GROWATT 10KW ON-GRID MOD 10KTL3-X Trifazat Instructions

June 9, 2024
Growatt

GROWATT logo1 MOD 7-15KTL3-X &MOD 7-11KTL3-X-AU&
MOD 7-11 KTL3-X-AU(NDS) &
MOD 12-15KTL3-X(NDS) Quick Guide

1. Overview

     GROWATT 10KTL3-X - Overview 4

(1) Front panel          (2) Touch button           (3) LCD screen
(4) LED indicator     (5) Mounting bracket     (6) Heat sink
(7) DC switch           (8) PV terminal              (9) RS485 port
(10) USB port           (11) Vent valve               (12) AC terminal

Note: Dual MPPTs for MOD 3-11KTL3-X&MOD 3-6KTL3-X(NDS), one string input per MPPT. Dual MPPTs for MOD 7-11KTL3-X-AU& MOD 7-11KTL3-X-AU(NDS)&MOD 12-15KTL3-X &MOD 12-15KTL3-X(NDS), one MPPT has one string, and other one has two strings.

Note:

  1. This document is for quick installation guidance only, please refer to User Manual for more details.
  2. Growatt shall not be liable for any damage resulting from unproper installation.
2. Installation
System overview

GROWATT 10KTL3-X - Installation 1

  1. PV Array
  2. Inverter
  3. Grid
  4. Electrical Grid
  5. AC Breaker
  6. Breaker
  7. Load
  8. DC Breaker
2.1 Installation requirements

GROWATT 10KTL3-X - Installation 2

2.2 Wall mounting

GROWATT 10KTL3-X - Installation 3

Note:

  1. When drilling holes in the wall, avoid water and electricity pipes, otherwise it may cause danger.
2.3 Communication module installation

Install

  1. Inverter side

Uninstall

  1. Inverter side
3. Electrical connection

Please prepare the cable before connecting as follows.

No. Cable name Type Recommend model
1 Protective grounding wire Single multi-core yellow-green wire 6mm²
2 AC output wire Two multi-core or three polychromatic copper wires 6mm²
3 PV input wire PV wire (such as PV1-F) 4mm² – 6mm²
4 Communication wire RS485 /

Note:

  1. Please make sure all switches are in “OFF” position before wiring. For personal safety, please do not operate with electricity.
  2. If the diameter of the cable does not match the terminal, or the cable is aluminum wire, please contact our after-sales personnel.
3.1 Grounding
3.2 AC output connection

1

| 2

| 3

---|---|---
4

GROWATT 10KTL3-X - Electrical connection 2d

| 5

3.3 DC connection

3.3.1 PV input terminal installation

1

GROWATT 10KTL3-X - Electrical connection 3

  1. Positive metal terminal
  2. Negative metal terminal

| 2

Please make sure the cable can not be pulled out after pressing.

| 3

GROWATT 10KTL3-X - Electrical connection 5

  1. Negative metal terminal

Pull the PV cable make sure there is no loose or shaking.

---|---|---
4

GROWATT 10KTL3-X - Electrical connection 6

  1. Positive metal terminal
  2. Negative metal terminal

| 5

GROWATT 10KTL3-X - Electrical connection 7 Make sure the cable polarity is correct and voltage is less than 1100V.

3.3.2 Plug in PV terminal

1

| 2

| Note:

  1. Before installing the PV terminal, please double-check that the PV input voltage and current do not exceed the MPPT limits.
  2. When installing the PV terminal, pay attention to the difference between the positive and negative poles and the one-to-one correspondence between the terminals and the machine.
  3. There is a “click” sound when the terminal is connected,please gently pulling the PV wire to make sure there is no loose or pulling off.

---|---|---

3.3.3 Communication cable installation

GROWATT 10KTL3-X - Electrical connection 10

  1. Inverter side

GROWATT 10KTL3-X - Electrical connection 11

  1. connect to RRCR

No.

| RRCR Description|

Active Power

---|---|---

9

| K1-out| 0%

10

| K2-out| 30%

11

| K3-out| 60%

12

| K4-out| 100%

13

| Relays common node| /

14

| /| /

No.

| Description|

Remarks

---|---|---

1

| +12V| Dry junction : external relay coil interface, power is not more than 2W

2

| COM

3

| RS485A1| RS485 communication port

4

| RS485B1

5

| RS485A2| BAT communication port(reserved)

6

| RS485B2

7

| RS485A3| Meter communication port

8

| RS485B3

9

| DRM1/5| Relay contact 1 input

10

| DRM2/6| Relay contact 2 input

11

| DRM3/7| Relay contact 3 input

12

| DRM4/8| Relay contact 4 input

13

| REF/GEN| GND

14

| DRM0/COM| /

Note:
When connecting the communication line,port 15 and 16 are not connected, as for the other function,please refer to the above table according to the customer needs.

4. Connecting Meter

The following table describes how we can connect EASTRON meter (TPM-E)to inverter:

GROWATT 10KTL3-X - Connecting Meter

Meter Pin NO.

| Description| Meter Connection
---|---|---
1/2/3/4| L1/L2/L3/N-in|

Grid L1/L2/L3/N

5/6/7/8

| L1/L2/L3/N-out| AC connector & Load L1/L2/L3/N
A| RS485A|

SYS COM Pin 7 RS485A2

B

| RS485B|

SYS COM Pin 8 RS485B2

5. Post-installation check

No.

|

Acceptance criteria

---|---

1

| The inverter is installed correctly, firmly and reliably.

2

| The ground wire connected well and the connection is firm and reliable.

3

| All switches are in the OFF state.

4

| All wiring is correct and securely connected.

5

| The requirements, wiring of the cable is reasonable, and there is no meets the phenomenon of broken skin.

6

| The RS485 communication cable is installed correctly and firmly.

7

| The cable tie port is trimmed well without leaving sharp corners, meets the requirements of the user.

8

| All exposed terminals are well protected and there are no vacant ports.

9

| Pay attention to clean up all construction residues.

6. Power on and off steps

Note:
Before turning the inverter on, please make sure the PV input voltage and current are within the MPPT limits.
Follow the steps below to turn the inverter on:

  1. Switch on the build-in DC isolator at the bottom of the inverter.
  2. Switch on the PV Array and DC isolator next to your inverter, if you can not find this switch, skip this step.
  3. Switch on the Solar AC isolator if the inverter is more than 3 meters away from your switchboard.
  4. Switch on the solar supply main switch in the switch board.

To shut down your system, follow this guide in reverse order.

7. Status of PV grid inverter

Customer can read more information by push button.

Mark

| Describe|

Explain

---|---|---
|

Touch mark

| Single touch| Switch the display interface or the current number plus 1
Double touch|

Enter the setting state or confirm

Triple touch

| Return to the previous display interface
Long press for 5s|

The current data returns to the default value

|

Inverter status indicator

| Red| Fault
Green|

Normal operation

Red light flashing

|

Warning

It can display the basic information of inverter through LCD display screen (PV/AC voltage, PV power, AC current, total power, generating capacity, etc.).

8. Export limitation setting

GROWATT 10KTL3-X - Limitation Setting

If the local grid company requires to limit the output power from your inverter systems, we introduce the concept of Export Limit Rate. The ratio of your system output power divided by the rated power of the inverter is called Export Limited Rate. For example, if the local grid company only accepts 4kW from your 5kW system, then the Export Limit Rate of 5kW inverter should be 80%.

9. Service and contact

Shenzhen Growatt New Energy Co., Ltd
4-13/F, Building A, Sino-German(Europe) Industrial Park,
Hangcheng Ave, Guxing Community, Xixiang Subdistrict,
Bao’an District, Shenzhen, China
T      +86 0755 2747 1942
E      service@ginverter.com
W      www.ginverter.com

GROWATT 10KTL3-X - QR Code GROWATT 10KTL3-X - Facebook  GROWATT