.2 Basic Data
Model
MAX-X Series Inverter MAX-X Series Inverter
with package
Width 970 1095
3.3 Nameplate
Mark H I J K L M
Description COM interface Corner guard Waterproof silicone pad Junction Box
Ground screw hole
Heat sink
Size(mm) Height
640
Thickness 345
Weight (kg) 84
765
500
98
Note: Other models of MAX-X series share the same label design with
MAX125KTL3-X LV, only with different model name and parameters, detail
parameter please refer to specification in Chapter 10.
6
3.4 Working Principle
The MAX-X series inverter works as follows: 1>The PV panels gather solar to
generate DC power to inverter. 2>With input current detection circuit, it can
monitor all the PV panels’ working status and use MPPT to track the maximum
power point. 3>With inverter circuit change DC power to AC power, and feed
power back to grid per grid reuqirement. 4>With output isolation relay can
isolate AC output and grid, if anything goes wrong on either inverter side or
grid side, isolation relay can disconnect inverter immediately.
On-grid connection system diagram:
A
symbol A B
B
C
D
Fig 3.4
Description symbol
Description
PV string Inverter
C
Electric meter
D
Gird
3.5 Inverter Storage
1>Do not unpack the inverter and store it in a ventilation dry place . 2>Keep
the storage temperature at -30 – +60 and humidity at 0-95%. 3>A maximum of
three inverters with package can be stacked. 4>If the inverter has been long-
term stored, inspections and tests should be conducted by qualified personnel
before it is put into use.
After being stored for a month or longer, the inverter’s time and date could
be wrong, you need set the time and date before using, for more details please
refer to Chapter 7.1 inverter commissioning.
3.6 Grid Types
The MAX-X series, MAX100-133KTL3-X LV inverters connect to the grid like
following drawing 3.5,MAX 125-150KTL3-X MV inverters connect to the grid like
following drawing3.6.
7
400V
230V
400V
230V
230V
4 80V
480V
400V
Fig 3.5
4 80V
Fig 3.6
3.7 AFCI Detection Function
AFCI (Arc Fault Circuit Interrupter) is a kind of circuit protection device,
the main function is to prevent the fire caused by fault arc.The electrical
insulation aging, breakage, loose connection, air breakdown caused by air
humidity and so on, all of these may cause an electric spark,which is called
arc. The AFCI function of the MAX-X series inverter is optional, and the
detection equipment is assembled inside the inverter. When an arc-drawing
condition is detected on the PV input side, the arc current could be detected
by the CT assembled on the PV input-side wire. Then the inverter will shut
down. Meanwhile, the inverter will display the corresponding fault message and
the buzzer will sound, which could help to avoid harm and economic loss to the
user.
NOTE: AFCI function is optional.
3.8 Anti-PID Function
The full name of PID is Potential Induced Degradation. Since the PID effect, a
large amount of charge could accumulate on the surface of the photovoltaic
module, which makes the surface passivation of the module worse. Eventually,
the fill factor, opencircuit voltage, and short-circuit current of the module
are reduced, and the power of the photovoltaic module is attenuated. The Anti-
PID function uses the principle of reversible PID changes. MAX-X series
inverters rectify AC voltage at night and boost it to generate a DC voltage.
The DC voltage is connected to PV + and the ground respectively. When add a
positive bias voltage to the module to make the PID effect reverse,the Anti-
PID function could repair the photovoltaic modules at night and prolong the
service life of photovoltaic modules.
NOTE: Anti-PID function is optional.
8
4 Unpacking
Checking before installation 1>Before unpacking the inverter, check the outer
packing materials for damage. 2>After unpacking the inverter, check that the
contents are intact and complete. If any damage is found or any component is
missing, contact your supplier.
Package contents:
A
B
C
D
E
F
Mark A B C D E F G H I J K L
G
H
I
J
Fig 4.1
K
L
Descriptions Inverter
Wall mount PV + terminal, PV- terminal
PV terminal metal core Removal tool of PV terminals
Installation manual Warranty card
Communication terminal Removal handle(opt)
M1090 Expansion screw M628 stainless steel screw AC wiring copper terminal
(opt)
Number 1 1
20/20 20/20
1 1 1 1 2 4 2 4 or 5
9
Installation 5
CAUTION
·To prevent device damage and personal injury, keep balance when moving the inverter because it is heavy. ·Do not place the inverter with its wiring and signal terminals at the bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter. ·When placing inverter on the floor, put foam or paper under the inverter to protect its cover.
5.1 Basic Installation Requirements
A. Ensure that the installation wall is solid enough to bear the
inverter(Inverter weight please refer to installation manual Chapter3, 3.2 ).
B. There must be enough installation space to fit the size of inverter. C. Do
not install inverter on flammable or heat-intolerant buildings. D. This
inverter is IP 66 protection, you can install it indoor or outdoor. E. To
avoid inverter performance de-rate due to the over heat, please do not expose
the inverter under direct sunlight. F. The installation humidity should be
from 0-95%. G. The surrounding temperature of inverter should be from -30 –
+60. H. Inverter should be installed in a vertically or rear tilted surface,
please refer to following drawings.
Fig 5.1 I. To ensure the inverter can work smoothly and easy for personnel to operate, please notice there is sufficient space for inverter, refer to following drawing.
600mm
600mm
1000mm
600mm
600mm
Fig 5.2
10
J. Do not install inverter close to strong electromagnetic signal. K. Install
the inverter out of children’s reach.
5.2 Installation Environment Requirements
A. Although the inverter’s protection level is IP 66, to extent inverter
lifespan you still need to avoid rain and snow, please refer to following
drawings.
Fig 5.3 B. To reduce the de-rate performance of the inverter and extend
inverter’s life span, we strongly recommend you install an awning, for the
distance between an awning and inverter, please refer to following drawing.
Fig 5.4 C.When you install multiple inverters on one surface, inverters should
be installed as following drawing. 11
Fig 5.5 D. Do not install inverter into an enclosed space like following
drawing.
Fig 5.6
5.3 Moving Requirements
·The inverter is heavy, please move it with care and keep balance to avoid
personnel injury. ·Do not place the inverter with its wiring and signal
terminals at the WARNING bottom contacting with floor or any other object
because the terminals are not designed to support the weight of inverter. Plan
1 1>As shown in Fig5.7, use a rope to tie at ring and handle, lift the
inverter from package and move to installation position. 2>When you are moving
the inverter, please keep the balance.
Notice: There is front and bottom mark on the package.
12
Plan 2(Optional):
1>As shown in Fig5.8, 4-6 persons lift the inverter out of package, swap the
ring to
moving handles.
2>When you are moving the inverter, please keep the balance. Notice: There
will be front and bottom mark on the package.
1>Use the wall mount plate as a template drill holes on the wall and put in expansion bolts.
Fig 5.7
Fig 5.8
5.4 Wall Mount Bracket Installation
Before install the inverter you need install the wall mount bracket so that
the inverter can be firmly installed on the wall. Wall mount plan:
Fig 5.9 13
Fig 5.10 NoticeExpansion bolt should be installed on solid walls with at least
100mm thickness. 2>Follow the following drawing put the bolt to install the
wall mount plate on the wall.
Fig 5.11 Notice: Do not install inverter unless you have confirmed the wall
mount plate has been firmly installed on the wall.
5.5 Installing The Inverter
After the wall mount bracket has been firmly installed on the wall , put the
inverter on that plate. 1>Use the rope(must meet the weight requirement of the
inverter) through two rings and lift the inverter up, just as following
Figure. 2>Before hanging the inverter on the wall mount bracket use screws to
fix the inverter and please keep the inverter balance. 3>Check the inverter if
it is firm enough and lock all the screws.
14
5.12
5.13
5.14 15
Connecting Cable 6
Decisive Voltage Class (DVC) indicated for ports
Port Name
Class
AC
C
DC
C
DRMS
A
RS485&USB
A
6.1 Connection on AC side
·Before electrical connection, please ensure the inverter DC switch is at
“OFF” also disconnect AC switch, otherwise the high voltage from inverter may
cause life risk. ·Only trained authorized electrical technician can do the
electric connection also please follow the connection procedures in this
manual DANGER along with local country’s regulations. ·High voltage may cause
electric shocks and serious injury please do not touch the inverter. ·Please
do not store inverter in area with flammable and explosive material.
·Each inverter must install one AC breaker, AC breaker is forbidden to share
with other inverters. WARNING ·It is forbidden to add load between inverter
and breaker.
Preparation before connection:
1>Disconnect inverter DC switch and AC breaker or switch. 2>When you lock the
AC cable’s screw, the torque force should be 30kgf·cm.
When you lock the cover screw, the torque force should be 20kgf·cm. 3>Measure
the grid voltage and frequency, please refer to chapter 10. AC breaker
specification
Inverter model MAX 100KTL3-X LV MAX 110KTL3-X LV MAX 120KTL3-X LV MAX 125KTL3-X LV MAX 133KTL3-X LV MAX 125KTL3-X MV MAX 136KTL3-X MV MAX 150KTL3-X MV
Breaker model 200A/400Vac 250A/400Vac 250A/400Vac 250A/400Vac 250A/400Vac 200A/500Vac 250A/500Vac 250A/500Vac
16
Cable specification:
Inverter Model
MAX 100KTL3-X LV MAX 110KTL3-X LV MAX 120KTL3-X LV MAX 125KTL3-X LV MAX
133KTL3-X LV MAX 125KTL3-X MV MAX 136KTL3-X MV MAX 150KTL3-X MV
Copper wire crosssectional area(mm²)
70-240
Copper wire recommendation (mm²)
Aluminum wire recommendation (mm²)
70
95
Notice:The cable must be unbroken.
When using aluminum alloy cables, please use copper-aluminum transition
terminals.
AC side connection steps:
·If the cable is thick, after tightening the cable do not shake it and ensure the cable is well-connected and then start the inverter. Loose connection WARNING may cause overheat.
1>Following drawing shows inverter’s AC terminal, R, S, T are three live lines, N is Neutral line.
2>Determine the stripping length (approximately 30mm) according to the specifications of the crimping terminal. Use crimping tools to crimp the wires and terminals, then connect the cables to the corresponding channels through the waterproof interface, and tighten the screws.
Diagram of how to install a terminal:
Fig 6.2
Fig 6.3 3>Apply fireproof mud to the threading holes on the waterproof
silicone pad to prevent the risk of water ingress, as shown in the figure
below.
·The gaps in the cable threading holes must be blocked,otherwise there will be
a risk of water leakage. WARNING
Fig 6.1 17
Fig 6.4 18
6.2 Connection On DC Side
·Before electrical connection, please ensure the inverter DC switch is at
“OFF” also disconnect AC switch, otherwise the high voltage from inverter may
cause life risk. ·Only trained authorized electrical technician can do the
electric connection also please follow the connection procedures in this
manual along with local DANGER country’s regulations. ·High voltage may cause
electric shocks and serious injury please do not touch the inverter. ·Do not
place flammable or explosive materials around the inverter.
Notice: The sunlight will generate voltage on the solar panels, after serial
connection, the high voltage may injure personnel, so before connect DC input
cable you need cover solar panels with light-tight materials and make sure the
inverter DC switch is at “OFF” status, otherwise high voltage may injure
personnel.
·Each string’s maximum open circuit voltage cannot exceed 1100Vdc, other-
wise it could lead to fire or damage the inverter. If the inverter was damaged
by higher maximum open circuit voltage (higher than 1100Vdc) product
WARNING
warranty will ·The inverter
be forfeited and Growatt will not take any responsibility. shall be used with IEC 61730 Class A rating PV module.
·When the group is suspended, be sure to use dust plugs to block up to
prevent entering the water into the dust.
1>Each string solar panels should be same brand and same model. 2>Under any circumstance, the maximum short circuit current should not exceed 32A. 3>The total panels power should not exceed 1.5 times of inverter input power. 4>To optimize system settings, recommend two strings with same amount solar panels. Notice: Connectors need to be fit with male and female terminals, before connecting panels with inverter please make sure the positive pole and negative pole, namely the solar panels’positve pole connect to”+” negative pole connect to”-“.
Fig 6.5
5>Decide the length of peeling base on cable terminal, use the wire stripper
to connect cable and terminal, and separately connect to specific connector.
19
6>Connect the positive and negative poles to inverter terminals, different inverter’s maximum single string input current please refer to following table.
Inverter model
Max. single string input current
MAX-X serial inverter
16A*2
7>Cable specifications:
Inverter model MAX-X serial inverter
Cross-sectional 4-6
Recommendation 4
Cable outer 4.5-7.8
Notice1.Under any circumstance, the total current of all strings cannot exceed the inverter’s maximum current. 2. Do not touch any working solar panels. 3. Make sure the cable is unbroken.
6.3 Connection Of Communication Cables
6.3.1 RS485 port
RS485 can carry out single-machine communication or multi-machine (32pcs)
longdistance (500 meters) high-speed (baud rate 38400) communication. It is
recommended to use twisted-pair shielded wire for RS485 communication line.
For single-machine communication, the communication line can be connected to
pin 3/4, and its shielding layer can be connected to pin 1. When multiple
machines are connected in parallel, two RS485-1 ports can be connected at the
same time. When used, the shielding layer can be connected to pin 1/2.
Port
PIN
Shield ground ½
3
RS485-1 IN
4
5
RS485-1 OUT
6
7
RS485-2
8
Description 485-1 PE Shield
485-1 A1 485-1 B1 485-1 A1 485-1 B1 485-2 A1
Fig 6.6 Port
DRMS
PIN Fig 6D.e6scription
9
DRM1/5
10
DRM2/6
11
DRM3/7
12
DRM4/8
13
REF/GEN
14
DRM0/COM
485-2 B1
RS485-1Matching resistance
15/16
485-1Matching resistance
Notice: When multiple inverters communicate in parallel, the last machine
needs to add matching resistance. The method is to use a wire to connect the
pin 15/16 together.
20
In MAX-X series inverters, RS485 interface is standard. The connection steps
of RS485 communication line are as follows: 1) Unscrew the waterproof cover of
the COM interface and remove it. 2) Connect the RS485 communication line to
the port of 485-1. 3) The inverter is connected hand in hand through the RS485
communication line, and the end of the communication line 485_A/B is connected
to the monitoring equipment to realize multi-machine remote monitoring. Note:
When locking the RS485 cable screw, the torque is 4kgf·cm.
Fig 6.7
6.3.2 USB port The MAX-X series inverters are equipped with a USB interface as
standard, which can be connected to a USB to WIFI module, Shine GPRS-X2, Shine
WIFI-X, Shine 4G-X, Shine Link-X and other optional monitoring modules to
realize remote Monitoring function. In addition, you can also quickly upgrade
the inverter software through the U disk. Steps to install the monitoring
module: 1> Loosen the waterproof cover of the USB interface and remove it. 2>
As shown in Figure 6.8A, insert the Shine GPRS-X2 module into the USB
interface, and the LED of the Shine GPRS-X2 module will be on. 3> As shown in
Figure 6.8B, make sure that the is facing upwards, insert the monitoring
module into the USB interface, and tighten the lock. Note: If you use a USB to
WIFI module, when the operator leaves, please take the module and the data
cable away, and tighten the waterproof cover to prevent water from entering
the interface.
Installation up
Fig 6.8A
The Inverter Side
Remove
The Inverter Side
The Inverter Side The Inverter Side
Fig 6.8B
21
22
6.4 Connecting The Ground Cables
In this solar system all the unloaded metal components and cases should be
connected to the ground. Single inverter need grounding over a PE point,
multiple inverters need connect all the inverter PE cable and solar panels
shelves to the same grounding point to achieve equipotential. The grounding
steps as following: Take out the ground screw at the inverter bottom, connect
the ground cables as following figure. Notice: 1.The machine is safely
separated from the lightning protection and the distance is as far as
possible. 2.Do not expose Grounding terminal in the air and precaution for the
rain. 3.When you lock the case ground screw, the torque force should be
60kgf·cm.
Fig 6.9
According to the relevant provisions of IEC 61643-32 “Connecting to photovoltaic devices surge protectors – selection and use of guidelines”, whether for household or outdoor photovoltaic power plants, it is necessary to ensure the implementation of lightning protection measures for photovoltaic systems:
WARNING
The lightning protection measures for photovoltaic systems shall be carried out in accordance with the corresponding national standards and IEC standards. Otherwise, photovoltaic devices such as components, inverters and power distribution facilities may be damaged by lightning. In this case, the company does not carry out warranty and assumes any responsibility.
23
Lightning down the line
Lightning protection device
Photovoltaic panel
Safety
interval S
4
Inverter
1
2
Grounding bar
Distribution Cabinet
3
Power grid
SPD
Lightning down the line
Equipment ground wire Total grounding point
Fig 6.10
1It is generally recommended to install lightning protection devices (such as
lightning rods / lightning protection belts and down conductors) to prevent
lightning from hitting the PV array. 2 Lightning protection devices and down-
conductors and related equipment in photovoltaic systems (including
photovoltaic panels, inverters, cables, power distribution equipment) should
maintain a safe separation distance S. Suggested value of S: According to the
general 5 storey height (about 15m) building roof, S takes 2.5m enough, this
distance can be simplified according to the inverse relationship of the floor
height. A. When the safety distance S is satisfied: The position of the figure
should be equipped with a lightning protection module. In general, it is
recommended to install Type II in position and Type I in position . B. When
the safety and safety distance S is not met: In addition to position 3, Type I
lightning protection module should be installed in Figure
. 3 The lightning down conductor and the equipment ground wire eventually sink
at a total ground point, but the two cannot share the wire. That is, the
equipment grounding wire should be pulled separately, and the wire diameter
requirement >6mm² when the safety interval distance S is satisfied. 4 About
the above lightning protection lightning receptor system related design
reference GB/T 21714.3-2015.
24
7 Commissioning 7.1 Commission The Inverter ·If the inverter is stored over
one month, its default time and date may looks wrong, the time and date should
be reset before connection to the grid. The inverter will be set to the
appropriate model according to the standards of different countries or regions
before leaving the factory. For example, the inverters shipped to Australia
are configured as Australian model in the factory. Note: The inverter is
configured for Australia at the factory. 7.1.1 Set inverter address After
inverter is started normally, inverter address can be set via RS485/USB
converting to WIFI.When multiple inverters are connected in parallel via
RS485, the inverter must be set to a different communication address. When a
single inverter communicates, the default communication address can be used.
Note: The default communication address of the inverter is 1, which can be set
to 1-254.
7.1.1.1 Set RS485 address with Shinebus The 485 address of the inverter can be
modified by Shinebus This operation is
performed by a professional.
7.1.1.2 Set RS485 address on ShinePhone APP Refer to 8.2 download mobile APP
ShinePhone and connect to inverter WIFI to enter local monitoring page, this
operation is performed by a professional. 1>Click “Parameters”; 2>Enter
passwor.(When you use it for the first time, you need to set the password
first. Click “Reset password” to enter the OSS account number and password.
The distributor and installer can apply for the OSS account from Growatt.
Click “Sign in” to set the password. After the setting is successful, you can
start using it.) 3>Click top item “COM Address”; 4>Click the “Read” button in
the upper right corner to read the current communication address of the
inverter; 5> Set inverter com address; 6>Read inverter com address to ensure
setting is successful;
25
3 2 1
4
5 6
7
8 9
Fig 7.1
26
7.1.2 Set inverter time and date Method 1: Please refer to section 8.2.1 and
login ShinePhone APP.Click “system time(45-50)”to set inverter time and date
on the parameter setting page.
Fig 7.2
7.2 Operation Mode
7.2.1 Waiting mode When the DC voltage is more than 180Vdc, inverter will be
powered on and enters the “waiting” state. At this mode, inverter will check
the system parameter. If the system is normal and PV voltage is more than
195Vdc, inverter will try to connect to the grid. 7.2.2 Working mode At this
mode, inverter work normally,and the Power or fault code indicator light shows
the power delivered by the inverter to the grid. When the DC voltage is more
than 180Vdc,inverter converts the DC power generated by the PV modules into AC
power and supplies them to the grid. When the DC voltage is lower than 180Vdc,
inverter will enter into “waiting” state and try to connect to the grid, at
this status, inverter consume very small power to check the internal system
status. Note: only when the PV modules supply enough power(voltage 195Vdc)
then the inverter will start automatically. 27
7.2.3 Fault mode Inverter intelligent control system will continuously monitor
and adjust system status.When there is a fault detected, LED will show the
fault message. Note: Please refer to section 8.2 to check the fault message
and take corrective measures.
7.2.4 Off mode When the sunlight is weak or no light, inverter will stop
working automatically. When it is off, inverter will not consume gird power or
PV module. At the same time, the LED of inverter will be turned off. Note:
When PV string DC voltage is too low(150Vdc), inverter will be off.
7.3 LED Display
Inverter current operation status can be visually checked from LED display
directly.
E
A
D
B
C
Fig 7.3
Fig 7.4
Description of LED status
Position of LED
Type of LED
Inverter status
LED status
A
PV voltage indicator light
PV voltage reaches grid voltage PV voltage does not reach the grid voltage
Green light is on Light is not on
Inverter is in the grid state Green light is on
B
AC voltage
No AC voltage
indicator light
Light is not on
With AC voltage, inverter is in the grid countdown state
The green light flashes slowly, and the alarm or fault indicator light is not on
28
Description of LED status
Position
of LED
Type of LED
B
AC voltage indicator light
Inverter status
LED status
With AC voltage, inverter is in a fault state
The green light flashes slowly, and the alarm or fault indicator light is steady red.
Inverter works normally Light is not on
C
Alarm or fault indicator light
Inverter is in alarm state Red light flashes slowly
Inverter is in fault state
Red light is on
Inverter has external communication, such as RS485, GPRS, etc.
Green light is on
D
Communication Inverter has no external
indicator light
communication
Light is not on
Inverter upgrade or USB interface is reading and writing data
Green light flashes
Inverter is in the grid state
The eight LEDs from left to right represent the power of the inverter: if 8 green lights are on, it represents 100% of the inverter power. As shown in Figure 7.3, it represents 37.5% of the inverter power, and so on.
Power or fault
E
code indicator
light
The 8 LED lights from right to left represent the fault codes currently reported by the
inverter. From right to left, they
represent 1, 2, 4, 8, 16, 32, 64,
Inverter is in fault state
and 128. For example, the first and fourth green LEDs on the
right are always on, which
means 1+8=9. In addition, add
200 to get 209, which means
the inverter reports fault 209,
and so on.
29
Monitoring 8
8.1 Remote Data Monitoring
MAX-X series inverter remote monitoring ways include APP(ShinePhone) and
server Web page, RS485,GPRS,4G,PLC(reserved) can satisfy both ways of
monitoring. 8.1.1 Mobile phone APP(ShinePhone) remote monitoring 1>Scan the
following QR code, or download from Android store or App store by searching
“Shinephone”, download and install software.
Fig 8.1 Note: 1.Make you it’s the latest version.
2.Please find more details on http://server.growatt.com.
2>Users can register their mobile APP account by following the steps below:
Run ShinePhone, go to login page, click “register”.Registration is required to
fill in the information, with the * is required, the agreement is mandatory,
you can log in to the main interface of ShinePhone after registration, the
registration page and the main interface are as shown below. Shinephone login
and main page:
Fig 8.2
Fig 8.3 30
Device page: 1>Main page top middle is the name of current plant, user can click the “” button to switch to other plants under this account. 2>User can add datalogger,check datalogger and add plant by click”+”button at the top right corner. 3>Top half shows current plant power, revenue today and total production. 4>My device list shows current plant device, user can see more details by click the device, left cross the device to stick the device and edit, edit operation includes change device alias, icon,and delete device.
2>User can add datalogger at the datalogger list page to add a datalogger,
edit, delete, configure etc. 3>User can add more plants with the add Plant
function.
Device page and function: 1>Device page: User can click the device to see more
details, the device page show current power and Energy today and daily power
chart, user can find more with control,parameter, data and Events page.
2>Control: user set inverter on/off, set active power, set reactive power, set
PF, set inverter time, set grid voltage high, set grid voltage low. The
operation password is : inverter+date, for example inverter20170722.
3>Parameter: user can see device SN, rated power, firmware version, PV1
voltage, current, and power etc.
Fig 8.4 add datalogger
Fig 8.5 datalogger list
Fig 8.6 add plant
Datalogger: 1>User can add more datalogger under the particular plant.
Way: Click “+” in the upper right corner of the device page and select “Add
Collector (WiFi/GPRS, etc.)”, as shown in Figure 8.7. Note: You can choose to
manually enter the collector serial number for addition, or you can add it by
scanning the barcode on the nameplate.
Fig 8.7 31
Fig 8.8
Fig 8.9
Fig 8.10
4>Data page: user can see the PV power, voltage, current, R phase power, S phase power, S phase power, T phase power, output power by day, month, year, by finger up cross the screen. 5>Events: User can see the fault message if there it is.
32
Fig 8.11
Fig 8.12
. . 8 1 2 GPRS /4G
. . . 8 1 2 1 Register account
1>Register account Open browser, input “server.growatt.com”, click “New User”
at login page, input the necessary information then go back to login page,
input the registered username and password, click “Sign In”.
Fig 8.14
2>Add datalogger At Plant page, click device manage, then click add
datalogger, input the SN and valid code then save, after device is powered on,
datalogger will show after 5mins, also the device will come online(our device
is monitored by datalogger, so need to add the datalogger here first).
Fig 8.13 33
Fig 8.15 34
Fig 8.16
Fig 8.17
Fig 8.19 B. Plant data page can check device power, voltage curve by time, day, month or year.
Fig 8.18 3> Data reading A.Basic production reading, Energy today, total production, revenue today and accumulative revenue are showing on this page.
Fig 8.20
35
36
4>Set up the equipment The device management page selects MAX. The serial number of the device to be set can be found in the list. Notice: The following operations are requested by professionals.
Fig 8.21
Fig 8.22 5>Check detailed data Double-click the device serial number in the
device list. The detailed data page is displayed. Data pages can be viewed by
date or exported.
Fig 8.23 37
Fig 8.24
8.1.2.2 Shinemaster monitoring This is a cost-effective and compact monitoring
device that is specially designed for solar power plants, with a high-speed
CPU and a stable Linux system that intelligently records the user’s system
characteristics.
Multiple inverters
ShineMaster
cable
Router
485-1 IN
485-1 OUT 485-1 IN
Add matching resistance
RS485 twisted pair cable
Feature 1> A versatile and high-performance communication data logger that
notifies the user
of system status at any time.
2> Flexible parameter setting, system information management, error prompting
and
recording, high-capacity storage. 3> Collect data and upload data to Growatt
in real time over the network.
Note: The smart meter and environmental monitor must be Growatt’s designated
manufacturer, otherwise monitoring will not be possible. When RS485 of
multiple
machines is used in parallel, please connect the ground wire according to
section 6.3.1.
38
The system framework of communication monitoring is shown in the figure below.
Users can choose the most suitable monitoring method according to the actual
situation.
Multiple inverters RS 485
GPRS/4G
ShineMaster
Computer
Connecting communication cable
router Connecting communication cable
Internet
Connecting communication cable 4G/GPRS
Connecting communication cable 4G/GPRS
DB
data storage
Computer
Phone
Pad
39
1>ShineMaster IP Address query A.The PC and shinemaster lan ports are
connected to the router’s port through the network cable, so that they are in
the same local area network. B. Go to the router’s management page and check
the “Internet host list” to query the IP address of the ShineMaster serial
number as the name of the connected device. This IP is the IP address assigned
by the router to the ShineMaster. If you do not know how to do this, contact
your network administrator for operation. Note: The router needs to enable
automatic IP assignment, that is, open the DHCP function. C. Enter the
shinemaster IP address in the browser to enter the shinemaster built-in page.
2>ShineMaster Built-in page access Before accessing, check whether the
communication cable between the devices is securely connected. After the check
is correct, you can enter the ShineMaster IP address in the IE browser to
access the built-in page of the ShineMaster. As long as the ShineMaster is on
the same network segment as the computer you are accessing, you can access the
ShineMaster built-in server. A.If the user successfully visits the shinemaster
built-in page, they can go directly to the built-in page login interface, as
shown in figure 8.25 below.
Fig 8.25 B. Enter user name and password, default login username: admin
password: admin. click login after filling in, enter growatt shinemaster
system page. 3>ShineMaster Data collector status view Click on the status of
the shinemaster data collector to view shinemaster”system state information”,
“serial number,” server address, “number of connected devices,” and so on.
40
2)Select the type of photovoltaic device monitored in the second drop-down list.
Fig 8.26 4>ShineMaster Data collector add or delete device ShineMaster Before
monitoring photovoltaic devices, we need to enter the page of the built-in
shinemaster data collector settings to add devices. A. Add device
1)Select the monitoring mode for monitoring photovoltaic devices in the first
drop-
down list of add or remove devices.
Fig 8.27
41
Fig 8.28 3)Fill in the third drop-down list with the photovoltaic device
correspondence address.
Fig 8.29 4)Select “Add” and then click “Save”. 5)Go to the device status page
after saving success to confirm that the device was added successfully.
Fig 8.30 42
B. Delete device 1)Select the first drop-down list of “add or remove devices”
to monitor the monitoing mode of photovoltaic devices. 2)Select the type of
photovoltaic device monitored in the second drop-down list. 3)Fill in the
third drop-down list with the photovoltaic device correspondenc address..
4)Select the following “del” and click Save to complete the device addition.
5)Enter the device status page after successful save to confirm that the
device was deleted successfully.
5>ShineMaster Data upload to ShineServer A. RegisterLogin 1)Enter the server
domain name in the computer browser to enter the shineserver login page, if
you are logged in for the first time, please register the user name. Enter the
domain name access page, as shown in figure 8.32 below. Chinese user server
domain namehttp://server-cn.growatt.com. The domain name of the international
user server ishttp://server.growatt.com.
Fig 8.32
B. View monitoring data 1) After registration is complete, jump to the
shineserver main interface automatically. Click on “power station” and “work
information” to display the information for the power station’s total power
flow chart on the same day. The drop-down list “Select collector” allows you
to view the daily power flow chart of a single inverter for the power station.
Fig 8.31
2Register user name, input user information according to prompt, after
information is completed, click “register”. Note: “collector serial number”
and “collector check code” see shinemaster serialnumber box or guarantee box.
43
Fig 8.33 44
- By clicking on “power station” and “equipment management” in turn, the
real-time data of “data collector”, “inverter”, “environment monitor”,
“intelligent meter” and “confluence box” MAX “can be viewed.
8.2 Local Data Monitoring
MAX-X series Inverter local data monitoring mode has a mobile phone app phone) and PC direct connection, udisk, details are as follows.
8.2.1 Mobile phone app (Shinephone) Local Monitoring 8.2.1.1 Log on to app for local monitoring Method 1 When you open the app login front page, click the top right corner toolbox icon. Pop up the toolbox, click the local debugging tool, and you can get the wifi name of the collector by scanning the QR code or barcode(The default password for WIFI is 12345678. If you have already connected, you can click “Skip” to connect directly to the WIFI.)
Fig 8.34 Method 2 Open app enter user name and password click login, enter me
(personal center). Click the enter tool, find the local debugger to enter, and
you can get the wifi name of the collector by scanning the QR code or
barcode(The default password for WIFI is 12345678. If you have already
connected, you can click “Skip” to connect directly to the WIFI.)
45
Fig 8.35
8.2.1.2 Use of local monitoring and debugging When viewing local monitoring,
you must keep the phone’s wifi connected to the collector’s wifi to view local
monitoring (to enter the local monitoring page, first click auto refresh to
get the latest data information). Electricity generation: the option to view
the latest generation, daily generation, monthly and annual generation of
detailed information; Power: you can see the current power and rated power
value; failure: can read the equipment detailed fault information.
1>device control Note: In addition to resetting the password to connect to the
network, other WIFI modules that must connect to the collector can view
information. A.Reset password Need network connection login oss account to set
up or modify the local debug password. B.Setting configuration The
configuration data of inverter, voltage, power and so on can be modified
according to the usage (Fig 8.36).
46
Fig 8.36
C.Parameter configuration The parameter data of the equipment can be modified
according to the usage (Fig 8.37).
D.Intelligent detection Detailed and accurate view of the device’s detailed
data and status (Fig 8.38).
Fig 8.38 E.Intelligent I-V curve scanning Can remotely scan each mppt (Fig 8.39).
Fig 8.37 47
Fig 8.39 48
F.Fault recording detection Remote, fast and accurate fault location (Fig
8.40).
Fig 8.40 G.Real-time recording detection Inverter voltage and current quality
can be observed in real time (Fig 8.41).
H.One click diagnosis I-V curve diagnosis, grid waveform, THDV and cable
impedance detection all at one click(Fig 8.42).
I.High level setting According to the register address set parameters
(professionals).
J.Device information Check PV voltage/current, string voltage/current,
ACvoltage/current/power/frequency, PID voltage/current, internal parameters
and device detail information and parameters ( Fig 8.43).
Fig 8.41 49
Fig 8.42 50
2>Fault Recording Create the bconfig.txt file under the root of the U disk, write the following content, then insert the U disk that can be read fault information, then generates a form under the files in the root director y, A total of 60 fault recording information is stored, the latest Numbers is 0.
Fig 8.43
8.2.2 U Disk Monitoring Refer to 6.3.2 USB to WIFI/ U disk communicate
connection, the local monitoring of U disk can realize the functions of
software burning, fault recording, curve analysis and realtime recording.
Details are as follows: 1>Firmware Programming Create the bconfig.txt file
under the root of the U disk, write to the following content, then insert the
U disk to programming. Note the M3 program needs to be programming at last
time.
Fig 8.45 3>Curve Analysis Create the bconfig.txt file under the root of the U disk, write the following content, the insert U disk to record I-V curve, then generates a form under the files in the root directory.
Fime name
Fig 8.44 51
Fig 8.46 52
4>Real Time Recording Create the bconfig.txt file under the root of the U
disk, write the following content,then insert U disk to read real time
recording informationthen generates a form under the files in the root
directorythe form record’s waveform is consistent with the ID of the command
setting.
Fig 8.47
53
. . 9.1 Routine Maintenance
9 1 1 Cleaning Inverter
System Maintenance 9
·Before any operation, please disconnect the DC switch and AC switch, and DANGER wait for at least 5 minutes until internal capacitance discharge completely.
1>Check the ambient temperature and dust of the inverter, clean the inverter
when necessary. 2>Observe whether the air outlets is normal, when necessary,
clean the air outlets or clean the fan step by step, steps refer to 9.1.2.
. . 9 1 2 Fan Maintenance
DANGER
·It must be carried out by qualified, trained personnel and comply with all prevailing local code and regulations. ·Please disconnect the DC switch and AC switch before any operation, and wait for at least 5 minutes until the internal bus capacitance discharge completely.
·Do not use the air pump cleaning fan, which may cause fan damage. WARNING
When the Growatt MAX-X series inverter work in high temperature environment,
good ventilation and heat dissipation can effectively reduce the chance of
load derating. Inverter equipped with internal cooling fans, when the internal
temperature is too high, the fans work in to reduce the internal temperature.
When the inverter is derating because of the internal temperature is too high,
the following are the possible reasons or solutions. 1)Fan is blocked or the
heat sink gathers too much dust, it needs to clean the fan, fan cover or heat
sink. 2)Fan is damaged, it need to replace the fan. 3)Poor ventilation of the
installation location, it needs to select the appropriate installation
location according to the basic installation requirements. Fan cleaning and
replacement procedure; 1>Please ensure that the DC side and AC side of the
inverter have been disconnected before cleaning or replacement of the fan. 1)
Turn off DC switch. 2) Disconnect DC terminals from inverter(Users need tools
to disconnect the DC connection terminals). 3) Turn off AC switch. 2>Remove
the screws on the fan guards with a cross screwdriver. it is shown as below.
54
Fig 9.1 External fan view
Fig 9.2 Internal fan view 3>Disconnect the wire connector of the fans with a
flat head screw driver and remove the fans from the fan guards, it is shown as
below.
Fig 9.3
Fig 9.4 External fan view 55
Fig 9.5 Internal fan view
NoticeMAX-X series inverter has seven fansinternal fan2Pcsexternal fan5Pcs).
4>Clean fan, fan guards and heat sink or replace fan. 1) Clean the fan and fan
guards with air pump, brush or a damp cloth. 2) Remove each fan separately for
cleaning if necessary. 3) Remove the fan that need to replace with a cross
screwdriver, replace a new fan. 4) Tidy up the wire.
5>Install the fan, fan guard fixed and the inverter again.
9.2 Trouble Shooting
DANGER
·It must be operated by well-trained professional electrical technicians and abide by this manual. ·Normally grounded conductors may be ungrounded and energized when a PV isolation low is indicated. ·Risk of electric shock.
9.2.1 Warning Warnings identify the current status of the inverter(Max), warnings do not related to a fault and it does not affect the normal running of the inverter. When a warning with a number after it appears in the display, it indicates a warning code and is usually cleared through an orderly shutdown /re-set or a self-corrective action performed by the inverter.
56
Warning Warning 200 Warning 201 Warning 202 Warning 203 Warning 204 Warning
205 Warning 206 Warning 207 Warning 208 Warning 209 Warning 210 Warning 300
warning301 Warning 302 Warning 310
Warning 400
Warning 401
Description
Suggestion
String Fault String abnormal DC SPD warning PV Circuit short Dryconnect
function abnormal PV Boost driver abnormal AC SPD warning USB Over-Current DC
Fuse Open PV Voltage High
PV Reversed No AC Connection
AC V Outrange
AC F Outrange
NE abnormal
Fan warning
Meter abnormal
1.After shutdown,check the panel is normal. 2.Contact Growatt. 1.After
shutdown,check the panel is normal. 2.Contact Growatt.
1. After shutdown,check the DC SPD. 2. Contact Growatt.
1. Check if the PV circuit is shortcircuited. 2. Contact Growatt. 1. After
shutdown,check the dry Dryconnect wiring. 2. Contact Growatt.
1. Restart inverter. 2. Contact Growatt.
1. After shutdown,check the AC SPD. 2. Contact Growatt.
1. unplug the U disk. 2. Re-access U disk after shutdown. 3. Contact Growatt.
1. After shutdown,check fuse. 2. Contact Growatt.
1. Immediately disconnect the DC switch and check the voltage. 2. Contact
Growatt.
1. Check PV input terminals. 2. Contact Growatt. 1. Please confirm grid is
lost or not. 2. Contact Growatt.
1. Check the AC voltage is in the range of standard voltage in specification.
2. Contact Growatt.
1. Check the frequency is in the range of specification or not. 2. Contact
Growatt.
1. Check if the neutral and ground cables are well connected, 2. Contact
Growatt
1. After shutdown,Check the fan connection. 2. Replace the fan. 3. Contact
Growatt.
1. Check if the communication between the inverter and the meter is abnormal.
2. Contact Growatt.
57
Warning Warning 404 Warning 405 Warning 406 Warning 407 Warning 408 Warning 409
Description EEPROM abnormal Firmware version abnormal Boost module error Over
Temperature
NTC broken Reactive abnormal
Suggestion
1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact
Growatt. 1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2.
Contact Growatt. 1. Restart inverter. 2. Contact Growatt. 1. Check if
shinemaster is abnormal. 2. Contact Growatt.
NoticeMAX series inverter has two external fans and five Internal fan. If the
suggestions do not work, please contact to Growatt.
9.2.2 Error Errors codes identify a possible equipment failure, fault or
incorrect inverter setting or configuration, any or all attempts to correct or
clear a fault must be performed by qualified personnel. Typically, the error
code can be cleared once the cause or fault is removed. Some of error code as
table shows below, may indicate a fatal error and require you to contact the
supplier or Growatt for help.
58
Error
Error 200
Error 201 Error 202 Error 203 Error 204 Error 300 Error 301 Error 302 Error
303
Error 304 Error 400 Error 401 Error 402 Error 403 Error 404 Error 405 Error
406 Error 407
Description
Suggestion
AFCI Fault
1. After shutdown,check the panel terminal. 2. Restart inverter. 3. Contact Growatt.
Residual I High PV Voltage High PV Isolation Low
PV Reversed AC V Outrange
1. Restart inverter. 2. Contact Growatt.
1. Immediately disconnect the DC switch and check the voltage. 2. Contact
Growatt. 1. After shutdown, check if the panel shell is reliably grounded. 2.
Contact Growatt. 1. After shutdown, check PV input terminals. 2. Contact
Growatt.
1. Check grid voltage. 2. Contact Growatt.
AC terminals reversed
1. Check AC terminals. 2. Contact Growatt.
No AC Connection
NE abnormal
AC F Outrange
DCI bias abnormal DC Voltage High Fault Output DC current too high
1. After shutdown,check AC wiring. 2. Contact Growatt.
1. After shutdown,ensure that the ground wire is reliably connected. 2.
Contact Growatt.
1. Check the frequency is in the range of specification or not. 2. Contact
Growatt.
1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact
Growatt.
1. Restart inverter. 2. Contact Growatt.
Output current unbalance
1. Restart inverter. 2. Contact Growatt.
Bus sample fault
1. Restart inverter. 2. Contact Growatt.
Relay fault
1. Restart inverter. 2. Contact Growatt.
Init model fault
1. Restart inverter. 2. Contact Growatt.
AutoTest failure
1. Restart inverter. 2. Contact Growatt.
59
Error Error 408 Error 409 Error 411 Error 412 Error 413 Error 414 Error 415 Error 416 Error 417 Error 418 Error 420 Error 421 Error 422 Error 425 Error 426 Error 427 Error 428 Error 429
Description
Suggestion
NTC Temperature too high
1. Restart inverter. 2. Contact Growatt.
Bus voltage abnormal
1. Restart inverter. 2. Contact Growatt.
Communication fault
1. Restart inverter. 2. Contact Growatt.
Temperature sensor abnormal
1. Restart inverter. 2. Contact Growatt.
IGBT drive fault
1. Restart inverter. 2. Contact Growatt.
EEPROM fault
1. Check if shinemaster is abnormal. 2. Contact Growatt.
Internal power test fail
1. Restart inverter. 2. Contact Growatt.
Over current protected
1. Restart inverter. 2. Contact Growatt.
System protocol abnormal
1. Restart inverter. 2. Contact Growatt.
firmware version abnormal
1. Restart inverter. 2. Contact Growatt.
GFCI Module damage
1. Restart inverter. 2. Contact Growatt.
CPLD abnormal
1. Restart inverter. 2. Contact Growatt.
Sampling is inconsistent
1. Restart inverter. 2. Contact Growatt.
AFCI self-test fault
1. Restart inverter. 2. Contact Growatt.
PV current abnormal
1. Restart inverter. 2. Contact Growatt.
AC current abnormal
1. Restart inverter. 2. Contact Growatt.
Boost Short Out
1. Contact Growatt.
Bus voltage softstart fail
1. Restart inverter. 2. Contact Growatt.
60
10 Specification
Model
MAX
Specifications
100KTL3-X LV
Input Data(DC)
MAX 110KTL3-X LV
MAX 120KTL3-X LV
MAX 125KTL3 LV
Max.recommended PV power(for module STC)
Max. DC voltage
Start voltage
150kW
165kW
180kW
1100V 195V
187.5kW
Nominal voltage
600V
MPP voltage range
180V-1000V
No. of MPP trackers
10
No. of PV strings per MPP trackers
2
Max. input current per MPP trackers
Max. short-circuit current per MPP trackers DC overvoltage category
Output Data(AC)
32A 40A Category II
AC nominal power
100kW
110kW
120kW
125kW
Max. AC apparent power
Nominal AC voltage/range
AC grid frequency/range
Max. output current
Power factor(@nominal)
Max. inrush current/duration
Max. output facult current/duration
Adjustable power factor
110kVA
167.1A@380V 158.8A@400V
121kVA
132kVA
230V/400V 340-440VAC
50/60Hz 45-55Hz/55-65Hz
183.8A@380V 200.5A@380V 174.6A@400V 190.5A@400V
0.99
20KA/tr:8us,tf:20us
400A/30us
0.8leading …0.8lagging
137.5kVA
208.9A@380V 198.5A@400V
THDi AC grid connection type
<3% 3W/N/PE
61
AC overvoltage category
efficiency
Max. efficiency
Euro-eta Protection devices
DC reverse-polarity protection DC switch
DC Surge protection Insulation resistance monitoring AC surge protection
Grid monitoring
Anti-islanding protection Residual-current monitoring unit String monitoring
Anti-PID function AFCI protection
General data Dimensions (W /H / D) in mm Max. inrush current/duration Weight
Operating temperature range Altitude
Internal consumption at Topology
Cooling
Protection degree
Relative humidity
98.4%
Category III
98.8%
98.5%
98.5%
Yes Yes Type II
Yes
Yes Yes Yes
Yes Yes Optional Optional
970640345mm
20KA/tr:8us,tf:20us 84kg
-30- +60
4000m <1W(Note1) Transformerless Smart air cooling
IP66 0~100%
98.5% 62
DC connection AC connection Interfaces Display RS485/USB PLC/GPRS/4G Warranty:
5 /10 years Certificates and approvals
Grid regulation
H4/MC4(Optional) OT/DT terminal
LED/WIFI+APP Yes
Optional Optional
AS/NZS 4777.2,CEI 0-21,CEI 0-16,VDE-AR-N 4105, DIN V VDE V 0126-1-1,UTE C
15-712-1,EN 50438,
IEC 60068,IEC 61683,IEC 62116,IEC 61727, MEA,PEA,DRRG/DEWA:2016,BDEW,G59/3
EMC
EN61000-6-2,EN61000-6-4
Safety
IEC/EN62109-1,IEC/EN62109-2
Note1: If with AC power supply function, self-consumption at night is less than 15W.
63
Model Specifications Input Data(DC)
MAX 133KTL3-X LV
MAX
MAX
125KTL3-X MV 136KTL3-X MV
Max.recommended PV power(for module STC)
Max. DC voltage
Start voltage
199.5kW
165kW
180kW
1100V 195V
Nominal voltage
600V
720V
720V
MPP voltage range
180V-1000V
No. of MPP trackers
10
No. of PV strings per MPP trackers
2
Max. input current per MPP trackers
32A
Max. short-circuit current per MPP trackers DC overvoltage category
Output Data(AC)
40A Category II
AC nominal power
133kW
125kW
136kW
Max. AC apparent power
Nominal AC voltage/range
AC grid frequency/range
Max. output current
Power factor(@nominal)
Max. inrush current/duration
Max. output facult current/duration
Adjustable power factor
146.3kVA 230V/400V 340-440VAC
222.3A@380V 211.2A@400V
137.5kVA
149.6kVA
277V/480V
277V/480V
408-528VAC 408-528VAC
50/60Hz 45-55Hz/55-65Hz
165.4A
179.9A
0.99
20KA/tr:8us,tf:20us
400A/30us
0.8leading …0.8lagging
THDi AC grid connection type
3W/N/PE
<3%
3W+PE
3W+PE
MAX 150KTL3 MV
187.5kW 720V
150kW 165kVA 277V/480V 408-528VAC 198.5A
3W+PE
64
AC overvoltage category
efficiency
Max. efficiency
Euro-eta
Protection devices
DC reverse-polarity protection DC switch
DC Surge protection Insulation resistance monitoring AC surge protection
Grid monitoring
Anti-islanding protection Residual-current monitoring unit String monitoring
Anti-PID function
AFCI protection
General data
Dimensions (W /H / D) in mm Max. inrush current/duration Weight Operating
temperature range Altitude
Internal consumption at
Topology
Cooling
Protection degree
Relative humidity
98.8%
65
Category III
99%
99%
98.5%
Yes Yes Type II
Yes
Yes Yes Yes
Yes Yes Optional Optional
970640345mm
20KA/tr:8us,tf:20us 84kg
-30- +60
4000m <1W(Note1) Transformerless Smart air cooling
IP66 0~100%
99%
DC connection AC connection Interfaces Display RS485/USB PLC/GPRS/4G Warranty:
5 /10 years Certificates and approvals
Grid regulation
H4/MC4(Optional) OT/DT terminal
LED/WIFI+APP Yes
Optional Optional
AS/NZS 4777.2,CEI 0-21,CEI 0-16,VDE-AR-N 4105, DIN V VDE V 0126-1-1,UTE C
15-712-1,EN 50438,
IEC 60068,IEC 61683,IEC 62116,IEC 61727, MEA,PEA,DRRG/DEWA:2016,BDEW,G59/3
EMC
EN61000-6-2,EN61000-6-4
Safety
IEC/EN62109-1,IEC/EN62109-2
Note1: If with AC power supply function, self-consumption at night is less than 15W.
66
11 Decommissioning
If the inverter does not operate in the future, it needs to be properly
disposed. The steps are as follows: 1>Disconnect the external AC short circuit
and prevent reconnection due to misoperation. 2>Turn the DC switch to “OFF”
position. 3>Wait at least 5 minutes until the internal capacitor discharge is
completed. 4>Disconnect the AC connector. 5>Disconnect DC connector. 6>Remove
the inverter from the wall. 7>Disposing of the inverter.
11.1 Disposing Of The MAX-X Series Inverter
Do not dispose of MAX series inverter together with household waste. Please
accordance with the disposal regulations for electronic waste which apply at
the installation site at that time. Ensure that the old unit and, where
applicable, any accessories are disposed of in a proper manner.
12 Quality assurance
Please refer to related file.
Contact 13
If you have technical problems concerning our products, contact your installer
or Growatt, please provide information below for better support. 1>Inverter
type 2>Serial number of inverter 3>Error code of inverter 4>LED status of
inverter 5>DC input voltage of inverter (Modules information) 6>Inverter
communication method
Shenzhen Growatt New Energy Co.,Ltd 4-13/F,Building A,Sino-German(Europe)
Industrial Park, Hangcheng Ave,Bao’an District, Shenzhen, China T +86 0755
2747 1942 E service@ginverter.com W www.ginverter.com
67
68
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>