GROWATT MAX 80-150KTL3 Inversor On Grid User Manual

June 10, 2024
Growatt

MAX 80-150KTL3 Inversor On Grid

Product Information

The MAX-X Series solar inverters from Shenzhen Growatt New
Energy Co., Ltd are designed to convert the DC power generated by
solar panels into AC power suitable for use in homes or businesses.
The inverters are equipped with AFCI detection function and
anti-PID function to ensure the safety and reliability of the
system. The inverter can also be remotely monitored through a
communication cable connection.

Applicable Personnel

Only qualified electrical technicians should install the MAX-X
series inverter. To ensure proper installation and operation, it is
important to read through the installation and operation manual
carefully and follow all safety precautions. If there are any
problems during installation or operation, contact the
manufacturer’s customer service hotline or log on to their website
for assistance.

Safety Precautions

  • Read through the entire manual before installation to avoid
    damage caused by improper installation.

  • All operations and connections must be done by a trained and
    qualified electrical technician.

  • Do not touch any inside part of the inverter except for
    terminals during installation.

  • All electrical connections must meet local safety
    regulations.

  • Contact an authorized technician for maintenance and
    replacement of parts.

  • Get local power supplier’s permit before connecting the
    inverter to the grid.

Product Usage Instructions

Installation

Before installation, make sure to read through the entire
installation and operation manual. All operations and connections
must be done by a trained and qualified electrical technician. The
following steps should be taken:

  1. Ensure that all electrical connections meet local safety
    regulations.

  2. Connect the AC side and DC side cables as instructed in the
    manual.

  3. Connect the communication cables between the inverter and
    monitoring device.

  4. Connect the ground cables.

  5. Install the inverter on a wall or other suitable location,
    taking into account the installation environment requirements.

Commissioning

After installation, the inverter needs to be commissioned before
it can start working. The following steps should be taken:

  1. Turn on the AC and DC switches on the inverter.

  2. The inverter will enter “Standby” mode, and then “Startup”
    mode. Check the LED display for any error codes.

  3. If there are no error codes, the inverter will enter “Normal”
    mode and start working.

Monitoring

The MAX-X series inverters can be monitored remotely through a
communication cable connection. The monitoring device should be
installed according to the manufacturer’s instructions. The
following steps should be taken:

  1. Install the monitoring device according to the manufacturer’s
    instructions.

  2. Connect the communication cables between the monitoring device
    and inverter.

  3. Use the monitoring device to check the performance of the
    inverter and identify any issues that may arise.

Maintenance

To ensure proper operation of the inverter, routine maintenance
should be performed by an authorized technician. The following
steps should be taken:

  1. Disconnect the AC and DC switches before performing any
    maintenance.

  2. Check for any damage or wear on the components, and replace as
    necessary.

  3. Clean the inverter and surrounding area regularly to prevent
    dust build-up.

Download Manual

Growatt New Energy

Shenzhen Growatt New Energy Co., Ltd 4-13/F,BuildingA,Sino- German(Europe)IndustrialPark, HangchengAve,Bao’anDistrict,Shenzhen,China T:+86 755 27471942 E:service@ginverter.com W:www.ginverter.com

GR-UM-241-A-00

Installation & Operation Manual

1 Overview 2 Safety Precautions 3 Product Introduction 4 Unpacking 5 Installation

List
1.1 Product Overview 1.2 Applicable Personnel
2.1 Safety Overview 2.2 Symbol 2.3 Meaning of Symbol
3.1 Appearance 3.2 Dimensions 3.3 Nameplate 3.4 Working Principle 3.5 Inverter Storage 3.6 Grid Types 3.7 AFCI Detection Function 3.8 Anti-PID Function
5.1 Basic Installation Requirements 5.2 Installation Environment
Requirements 5.3 Moving Requirements 5.4 Wall Mounted Installation 5.5 Installing the Inverter

6 Connecting Cables 7 System Commissioning 8 Monitoring 9 Maintenance 10 Product Specification

6.1 Connection on AC side 6.2 Connection on DC side 6.3 Connection of Communication
Cables 6.4 Connecting the Ground Cables
7.1 Inverter Commissioning 7.2 Modes 7.3 LED display
8.1 Remote Data Monitoring 8.2 Local Data Monitoring
9.1 Routine Maintenance 9.2 Trouble Shooting

11 Decommissioning 12 Quality Assurance 13 Contact Us

1 Overview
1.1 Product Overview
This manual is aimed at providing sufficient information and installing instruction for consumers buying Shenzhen Growatt New Energy Co.,Ltd (short as Growatt) MAX-X Series solar inverters. Please read this manual carefully before using the MAX-X series inverters and store the manual in a reachable place for an authorized technician. No further notice if there is any change in this manual.
1.2 Applicable Personnel
Only qualified electrical technicians are allowed to install MAX-X series inverter. With reading through this manual and following all the precautions, qualified electrical technician can properly install MAX-X serial inverter, finish trouble shooting and communication settings.
If there is any problem during the installation, the installer can either log on www.ginverter.com and leave a message or call consumer service hotline +86 755
27471942.

2 Safety Precautions
2.1 Safety Overview
1>Before installation please make sure reading through this manual, any damage caused by improper installation, Growatt reserve the right to disclaim any warranty. 2>All the operations and connections must be done by trained qualified electrical technician. 3>During installation except for terminals, do not touch any inside part of the inverter. 4>All the electrical connections must meet local country’s safety regulations.
5>If you need maintenance for this inverter, please contact our local authorized
installing and maintenance technician. 6>You must get the local power supplier’s permit before connecting this inverter to the grid.

H a n d l e P r o c e s s

WARNING

·The inverter is heavy,please treat with care while handling,in case of crushing injury.

Installation NOTICE

·Before installation,please read through this manual,any damage cause by improper installation,Growatt reserve the right to disclaim any warranty.

DANGER

·Ensure that the inverter is not connected to a power supply and is not power on before installation.

1

WARNING

·Please follow this installation manual as installation condition environment,space and so on. ·Please install the inverter in a dry and ventilated environment,otherwise may affect the performance of the inverter. ·Please follow the installation procedures in this manual.

Electrical Connections:

DANGER

·Before electrical connection, please ensure the inverter DC switch is
at “OFF” also disconnect AC switch, otherwise the high voltage from
inverter may cause life risk. ·Only trained authorized electrical technician can do the electric connection also please follow the connection procedures in this
manual along with local country’s regulations. ·High voltage may cause electric shocks and serious injury please
do not touch the inverter. ·Please do not store inverter in area with flammable and explosive material.

WARNING

·Each inverter must install one AC breaker; AC breaker is forbidden to share with other inverters.
·It is forbidden to add load between inverter and breaker. ·If the cable is thick, after tightening the cable do not shake it and ensure the cable is well-connected and then start the inverter.Loose connection may cause overheat. ·Before connecting between PV panels and inverter please ensure the positive and negative poles are correct connected.

Maintenance and replacement:

DANGER

·Must be installed by trained and authorized electrical technician and accurately follow this manual. ·Please disconnect the DC and AC switch for at least five minutes, all the operations should be carried after power disconnection. ·If there is PV isolation low alarm, the inverter case may be ungrounded, please do not touch the inverter case. ·High voltage of inverter may result in electric shock.

WARNING

·For better cooling purpose, please regularly clean the fans. ·Do not use air pump to clean the fans, cause it may damage the fans.

2

Other

·After you receiving the inverter please check the packing materials for damage,if there is any damage please contact your supplier.

WARNING

·The Max PV input voltage should not exceed 1100V. ·For the disposed inverter,the consumer should dispose it according to local disposal rules for electrical equipment waste.

2.2 Symbol Conventions

Symbol

Description

DANGER WARNING

Indicates an imminently hazardous situation which,if not avoided, will result in serious injury or death. Indicates potentially hazardous situation which,if not avoided,will result in serious injury or death.

CAUTION

Indicates potentially hazardous situation which,if not avoided,will result in minor or moderate injury.

NOTICE

Indicates certain hazardous situation which,if not avoided,will rusult in property damage.

Reminds operator to read installation manual before operating or installing inverter.

2.3 Lable Description

Symbol

Name

Meaning

High Voltage Electric Shock

Inverter operating with high voltage,any operation regarding inverter need to be done by trained and authorized electrical technician.

Burn Warning

Do not touch a running inverter cause it generates high temperature on the case.

Protective Grounding

Connect inverter to grounding bar.

Delay discharge

Residual voltage exists after the inverter is powered off,it takes 5 minutes for the inverter to discharge to the safe voltage.

Read the installation
manual

Reminds operator to read installation manual before operating or installing inverter.

DC

Means this terminal is for DC side.

AC

Means this terminal is for AC side.

CE Mark

The inverter complies with the requirements of the applicable CE guidelines.

3

4

3 Product Introduction
3.1 Appearance
Front view:

Bottom view(Termial):

Fig 3.1

Side view:

Fig 3.2

Fig 3.3 5

Mark A B C D E F G

Description Front panel LED PV terminal DC switch
Breathing valve External fans USB interface

3.2 Basic Data

Model
MAX-X Series Inverter MAX-X Series Inverter
with package

Width 970 1095

3.3 Nameplate

Mark H I J K L M

Description COM interface Corner guard Waterproof silicone pad Junction Box Ground screw hole
Heat sink

Size(mm) Height
640

Thickness 345

Weight (kg) 84

765

500

98

Note: Other models of MAX-X series share the same label design with MAX125KTL3-X LV, only with different model name and parameters, detail parameter please refer to specification in Chapter 10.
6

3.4 Working Principle
The MAX-X series inverter works as follows: 1>The PV panels gather solar to generate DC power to inverter. 2>With input current detection circuit, it can monitor all the PV panels’ working status and use MPPT to track the maximum power point. 3>With inverter circuit change DC power to AC power, and feed power back to grid per grid reuqirement. 4>With output isolation relay can isolate AC output and grid, if anything goes wrong on either inverter side or grid side, isolation relay can disconnect inverter immediately.
On-grid connection system diagram:

A
symbol A B

B

C

D

Fig 3.4

Description symbol

Description

PV string Inverter

C

Electric meter

D

Gird

3.5 Inverter Storage
1>Do not unpack the inverter and store it in a ventilation dry place . 2>Keep the storage temperature at -30 – +60 and humidity at 0-95%. 3>A maximum of three inverters with package can be stacked. 4>If the inverter has been long- term stored, inspections and tests should be conducted by qualified personnel before it is put into use.
After being stored for a month or longer, the inverter’s time and date could be wrong, you need set the time and date before using, for more details please refer to Chapter 7.1 inverter commissioning.

3.6 Grid Types
The MAX-X series, MAX100-133KTL3-X LV inverters connect to the grid like following drawing 3.5,MAX 125-150KTL3-X MV inverters connect to the grid like following drawing3.6.

7

400V

230V

400V

230V

230V

4 80V

480V

400V
Fig 3.5

4 80V
Fig 3.6

3.7 AFCI Detection Function
AFCI (Arc Fault Circuit Interrupter) is a kind of circuit protection device, the main function is to prevent the fire caused by fault arc.The electrical insulation aging, breakage, loose connection, air breakdown caused by air humidity and so on, all of these may cause an electric spark,which is called arc. The AFCI function of the MAX-X series inverter is optional, and the detection equipment is assembled inside the inverter. When an arc-drawing condition is detected on the PV input side, the arc current could be detected by the CT assembled on the PV input-side wire. Then the inverter will shut down. Meanwhile, the inverter will display the corresponding fault message and the buzzer will sound, which could help to avoid harm and economic loss to the user.

NOTE: AFCI function is optional.

3.8 Anti-PID Function
The full name of PID is Potential Induced Degradation. Since the PID effect, a large amount of charge could accumulate on the surface of the photovoltaic module, which makes the surface passivation of the module worse. Eventually, the fill factor, opencircuit voltage, and short-circuit current of the module are reduced, and the power of the photovoltaic module is attenuated. The Anti- PID function uses the principle of reversible PID changes. MAX-X series inverters rectify AC voltage at night and boost it to generate a DC voltage. The DC voltage is connected to PV + and the ground respectively. When add a positive bias voltage to the module to make the PID effect reverse,the Anti- PID function could repair the photovoltaic modules at night and prolong the service life of photovoltaic modules.
NOTE: Anti-PID function is optional.

8

4 Unpacking
Checking before installation 1>Before unpacking the inverter, check the outer packing materials for damage. 2>After unpacking the inverter, check that the contents are intact and complete. If any damage is found or any component is missing, contact your supplier.
Package contents:

A

B

C

D

E

F
Mark A B C D E F G H I J K L

G

H

I

J

Fig 4.1

K

L

Descriptions Inverter
Wall mount PV + terminal, PV- terminal
PV terminal metal core Removal tool of PV terminals
Installation manual Warranty card
Communication terminal Removal handle(opt)
M1090 Expansion screw M628 stainless steel screw AC wiring copper terminal (opt)

Number 1 1
20/20 20/20
1 1 1 1 2 4 2 4 or 5

9

Installation 5

CAUTION

·To prevent device damage and personal injury, keep balance when moving the inverter because it is heavy. ·Do not place the inverter with its wiring and signal terminals at the bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter. ·When placing inverter on the floor, put foam or paper under the inverter to protect its cover.

5.1 Basic Installation Requirements
A. Ensure that the installation wall is solid enough to bear the inverter(Inverter weight please refer to installation manual Chapter3, 3.2 ). B. There must be enough installation space to fit the size of inverter. C. Do not install inverter on flammable or heat-intolerant buildings. D. This inverter is IP 66 protection, you can install it indoor or outdoor. E. To avoid inverter performance de-rate due to the over heat, please do not expose the inverter under direct sunlight. F. The installation humidity should be from 0-95%. G. The surrounding temperature of inverter should be from -30 – +60. H. Inverter should be installed in a vertically or rear tilted surface, please refer to following drawings.

Fig 5.1 I. To ensure the inverter can work smoothly and easy for personnel to operate, please notice there is sufficient space for inverter, refer to following drawing.

600mm

600mm

1000mm

600mm

600mm

Fig 5.2

10

J. Do not install inverter close to strong electromagnetic signal. K. Install the inverter out of children’s reach.
5.2 Installation Environment Requirements
A. Although the inverter’s protection level is IP 66, to extent inverter lifespan you still need to avoid rain and snow, please refer to following drawings.

Fig 5.3 B. To reduce the de-rate performance of the inverter and extend inverter’s life span, we strongly recommend you install an awning, for the distance between an awning and inverter, please refer to following drawing.
Fig 5.4 C.When you install multiple inverters on one surface, inverters should be installed as following drawing. 11

Fig 5.5 D. Do not install inverter into an enclosed space like following drawing.
Fig 5.6
5.3 Moving Requirements
·The inverter is heavy, please move it with care and keep balance to avoid personnel injury. ·Do not place the inverter with its wiring and signal terminals at the WARNING bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter. Plan 1 1>As shown in Fig5.7, use a rope to tie at ring and handle, lift the inverter from package and move to installation position. 2>When you are moving the inverter, please keep the balance.
Notice: There is front and bottom mark on the package.
12

Plan 2(Optional):
1>As shown in Fig5.8, 4-6 persons lift the inverter out of package, swap the ring to
moving handles.
2>When you are moving the inverter, please keep the balance. Notice: There will be front and bottom mark on the package.

1>Use the wall mount plate as a template drill holes on the wall and put in expansion bolts.

Fig 5.7

Fig 5.8

5.4 Wall Mount Bracket Installation
Before install the inverter you need install the wall mount bracket so that the inverter can be firmly installed on the wall. Wall mount plan:

Fig 5.9 13

Fig 5.10 NoticeExpansion bolt should be installed on solid walls with at least 100mm thickness. 2>Follow the following drawing put the bolt to install the wall mount plate on the wall.
Fig 5.11 Notice: Do not install inverter unless you have confirmed the wall mount plate has been firmly installed on the wall.
5.5 Installing The Inverter
After the wall mount bracket has been firmly installed on the wall , put the inverter on that plate. 1>Use the rope(must meet the weight requirement of the inverter) through two rings and lift the inverter up, just as following Figure. 2>Before hanging the inverter on the wall mount bracket use screws to fix the inverter and please keep the inverter balance. 3>Check the inverter if it is firm enough and lock all the screws.
14

5.12

5.13

5.14 15

Connecting Cable 6

Decisive Voltage Class (DVC) indicated for ports

Port Name

Class

AC

C

DC

C

DRMS

A

RS485&USB

A

6.1 Connection on AC side
·Before electrical connection, please ensure the inverter DC switch is at “OFF” also disconnect AC switch, otherwise the high voltage from inverter may cause life risk. ·Only trained authorized electrical technician can do the electric connection also please follow the connection procedures in this manual DANGER along with local country’s regulations. ·High voltage may cause electric shocks and serious injury please do not touch the inverter. ·Please do not store inverter in area with flammable and explosive material.
·Each inverter must install one AC breaker, AC breaker is forbidden to share with other inverters. WARNING ·It is forbidden to add load between inverter and breaker.
Preparation before connection:
1>Disconnect inverter DC switch and AC breaker or switch. 2>When you lock the AC cable’s screw, the torque force should be 30kgf·cm.
When you lock the cover screw, the torque force should be 20kgf·cm. 3>Measure the grid voltage and frequency, please refer to chapter 10. AC breaker specification

Inverter model MAX 100KTL3-X LV MAX 110KTL3-X LV MAX 120KTL3-X LV MAX 125KTL3-X LV MAX 133KTL3-X LV MAX 125KTL3-X MV MAX 136KTL3-X MV MAX 150KTL3-X MV

Breaker model 200A/400Vac 250A/400Vac 250A/400Vac 250A/400Vac 250A/400Vac 200A/500Vac 250A/500Vac 250A/500Vac

16

Cable specification:

Inverter Model
MAX 100KTL3-X LV MAX 110KTL3-X LV MAX 120KTL3-X LV MAX 125KTL3-X LV MAX 133KTL3-X LV MAX 125KTL3-X MV MAX 136KTL3-X MV MAX 150KTL3-X MV

Copper wire crosssectional area(mm²)
70-240

Copper wire recommendation (mm²)

Aluminum wire recommendation (mm²)

70

95

Notice:The cable must be unbroken.
When using aluminum alloy cables, please use copper-aluminum transition terminals.

AC side connection steps:

·If the cable is thick, after tightening the cable do not shake it and ensure the cable is well-connected and then start the inverter. Loose connection WARNING may cause overheat.

1>Following drawing shows inverter’s AC terminal, R, S, T are three live lines, N is Neutral line.

2>Determine the stripping length (approximately 30mm) according to the specifications of the crimping terminal. Use crimping tools to crimp the wires and terminals, then connect the cables to the corresponding channels through the waterproof interface, and tighten the screws.

Diagram of how to install a terminal:

Fig 6.2

Fig 6.3 3>Apply fireproof mud to the threading holes on the waterproof silicone pad to prevent the risk of water ingress, as shown in the figure below.
·The gaps in the cable threading holes must be blocked,otherwise there will be a risk of water leakage. WARNING

Fig 6.1 17

Fig 6.4 18

6.2 Connection On DC Side
·Before electrical connection, please ensure the inverter DC switch is at “OFF” also disconnect AC switch, otherwise the high voltage from inverter may cause life risk. ·Only trained authorized electrical technician can do the electric connection also please follow the connection procedures in this manual along with local DANGER country’s regulations. ·High voltage may cause electric shocks and serious injury please do not touch the inverter. ·Do not place flammable or explosive materials around the inverter.
Notice: The sunlight will generate voltage on the solar panels, after serial connection, the high voltage may injure personnel, so before connect DC input cable you need cover solar panels with light-tight materials and make sure the inverter DC switch is at “OFF” status, otherwise high voltage may injure personnel.

·Each string’s maximum open circuit voltage cannot exceed 1100Vdc, other-

wise it could lead to fire or damage the inverter. If the inverter was damaged

by higher maximum open circuit voltage (higher than 1100Vdc) product

WARNING

warranty will ·The inverter

be forfeited and Growatt will not take any responsibility. shall be used with IEC 61730 Class A rating PV module.

·When the group is suspended, be sure to use dust plugs to block up to

prevent entering the water into the dust.

1>Each string solar panels should be same brand and same model. 2>Under any circumstance, the maximum short circuit current should not exceed 32A. 3>The total panels power should not exceed 1.5 times of inverter input power. 4>To optimize system settings, recommend two strings with same amount solar panels. Notice: Connectors need to be fit with male and female terminals, before connecting panels with inverter please make sure the positive pole and negative pole, namely the solar panels’positve pole connect to”+” negative pole connect to”-“.

Fig 6.5
5>Decide the length of peeling base on cable terminal, use the wire stripper to connect cable and terminal, and separately connect to specific connector. 19

6>Connect the positive and negative poles to inverter terminals, different inverter’s maximum single string input current please refer to following table.

Inverter model

Max. single string input current

MAX-X serial inverter

16A*2

7>Cable specifications:

Inverter model MAX-X serial inverter

Cross-sectional 4-6

Recommendation 4

Cable outer 4.5-7.8

Notice1.Under any circumstance, the total current of all strings cannot exceed the inverter’s maximum current. 2. Do not touch any working solar panels. 3. Make sure the cable is unbroken.

6.3 Connection Of Communication Cables
6.3.1 RS485 port
RS485 can carry out single-machine communication or multi-machine (32pcs) longdistance (500 meters) high-speed (baud rate 38400) communication. It is recommended to use twisted-pair shielded wire for RS485 communication line. For single-machine communication, the communication line can be connected to pin 3/4, and its shielding layer can be connected to pin 1. When multiple machines are connected in parallel, two RS485-1 ports can be connected at the same time. When used, the shielding layer can be connected to pin 1/2.

Port

PIN

Shield ground ½

3

RS485-1 IN

4

5

RS485-1 OUT

6

7

RS485-2

8

Description 485-1 PE Shield
485-1 A1 485-1 B1 485-1 A1 485-1 B1 485-2 A1

Fig 6.6 Port
DRMS

PIN Fig 6D.e6scription

9

DRM1/5

10

DRM2/6

11

DRM3/7

12

DRM4/8

13

REF/GEN

14

DRM0/COM

485-2 B1

RS485-1Matching resistance

15/16

485-1Matching resistance

Notice: When multiple inverters communicate in parallel, the last machine needs to add matching resistance. The method is to use a wire to connect the pin 15/16 together.
20

In MAX-X series inverters, RS485 interface is standard. The connection steps of RS485 communication line are as follows: 1) Unscrew the waterproof cover of the COM interface and remove it. 2) Connect the RS485 communication line to the port of 485-1. 3) The inverter is connected hand in hand through the RS485 communication line, and the end of the communication line 485_A/B is connected to the monitoring equipment to realize multi-machine remote monitoring. Note: When locking the RS485 cable screw, the torque is 4kgf·cm.
Fig 6.7
6.3.2 USB port The MAX-X series inverters are equipped with a USB interface as standard, which can be connected to a USB to WIFI module, Shine GPRS-X2, Shine WIFI-X, Shine 4G-X, Shine Link-X and other optional monitoring modules to realize remote Monitoring function. In addition, you can also quickly upgrade the inverter software through the U disk. Steps to install the monitoring module: 1> Loosen the waterproof cover of the USB interface and remove it. 2> As shown in Figure 6.8A, insert the Shine GPRS-X2 module into the USB interface, and the LED of the Shine GPRS-X2 module will be on. 3> As shown in Figure 6.8B, make sure that the is facing upwards, insert the monitoring module into the USB interface, and tighten the lock. Note: If you use a USB to WIFI module, when the operator leaves, please take the module and the data cable away, and tighten the waterproof cover to prevent water from entering the interface.

Installation up

Fig 6.8A

The Inverter Side

Remove

The Inverter Side

The Inverter Side The Inverter Side

Fig 6.8B

21

22

6.4 Connecting The Ground Cables
In this solar system all the unloaded metal components and cases should be connected to the ground. Single inverter need grounding over a PE point, multiple inverters need connect all the inverter PE cable and solar panels shelves to the same grounding point to achieve equipotential. The grounding steps as following: Take out the ground screw at the inverter bottom, connect the ground cables as following figure. Notice: 1.The machine is safely separated from the lightning protection and the distance is as far as possible. 2.Do not expose Grounding terminal in the air and precaution for the rain. 3.When you lock the case ground screw, the torque force should be 60kgf·cm.

Fig 6.9

According to the relevant provisions of IEC 61643-32 “Connecting to photovoltaic devices surge protectors – selection and use of guidelines”, whether for household or outdoor photovoltaic power plants, it is necessary to ensure the implementation of lightning protection measures for photovoltaic systems:

WARNING

The lightning protection measures for photovoltaic systems shall be carried out in accordance with the corresponding national standards and IEC standards. Otherwise, photovoltaic devices such as components, inverters and power distribution facilities may be damaged by lightning. In this case, the company does not carry out warranty and assumes any responsibility.

23

Lightning down the line

Lightning protection device

Photovoltaic panel

Safety

interval S

4

Inverter

1

2

Grounding bar

Distribution Cabinet

3

Power grid

SPD

Lightning down the line

Equipment ground wire Total grounding point

Fig 6.10

1It is generally recommended to install lightning protection devices (such as lightning rods / lightning protection belts and down conductors) to prevent lightning from hitting the PV array. 2 Lightning protection devices and down- conductors and related equipment in photovoltaic systems (including photovoltaic panels, inverters, cables, power distribution equipment) should maintain a safe separation distance S. Suggested value of S: According to the general 5 storey height (about 15m) building roof, S takes 2.5m enough, this distance can be simplified according to the inverse relationship of the floor height. A. When the safety distance S is satisfied: The position of the figure should be equipped with a lightning protection module. In general, it is recommended to install Type II in position and Type I in position . B. When the safety and safety distance S is not met: In addition to position 3, Type I lightning protection module should be installed in Figure
. 3 The lightning down conductor and the equipment ground wire eventually sink at a total ground point, but the two cannot share the wire. That is, the equipment grounding wire should be pulled separately, and the wire diameter requirement >6mm² when the safety interval distance S is satisfied. 4 About the above lightning protection lightning receptor system related design reference GB/T 21714.3-2015.

24

7 Commissioning 7.1 Commission The Inverter ·If the inverter is stored over one month, its default time and date may looks wrong, the time and date should be reset before connection to the grid. The inverter will be set to the appropriate model according to the standards of different countries or regions before leaving the factory. For example, the inverters shipped to Australia are configured as Australian model in the factory. Note: The inverter is configured for Australia at the factory. 7.1.1 Set inverter address After inverter is started normally, inverter address can be set via RS485/USB converting to WIFI.When multiple inverters are connected in parallel via RS485, the inverter must be set to a different communication address. When a single inverter communicates, the default communication address can be used. Note: The default communication address of the inverter is 1, which can be set to 1-254.
7.1.1.1 Set RS485 address with Shinebus The 485 address of the inverter can be modified by Shinebus This operation is
performed by a professional.
7.1.1.2 Set RS485 address on ShinePhone APP Refer to 8.2 download mobile APP ShinePhone and connect to inverter WIFI to enter local monitoring page, this operation is performed by a professional. 1>Click “Parameters”; 2>Enter passwor.(When you use it for the first time, you need to set the password first. Click “Reset password” to enter the OSS account number and password. The distributor and installer can apply for the OSS account from Growatt. Click “Sign in” to set the password. After the setting is successful, you can start using it.) 3>Click top item “COM Address”; 4>Click the “Read” button in the upper right corner to read the current communication address of the inverter; 5> Set inverter com address; 6>Read inverter com address to ensure setting is successful;
25

3 2 1
4
5 6
7
8 9

Fig 7.1

26

7.1.2 Set inverter time and date Method 1: Please refer to section 8.2.1 and login ShinePhone APP.Click “system time(45-50)”to set inverter time and date on the parameter setting page.
Fig 7.2
7.2 Operation Mode
7.2.1 Waiting mode When the DC voltage is more than 180Vdc, inverter will be powered on and enters the “waiting” state. At this mode, inverter will check the system parameter. If the system is normal and PV voltage is more than 195Vdc, inverter will try to connect to the grid. 7.2.2 Working mode At this mode, inverter work normally,and the Power or fault code indicator light shows the power delivered by the inverter to the grid. When the DC voltage is more than 180Vdc,inverter converts the DC power generated by the PV modules into AC power and supplies them to the grid. When the DC voltage is lower than 180Vdc, inverter will enter into “waiting” state and try to connect to the grid, at this status, inverter consume very small power to check the internal system status. Note: only when the PV modules supply enough power(voltage 195Vdc) then the inverter will start automatically. 27

7.2.3 Fault mode Inverter intelligent control system will continuously monitor and adjust system status.When there is a fault detected, LED will show the fault message. Note: Please refer to section 8.2 to check the fault message and take corrective measures.
7.2.4 Off mode When the sunlight is weak or no light, inverter will stop working automatically. When it is off, inverter will not consume gird power or PV module. At the same time, the LED of inverter will be turned off. Note: When PV string DC voltage is too low(150Vdc), inverter will be off.
7.3 LED Display
Inverter current operation status can be visually checked from LED display directly.

E

A

D

B

C

Fig 7.3

Fig 7.4

Description of LED status

Position of LED

Type of LED

Inverter status

LED status

A

PV voltage indicator light

PV voltage reaches grid voltage PV voltage does not reach the grid voltage

Green light is on Light is not on

Inverter is in the grid state Green light is on

B

AC voltage

No AC voltage

indicator light

Light is not on

With AC voltage, inverter is in the grid countdown state

The green light flashes slowly, and the alarm or fault indicator light is not on

28

Description of LED status

Position

of LED

Type of LED

B

AC voltage indicator light

Inverter status

LED status

With AC voltage, inverter is in a fault state

The green light flashes slowly, and the alarm or fault indicator light is steady red.

Inverter works normally Light is not on

C

Alarm or fault indicator light

Inverter is in alarm state Red light flashes slowly

Inverter is in fault state

Red light is on

Inverter has external communication, such as RS485, GPRS, etc.

Green light is on

D

Communication Inverter has no external

indicator light

communication

Light is not on

Inverter upgrade or USB interface is reading and writing data

Green light flashes

Inverter is in the grid state

The eight LEDs from left to right represent the power of the inverter: if 8 green lights are on, it represents 100% of the inverter power. As shown in Figure 7.3, it represents 37.5% of the inverter power, and so on.

Power or fault

E

code indicator

light

The 8 LED lights from right to left represent the fault codes currently reported by the

inverter. From right to left, they

represent 1, 2, 4, 8, 16, 32, 64,

Inverter is in fault state

and 128. For example, the first and fourth green LEDs on the

right are always on, which

means 1+8=9. In addition, add

200 to get 209, which means

the inverter reports fault 209,

and so on.

29

Monitoring 8
8.1 Remote Data Monitoring
MAX-X series inverter remote monitoring ways include APP(ShinePhone) and server Web page, RS485,GPRS,4G,PLC(reserved) can satisfy both ways of monitoring. 8.1.1 Mobile phone APP(ShinePhone) remote monitoring 1>Scan the following QR code, or download from Android store or App store by searching “Shinephone”, download and install software.
Fig 8.1 Note: 1.Make you it’s the latest version.
2.Please find more details on http://server.growatt.com.
2>Users can register their mobile APP account by following the steps below:
Run ShinePhone, go to login page, click “register”.Registration is required to fill in the information, with the * is required, the agreement is mandatory, you can log in to the main interface of ShinePhone after registration, the registration page and the main interface are as shown below. Shinephone login and main page:

Fig 8.2

Fig 8.3 30

Device page: 1>Main page top middle is the name of current plant, user can click the “” button to switch to other plants under this account. 2>User can add datalogger,check datalogger and add plant by click”+”button at the top right corner. 3>Top half shows current plant power, revenue today and total production. 4>My device list shows current plant device, user can see more details by click the device, left cross the device to stick the device and edit, edit operation includes change device alias, icon,and delete device.

2>User can add datalogger at the datalogger list page to add a datalogger, edit, delete, configure etc. 3>User can add more plants with the add Plant function.
Device page and function: 1>Device page: User can click the device to see more details, the device page show current power and Energy today and daily power chart, user can find more with control,parameter, data and Events page. 2>Control: user set inverter on/off, set active power, set reactive power, set PF, set inverter time, set grid voltage high, set grid voltage low. The operation password is : inverter+date, for example inverter20170722. 3>Parameter: user can see device SN, rated power, firmware version, PV1 voltage, current, and power etc.

Fig 8.4 add datalogger

Fig 8.5 datalogger list

Fig 8.6 add plant

Datalogger: 1>User can add more datalogger under the particular plant.
Way: Click “+” in the upper right corner of the device page and select “Add Collector (WiFi/GPRS, etc.)”, as shown in Figure 8.7. Note: You can choose to manually enter the collector serial number for addition, or you can add it by scanning the barcode on the nameplate.

Fig 8.7 31

Fig 8.8

Fig 8.9

Fig 8.10

4>Data page: user can see the PV power, voltage, current, R phase power, S phase power, S phase power, T phase power, output power by day, month, year, by finger up cross the screen. 5>Events: User can see the fault message if there it is.

32

Fig 8.11

Fig 8.12

. . 8 1 2 GPRS /4G
. . . 8 1 2 1 Register account
1>Register account Open browser, input “server.growatt.com”, click “New User” at login page, input the necessary information then go back to login page, input the registered username and password, click “Sign In”.

Fig 8.14
2>Add datalogger At Plant page, click device manage, then click add datalogger, input the SN and valid code then save, after device is powered on, datalogger will show after 5mins, also the device will come online(our device is monitored by datalogger, so need to add the datalogger here first).

Fig 8.13 33

Fig 8.15 34

Fig 8.16

Fig 8.17

Fig 8.19 B. Plant data page can check device power, voltage curve by time, day, month or year.

Fig 8.18 3> Data reading A.Basic production reading, Energy today, total production, revenue today and accumulative revenue are showing on this page.

Fig 8.20

35

36

4>Set up the equipment The device management page selects MAX. The serial number of the device to be set can be found in the list. Notice: The following operations are requested by professionals.

Fig 8.21
Fig 8.22 5>Check detailed data Double-click the device serial number in the device list. The detailed data page is displayed. Data pages can be viewed by date or exported.
Fig 8.23 37

Fig 8.24
8.1.2.2 Shinemaster monitoring This is a cost-effective and compact monitoring device that is specially designed for solar power plants, with a high-speed CPU and a stable Linux system that intelligently records the user’s system characteristics.

Multiple inverters

ShineMaster

cable

Router

485-1 IN

485-1 OUT 485-1 IN

Add matching resistance

RS485 twisted pair cable

Feature 1> A versatile and high-performance communication data logger that notifies the user
of system status at any time.
2> Flexible parameter setting, system information management, error prompting and
recording, high-capacity storage. 3> Collect data and upload data to Growatt in real time over the network.
Note: The smart meter and environmental monitor must be Growatt’s designated manufacturer, otherwise monitoring will not be possible. When RS485 of multiple
machines is used in parallel, please connect the ground wire according to section 6.3.1.

38

The system framework of communication monitoring is shown in the figure below. Users can choose the most suitable monitoring method according to the actual situation.
Multiple inverters RS 485

GPRS/4G

ShineMaster

Computer

Connecting communication cable

router Connecting communication cable

Internet
Connecting communication cable 4G/GPRS

Connecting communication cable 4G/GPRS

DB
data storage

Computer

Phone

Pad

39

1>ShineMaster IP Address query A.The PC and shinemaster lan ports are connected to the router’s port through the network cable, so that they are in the same local area network. B. Go to the router’s management page and check the “Internet host list” to query the IP address of the ShineMaster serial number as the name of the connected device. This IP is the IP address assigned by the router to the ShineMaster. If you do not know how to do this, contact your network administrator for operation. Note: The router needs to enable automatic IP assignment, that is, open the DHCP function. C. Enter the shinemaster IP address in the browser to enter the shinemaster built-in page. 2>ShineMaster Built-in page access Before accessing, check whether the communication cable between the devices is securely connected. After the check is correct, you can enter the ShineMaster IP address in the IE browser to access the built-in page of the ShineMaster. As long as the ShineMaster is on the same network segment as the computer you are accessing, you can access the ShineMaster built-in server. A.If the user successfully visits the shinemaster built-in page, they can go directly to the built-in page login interface, as shown in figure 8.25 below.
Fig 8.25 B. Enter user name and password, default login username: admin password: admin. click login after filling in, enter growatt shinemaster system page. 3>ShineMaster Data collector status view Click on the status of the shinemaster data collector to view shinemaster”system state information”, “serial number,” server address, “number of connected devices,” and so on.
40

2)Select the type of photovoltaic device monitored in the second drop-down list.

Fig 8.26 4>ShineMaster Data collector add or delete device ShineMaster Before monitoring photovoltaic devices, we need to enter the page of the built-in shinemaster data collector settings to add devices. A. Add device
1)Select the monitoring mode for monitoring photovoltaic devices in the first drop-
down list of add or remove devices.
Fig 8.27
41

Fig 8.28 3)Fill in the third drop-down list with the photovoltaic device correspondence address.
Fig 8.29 4)Select “Add” and then click “Save”. 5)Go to the device status page after saving success to confirm that the device was added successfully.
Fig 8.30 42

B. Delete device 1)Select the first drop-down list of “add or remove devices” to monitor the monitoing mode of photovoltaic devices. 2)Select the type of photovoltaic device monitored in the second drop-down list. 3)Fill in the third drop-down list with the photovoltaic device correspondenc address.. 4)Select the following “del” and click Save to complete the device addition. 5)Enter the device status page after successful save to confirm that the device was deleted successfully.
5>ShineMaster Data upload to ShineServer A. RegisterLogin 1)Enter the server domain name in the computer browser to enter the shineserver login page, if you are logged in for the first time, please register the user name. Enter the domain name access page, as shown in figure 8.32 below. Chinese user server domain namehttp://server-cn.growatt.com. The domain name of the international user server ishttp://server.growatt.com.

Fig 8.32
B. View monitoring data 1) After registration is complete, jump to the shineserver main interface automatically. Click on “power station” and “work information” to display the information for the power station’s total power flow chart on the same day. The drop-down list “Select collector” allows you to view the daily power flow chart of a single inverter for the power station.

Fig 8.31
2Register user name, input user information according to prompt, after information is completed, click “register”. Note: “collector serial number” and “collector check code” see shinemaster serialnumber box or guarantee box.
43

Fig 8.33 44

  1. By clicking on “power station” and “equipment management” in turn, the real-time data of “data collector”, “inverter”, “environment monitor”, “intelligent meter” and “confluence box” MAX “can be viewed.
    8.2 Local Data Monitoring
    MAX-X series Inverter local data monitoring mode has a mobile phone app phone) and PC direct connection, udisk, details are as follows.
    8.2.1 Mobile phone app (Shinephone) Local Monitoring 8.2.1.1 Log on to app for local monitoring Method 1 When you open the app login front page, click the top right corner toolbox icon. Pop up the toolbox, click the local debugging tool, and you can get the wifi name of the collector by scanning the QR code or barcode(The default password for WIFI is 12345678. If you have already connected, you can click “Skip” to connect directly to the WIFI.)

Fig 8.34 Method 2 Open app enter user name and password click login, enter me (personal center). Click the enter tool, find the local debugger to enter, and you can get the wifi name of the collector by scanning the QR code or barcode(The default password for WIFI is 12345678. If you have already connected, you can click “Skip” to connect directly to the WIFI.)
45

Fig 8.35
8.2.1.2 Use of local monitoring and debugging When viewing local monitoring, you must keep the phone’s wifi connected to the collector’s wifi to view local monitoring (to enter the local monitoring page, first click auto refresh to get the latest data information). Electricity generation: the option to view the latest generation, daily generation, monthly and annual generation of detailed information; Power: you can see the current power and rated power value; failure: can read the equipment detailed fault information.
1>device control Note: In addition to resetting the password to connect to the network, other WIFI modules that must connect to the collector can view information. A.Reset password Need network connection login oss account to set up or modify the local debug password. B.Setting configuration The configuration data of inverter, voltage, power and so on can be modified according to the usage (Fig 8.36).
46

Fig 8.36
C.Parameter configuration The parameter data of the equipment can be modified according to the usage (Fig 8.37).
D.Intelligent detection Detailed and accurate view of the device’s detailed data and status (Fig 8.38).

Fig 8.38 E.Intelligent I-V curve scanning Can remotely scan each mppt (Fig 8.39).

Fig 8.37 47

Fig 8.39 48

F.Fault recording detection Remote, fast and accurate fault location (Fig 8.40).
Fig 8.40 G.Real-time recording detection Inverter voltage and current quality can be observed in real time (Fig 8.41).

H.One click diagnosis I-V curve diagnosis, grid waveform, THDV and cable impedance detection all at one click(Fig 8.42).
I.High level setting According to the register address set parameters (professionals).
J.Device information Check PV voltage/current, string voltage/current, ACvoltage/current/power/frequency, PID voltage/current, internal parameters and device detail information and parameters ( Fig 8.43).

Fig 8.41 49

Fig 8.42 50

2>Fault Recording Create the bconfig.txt file under the root of the U disk, write the following content, then insert the U disk that can be read fault information, then generates a form under the files in the root director y, A total of 60 fault recording information is stored, the latest Numbers is 0.

Fig 8.43
8.2.2 U Disk Monitoring Refer to 6.3.2 USB to WIFI/ U disk communicate connection, the local monitoring of U disk can realize the functions of software burning, fault recording, curve analysis and realtime recording. Details are as follows: 1>Firmware Programming Create the bconfig.txt file under the root of the U disk, write to the following content, then insert the U disk to programming. Note the M3 program needs to be programming at last time.

Fig 8.45 3>Curve Analysis Create the bconfig.txt file under the root of the U disk, write the following content, the insert U disk to record I-V curve, then generates a form under the files in the root directory.

Fime name
Fig 8.44 51

Fig 8.46 52

4>Real Time Recording Create the bconfig.txt file under the root of the U disk, write the following content,then insert U disk to read real time recording informationthen generates a form under the files in the root directorythe form record’s waveform is consistent with the ID of the command setting.
Fig 8.47
53

. . 9.1 Routine Maintenance
9 1 1 Cleaning Inverter

System Maintenance 9

·Before any operation, please disconnect the DC switch and AC switch, and DANGER wait for at least 5 minutes until internal capacitance discharge completely.

1>Check the ambient temperature and dust of the inverter, clean the inverter when necessary. 2>Observe whether the air outlets is normal, when necessary, clean the air outlets or clean the fan step by step, steps refer to 9.1.2.
. . 9 1 2 Fan Maintenance

DANGER

·It must be carried out by qualified, trained personnel and comply with all prevailing local code and regulations. ·Please disconnect the DC switch and AC switch before any operation, and wait for at least 5 minutes until the internal bus capacitance discharge completely.

·Do not use the air pump cleaning fan, which may cause fan damage. WARNING
When the Growatt MAX-X series inverter work in high temperature environment, good ventilation and heat dissipation can effectively reduce the chance of load derating. Inverter equipped with internal cooling fans, when the internal temperature is too high, the fans work in to reduce the internal temperature. When the inverter is derating because of the internal temperature is too high, the following are the possible reasons or solutions. 1)Fan is blocked or the heat sink gathers too much dust, it needs to clean the fan, fan cover or heat sink. 2)Fan is damaged, it need to replace the fan. 3)Poor ventilation of the installation location, it needs to select the appropriate installation location according to the basic installation requirements. Fan cleaning and replacement procedure; 1>Please ensure that the DC side and AC side of the inverter have been disconnected before cleaning or replacement of the fan. 1) Turn off DC switch. 2) Disconnect DC terminals from inverter(Users need tools to disconnect the DC connection terminals). 3) Turn off AC switch. 2>Remove the screws on the fan guards with a cross screwdriver. it is shown as below.

54

Fig 9.1 External fan view
Fig 9.2 Internal fan view 3>Disconnect the wire connector of the fans with a flat head screw driver and remove the fans from the fan guards, it is shown as below.
Fig 9.3
Fig 9.4 External fan view 55

Fig 9.5 Internal fan view
NoticeMAX-X series inverter has seven fansinternal fan2Pcsexternal fan5Pcs). 4>Clean fan, fan guards and heat sink or replace fan. 1) Clean the fan and fan guards with air pump, brush or a damp cloth. 2) Remove each fan separately for cleaning if necessary. 3) Remove the fan that need to replace with a cross screwdriver, replace a new fan. 4) Tidy up the wire.
5>Install the fan, fan guard fixed and the inverter again.

9.2 Trouble Shooting

DANGER

·It must be operated by well-trained professional electrical technicians and abide by this manual. ·Normally grounded conductors may be ungrounded and energized when a PV isolation low is indicated. ·Risk of electric shock.

9.2.1 Warning Warnings identify the current status of the inverter(Max), warnings do not related to a fault and it does not affect the normal running of the inverter. When a warning with a number after it appears in the display, it indicates a warning code and is usually cleared through an orderly shutdown /re-set or a self-corrective action performed by the inverter.

56

Warning Warning 200 Warning 201 Warning 202 Warning 203 Warning 204 Warning 205 Warning 206 Warning 207 Warning 208 Warning 209 Warning 210 Warning 300 warning301 Warning 302 Warning 310
Warning 400
Warning 401

Description

Suggestion

String Fault String abnormal DC SPD warning PV Circuit short Dryconnect function abnormal PV Boost driver abnormal AC SPD warning USB Over-Current DC Fuse Open PV Voltage High
PV Reversed No AC Connection
AC V Outrange
AC F Outrange
NE abnormal
Fan warning
Meter abnormal

1.After shutdown,check the panel is normal. 2.Contact Growatt. 1.After shutdown,check the panel is normal. 2.Contact Growatt.
1. After shutdown,check the DC SPD. 2. Contact Growatt.
1. Check if the PV circuit is shortcircuited. 2. Contact Growatt. 1. After shutdown,check the dry Dryconnect wiring. 2. Contact Growatt.
1. Restart inverter. 2. Contact Growatt.
1. After shutdown,check the AC SPD. 2. Contact Growatt.
1. unplug the U disk. 2. Re-access U disk after shutdown. 3. Contact Growatt.
1. After shutdown,check fuse. 2. Contact Growatt.
1. Immediately disconnect the DC switch and check the voltage. 2. Contact Growatt.
1. Check PV input terminals. 2. Contact Growatt. 1. Please confirm grid is lost or not. 2. Contact Growatt.
1. Check the AC voltage is in the range of standard voltage in specification. 2. Contact Growatt.
1. Check the frequency is in the range of specification or not. 2. Contact Growatt.
1. Check if the neutral and ground cables are well connected, 2. Contact Growatt
1. After shutdown,Check the fan connection. 2. Replace the fan. 3. Contact Growatt.
1. Check if the communication between the inverter and the meter is abnormal. 2. Contact Growatt.

57

Warning Warning 404 Warning 405 Warning 406 Warning 407 Warning 408 Warning 409

Description EEPROM abnormal Firmware version abnormal Boost module error Over Temperature
NTC broken Reactive abnormal

Suggestion
1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact Growatt. 1. Check if shinemaster is abnormal. 2. Contact Growatt.

NoticeMAX series inverter has two external fans and five Internal fan. If the suggestions do not work, please contact to Growatt.
9.2.2 Error Errors codes identify a possible equipment failure, fault or incorrect inverter setting or configuration, any or all attempts to correct or clear a fault must be performed by qualified personnel. Typically, the error code can be cleared once the cause or fault is removed. Some of error code as table shows below, may indicate a fatal error and require you to contact the supplier or Growatt for help.

58

Error
Error 200
Error 201 Error 202 Error 203 Error 204 Error 300 Error 301 Error 302 Error 303
Error 304 Error 400 Error 401 Error 402 Error 403 Error 404 Error 405 Error 406 Error 407

Description

Suggestion

AFCI Fault

1. After shutdown,check the panel terminal. 2. Restart inverter. 3. Contact Growatt.

Residual I High PV Voltage High PV Isolation Low
PV Reversed AC V Outrange

1. Restart inverter. 2. Contact Growatt.
1. Immediately disconnect the DC switch and check the voltage. 2. Contact Growatt. 1. After shutdown, check if the panel shell is reliably grounded. 2. Contact Growatt. 1. After shutdown, check PV input terminals. 2. Contact Growatt.
1. Check grid voltage. 2. Contact Growatt.

AC terminals reversed

1. Check AC terminals. 2. Contact Growatt.

No AC Connection
NE abnormal
AC F Outrange
DCI bias abnormal DC Voltage High Fault Output DC current too high

1. After shutdown,check AC wiring. 2. Contact Growatt.
1. After shutdown,ensure that the ground wire is reliably connected. 2. Contact Growatt.
1. Check the frequency is in the range of specification or not. 2. Contact Growatt.
1. Restart inverter. 2. Contact Growatt. 1. Restart inverter. 2. Contact Growatt.
1. Restart inverter. 2. Contact Growatt.

Output current unbalance

1. Restart inverter. 2. Contact Growatt.

Bus sample fault

1. Restart inverter. 2. Contact Growatt.

Relay fault

1. Restart inverter. 2. Contact Growatt.

Init model fault

1. Restart inverter. 2. Contact Growatt.

AutoTest failure

1. Restart inverter. 2. Contact Growatt.

59

Error Error 408 Error 409 Error 411 Error 412 Error 413 Error 414 Error 415 Error 416 Error 417 Error 418 Error 420 Error 421 Error 422 Error 425 Error 426 Error 427 Error 428 Error 429

Description

Suggestion

NTC Temperature too high

1. Restart inverter. 2. Contact Growatt.

Bus voltage abnormal

1. Restart inverter. 2. Contact Growatt.

Communication fault

1. Restart inverter. 2. Contact Growatt.

Temperature sensor abnormal

1. Restart inverter. 2. Contact Growatt.

IGBT drive fault

1. Restart inverter. 2. Contact Growatt.

EEPROM fault

1. Check if shinemaster is abnormal. 2. Contact Growatt.

Internal power test fail

1. Restart inverter. 2. Contact Growatt.

Over current protected

1. Restart inverter. 2. Contact Growatt.

System protocol abnormal

1. Restart inverter. 2. Contact Growatt.

firmware version abnormal

1. Restart inverter. 2. Contact Growatt.

GFCI Module damage

1. Restart inverter. 2. Contact Growatt.

CPLD abnormal

1. Restart inverter. 2. Contact Growatt.

Sampling is inconsistent

1. Restart inverter. 2. Contact Growatt.

AFCI self-test fault

1. Restart inverter. 2. Contact Growatt.

PV current abnormal

1. Restart inverter. 2. Contact Growatt.

AC current abnormal

1. Restart inverter. 2. Contact Growatt.

Boost Short Out

1. Contact Growatt.

Bus voltage softstart fail

1. Restart inverter. 2. Contact Growatt.

60

10 Specification

Model

MAX

Specifications

100KTL3-X LV

Input Data(DC)

MAX 110KTL3-X LV

MAX 120KTL3-X LV

MAX 125KTL3 LV

Max.recommended PV power(for module STC)
Max. DC voltage
Start voltage

150kW

165kW

180kW

1100V 195V

187.5kW

Nominal voltage

600V

MPP voltage range

180V-1000V

No. of MPP trackers

10

No. of PV strings per MPP trackers

2

Max. input current per MPP trackers
Max. short-circuit current per MPP trackers DC overvoltage category
Output Data(AC)

32A 40A Category II

AC nominal power

100kW

110kW

120kW

125kW

Max. AC apparent power
Nominal AC voltage/range
AC grid frequency/range
Max. output current
Power factor(@nominal)
Max. inrush current/duration
Max. output facult current/duration
Adjustable power factor

110kVA
167.1A@380V 158.8A@400V

121kVA

132kVA

230V/400V 340-440VAC
50/60Hz 45-55Hz/55-65Hz
183.8A@380V 200.5A@380V 174.6A@400V 190.5A@400V

0.99

20KA/tr:8us,tf:20us

400A/30us

0.8leading …0.8lagging

137.5kVA
208.9A@380V 198.5A@400V

THDi AC grid connection type

<3% 3W/N/PE

61

AC overvoltage category
efficiency
Max. efficiency
Euro-eta Protection devices
DC reverse-polarity protection DC switch
DC Surge protection Insulation resistance monitoring AC surge protection
Grid monitoring
Anti-islanding protection Residual-current monitoring unit String monitoring
Anti-PID function AFCI protection
General data Dimensions (W /H / D) in mm Max. inrush current/duration Weight Operating temperature range Altitude
Internal consumption at Topology
Cooling
Protection degree
Relative humidity

98.4%

Category III

98.8%

98.5%

98.5%

Yes Yes Type II
Yes
Yes Yes Yes
Yes Yes Optional Optional

970640345mm
20KA/tr:8us,tf:20us 84kg
-30- +60
4000m <1W(Note1) Transformerless Smart air cooling
IP66 0~100%

98.5% 62

DC connection AC connection Interfaces Display RS485/USB PLC/GPRS/4G Warranty: 5 /10 years Certificates and approvals
Grid regulation

H4/MC4(Optional) OT/DT terminal
LED/WIFI+APP Yes
Optional Optional
AS/NZS 4777.2,CEI 0-21,CEI 0-16,VDE-AR-N 4105, DIN V VDE V 0126-1-1,UTE C 15-712-1,EN 50438,
IEC 60068,IEC 61683,IEC 62116,IEC 61727, MEA,PEA,DRRG/DEWA:2016,BDEW,G59/3

EMC

EN61000-6-2,EN61000-6-4

Safety

IEC/EN62109-1,IEC/EN62109-2

Note1: If with AC power supply function, self-consumption at night is less than 15W.

63

Model Specifications Input Data(DC)

MAX 133KTL3-X LV

MAX

MAX

125KTL3-X MV 136KTL3-X MV

Max.recommended PV power(for module STC)
Max. DC voltage
Start voltage

199.5kW

165kW

180kW

1100V 195V

Nominal voltage

600V

720V

720V

MPP voltage range

180V-1000V

No. of MPP trackers

10

No. of PV strings per MPP trackers

2

Max. input current per MPP trackers

32A

Max. short-circuit current per MPP trackers DC overvoltage category
Output Data(AC)

40A Category II

AC nominal power

133kW

125kW

136kW

Max. AC apparent power
Nominal AC voltage/range
AC grid frequency/range
Max. output current
Power factor(@nominal)
Max. inrush current/duration
Max. output facult current/duration
Adjustable power factor

146.3kVA 230V/400V 340-440VAC
222.3A@380V 211.2A@400V

137.5kVA

149.6kVA

277V/480V

277V/480V

408-528VAC 408-528VAC

50/60Hz 45-55Hz/55-65Hz

165.4A

179.9A

0.99

20KA/tr:8us,tf:20us

400A/30us

0.8leading …0.8lagging

THDi AC grid connection type

3W/N/PE

<3%

3W+PE

3W+PE

MAX 150KTL3 MV
187.5kW 720V
150kW 165kVA 277V/480V 408-528VAC 198.5A
3W+PE

64

AC overvoltage category
efficiency
Max. efficiency
Euro-eta
Protection devices
DC reverse-polarity protection DC switch
DC Surge protection Insulation resistance monitoring AC surge protection
Grid monitoring
Anti-islanding protection Residual-current monitoring unit String monitoring
Anti-PID function
AFCI protection
General data
Dimensions (W /H / D) in mm Max. inrush current/duration Weight Operating temperature range Altitude
Internal consumption at
Topology
Cooling
Protection degree
Relative humidity

98.8%

65

Category III

99%

99%

98.5%

Yes Yes Type II
Yes
Yes Yes Yes
Yes Yes Optional Optional

970640345mm
20KA/tr:8us,tf:20us 84kg
-30- +60
4000m <1W(Note1) Transformerless Smart air cooling
IP66 0~100%

99%

DC connection AC connection Interfaces Display RS485/USB PLC/GPRS/4G Warranty: 5 /10 years Certificates and approvals
Grid regulation

H4/MC4(Optional) OT/DT terminal
LED/WIFI+APP Yes
Optional Optional
AS/NZS 4777.2,CEI 0-21,CEI 0-16,VDE-AR-N 4105, DIN V VDE V 0126-1-1,UTE C 15-712-1,EN 50438,
IEC 60068,IEC 61683,IEC 62116,IEC 61727, MEA,PEA,DRRG/DEWA:2016,BDEW,G59/3

EMC

EN61000-6-2,EN61000-6-4

Safety

IEC/EN62109-1,IEC/EN62109-2

Note1: If with AC power supply function, self-consumption at night is less than 15W.

66

11 Decommissioning
If the inverter does not operate in the future, it needs to be properly disposed. The steps are as follows: 1>Disconnect the external AC short circuit and prevent reconnection due to misoperation. 2>Turn the DC switch to “OFF” position. 3>Wait at least 5 minutes until the internal capacitor discharge is completed. 4>Disconnect the AC connector. 5>Disconnect DC connector. 6>Remove the inverter from the wall. 7>Disposing of the inverter.
11.1 Disposing Of The MAX-X Series Inverter
Do not dispose of MAX series inverter together with household waste. Please accordance with the disposal regulations for electronic waste which apply at the installation site at that time. Ensure that the old unit and, where applicable, any accessories are disposed of in a proper manner.
12 Quality assurance
Please refer to related file.

Contact 13
If you have technical problems concerning our products, contact your installer or Growatt, please provide information below for better support. 1>Inverter type 2>Serial number of inverter 3>Error code of inverter 4>LED status of inverter 5>DC input voltage of inverter (Modules information) 6>Inverter communication method
Shenzhen Growatt New Energy Co.,Ltd 4-13/F,Building A,Sino-German(Europe) Industrial Park, Hangcheng Ave,Bao’an District, Shenzhen, China T +86 0755 2747 1942 E service@ginverter.com W www.ginverter.com

67

68

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Growatt User Manuals

Related Manuals