EUCHNER BR-CC-FLX Transponder Coded Safety Switch with Guard Locking Instruction Manual
- June 9, 2024
- EUCHNER
Table of Contents
BR-CC-FLX Transponder Coded Safety Switch with Guard Locking
Operating Instructions
Transponder-Coded Safety Switch with Guard Locking for Process Protection
CTS-C2-BP/BR-CC-FLX EN
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
Contents
1. About this document………………………………………………………………………………… 4
1.1. Scope…………………………………………………………………………………………………………………………..4 1.2. Target group
………………………………………………………………………………………………………………….4 1.3. Key to
symbols……………………………………………………………………………………………………………….4 1.4. Supplementary
documents ………………………………………………………………………………………………..4
2. Correct use ……………………………………………………………………………………………. 5
3. Description of the safety function ……………………………………………………………….. 7
4. Exclusion of liability and warranty ………………………………………………………………. 8
5. General safety precautions ……………………………………………………………………….. 8
6. Function ………………………………………………………………………………………………… 9
6.1. Monitoring of the guard locking for process protection
…………………………………………………………….9 6.2. Monitoring outputs/status bits
……………………………………………………………………………………………9
6.2.1. Guard locking signal OL ………………………………………………………………………………………9 6.2.2. Door
position 1 signal OD…………………………………………………………………………………..10 6.2.3. Door position 2
signal OT …………………………………………………………………………………..10 6.2.4. Diagnostic signal OI
………………………………………………………………………………………….10 6.2.5. Escape release signal OER
………………………………………………………………………………..10 6.2.6. Status signal
OM………………………………………………………………………………………………10 6.2.7. Locking element signal
OLS………………………………………………………………………………..10 6.2.8. Communication connection
C………………………………………………………………………………10 6.3. Guard locking for process
protection………………………………………………………………………………….10 6.4. Switching states
……………………………………………………………………………………………………………11
7. Manual release……………………………………………………………………………………… 12
7.1. Auxiliary release…………………………………………………………………………………………………………….12 7.1.1.
Actuating auxiliary release ………………………………………………………………………………….12
7.2. Escape release……………………………………………………………………………………………………………..13 7.2.1.
Actuating escape release …………………………………………………………………………………..13
8. Mounting……………………………………………………………………………………………… 14
9. Electrical connection ……………………………………………………………………………… 17
9.1. Notes about ………………………………………………………………………………………………………….18 9.2. Safety in
case of faults……………………………………………………………………………………………………18 9.3. Fuse protection
for power supply ………………………………………………………………………………………18 9.4. Requirements for
connecting cables…………………………………………………………………………………..19 9.5. Connector assignment
of safety switches CTS-…-VAB-… with plug connector 2 x M12 …………………..19 9.6.
Connector assignment of safety switches CTS-…-VSA-… with plug connector M12,
8-pin …………………. 20 9.7. Notes on operation with safe control systems
………………………………………………………………………21 9.8. Connection without and with IO-Link
communication……………………………………………………………….21
9.8.1. Connection without IO-Link communication ……………………………………………………………..21
9.8.2. Connection with IO-Link communication………………………………………………………………….21
2
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
10. Connection of a single CTS-C2-BP/BR-CC-FLX (separate operation) ………………… 22
11. Connection of several devices in a chain (series connection)………………………….. 23
11.1. Series connection with wiring in the control cabinet ……………………………………………………………….23
11.2.
Series connection with Y-distributors ………………………………………………………………………………….23
11.2.1. Maximum cable lengths with BR switch chains…………………………………………………………24
11.2.2. Determining cable lengths using the example
table…………………………………………………..24 11.2.3. Connector assignment of Y-distributor for
series connection without IO-Link communication 25 11.2.4. Connector
assignment of Y-distributor for series connection with IO-Link communication
…..27
12. Using communication data………………………………………………………………………. 28
12.1. Connection to a BR/IO-Link Gateway GWY-CB……………………………………………………………………….28
12.2. Connection to a safety relay ESM-CB………………………………………………………………………………….28
12.3.
Overview of the communication data ………………………………………………………………………………….29 12.3.1. Cyclical data (process data)………………………………………………………………………………..29 12.3.2. Acyclical data (device data and events)………………………………………………………………….29
13. Setup ………………………………………………………………………………………………….. 31
13.1. Configuring device and teaching-in actuator for the first time……………………………………………………31
13.2. Teaching-in new actuator (only for evaluation of the actuator with a high coding level)…………………….32
13.3.
Functional check……………………………………………………………………………………………………………33 13.3.1. Mechanical function test …………………………………………………………………………………….33 13.3.2. Electrical function test……………………………………………………………………………………….33
14. Factory reset………………………………………………………………………………………… 34
15. Status and error messages ……………………………………………………………………… 34
15.1. LED displays ………………………………………………………………………………………………………………..34 15.2. Status
messages…………………………………………………………………………………………………………..35 15.3. Error
messages…………………………………………………………………………………………………………….36 15.4. Acknowledging error
messages ………………………………………………………………………………………..37
16. Technical data ………………………………………………………………………………………. 38
16.1. Technical data for safety switch CTS-C2-BP/BR-CC-FLX
…………………………………………………………..38 16.1.1. Typical system
times…………………………………………………………………………………………39
16.2. Radio frequency approvals……………………………………………………………………………………………….40 16.3.
Dimension drawing of safety switch CTS……………………………………………………………………………..41 16.4.
Technical data for actuator A-FLX-D-0.-… …………………………………………………………………………….42
16.4.1. Dimension drawing for actuatorA-FLX-D-0.-……………………………………………………………..42
17. Ordering information and accessories ……………………………………………………….. 43
18. Inspection and service ……………………………………………………………………………. 43
19. Service ……………………………………………………………………………………………….. 43 EN
20. Declaration of conformity ……………………………………………………………………….. 43
MAN20001531-01-09/22 (translation of the original operating instructions)
3
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
1. About this document
1.1. Scope
These operating instructions apply to all CTS-C2-BP/BR-CC-FLX… of version
V2.0.X. These operating instructions, the document Safety information and any
available data sheet form the complete user information for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as
well as setup and servicing staff possessing special expertise in handling
safety components.
1.3. Key to symbols
Symbol/depiction
Meaning Monitoring the position of the guard locking and active monitoring of the guard locking for process protection, high coding level Monitoring the position of the guard locking and active monitoring of the guard locking for process protection, low coding level Monitoring the position of the guard locking and optional monitoring of the guard locking for process protection, high coding level Monitoring the position of the guard locking and optional monitoring of the guard locking for process protection, low coding level
Printed document
Internet www
Document is available for download at www.euchner.com
DANGER WARNING CAUTION
Safety precautions Danger of death or severe injuries Warning about possible injuries Caution slight injuries possible
NOTICE Important!
Tip
Notice about possible device damage Important information
Useful information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title (document number)
Safety information (2525460)
Operating Instructions (MAN20001531)
Contents Basic safety information (this document)
Declaration of conformity Declaration of conformity
Possibly available data sheet
Item-specific information about deviations or additions
Internet www Internet www
Internet www
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc. no. in the search box.
4
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
2. Correct use
Safety switches series CTS-C2-BP/BR-CC-FLX are interlocking devices with guard
locking solenoid (type 4) for process protection without safe guard locking
monitoring. The device complies with the requirements according to EN IEC
60947-5-3.
The device can be configured with the aid of a function actuators. Depending
on the function actuator taught-in, the monitoring of the guard locking for
process protection is permanently active or available as an additional option
and the evaluation of the actuator code has a high or low coding level.
Table 1: System components
Safety switch
Active High coding level
Function actuator
Monitoring of the guard locking for process protection
Optional
Active
High coding level
Low coding level
Optional Low coding level
CTS-C2-BP/BR-CC-FLX…
A-FLX-D-0C-167919
A-FLX-D-0D-169044
A-FLX-D-0E-169045
A-FLX-D-0F-169046
If monitoring of the guard locking for process protection is active, the
following applies:
In combination with a movable guard and the machine control, this safety
component prevents dangerous machine functions from occurring while the guard
is open. A stop command is triggered if the guard is opened during the
dangerous machine function or the guard locking is unlocked.
This means: Ì Starting commands that cause a dangerous machine function must
become active only when the guard is closed
and locked. Ì Opening the guard must trigger a stop command. Ì Closing and
locking a guard must not cause automatic starting of a dangerous machine
function. A separate
start command must be issued. For exceptions, refer to EN ISO 12100 or
relevant C-standards.
If monitoring of the guard locking for process protection is optional, the
following applies:
In combination with a movable guard and the machine control, this safety
component prevents dangerous machine functions from occurring while the guard
is open. A stop command is triggered if the guard is opened during the
dangerous machine function.
This means: Ì Starting commands that cause a dangerous machine function must
become active only when the guard is closed. Ì Opening the guard must trigger
a stop command. Ì Closing a guard must not cause automatic starting of a
dangerous machine function. A separate start command
must be issued. For exceptions, refer to EN ISO 12100 or relevant C-standards.
If the evaluation of the actuator code has a high coding level, the following
applies: Ì The actuator must be assigned to the safety switch by a teach-in
operation so that it is detected by the system.
This unambiguous assignment ensures a particularly high level of protection
against tampering. The system thus possesses a high coding level.
If the evaluation of the actuator code has a low coding level, the following
applies:
EN Ì With the low coding level a specific code is not requested but instead it
is only checked whether the actuator
is of a type that can be detected by the system. There is no exact comparison
of the actuator code with the taught-in code in the safety switch. The system
possesses a low coding level.
MAN20001531-01-09/22 (translation of the original operating instructions)
5
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
Before the device is used, a risk assessment must be performed on the machine,
e.g. according to the following standards: Ì EN ISO 13849-1 Ì EN ISO 12100 Ì
IEC 62061
Correct use includes observing the relevant requirements for installation and
operation, particularly based on the following standards: Ì EN ISO 13849-1 Ì
EN ISO 14119 Ì EN 60204-1
The safety switch is allowed to be operated only in conjunction with the
intended EUCHNER actuators and the related connection components from EUCHNER.
On the use of different actuators or other connection components, EUCHNER
provides no warranty for safe function.
Safety switches in the version CTS-…-BR can be integrated into a BR device
chain. Connection of several devices in a BR switch chain is permitted only
using devices intended for series connection in a BR switch chain. Check this
in the specifications of the device in question.
Important!
Ì The user is responsible for the proper integration of the device into a safe
overall system. For this purpose, the overall system must be validated, e.g.
according to EN ISO 13849-2.
Ì It is only allowed to use components that are permissible according to the
Table 1: System components.
6
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
3. Description of the safety function
Devices from this series feature the following safety functions:
Monitoring of the guard position (interlocking device according to EN ISO
14119) Ì Safety function: the safety outputs are switched off when the guard
is open (see chapter 6. Function on page 9). Ì Safety characteristics:
category, Performance Level, PFHD (see chapter 16. Technical data on page 38).
The following additionally applies in a BR series connection: Ì The safety
outputs are switched on only when the device receives a corresponding signal
from its predecessor in the chain.
NOTICE
You can regard the complete BR device chain as one subsystem during calculation. The following calculation method applies to the PFHD value:
BR-Device #1 … n
External Evaluation (e.g. PLC)
1 PFHD,1
2 PFHD,2
n PFHD,n
PFHD,ext
n
PFHD ges = PFHD,k + PFHd,ext k=1
Alternatively, the simplified method according to section 6.3 of EN
13849-1:2015 can be used for calculation.
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
7
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above,
or if the safety regulations are not followed, or if any servicing is not
performed as required, liability will be excluded and the warranty void.
5. General safety precautions
Safety switches fulfill personnel protection functions. Incorrect installation
or tampering can lead to fatal injuries to personnel.
Check the safe function of the safeguard particularly Ì after any setup work Ì
after the replacement of a system component Ì after an extended period without
use Ì after every fault Ì after any reconfiguration of the device
Independent of these checks, the safe function of the safeguard should be
checked at suitable intervals as part of the maintenance schedule.
WARNING
Danger to life due to improper installation or due to bypassing (tampering).
Safety components fulfill a personnel protection function. Ì Safety components
must not be bypassed, turned away, removed or otherwise rendered ineffective.
On this topic pay attention in particular to the measures for reducing the
possibility of bypassing according to EN ISO 14119:2013, section 7. Ì The
switching operation must be triggered only by actuators designated for this
purpose. Ì Prevent bypassing by means of replacement actuators (only for low
coding level evaluation). For this purpose, restrict access to actuators and
to keys for releases, for example. Ì Make sure the guard cannot be closed
unintentionally, e.g. during servicing. For this purpose, a lockout bar can be
used, for instance. Ì Mounting, electrical connection and setup only by
authorized personnel possessing the following knowledge: – specialist
knowledge in handling safety components – knowledge about the applicable EMC
regulations – knowledge about the applicable regulations on operational safety
and accident prevention.
NOTICE
Risk of damage Ì The guard locking function can no longer be ensured if an
actuator is broken. Opening the door will
immediately switch off the safety outputs. Regularly check the actuator for
mechanical damage.
Important!
Prior to use, read the operating instructions and keep these in a safe place.
Ensure the operating instructions are always available during mounting, setup
and servicing. You can download the operating instructions from
www.euchner.com.
8
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
6. Function
The device monitors the position of movable guards.
The system consists of the following components: coded actuator (transponder)
and switch.
The coding level of the system depends on the configuration of the device (see
chapter 13.1. Configuring device and teaching-in actuator for the first time
on page 31).
When the guard is closed, the actuator is moved into the safety switch. When
the operating distances are reached, power is supplied to the actuator by the
switch and data are transferred.
Switch
Coded actuator
The door position 1 signal OD is set if a permissible code is detected. Guard
locking is activated automatically if power is present at the guard locking
solenoid. The switching conditions for the safety outputs are dependent on the
configuration of the monitoring of the guard locking for process protection
(see chapter 6.4. Switching states on page 11).
If there is a fault in the safety switch, the safety outputs are switched off
and the DIA LED illuminates or flashes red (see chapter 15.3. Error messages
on page 36). The occurrence of faults is detected at the latest on the next
demand to close the safety outputs (e.g. on starting).
6.1. Monitoring of the guard locking for process protection
The device is configured with the aid of the function actuator. Depending on
the function actuator taught-in, the monitoring of the guard locking for
process protection is permanently active or available as an additional option.
Further information about the possible settings is available in the chapter
13.1. Configuring device and teaching-in actuator for the first time on page
31.
If monitoring of the guard locking for process protection is active, the
following applies:
All versions feature two safe outputs for monitoring the guard locking for
process protection. The safety outputs FO1A and FO1B are switched off and the
guard locking signal OL is cleared when guard locking is released.
If monitoring of the guard locking for process protection is optional, the
following applies:
All versions feature two safe outputs for monitoring the door position as well
as the status signal OL for monitoring the guard locking for process
protection; this signal can be evaluated optionally. The safety outputs FO1A
and FO1B are switched off and the door position 1 signal OD is cleared when
the guard is opened.
The following switching conditions apply to the safety outputs FO1A and FO1B:
No fault in the device Guard closed Guard locking active
6.2. Monitoring outputs/status bits
Monitoring of the guard locking for process protection
Active (ON)
Optional (OFF)
TRUE (ON)
TRUE (ON)
TRUE (ON)
TRUE (ON)
TRUE (ON)
irrelevant
EN
Depending on version, the signals listed in the following are available as a status bit or at the monitoring output. The status bits are evaluated via the BR/IO-Link Gateway. Please refer to the corresponding data sheet for further information.
6.2.1. Guard locking signal OL The guard locking signal is present if the guard locking is active.
MAN20001531-01-09/22 (translation of the original operating instructions)
9
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
6.2.2. Door position 1 signal OD The door position 1 signal is sent as soon as
the actuator is inserted into the switch head (state: guard closed and not
locked). The signal is also present if the guard locking is active.
6.2.3. Door position 2 signal OT The door position 2 signal is present if the
actuator is completely inserted in the switch head and the guard locking can
be activated. In normal ambient conditions, the signal OT is sent after the
signal OD as an additional door monitoring contact. The signal is also present
if the guard locking is active (see chapter 6.4. Switching states on page 11).
6.2.4. Diagnostic signal OI The diagnostic signal is present if there is an
error (switch-on condition as for DIA LED).
6.2.5. Escape release signal OER The escape release signal is present if the
device has been released manually (see chapter 7. Manual release on page 12).
The signal is reset if the guard locking is re-activated or a reset has been
undertaken.
6.2.6. Status signal OM The status signal is present if the device’s safety
outputs are switched.
6.2.7. Locking element signal OLS The locking element signal is present if the
locking element is stuck and it is therefore not possible to
activate/deactivate guard locking. The signal is reset as soon as the actuator
is no longer under tensile stress or the locking element is no longer jammed.
6.2.8. Communication connection C A monitoring output with the suffix C has
the additional function of providing a communication connection to a BR/IO-
Link Gateway. The switch delivers cyclical and acyclical data. You will find
an overview of the communication data in chapter 12. Using communication data
on page 28. If no BR/IO-Link Gateway is connected, this output behaves like a
monitoring output.
6.3. Guard locking for process protection
(guard locking actuated by power-ON and released by spring force)
Important! Malfunctions due to incorrect use. Ì The actuator must not be under
tensile stress during release. Ì The guard locking is only activated if, in
addition to the power at the guard locking solenoid, the
operating voltage is applied to the device.
The magnetically actuated guard locking operates according to the open-circuit
current principle. If the voltage is interrupted at the solenoid, the guard
locking is released and the guard can be opened directly. The guard can be
opened as long as no power is applied to the guard locking solenoid or there
is no operating voltage at the device. If power is applied to the guard
locking solenoid and the actuator is completely inserted, the guard locking
pin is held in the extended position and the guard is locked. Activating guard
locking: close guard; apply power to the solenoid and operating voltage.
Releasing guard locking: disconnect power from the solenoid or operating
voltage.
10
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
6.4. Switching states
The detailed switching states for your switch can be found in chapter 15.
Status and error messages on page 34. All safety outputs, signals and display
LEDs are described there.
Guard closed and locked
Guard closed and not locked, ready for locking
Guard closed and not locked
Guard open
Power at the guard locking solenoid
on
Safety outputs FO1A and FO1B
on
Guard locking signal OL
on
Door position 1 signal OD
on
Door position 2 signal OT
on
off
off
on
off on on
off
off
on
off on off
irrelevant
off
off off off
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
11
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
7. Manual release
Some situations require the guard locking to be released manually (e.g.
malfunctions or an emergency). A function test must be performed after
release.
More information on this topic can be found in the standard EN ISO 14119:2013,
section 5.7.5.1. The device can feature the following release functions:
7.1. Auxiliary release
If malfunctions occur, the guard locking can be released with the auxiliary
release irrespective of the state of the solenoid.
Important!
Ì The actuator must not be under tensile stress during manual release.
Ì To prevent tampering, the auxiliary release must be sealed with sealing
lacquer, for example, before the switch is set up.
Ì Loss of the release function due to mounting errors or damage during
mounting.
Ì Check the release function every time after mounting. Ì The auxiliary
release is not a safety function. Ì The correct function must be checked at
regular intervals. Ì Observe the notes on any available data sheets.
Auxiliary release on the front
Auxiliary release on the rear
7.1.1. Actuating auxiliary release 1. Remove seal or make a hole. 2. Using a
screwdriver, turn the auxiliary release to in the direction of the arrow. ¨ If
the guard locking was activated, it is unlocked.
If monitoring of the guard locking for process protection is active, the
following applies: ¨ The guard locking signal OL and the safety outputs are
switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨ The
LOCK LED flashes orange slowly. If monitoring of the guard locking for process
protection is optional, the following applies: ¨ The guard locking signal OL
is switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨
The LOCK LED flashes orange slowly.
3. Using a screwdriver, turn the auxiliary release to in the opposite
direction to the arrow to reset. 4. Seal with sealing lacquer. 5. Close the
guard. ¨ The device operates normally again. 6. Check correct function of the
device.
12
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
7.2. Escape release
The escape release can be retrofitted.
The escape release permits opening of a locked guard from the danger zone
without tools (see chapter 16.3. Dimension drawing of safety switch CTS on
page 41).
Important!
Ì It must be possible to actuate the escape release manually from inside the
protected area without tools.
Ì It must not be possible to reach the escape release from the outside. Ì The
actuator must not be under tensile stress during manual release. Ì The escape
release meets the requirements of Category B according
to EN ISO 13849-1:2015.
Escape release
7.2.1. Actuating escape release 1. Press the red release knob to the end stop.
¨ If the guard locking was activated, it is unlocked.
If monitoring of the guard locking for process protection is active, the
following applies: ¨ The guard locking signal OL and the safety outputs are
switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨ The
LOCK LED flashes orange slowly. If monitoring of the guard locking for process
protection is optional, the following applies: ¨ The guard locking signal OL
is switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨
The LOCK LED flashes orange slowly.
2. Pull out the escape release knob to reset the escape release. 3. Close the
guard. ¨ The device operates normally again. 4. Check correct function of the
device.
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
13
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
8. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away,
removed or otherwise rendered ineffective. Ì Observe EN ISO 14119:2013,
section 7, for information about reducing the possibilities for bypassing
an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect
installation. Ì Safety switches and actuators must not be used as an end stop.
Ì Observe EN ISO 14119:2014, sections 5.2 and 5.3, for information about
mounting the safety switch
and the actuator. The following specifications must be observed: – Mounting
with screws of property class 8.8 or higher. – The minimum screw diameter is 5
mm. – Secure the fixing material against loosening (e.g. by means of medium-
strength positive screw
locking). Ì Protect the switch against damage, as well as against penetrating
foreign objects such as swarf,
sand and blasting shot, etc. Ì Observe the min. door radii (see chapter
16.4.1. Dimension drawing for actuatorA-FLX-D-0.-… on page
42). Ì Observe the maximum permissible inclination angles between switch and
actuator (see Fig. 4). Ì Observe the tightening torque for fastening the
switch and the actuator (see Fig. 3):
– Actuator: 6 Nm – Switch head: 6 Nm – Switch housing: 3 Nm Ì The side of the
switch in contact and the rear of the actuator must lie fully on the mounting
surface. Ì Actuator and safety switch must be mounted such that the actuator
is perpendicularly and completely inserted into the switch when the guard is
closed (seeFig. 2). The guard locking function is not assured if installation
is incorrect.
If monitoring of the guard locking for process protection is optional, the
following applies:
Important!
Ì From the assured release distance Sar, the safety outputs are safely shut
down. To achieve the assured release distance Sar the actuator must be pulled
completely out of the switch head.
Ì To achieve the assured operating distance Sao the actuator must be inserted
completely into the switch head.
14
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
C
B
A
Fig. 1: Front (A) and side (B, C) mounting
Fig. 2: Actuator alignment MAN20001531-01-09/22 (translation of the original operating instructions)
EN
15
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
2 x M5 (6 Nm)
M5 (6 Nm)
r 200
M5 (3 Nm)
Fig. 3: Installation example
2 2
6°
6°
3,5° 3,5°
Fig. 4: Maximum center offset and maximum actuator deflection
16
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9. Electrical connection
The following connection options are available: Ì Separate operation Ì Series
connection with wiring in the control cabinet Ì Series connection with
Y-distributors Ì Connection without IO-Link communication Ì Connection with
IO-Link communication
WARNING
In the event of a fault, loss of the safety function due to incorrect
connection. Ì To ensure safety, both safety outputs must always be evaluated.
Ì Monitoring outputs must not be used as safety outputs. Ì Lay the connecting
cables with protection to prevent short circuits.
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect
connection. Ì Do not use a control system with pulsing or switch off the
pulsing function in your control system.
The device generates its own test pulses on the safety outputs. A downstream
control system must tolerate these test pulses, which may have a length of up
to 300 µs. Depending on the inertia of the downstream device (control system,
relay, etc.), this can lead to short switching processes. The test pulses are
output only with the safety outputs switched off during device start. Ì The
inputs on a connected evaluation unit must be positive switching, as the two
outputs on the safety switch deliver a level of +24 V in the switched-on
state. Ì All the electrical connections must either be isolated from the mains
supply by a safety transformer according to IEC 61558-2-6 with limited output
voltage in the event of a fault, or by other equivalent insulation measures
(SELV). Ì All electrical outputs must have an adequate protective circuit for
inductive loads. The outputs must be protected with a free-wheeling diode for
this purpose. RC interference suppression units must not be used. Ì Power
devices which are a powerful source of interference must be installed in a
separate location away from the input and output circuits for signal
processing. The cable routing for safety circuits should be as far away as
possible from the cables of the power circuits. Ì To prevent EMC interference,
the physical environmental and operating conditions at the installation site
of the device must comply with the requirements according to the standard EN
60204-1 (EMC). Ì Pay attention to any interference fields from devices such as
frequency converters or induction heating systems. Observe the EMC
instructions in the manuals from the respective manufacturer. Ì If the
solenoid is operated with a frequency of more than 0.2 Hz, the device may
react with a delay. Ì In devices with IMP/IMM inputs, the power supply for the
evaluation electronics is separate from the power supply for the guard locking
solenoid. If different power supplies are used, they must have the same
reference potential. Ì For device variants with two connecting cables, both
cables must be laid in the same cable duct.
Important!
EN If the device does not appear to function when the operating voltage is
applied (e.g. STATE LED does
not flash), the safety switch must be returned to the manufacturer.
MAN20001531-01-09/22 (translation of the original operating instructions)
17
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9.1.
Notes about
Important!
Ì This device is intended to be used with a Class 2 power source in accordance
to UL1310. As an alternative an LV/C (Limited Voltage/Current) power source
with the following properties can be used: This device shall be used with a
suitable isolating source in conjunction with a fuse in accordance to UL248.
The fuse shall be rated max. 3.3 A and be installed in the max. 30 V DC power
supply to the device in order to limit the available current to comply with
the UL requirements. Please note possibly lower connection ratings for your
device (refer to the technical data).
Ì For use and application as per the requirements of UL 1) a connecting cable
listed under the UL category code CYJV/7, min. 24 AWG, min. 80 °C, must be
used.
- Note on the scope of the UL approval: the devices have been tested as per the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock and fire).
9.2. Safety in case of faults
Ì The operating voltage UB and the solenoid operating voltage UIMP are reverse
polarity protected. Ì The safety outputs FO1A/FO1B are short circuit-proof. Ì
A short circuit between the safety outputs is detected on starting or when the
safety outputs are activated by the device. Ì A short circuit in the cable can
be excluded by laying the cable with protection.
9.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number
of switches and the current required for the outputs. The following rules
apply:
Max. current consumption of an individual switch Imax Imax UB = IUB_1 + IFO1A+FO1B + IOX1 + IOX2
IUB_1 = Switch operating current (max. 50 mA)
IOX
= Load current of monitoring output (max. 20 mA per monitoring output)
IFO1A+FO1B = Load current of safety outputs FO1A + FO1B (2 x max. 80 mA)
Imax IMP = Solenoid operating current (max. 500 mA)
Max. current consumption of a switch chain Imax UB Imax UB = IFO1A+FO1B + n x (IUB_2 + IOX1 + IOX2)
n
= Number of connected switches
IUB_2 = Switch operating current (max. 80 mA)
Important! If there are further monitoring outputs, their load current must be taken into account.
18
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9.4.
Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect
connecting cables. Ì Use connection components and connecting cables from
EUCHNER. Ì On the use of other connection components, the requirements in the
following table apply. EUCHNER
provides no warranty for safe function in case of failure to comply with these
requirements.
Observe the following requirements with respect to the connecting cables:
For safety switches CTS-…-VAB-… with plug connector 2 x M12
Parameter Conductor cross-section, min. R max. C max. L max. Recommended cable type
Value 0.25 80 120 0.65 LIYY 8 x 0.25 mm² or 5 x 0.34 mm²
For safety switches CTS-…-VSA-… with plug connector M12, 8-pin
Parameter Conductor cross-section, min. R max. C max. L max. Recommended cable type
Value 0.25 80 120 0.65 LIYY 8 x 0.34 mm²
Unit mm² W/km nF/km mH/km
Unit mm² W/km nF/km mH/km
9.5. Connector assignment of safety switches CTS-…-VAB-… with plug connector 2 x M12
Plug connector (view of connection side)
2 x M12
X1.2 X1.3
X1.4
X2.5 X2.2 X2.3
X1.1 X1.7 X1.6 X1.5 X1.8
X2.1
X2.4
Pin X1.1 X1.2
X1.3
X1.4
X1.5 X1.6 X1.7 X1.8
Designation FI1B UB
FO1A
FO1B
OX1 2) FI1A 0VUB
–
Function
Conductor coloring of connecting cable 1)
Enable input, channel B
WH
Electronics operating voltage, 24 V DC
BN
Safety output, channel A
Active monitoring of the guard locking for process protection:
ON, if door is closed and locked.
GN
Optional monitoring of the guard locking for process protec-
tion:
ON, if door is closed.
Safety output, channel B
Active monitoring of the guard locking for process protection:
ON, if door is closed and locked.
YE
Optional monitoring of the guard locking for process protec-
tion:
ON, if door is closed.
Door monitoring output 1
GY
Enable input, channel A
PK
Electronics operating voltage, 0 V DC
BU
n.c.
RD
EN
X2.1
IMM
Solenoid operating voltage, 0 V DC
BN
X2.2
OX2 2)
Door monitoring output 2
WH
X2.3
–
n.c.
BU
X2.4
IMP
Solenoid operating voltage, 24 V DC
BK
X2.5
–
n.c.
GY
- Only for standard EUCHNER connecting cable 2) The function of the
monitoring output OX is determined by the actuator taught-in. You will find
more detailed information in the data sheet 2153710 or
at www.euchner.com.
MAN20001531-01-09/22 (translation of the original operating instructions)
19
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9.6. Connector assignment of safety switches CTS-…-VSA-… with plug connector M12, 8-pin
Plug connector (view of connection side)
1 x M12
2 3
4
1 7 6 5 8
Pin
Designation
Function
Conductor coloring of connecting cable 1)
1
IMP
Solenoid operating voltage, 24 V DC
WH
2
UB
Electronics operating voltage, 24 V DC
BN
Safety output, channel A
Active monitoring of the guard locking for process protection:
3
FO1A
ON, if door is closed and locked.
GN
Optional monitoring of the guard locking for process protec-
tion:
ON, if door is closed.
Safety output, channel B
Active monitoring of the guard locking for process protection:
4
FO1B
ON, if door is closed and locked.
YE
Optional monitoring of the guard locking for process protec-
tion:
ON, if door is closed.
5
OX1 2)
Door monitoring output 1
GY
6
OX2 2)
Door monitoring output 2
PK
7
0VUB
Electronics operating voltage, 0 V DC
BU
8
IMM
Solenoid operating voltage, 0 V DC
RD
- Only for standard EUCHNER connecting cable 2) The function of the
monitoring output OX is determined by the actuator taught-in. You will find
more detailed information in the data sheet 2153710 or
at www.euchner.com.
20
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9.7. Notes on operation with safe control systems
Observe the following guidelines for connection to safe control systems: Ì Use
a common power supply for the control system and the connected safety
switches. Ì A pulsed power supply must not be used for UB. Tap the supply
voltage directly from the power supply unit. If the power
supply is connected to a terminal of a safe control system, this output must
provide sufficient electrical current. Ì The safety outputs FO1A and FO1B can
be connected to the safe inputs of a control system. Prerequisite: the input
must be
suitable for pulsed safety signals (OSSD signals, e.g. from light grids). The
control system must tolerate test pulses on the input signals. This normally
can be set up by parameter assignment in the control system. Observe the notes
of the control system manufacturer. For the test pulse duration of your safety
switch, refer to chapter 16. Technical data on page 38. Ì With series
connection: always connect inputs FI1A and FI1B directly to a power supply
unit or to outputs FO1A and FO1B of another EUCHNER BR device. Pulsed signals
must not be present at inputs FI1A and FI1B. A detailed example of connecting
and setting the parameters of the control system is available for many devices
at www.euchner.com, in the area Downloads/Applications/CTS. The features of
the respective device are dealt with there in greater detail.
9.8. Connection without and with IO-Link communication
9.8.1. Connection without IO-Link communication Only the safety and monitoring
outputs are switched with this connection method. With a series connection,
the safety signals are looped through from device to device.
9.8.2. Connection with IO-Link communication If, in addition to the safety
function, detailed monitoring and diagnostic data are to be processed, a BR
/IO-Link Gateway is required. To poll the communication data from the
connected device, communication connection C is routed to the BR/ IO-Link
Gateway. You will find further information in the operating instructions for
your BR/IO-Link Gateway.
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
21
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
10. Connection of a single CTS-C2-BP/BR-CC-FLX (separate operation)
WARNING
In the event of a fault, loss of the safety function due to incorrect
connection. Ì To ensure safety, both safety outputs FO1A and FO1B must always
be evaluated.
Important!
The example shows only an excerpt that is relevant for the connection of the
CTS system. The example illustrated here does not show complete system
planning. The user is responsible for safe integration into the overall
system. Detailed application examples can be found at www.euchner.com. Simply
enter the order number of your switch in the search box. You will find all
available connection examples for the device in Downloads.
24V DC 0 V
1
1
-F1
-F2
2
2
13
-S1
14
24V DC 0 V
-B1
Actuator config L+HC
IMP
UB
Actuator EUC.167919
1
2
Read Head
Locking active
Monitoring Outputs
Door Monitoring
Safety Outputs
EUC.169051
8
7
CTS-C2-BP-CC-FLX-AP-VSA-169051
0 V
IMM
UB
5
OL/C
6
OD
3
FO1A
4
FO1B
Connected load
Fig. 5: Connection example, separate operation
22
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
11. Connection of several devices in a chain (series connection)
WARNING
In the event of a fault, loss of the safety function due to incorrect
connection. Ì To ensure safety, both safety outputs FO1A and FO1B must always
be evaluated.
Important!
Ì A BR chain may contain a maximum of 20 safety switches. Ì The BR chain is
not permitted to be changed during operation. Ì The example shows only an
excerpt that is relevant for the connection of the CTS system. The
example illustrated here does not show complete system planning. The user is
responsible for safe integration into the overall system. Detailed application
examples can be found at www.euchner.com. Simply enter the order number of
your switch in the search box. You will find all available connection examples
for the device in Downloads. Ì Make sure you use the correct Y-distributors.
See chapter 11.2.3. Connector assignment of Y-distributor for series
connection without IO-Link communication on page 25 and chapter 11.2.4.
Connector assignment of Y-distributor for series connection with IO-Link
communication on page 27.
11.1. Series connection with wiring in the control cabinet
The series connection can be realized via additional terminals in a control
cabinet.
Important!
In case of series connection with IO-Link communication: Ì The safety outputs
are permanently assigned to the respective safety inputs of the downstream
switch. FO1A must be routed to FI1A and FO1B to FI1B. Ì If the connections are
interchanged (e.g. FO1A to FI1B), the downstream device will enter the fault
state.
11.2. Series connection with Y-distributors
The series connection is shown here based on the example of the version with
plug connector M12. The switches are connected one behind the other with the
aid of pre-assembled connecting cables and Y-distributors. If a safety door is
opened or if a fault occurs on one of the switches, the system shuts down the
machine.
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
23
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
11.2.1. Maximum cable lengths with BR switch chains
Important!
The maximum number of switches in a BR switch chain depends on many factors,
including the cable length. This case example shows a standard application.
You will find further connection examples at www.euchner.com.
l1
umin = 24 V
lmax =200 m l2
ln<100 m
SPS
iout
PLC
5 x 0,34 mm2
5 x 0,34 mm2
5 x 0,34 mm2
CTS # n
CTS # n-1
CTS # 1
11.2.2. Determining cable lengths using the example table
n Max. number of switches depending on the cable
length 5
6
10
IFO1A/FO1B (mA)
Possible output current per channel FO1A/FO1B
10 25 50 80 10 25 50 80 10 25 50 80
l1 (m)
Max. cable length from the last switch to the control system 150 100 80 50 120
90 70 50 70 60 50 40
24
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
11.2.3. Connector assignment of Y-distributor for series connection without
IO-Link communication (Only for BR version with plug connectors 2 x M12)
Important!
Ì The switch chain must always be terminated with strapping plug 097645. Ì A
higher-level control system cannot detect which safety door is open or on
which switch a fault has occurred
with this connection technology.
Plug connector X1
Y-distributor
Plug connector X2 / X3
Pin X1.1 X1.2 X1.3 X1.4 X1.5 X1.6 X1.7 X1.8
X1 Function FI1B UB FO1A FO1B n.c. FI1A 0VUB *
X1 Socket
6
5
7
8
1
4 3 2
097627
X2 X1
X3
X1 Socket
5
6
8
7
4
1
3
2
111696 112395
X2 X1
X3
With connecting cable
- Function and compatibility are dependent on the connector assignment of the device connected.
X2
Plug
4
1
3
5
2
5
2
1
3
4
X3
Socket
X2
Plug
4
3
5
1 2
1
2
3
4
5
X3
Socket
Pin X2.1 X2.2 X2.3 X2.4 X2.5
X2 Function UB FO1A 0 V FO1B *
Pin X3.1 X3.2 X3.3 X3.4 X3.5
X3 Function UB FI1A 0 V FI1B *
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
25
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
24V DC 0 V 1
-F1
2 13
-S1
14
-B1
Actuator config L+HC
Actuator EUC.167919
IMP
X2:4
Read Head
EUC.169613
CTS-C2-BR-CC-FLX-AP-VAB-169613
X2:1
IMM
UB
X1:2
n.c
n.c.
n.c.
X1:8 X2:3 X2:5
Monitoring Outputs
Locking active
Door Monitoring
X1:7
0 V UB
X1:5
OL/C
X2:2
OD
1
-F2
2
24V DC 0 V
FI1A
FI1B
X1:6
X1:1
Safety Inputs
Safety Outputs
X1:3
FO1A
X1:4
FO1B
-B2
Actuator config L+HC
IMP
Actuator EUC.167919
X2:4
Read Head
EUC.169613
CTS-C2-BR-CC-FLX-AP-VAB-169613
X2:1
IMM
UB
X1:2
n.c
n.c.
n.c.
X1:8 X2:3 X2:5
Monitoring Outputs
Locking active
Door Monitoring
X1:7
0 V UB
X1:5
OL/C
X2:2
OD
FI1A
FI1B
X1:6
X1:1
Safety Inputs
Safety Outputs
X1:3
FO1A
X1:4
FO1B
-B3
Actuator config L+HC
IMP
Actuator EUC.167919
X2:4
Read Head
EUC.169613
CTS-C2-BR-CC-FLX-AP-VAB-169613
X2:1
IMM
UB
X1:2
n.c
n.c.
n.c.
X1:8 X2:3 X2:5
Monitoring Outputs
Locking active
Door Monitoring
X1:7
0 V UB
X1:5
OL/C
X2:2
OD
FI1A
FI1B
X1:6
X1:1
Safety Inputs
Safety Outputs
X1:3
FO1A
X1:4
FO1B
Connected load
Fig. 6: Connection example for series connection
26
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
11.2.4. Connector assignment of Y-distributor for series connection with IO-
Link communication (Only for BR version with plug connectors 2 x M12)
Important! Ì These Y-distributors can be used only with device variants that
control guard locking via IO-Link communication. Ì The switch chain must
always be terminated with strapping plug 097645.
Plug connector X1
Y-distributor
Plug connector X2 / X3
Pin X1.1 X1.2 X1.3 X1.4 X1.5 X1.6 X1.7 X1.8
X1 Function FI1B UB FO1A FO1B C FI1A 0VUB n.c.
X1 Socket
6
5
7
8
1
4 3 2
157913
X2 X1
X3
X2
Plug
4
1
3
5
2
5
2
1
3
4
X3
Socket
X1 Socket
5
6
8
7
4
1
3
2
158192 158193
X2 X1
X3
With connecting cable
X2
Plug
4
5
1
3
2
2
1
3
4
5
X3
Socket
Pin X2.1 X2.2 X2.3 X2.4 X2.5
X2 Function UB FO1A 0 V FO1B C
Pin X3.1 X3.2 X3.3 X3.4 X3.5
X3 Function UB FI1A 0 V FI1B C
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
27
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
12. Using communication data
A BR/IO-Link Gateway is required to use the device’s communication data and
forward them to a higher-level bus system. The following devices are suitable:
Ì GWY-CB-1-BR-IO (BR/IO-Link Gateway) Ì ESM-CB (safety relay with integrated
BR/IO-Link Gateway)
12.1. Connection to a BR/IO-Link Gateway GWY-CB
The Gateway is an IO-Link device. Communication via IO-Link offers cyclical
(process data) and acyclical (device data and events) data exchange (see
chapter 12.3. Overview of the communication data on page 29). The
communication connection C on the device allows the diagnostic line to be
connected to the Gateway. The Ox/C connection represents a non-safety-related
communication channel between the Gateway and the connected devices. IO-Link
communication can be used for the following functions as well: Ì Reset for
acknowledging error messages
You will find further information in the operating instructions for your BR
/IO-Link Gateway.
12.2. Connection to a safety relay ESM-CB
The safety relay ESM-CB features an integrated BR/IO-Link Gateway. In addition
to functioning as an IO-Link device (see chapter 12.1. Connection to a BR/IO-
Link Gateway GWY-CB on page 28), the device can be used for connecting two
monitored single- or dual-channel sensor circuits. The sensor circuits
evaluate various signaling devices: Ì Sensor circuit S1 with short circuit
detection; suitable for single- or dual-channel safety sensors Ì Sensor
circuit S2, suitable for OSSD signals; short circuit detection by signaling
device
When at least one sensor circuit is interrupted, the safety relay initiates
the safe state. Different relay starting behaviors and various monitoring
functions are possible. The device’s safety outputs FO1A and FO1B are routed
to the OSSD inputs of the safety relay. The Ox/C connection of the device
allows the diagnostic line to be connected to the Gateway. You will find
further information in the operating instructions for your safety relay with
integrated BR/IO-Link Gateway.
28
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
12.3. Overview of the communication data
The switch transmits both process data that are continuously transmitted to
the evaluation unit (cyclical data) and data that can be polled specifically
as needed (acyclical data). For further information on connection and on the
communication data, refer to the operating instructions for your BR/IO-Link
Gateway.
12.3.1. Cyclical data (process data)
Table 2: Cyclical data (process data)
Byte 1 Byte 2
Bit 7 OI –
Bit 6 –
Bit 5 OER
–
Bit 4 –
Bit 3 OM OLS
Bit 2 –
Bit 1 OL
Bit 0 OD OT
Bit
Signal
Message
OI
Diagnostics
There is a fault, see chapter 15.3. Error messages on page 36.
OM
Status
The safety outputs of the device are switched.
OD
Door position 1
A valid actuator is detected in the actuating range, and the guard is closed.
OER
Escape release
The device has been unlocked manually.
OT
Door position 2
The actuator is inserted in the switch head and the guard locking can be activated.
OLS
Locking element
The locking element is stuck, see chapter 15.3. Error messages on page 36.
OL
Guard locking
Guard locking is active.
12.3.2. Acyclical data (device data and events)
After one of the commands listed below is sent, the requested data are
provided via the IO-Link Gateway. The reply message always consists of 8 bytes
in big endian format.
Example 1: Reply message in response to the command Send device ID number/serial number: 06 02 68 E0 00 01 17 00 In this example, the device’s ID number is 157920 and its serial number is 279.
Byte number Reply in hex Description Reply in dec.
Byte 0
Byte 1
06
02
User data length in bytes
6 bytes
Byte 2 68
Byte 3 E0
Device ID number
157920
Byte 4 00
Byte 5 01
Byte 6 17
Serial number
279
Byte 7 00 Padding data
Example 2: Reply message for the command Send current device configuration: 02 01 08 00 00 00 00 00 In this example, the device has the high coding level and guard locking monitoring is active.
Byte number Reply in hex Description
Reply in dec.
Byte 0
Byte 1
02
01
User data length in bytes
Coding level
2 bytes
High coding level
Byte 2 08 Guard lock monitoring
Active
Byte 3 00
Byte 4 00
Byte 5 00
Byte 6 00
Padding data
Byte 7 00
EN
MAN20001531-01-09/22 (translation of the original operating instructions)
29
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
Command
HEX
Meaning
2
Send device ID number/serial number
3
Send version number of the device
5
Send number of devices in series connection
8
Send number of starting processes
12
Send current error code
13
Send most recently saved error code
14
Send size of log file
15
Send entry from log file with index
16
Send current actuator code
17
Send taught-in actuator code
18
Send disabled actuator code
19
Send applied voltage in mV
0B
Send current device configuration
0F
Send number of teach-in operations, factory resets and resets for
acknowledging error messages
1A
Send current temperature in °C
1B
Send number of switching cycles
1D
Reset for acknowledging error messages 1)
1E
Factory reset
Number of bytes
6
5
1 3 1 1 1 1 5 5 5 2 2
3
1 3 1
Bytes 1 – 3 Bytes 4 – 6 Byte 1 Bytes 2 – 4
Reply Bit sequences
(big endian format) Device ID number Serial number {V} Version number
Bytes 3 – 4 Bytes 3 – 4 Bytes 3 – 4
Byte 1
Byte 2
Byte 1 Byte 2 Byte 3
0x00 – Coding level not configured 0x01 – High coding level 0x02 – Low coding level 0x00 – Guard lock monitoring not configured 0x05 – Guard lock monitoring optional 0x08 – Guard lock monitoring active Number of teach-in operations Number of factory resets Number of resets for acknowledging error messages
0x1E Factory reset performed
- Each BR device must be addressed individually in a chain.
For more information on these and other acyclical data, refer to the operating instructions for your BR/IO-Link Gateway.
30
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
13. Setup
13.1. Configuring device and teaching-in actuator for the first time
The device must be configured and the actuator must be allocated to the safety
switch before the system forms a functional unit. During configuration, with
the aid of a function actuator, the monitoring of the guard locking for
process protection is specified as permanently active or available as an
additional option. The coding level is also defined. As such the selection of
the actuator determines the function of the device.
Configuration and the teach-in operation occur simultaneously in the delivery
state or after a factory reset.
Actuator A-FLX-D-0C-167919 A-FLX-D-0D-169044 A-FLX-D-0E-169045 A-FLX-D-0F-169046
Monitoring of the guard locking for process protection Active
Optional
Active
Optional
Coding level High coding level High coding level Low coding level Low coding level
WARNING
Danger to life due to improper use Ì During the initial configuration or
reconfiguration after a factory reset, ensure that all risk assessment
measures for the selected function are performed.
Important!
Ì If the actuator to be taught-in is in the actuating range for less than 30
s, the device will not be configured and the actuator will not be taught-in.
Prerequisite: Ì The device is in the delivery state. A factory reset must be
performed before a preconfigured device can be reconfigured
(see chapter 14. Factory reset on page 34). Ì The device is isolated from the
operating voltage.
1. Apply operating voltage. ¨ The STATE LED flashes white quickly. The device is carrying out a self-test. ¨ The STATE LED illuminates white. The device is in unlimited teach-in standby. 2. Insert an actuator. ¨ The teach-in operation begins. The STATE LED flashes alternately white/violet slowly. ¨ The teach-in operation ends after approx. 30 s. The STATE LED flashes alternately green/blue quickly (approx. 3 Hz). 3. Switch off operating voltage for at least 3 s. ¨ The code of the actuator taught-in is activated in the safety switch. The actuator is valid. 4. Switch on operating voltage. ¨ The device operates normally.
EN
MAN20001531-01-09/22 (translation of the original operating instructions)
31
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
13.2. Teaching-in new actuator (only for evaluation of the actuator with a
high coding level)
Tip!
Prior to switching on the operating voltage, close the guard on which the
actuator to be taught-in is installed. The teach-in operation starts
immediately after switching on. This feature simplifies above all teach-in
with series connections and on large installations.
Important! Ì During a teach-in operation, the safety outputs are switched off,
i.e. the system is in the safe state. Ì The safety switch disables the code of
the preceding device if teach-in is carried out for a new actuator.
Teach-in is not possible again immediately for this device if a new teach-in
operation is carried out. The disabled code is released again in the safety
switch only after a third code has been taught-in. Ì The safety switch can be
operated only with the last actuator taught-in. Ì The number of teach-in
operations is unlimited. Ì If the actuator to be taught-in is within the
actuating range for less than 30 s, it will not be activated and the most
recently taught-in actuator will remain saved. The device indicates an error
(see chapter 15.3. Error messages on page 36).
Prerequisite: Ì The device is isolated from the operating voltage.
1. Make sure there is no actuator in the actuating range. 2. Apply operating
voltage. ¨ The STATE LED flashes white quickly (5 Hz). The device is carrying
out a self-test. ¨ The device is in teach-in standby for up to 3 minutes. The
STATE LED flashes green. 4. Insert an actuator that has not been taught-in. ¨
The teach-in operation begins. The STATE LED flashes alternately white/violet
slowly. ¨ The teach-in operation ends after approx. 30 s. The STATE LED
flashes alternately green/blue quickly (approx. 3 Hz). 5. Switch off operating
voltage for at least 3 s. ¨ The code of the new actuator taught-in is
activated in the safety switch. The actuator is valid. 6. Switch on operating
voltage. ¨ The device operates normally.
32
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
13.3. Functional check
WARNING
Danger of fatal injury as a result of faults in installation and functional
check. Ì Before carrying out the functional check, make sure that there are no
persons in the danger zone. Ì Observe the valid accident prevention
regulations.
13.3.1. Mechanical function test The actuator must slide easily into the switch. Close the guard several times to check the function.
13.3.2. Electrical function test After installation and after any fault, the
safety function must be fully checked. Proceed as follows:
If monitoring of the guard locking for process protection is active: 1. Switch
on operating voltage. ¨ The machine must not start automatically. ¨ The safety
switch carries out a self-test. The STATE LED then flashes green slowly. 2.
Close all guards. In case of guard locking by solenoid force: activate guard
locking. ¨ The machine must not start automatically. It must not be possible
to open the guard. ¨ The STATE LED illuminates green, the LOCK LED illuminates
orange. 3. Enable operation in the control system. ¨ It must not be possible
to deactivate guard locking as long as operation is enabled. 4. Unlock guard
locking if necessary and open guard. ¨ The machine must switch off and it must
not be possible to start it as long as the guard is open. Repeat steps 2 – 4
for each guard.
If monitoring of the guard locking for process protection is optional:
1. Switch on operating voltage.
¨ The machine must not start automatically.
¨ The safety switch carries out a self-test. The STATE LED then flashes green slowly.
2. Close all guards. As soon as the actuator is inserted into the switch, the safety outputs are switched on independent of the state of the guard locking.
¨ The machine must not start automatically.
¨ The STATE LED illuminates green. In addition, depending on the state of the guard locking, the LOCK LED illuminates orange permanently or with a short interruption.
3. Enable operation in the control system.
4. Unlock guard locking if necessary and open guard.
¨ The machine must switch off and it must not be possible to start it as long as the guard is open. Repeat steps 2 – 4 for each guard.
EN
MAN20001531-01-09/22 (translation of the original operating instructions)
33
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
14. Factory reset
A factory reset deletes the configuration and restores the device’s factory
settings.
To perform a factory reset, connect the two outputs FO1A and FO1B to 0 V
before switching on or send the command Ox1E via IO-Link communication (see
chapter 12.3.2. Acyclical data (device data and events) on page 29).
15. Status and error messages
15.1. LED displays
LED STATE LOCK DIA
Color RGB Orange Red
Key to symbols
2x LED STATE LOCK DIA
Important!
If you do not find the displayed device status in the following tables, this
indicates an internal device fault. Contact the manufacturer.
quickly slowly ¨ X
LED not illuminated LED illuminated LED flashes quickly (3 Hz) LED flashes slowly (0.6 Hz) LED flashes alternately Any state
34
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
15.2. Status messages
Operating mode
LED indicator
STATE RGB
LOCK Orange
Safety outputs FO1A / FO1B
Guard locking signal OL
Door position 1 signal
OD
Status
Self-test
Normal operation
white quickly 5 Hz
(CTS-BP: 2 s; CTS-BR: 5 s)
Self-test after operating voltage is switched on.
off
off
off
green quickly
No communication with the BR/IO-Link Gateway.
green
on
on
on
If guard locking monitoring is active: door is closed and locked. The safety outputs of the preceding device in a series connection are switched on.
green
on
off
on
slowly
If guard locking monitoring is optional: door is closed. The safety outputs of the preceding device in a series connection are switched on.
slowly
off slowly
on
on
Door is closed and not locked. The safety outputs of the preceding device in a series connection are switched off.
slowly
off
off
off
Door is open.
off
off
off
Door is open and ready for locking.
slowly
quickly
¨
white/orange slowly
slowly
off
off
X
The escape release has been actuated.
white
off
on
Device is in teach-in standby (see chapter 13.1. Configuring device and teaching-in actuator for the first time on page 31).
¨
white/violet slowly
off
X
off
Teach-in operation. Door is closed.
¨
green/blue quickly
X
X
Positive acknowledgment after successful teach-in operation.
¨
white/blue quickly
off
off
off
Factory reset
depending on the error
depending on the error
off
depending on the error Error message (see chapter 15.3. Error messages on page 36).
Teach-in operation
Factory reset
Error
EN
MAN20001531-01-09/22 (translation of the original operating instructions)
35
Error code via IO-Link Open/close door
Reset
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
15.3. Error messages
LED indicator
STATE RGB
LOCK
DIA
Orange
Red
Error
Troubleshooting
Acknowledging errors
Teach-in error
¨
0x1F
white/red slowly
0x25
blue quickly
0x42
blue slowly
0x45 blue
Input error
0x2E
0x30
0x31 0x32
violet slowly
0x36 0x37
Transponder/read error
0x44
blue slowly
0x46 blue
-0x47 0x48 0x89
blue quickly ¨
white/blue slowly ¨
blue/red quickly
Actuator removed from the actuating range prior to the end of the teach-in operation.
Check whether the actuator is outside the actuating range or in the limit range.
Disabled actuator detected during the teach-in operation: The actuator was
taught-in during the penultimate teach-in operation and is disabled for the
current teach-in operation.
Invalid actuator detected: The actuator is not intended for the current device
configuration.
Faulty or incompatible actuator detected: The actuator’s data structure cannot
be read. The actuator is faulty or is not suitable for the device.
Repeat the teach-in operation with a new actuator (see chapter 13.2. Teaching-
in new actuator (only for evaluation of the actuator with a high coding level)
on page 32).
Ì Perform the teach-in operation with an actuator intended for the current
device configuration.
Ì If the device is to be reconfigured, observe chapter 13.1. Configuring
device and teaching-in actuator for the first time on page 31.
Repeat teach-in operation with new actuator.
Different signal states at the safety inputs FI1A and FI1B during operation.
Different signal states at the safety inputs FI1A and FI1B during the self-
test.
Test pulses not detected at safety input FI1A or FI1B during operation.
Ì Check wiring. Ì Check preceding device in the switch chain.
Test pulses at safety input FI1A or FI1B not detected during self-test.
Invalid actuator detected during operation: The actuator is not intended for the current device configuration.
Faulty or incompatible actuator detected during operation: The actuator’s data
structure cannot be read. The actuator is faulty or is not suitable for the
device.
Disabled actuator detected during operation: The actuator is not the currently
valid actuator.
Use a valid actuator.
Actuator not taught-in detected during operation.
Ì Use the currently valid actuator. Ì Teach-in actuator.
Possibly mechanically damaged actuator detected during operation.
Ì Check actuator for any damage. If necessary, replace actuator.
Ì Check whether the actuator is outside the actuating range or in the limit
range.
36
(translation of the original operating instructions) MAN20001531-01-09/22
LED indicator
STATE RGB
LOCK
DIA
Orange
Red
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
Error
Troubleshooting
Acknowledging errors
Error code via IO-Link Open/close door
Reset
Output error 0x4C 0x4D
0x54 violet quickly
Environment error
0x60
¨
0x61 0x62
orange/red slowly
¨
0x63 Internal erroorraqnugicek/lyred
0x01 red
A HIGH signal is detected at safety output FO1A or FO1B during the self-test.
The voltage level at safety outputs FO1A and FO1B during operation does not
meet the requirements. External voltage might be present.
Check wiring.
Supply voltage too high. Supply voltage too low.
Device temperature too high. Device temperature too low.
Decrease supply voltage. Ì Increase supply voltage. Ì Check system
configuration: cable length, number
of devices in the switch chain.
Observe the specified temperature range (see chapter 16. Technical data on
page 38).
Internal device error
Restart the device. On repeated occurrence, contact the manufacturer.
15.4. Acknowledging error messages
If the DIA LED flashes inversely once, the error message can be acknowledged
by opening and closing the guard. If the error is still displayed afterward, a
reset must be performed. If the LED DIA is permanently illuminated, the error
message can be acknowledged only by a reset. The reset can be performed as
follows.
Reset
Centrally for all switches in
a chain
Each switch must be addressed indi-
vidually
Further information
By briefly disconnecting the power supply (at least 3 s)
–
–
Via the cyclical data of IO-Link communication
–
See operating instructions for the IO-Link Gateway
Via the acyclical data of IO-Link communication
–
See chapter 12.3.2. Acyclical data (device data and events) on page 29
Resetting to acknowledge error messages does not delete the configuration.
Important!
EN
Contact the manufacturer if the fault display is not reset after briefly disconnecting the power supply.
MAN20001531-01-09/22 (translation of the original operating instructions)
37
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16. Technical data
NOTICE If a data sheet is available for the product, the information on the
data sheet applies.
16.1. Technical data for safety switch CTS-C2-BP/BR-CC-FLX
Parameter
General Material – Switch head – Switch housing Installation orientation
Degree of protection Safety class acc. to EN IEC 61140 Degree of contamination
(external, acc. to EN 60947-1) Mechanical life Ambient temperature at UB = 24
V Actuator approach speed max. Actuating/extraction/retention force Locking
force Fmax Locking force FZh Weight Connection (depending on version)
Operating voltage UB (reverse polarity protected, regulated, residual ripple <
5%) Current consumption IUB at UB = 24 V The following applies to the approval
acc. to UL Switching load acc. to UL External fuse (operating voltage UB)
External fuse (solenoid operating voltage UIMP) Rated insulation voltage Ui
Rated impulse withstand voltage Uimp Rated conditional short-circuit current
Shock and vibration resistance EMC protection requirements Ready delay Risk
time for single device Risk time extension per device Turn-on time Discrepancy
time between both safety outputs acc. to EN 60947-5-3 Test pulse duration Test
pulse interval Safety outputs FO1A/FO1B Output voltage UFO1A/UFO1B 1) – HIGH
UFO1A/UFO1B – LOW UFO1A/UFO1B Switching current per safety output Utilization
category acc. to EN 60947-5-2
Switching frequency Monitoring outputs Ox/C Output voltage Max. load Solenoid
Solenoid operating voltage UIMP (reverse polarity protected, regulated,
residual ripple < 5%) Solenoid current consumption IIMP Connection rating at
max. switching frequency Duty cycle Reliability values acc. to EN ISO 13849-1
2) Category Performance Level (PL) PFHD Mission time
min.
Value typ.
max.
Die-cast zinc
Reinforced thermoplastic
Any
IP65/IP67/IP69/IP69K
III
3
1 x 106 operating cycles
-20
–
+55
20
Device dependent, see www.euchner.com
3900
3000
0.34
2 plug connectors M12, 5- and 8-pin / 1 plug connector M12, 8-pin
24 -15% / +20% (SELV)
50
Operation only with UL Class 2 power supply or equivalent measures
DC 24 V, class 2
1
–
8
1
–
8
–
–
32
–
–
0.5
100
Acc. to EN 60947-5-3
Acc. to EN 60947-5-3
–
–
1
–
–
200
10
–
–
400
–
–
10
0.3
96
–
–
Semiconductor outputs, p-switching, short circuit-proof
UB – 2
–
UB
0
–
1
1
–
80
DC-13 24 V 80 mA
Caution: outputs must be protected with a free-wheeling diode in case of inductive loads
–
–
0.2
p-switching, short circuit-proof
0.8 x UB
–
UB
20
24 V DC ± 20 %
–
–
500
9
100
Monitoring of the guard position
4
e
6.44 x 10-9/h
20
- Values at a switching current of 50 mA without taking into account the cable lengths 2) Refer to the declaration of conformity in chapter 20 for the issue date.
Unit
°C m/min
N N N kg
V DC mA
A A V kV A
s ms ms ms ms ms ms
V DC mA
Hz V DC mA
V DC mA W %
years
38
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16.1.1. Typical system times Refer to the technical data for the exact values.
Ready delay: After switching on, the device carries out a self-test. The
system is ready for operation only after this time. Turn-on time of safety
outputs: The max. reaction time ton is the time from the moment when the guard
is locked to the moment when the safety outputs switch on. Risk time according
to EN 60947-5-3: The risk time is the maximum time until at least one of the
safety outputs FO1A or FO1B switches off safely when the actuator is removed
from the actuating range. This also applies if an internal or external fault
occurs at this moment.
For optional guard locking monitoring for process protection the following
applies: if an actuator moves outside the actuating range, the safety outputs
FO1A and FO1B are switched off after the risk time at the latest. If several
devices are operated in a series connection, the risk time of the overall
device chain will increase with each device added. Use the following
calculation formula: tr = tr, e + (n x tl) tr = Total risk time tr, e = Risk
time for single device (see technical data) tl = Risk time extension per
device n = Number of additional devices (total number -1) Discrepancy time:
The safety outputs FO1A and FO1B switch with a slight delay in relation to
each other. They have the same signal state no later than after the
discrepancy time. Test pulses at the safety outputs: The device generates its
own test pulses on the safety outputs FO1A and FO1B. A downstream control
system must tolerate these test pulses. This can usually be set up in the
control systems by parameter assignment. If parameter assignment is not
possible for your control system or if shorter test pulses are required,
contact our support organization. The test pulses are output only if the
safety outputs are switched on.
EN
MAN20001531-01-09/22 (translation of the original operating instructions)
39
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16.2. Radio frequency approvals
FCC ID: 2AJ58-18
IC:
22052-18
FCC/IC-Requirements
This device complies with part 15 of the FCC Rules and with Industry Canada’s
licence-exempt RSSs. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- this device must accept any interference received, including interference
that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user`s authority
to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes :
(1) l’appareil ne doit pas produire de brouillage, et
(2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Supplier`s Declaration of Conformity 47 CFR § 2.1077 Compliance Information
Unique Identifier: CTS-C1-BP Series CTS-C1-BR Series CTS-C2-BP Series
CTS-C2-BR Series
Responsible Party U.S. Contact Information EUCHNER USA Inc. 1860 Jarvis
Avenue Elk Grove Village, Illinois 60007
info(at)euchner-usa.com http://www.euchner-usa.com
40
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16.3. Dimension drawing of safety switch CTS
MAN20001531-01-09/22 (translation of the original operating instructions)
EN
41
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16.4. Technical data for actuator A-FLX-D-0.-…
Parameter
Material – Mounting – Cover – Actuating element – Housing Weight Ambient
temperature Degree of protection Mechanical life Locking force, max. Locking
force FZh Installation orientation Overtravel Power supply
min.
Value typ.
Unit max.
Safety screws, galvanized steel 8.8
NBR
Stainless steel
fiber reinforced plastic, black
0.06
kg
-20
–
+55
°C
IP65/IP67/IP69/IP69K
1 x 106
3900
N
3000
N
Any
4
mm
Inductive via read head
16.4.1. Dimension drawing for actuatorA-FLX-D-0.-…
42
(translation of the original operating instructions) MAN20001531-01-09/22
Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
17. Ordering information and accessories
Tip!
Suitable accessories, e.g. cables or assembly material, can be found at
www.euchner.com. To order, enter the order number of your item in the search
box and open the item view. Accessories that can be combined with the item are
listed in Accessories.
18. Inspection and service
WARNING
Danger of severe injuries due to the loss of the safety function. Ì If damage
or wear is found, the complete switch and actuator assembly must be replaced.
Replace-
ment of individual parts or assemblies is not permitted. Ì Check the device
for proper function at regular intervals and after every fault. For
information about
possible time intervals, refer to EN ISO 14119:2013, section 8.2.
Regular inspection of the following is necessary to ensure trouble-free long-
term operation: Ì Check the switching function (see chapter 13.3. Functional
check on page 33) Check all additional functions (e.g. escape
release, lockout bar, etc.) Ì Check the secure mounting of the devices and the
connections Ì Check for contamination
No servicing is required. Repairs to the device are only allowed to be made by
the manufacturer.
NOTICE
The year of manufacture is given in the laser marking at the bottom right
corner. The current version number in the format (V X.X.X) can also be found
on the device.
19. Service
If servicing is required, please contact:
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen Germany
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com
20. Declaration of conformity
EN
The declaration of conformity is part of the operating instructions.
The complete EU declaration of conformity can also be found at www.euchner.com. Enter the order number of your device in the search box. The document is available under Downloads.
MAN20001531-01-09/22 (translation of the original operating instructions)
43
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen
Germany info@euchner.de www.euchner.com
Edition: MAN20001531-01-09/22 Title: Operating Instructions Transponder-Coded
Safety Switch CTS-C2-BP/BR-CC-FLX (translation of the original operating
instructions) Copyright: © EUCHNER GmbH + Co. KG, 09/2022
Subject to technical modifications; no responsibility is accepted for the
accuracy of this information.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>