EUCHNER BR-CC-FLX Transponder Coded Safety Switch with Guard Locking Instruction Manual

June 9, 2024
EUCHNER

BR-CC-FLX Transponder Coded Safety Switch with Guard Locking

Operating Instructions
Transponder-Coded Safety Switch with Guard Locking for Process Protection
CTS-C2-BP/BR-CC-FLX EN

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
Contents
1. About this document………………………………………………………………………………… 4
1.1. Scope…………………………………………………………………………………………………………………………..4 1.2. Target group ………………………………………………………………………………………………………………….4 1.3. Key to symbols……………………………………………………………………………………………………………….4 1.4. Supplementary documents ………………………………………………………………………………………………..4
2. Correct use ……………………………………………………………………………………………. 5
3. Description of the safety function ……………………………………………………………….. 7
4. Exclusion of liability and warranty ………………………………………………………………. 8
5. General safety precautions ……………………………………………………………………….. 8
6. Function ………………………………………………………………………………………………… 9
6.1. Monitoring of the guard locking for process protection …………………………………………………………….9 6.2. Monitoring outputs/status bits ……………………………………………………………………………………………9
6.2.1. Guard locking signal OL ………………………………………………………………………………………9 6.2.2. Door position 1 signal OD…………………………………………………………………………………..10 6.2.3. Door position 2 signal OT …………………………………………………………………………………..10 6.2.4. Diagnostic signal OI ………………………………………………………………………………………….10 6.2.5. Escape release signal OER ………………………………………………………………………………..10 6.2.6. Status signal OM………………………………………………………………………………………………10 6.2.7. Locking element signal OLS………………………………………………………………………………..10 6.2.8. Communication connection C………………………………………………………………………………10 6.3. Guard locking for process protection………………………………………………………………………………….10 6.4. Switching states ……………………………………………………………………………………………………………11
7. Manual release……………………………………………………………………………………… 12
7.1. Auxiliary release…………………………………………………………………………………………………………….12 7.1.1. Actuating auxiliary release ………………………………………………………………………………….12
7.2. Escape release……………………………………………………………………………………………………………..13 7.2.1. Actuating escape release …………………………………………………………………………………..13
8. Mounting……………………………………………………………………………………………… 14
9. Electrical connection ……………………………………………………………………………… 17
9.1. Notes about ………………………………………………………………………………………………………….18 9.2. Safety in case of faults……………………………………………………………………………………………………18 9.3. Fuse protection for power supply ………………………………………………………………………………………18 9.4. Requirements for connecting cables…………………………………………………………………………………..19 9.5. Connector assignment of safety switches CTS-…-VAB-… with plug connector 2 x M12 …………………..19 9.6. Connector assignment of safety switches CTS-…-VSA-… with plug connector M12, 8-pin …………………. 20 9.7. Notes on operation with safe control systems ………………………………………………………………………21 9.8. Connection without and with IO-Link communication……………………………………………………………….21
9.8.1. Connection without IO-Link communication ……………………………………………………………..21 9.8.2. Connection with IO-Link communication………………………………………………………………….21

2

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

10. Connection of a single CTS-C2-BP/BR-CC-FLX (separate operation) ………………… 22

11. Connection of several devices in a chain (series connection)………………………….. 23

11.1. Series connection with wiring in the control cabinet ……………………………………………………………….23

11.2.

Series connection with Y-distributors ………………………………………………………………………………….23
11.2.1. Maximum cable lengths with BR switch chains…………………………………………………………24 11.2.2. Determining cable lengths using the example table…………………………………………………..24 11.2.3. Connector assignment of Y-distributor for series connection without IO-Link communication 25 11.2.4. Connector assignment of Y-distributor for series connection with IO-Link communication …..27

12. Using communication data………………………………………………………………………. 28

12.1. Connection to a BR/IO-Link Gateway GWY-CB……………………………………………………………………….28

12.2. Connection to a safety relay ESM-CB………………………………………………………………………………….28

12.3.

Overview of the communication data ………………………………………………………………………………….29 12.3.1. Cyclical data (process data)………………………………………………………………………………..29 12.3.2. Acyclical data (device data and events)………………………………………………………………….29

13. Setup ………………………………………………………………………………………………….. 31

13.1. Configuring device and teaching-in actuator for the first time……………………………………………………31

13.2. Teaching-in new actuator (only for evaluation of the actuator with a high coding level)…………………….32

13.3.

Functional check……………………………………………………………………………………………………………33 13.3.1. Mechanical function test …………………………………………………………………………………….33 13.3.2. Electrical function test……………………………………………………………………………………….33

14. Factory reset………………………………………………………………………………………… 34

15. Status and error messages ……………………………………………………………………… 34
15.1. LED displays ………………………………………………………………………………………………………………..34 15.2. Status messages…………………………………………………………………………………………………………..35 15.3. Error messages…………………………………………………………………………………………………………….36 15.4. Acknowledging error messages ………………………………………………………………………………………..37

16. Technical data ………………………………………………………………………………………. 38
16.1. Technical data for safety switch CTS-C2-BP/BR-CC-FLX …………………………………………………………..38 16.1.1. Typical system times…………………………………………………………………………………………39
16.2. Radio frequency approvals……………………………………………………………………………………………….40 16.3. Dimension drawing of safety switch CTS……………………………………………………………………………..41 16.4. Technical data for actuator A-FLX-D-0.-… …………………………………………………………………………….42
16.4.1. Dimension drawing for actuatorA-FLX-D-0.-……………………………………………………………..42

17. Ordering information and accessories ……………………………………………………….. 43

18. Inspection and service ……………………………………………………………………………. 43

19. Service ……………………………………………………………………………………………….. 43 EN
20. Declaration of conformity ……………………………………………………………………….. 43

MAN20001531-01-09/22 (translation of the original operating instructions)

3

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

1. About this document
1.1. Scope
These operating instructions apply to all CTS-C2-BP/BR-CC-FLX… of version V2.0.X. These operating instructions, the document Safety information and any available data sheet form the complete user information for your device.

1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing special expertise in handling safety components.

1.3. Key to symbols

Symbol/depiction

Meaning Monitoring the position of the guard locking and active monitoring of the guard locking for process protection, high coding level Monitoring the position of the guard locking and active monitoring of the guard locking for process protection, low coding level Monitoring the position of the guard locking and optional monitoring of the guard locking for process protection, high coding level Monitoring the position of the guard locking and optional monitoring of the guard locking for process protection, low coding level

Printed document

Internet www

Document is available for download at www.euchner.com

DANGER WARNING CAUTION

Safety precautions Danger of death or severe injuries Warning about possible injuries Caution slight injuries possible

NOTICE Important!
Tip

Notice about possible device damage Important information
Useful information

1.4. Supplementary documents
The overall documentation for this device consists of the following documents:

Document title (document number)
Safety information (2525460)
Operating Instructions (MAN20001531)

Contents Basic safety information (this document)

Declaration of conformity Declaration of conformity

Possibly available data sheet

Item-specific information about deviations or additions

Internet www Internet www
Internet www

Important!

Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc. no. in the search box.

4

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

2. Correct use
Safety switches series CTS-C2-BP/BR-CC-FLX are interlocking devices with guard locking solenoid (type 4) for process protection without safe guard locking monitoring. The device complies with the requirements according to EN IEC 60947-5-3.
The device can be configured with the aid of a function actuators. Depending on the function actuator taught-in, the monitoring of the guard locking for process protection is permanently active or available as an additional option and the evaluation of the actuator code has a high or low coding level.

Table 1: System components

Safety switch

Active High coding level

Function actuator

Monitoring of the guard locking for process protection

Optional

Active

High coding level

Low coding level

Optional Low coding level

CTS-C2-BP/BR-CC-FLX…

A-FLX-D-0C-167919

A-FLX-D-0D-169044

A-FLX-D-0E-169045

A-FLX-D-0F-169046

If monitoring of the guard locking for process protection is active, the following applies:
In combination with a movable guard and the machine control, this safety component prevents dangerous machine functions from occurring while the guard is open. A stop command is triggered if the guard is opened during the dangerous machine function or the guard locking is unlocked.
This means: Ì Starting commands that cause a dangerous machine function must become active only when the guard is closed
and locked. Ì Opening the guard must trigger a stop command. Ì Closing and locking a guard must not cause automatic starting of a dangerous machine function. A separate
start command must be issued. For exceptions, refer to EN ISO 12100 or relevant C-standards.
If monitoring of the guard locking for process protection is optional, the following applies:
In combination with a movable guard and the machine control, this safety component prevents dangerous machine functions from occurring while the guard is open. A stop command is triggered if the guard is opened during the dangerous machine function.
This means: Ì Starting commands that cause a dangerous machine function must become active only when the guard is closed. Ì Opening the guard must trigger a stop command. Ì Closing a guard must not cause automatic starting of a dangerous machine function. A separate start command
must be issued. For exceptions, refer to EN ISO 12100 or relevant C-standards.
If the evaluation of the actuator code has a high coding level, the following applies: Ì The actuator must be assigned to the safety switch by a teach-in operation so that it is detected by the system.
This unambiguous assignment ensures a particularly high level of protection against tampering. The system thus possesses a high coding level.
If the evaluation of the actuator code has a low coding level, the following applies:
EN Ì With the low coding level a specific code is not requested but instead it is only checked whether the actuator
is of a type that can be detected by the system. There is no exact comparison of the actuator code with the taught-in code in the safety switch. The system possesses a low coding level.

MAN20001531-01-09/22 (translation of the original operating instructions)

5

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
Before the device is used, a risk assessment must be performed on the machine, e.g. according to the following standards: Ì EN ISO 13849-1 Ì EN ISO 12100 Ì IEC 62061
Correct use includes observing the relevant requirements for installation and operation, particularly based on the following standards: Ì EN ISO 13849-1 Ì EN ISO 14119 Ì EN 60204-1
The safety switch is allowed to be operated only in conjunction with the intended EUCHNER actuators and the related connection components from EUCHNER. On the use of different actuators or other connection components, EUCHNER provides no warranty for safe function.
Safety switches in the version CTS-…-BR can be integrated into a BR device chain. Connection of several devices in a BR switch chain is permitted only using devices intended for series connection in a BR switch chain. Check this in the specifications of the device in question.
Important!
Ì The user is responsible for the proper integration of the device into a safe overall system. For this purpose, the overall system must be validated, e.g. according to EN ISO 13849-2.
Ì It is only allowed to use components that are permissible according to the Table 1: System components.

6

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

3. Description of the safety function
Devices from this series feature the following safety functions:
Monitoring of the guard position (interlocking device according to EN ISO 14119) Ì Safety function: the safety outputs are switched off when the guard is open (see chapter 6. Function on page 9). Ì Safety characteristics: category, Performance Level, PFHD (see chapter 16. Technical data on page 38).
The following additionally applies in a BR series connection: Ì The safety outputs are switched on only when the device receives a corresponding signal from its predecessor in the chain.

NOTICE

You can regard the complete BR device chain as one subsystem during calculation. The following calculation method applies to the PFHD value:

BR-Device #1 … n

External Evaluation (e.g. PLC)

1 PFHD,1

2 PFHD,2

n PFHD,n

PFHD,ext

n
PFHD ges = PFHD,k + PFHd,ext k=1
Alternatively, the simplified method according to section 6.3 of EN 13849-1:2015 can be used for calculation.

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
7

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or if the safety regulations are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void.
5. General safety precautions
Safety switches fulfill personnel protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Check the safe function of the safeguard particularly Ì after any setup work Ì after the replacement of a system component Ì after an extended period without use Ì after every fault Ì after any reconfiguration of the device
Independent of these checks, the safe function of the safeguard should be checked at suitable intervals as part of the maintenance schedule.
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components fulfill a personnel protection function. Ì Safety components must not be bypassed, turned away, removed or otherwise rendered ineffective.
On this topic pay attention in particular to the measures for reducing the possibility of bypassing according to EN ISO 14119:2013, section 7. Ì The switching operation must be triggered only by actuators designated for this purpose. Ì Prevent bypassing by means of replacement actuators (only for low coding level evaluation). For this purpose, restrict access to actuators and to keys for releases, for example. Ì Make sure the guard cannot be closed unintentionally, e.g. during servicing. For this purpose, a lockout bar can be used, for instance. Ì Mounting, electrical connection and setup only by authorized personnel possessing the following knowledge: – specialist knowledge in handling safety components – knowledge about the applicable EMC regulations – knowledge about the applicable regulations on operational safety and accident prevention.
NOTICE
Risk of damage Ì The guard locking function can no longer be ensured if an actuator is broken. Opening the door will
immediately switch off the safety outputs. Regularly check the actuator for mechanical damage.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. You can download the operating instructions from www.euchner.com.

8

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

6. Function
The device monitors the position of movable guards.
The system consists of the following components: coded actuator (transponder) and switch.
The coding level of the system depends on the configuration of the device (see chapter 13.1. Configuring device and teaching-in actuator for the first time on page 31).
When the guard is closed, the actuator is moved into the safety switch. When the operating distances are reached, power is supplied to the actuator by the switch and data are transferred.

Switch

Coded actuator

The door position 1 signal OD is set if a permissible code is detected. Guard locking is activated automatically if power is present at the guard locking solenoid. The switching conditions for the safety outputs are dependent on the configuration of the monitoring of the guard locking for process protection (see chapter 6.4. Switching states on page 11).
If there is a fault in the safety switch, the safety outputs are switched off and the DIA LED illuminates or flashes red (see chapter 15.3. Error messages on page 36). The occurrence of faults is detected at the latest on the next demand to close the safety outputs (e.g. on starting).
6.1. Monitoring of the guard locking for process protection
The device is configured with the aid of the function actuator. Depending on the function actuator taught-in, the monitoring of the guard locking for process protection is permanently active or available as an additional option. Further information about the possible settings is available in the chapter 13.1. Configuring device and teaching-in actuator for the first time on page 31.
If monitoring of the guard locking for process protection is active, the following applies:
All versions feature two safe outputs for monitoring the guard locking for process protection. The safety outputs FO1A and FO1B are switched off and the guard locking signal OL is cleared when guard locking is released.
If monitoring of the guard locking for process protection is optional, the following applies:
All versions feature two safe outputs for monitoring the door position as well as the status signal OL for monitoring the guard locking for process protection; this signal can be evaluated optionally. The safety outputs FO1A and FO1B are switched off and the door position 1 signal OD is cleared when the guard is opened.

The following switching conditions apply to the safety outputs FO1A and FO1B:

No fault in the device Guard closed Guard locking active
6.2. Monitoring outputs/status bits

Monitoring of the guard locking for process protection

Active (ON)

Optional (OFF)

TRUE (ON)

TRUE (ON)

TRUE (ON)

TRUE (ON)

TRUE (ON)

irrelevant

EN

Depending on version, the signals listed in the following are available as a status bit or at the monitoring output. The status bits are evaluated via the BR/IO-Link Gateway. Please refer to the corresponding data sheet for further information.

6.2.1. Guard locking signal OL The guard locking signal is present if the guard locking is active.

MAN20001531-01-09/22 (translation of the original operating instructions)

9

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
6.2.2. Door position 1 signal OD The door position 1 signal is sent as soon as the actuator is inserted into the switch head (state: guard closed and not locked). The signal is also present if the guard locking is active.
6.2.3. Door position 2 signal OT The door position 2 signal is present if the actuator is completely inserted in the switch head and the guard locking can be activated. In normal ambient conditions, the signal OT is sent after the signal OD as an additional door monitoring contact. The signal is also present if the guard locking is active (see chapter 6.4. Switching states on page 11).
6.2.4. Diagnostic signal OI The diagnostic signal is present if there is an error (switch-on condition as for DIA LED).
6.2.5. Escape release signal OER The escape release signal is present if the device has been released manually (see chapter 7. Manual release on page 12). The signal is reset if the guard locking is re-activated or a reset has been undertaken.
6.2.6. Status signal OM The status signal is present if the device’s safety outputs are switched.
6.2.7. Locking element signal OLS The locking element signal is present if the locking element is stuck and it is therefore not possible to activate/deactivate guard locking. The signal is reset as soon as the actuator is no longer under tensile stress or the locking element is no longer jammed.
6.2.8. Communication connection C A monitoring output with the suffix C has the additional function of providing a communication connection to a BR/IO- Link Gateway. The switch delivers cyclical and acyclical data. You will find an overview of the communication data in chapter 12. Using communication data on page 28. If no BR/IO-Link Gateway is connected, this output behaves like a monitoring output.
6.3. Guard locking for process protection
(guard locking actuated by power-ON and released by spring force)
Important! Malfunctions due to incorrect use. Ì The actuator must not be under tensile stress during release. Ì The guard locking is only activated if, in addition to the power at the guard locking solenoid, the
operating voltage is applied to the device.
The magnetically actuated guard locking operates according to the open-circuit current principle. If the voltage is interrupted at the solenoid, the guard locking is released and the guard can be opened directly. The guard can be opened as long as no power is applied to the guard locking solenoid or there is no operating voltage at the device. If power is applied to the guard locking solenoid and the actuator is completely inserted, the guard locking pin is held in the extended position and the guard is locked. Activating guard locking: close guard; apply power to the solenoid and operating voltage. Releasing guard locking: disconnect power from the solenoid or operating voltage.

10

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

6.4. Switching states
The detailed switching states for your switch can be found in chapter 15. Status and error messages on page 34. All safety outputs, signals and display LEDs are described there.

Guard closed and locked

Guard closed and not locked, ready for locking

Guard closed and not locked

Guard open

Power at the guard locking solenoid

on

Safety outputs FO1A and FO1B

on

Guard locking signal OL

on

Door position 1 signal OD

on

Door position 2 signal OT

on

off

off

on

off on on

off

off

on

off on off

irrelevant
off
off off off

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
11

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

7. Manual release
Some situations require the guard locking to be released manually (e.g. malfunctions or an emergency). A function test must be performed after release.
More information on this topic can be found in the standard EN ISO 14119:2013, section 5.7.5.1. The device can feature the following release functions:

7.1. Auxiliary release
If malfunctions occur, the guard locking can be released with the auxiliary release irrespective of the state of the solenoid.
Important!
Ì The actuator must not be under tensile stress during manual release.
Ì To prevent tampering, the auxiliary release must be sealed with sealing lacquer, for example, before the switch is set up.
Ì Loss of the release function due to mounting errors or damage during mounting.
Ì Check the release function every time after mounting. Ì The auxiliary release is not a safety function. Ì The correct function must be checked at regular intervals. Ì Observe the notes on any available data sheets.

Auxiliary release on the front
Auxiliary release on the rear

7.1.1. Actuating auxiliary release 1. Remove seal or make a hole. 2. Using a screwdriver, turn the auxiliary release to in the direction of the arrow. ¨ If the guard locking was activated, it is unlocked.
If monitoring of the guard locking for process protection is active, the following applies: ¨ The guard locking signal OL and the safety outputs are switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨ The LOCK LED flashes orange slowly. If monitoring of the guard locking for process protection is optional, the following applies: ¨ The guard locking signal OL is switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨ The LOCK LED flashes orange slowly.
3. Using a screwdriver, turn the auxiliary release to in the opposite direction to the arrow to reset. 4. Seal with sealing lacquer. 5. Close the guard. ¨ The device operates normally again. 6. Check correct function of the device.

12

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

7.2. Escape release
The escape release can be retrofitted.
The escape release permits opening of a locked guard from the danger zone without tools (see chapter 16.3. Dimension drawing of safety switch CTS on page 41).
Important!
Ì It must be possible to actuate the escape release manually from inside the protected area without tools.
Ì It must not be possible to reach the escape release from the outside. Ì The actuator must not be under tensile stress during manual release. Ì The escape release meets the requirements of Category B according
to EN ISO 13849-1:2015.

Escape release

7.2.1. Actuating escape release 1. Press the red release knob to the end stop. ¨ If the guard locking was activated, it is unlocked.
If monitoring of the guard locking for process protection is active, the following applies: ¨ The guard locking signal OL and the safety outputs are switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨ The LOCK LED flashes orange slowly. If monitoring of the guard locking for process protection is optional, the following applies: ¨ The guard locking signal OL is switched off. ¨ The STATE LED flashes alternately white/orange slowly. ¨ The LOCK LED flashes orange slowly.
2. Pull out the escape release knob to reset the escape release. 3. Close the guard. ¨ The device operates normally again. 4. Check correct function of the device.

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
13

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
8. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective. Ì Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for bypassing
an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation. Ì Safety switches and actuators must not be used as an end stop. Ì Observe EN ISO 14119:2014, sections 5.2 and 5.3, for information about mounting the safety switch
and the actuator. The following specifications must be observed: – Mounting with screws of property class 8.8 or higher. – The minimum screw diameter is 5 mm. – Secure the fixing material against loosening (e.g. by means of medium- strength positive screw
locking). Ì Protect the switch against damage, as well as against penetrating foreign objects such as swarf,
sand and blasting shot, etc. Ì Observe the min. door radii (see chapter 16.4.1. Dimension drawing for actuatorA-FLX-D-0.-… on page
42). Ì Observe the maximum permissible inclination angles between switch and actuator (see Fig. 4). Ì Observe the tightening torque for fastening the switch and the actuator (see Fig. 3):
– Actuator: 6 Nm – Switch head: 6 Nm – Switch housing: 3 Nm Ì The side of the switch in contact and the rear of the actuator must lie fully on the mounting surface. Ì Actuator and safety switch must be mounted such that the actuator is perpendicularly and completely inserted into the switch when the guard is closed (seeFig. 2). The guard locking function is not assured if installation is incorrect.
If monitoring of the guard locking for process protection is optional, the following applies:
Important!
Ì From the assured release distance Sar, the safety outputs are safely shut down. To achieve the assured release distance Sar the actuator must be pulled completely out of the switch head.
Ì To achieve the assured operating distance Sao the actuator must be inserted completely into the switch head.

14

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

C

B

A

Fig. 1: Front (A) and side (B, C) mounting

Fig. 2: Actuator alignment MAN20001531-01-09/22 (translation of the original operating instructions)

EN
15

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
2 x M5 (6 Nm)

M5 (6 Nm)

r 200

M5 (3 Nm)

Fig. 3: Installation example
2 2

3,5° 3,5°

Fig. 4: Maximum center offset and maximum actuator deflection

16

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9. Electrical connection
The following connection options are available: Ì Separate operation Ì Series connection with wiring in the control cabinet Ì Series connection with Y-distributors Ì Connection without IO-Link communication Ì Connection with IO-Link communication
WARNING
In the event of a fault, loss of the safety function due to incorrect connection. Ì To ensure safety, both safety outputs must always be evaluated. Ì Monitoring outputs must not be used as safety outputs. Ì Lay the connecting cables with protection to prevent short circuits.
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection. Ì Do not use a control system with pulsing or switch off the pulsing function in your control system.
The device generates its own test pulses on the safety outputs. A downstream control system must tolerate these test pulses, which may have a length of up to 300 µs. Depending on the inertia of the downstream device (control system, relay, etc.), this can lead to short switching processes. The test pulses are output only with the safety outputs switched off during device start. Ì The inputs on a connected evaluation unit must be positive switching, as the two outputs on the safety switch deliver a level of +24 V in the switched-on state. Ì All the electrical connections must either be isolated from the mains supply by a safety transformer according to IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent insulation measures (SELV). Ì All electrical outputs must have an adequate protective circuit for inductive loads. The outputs must be protected with a free-wheeling diode for this purpose. RC interference suppression units must not be used. Ì Power devices which are a powerful source of interference must be installed in a separate location away from the input and output circuits for signal processing. The cable routing for safety circuits should be as far away as possible from the cables of the power circuits. Ì To prevent EMC interference, the physical environmental and operating conditions at the installation site of the device must comply with the requirements according to the standard EN 60204-1 (EMC). Ì Pay attention to any interference fields from devices such as frequency converters or induction heating systems. Observe the EMC instructions in the manuals from the respective manufacturer. Ì If the solenoid is operated with a frequency of more than 0.2 Hz, the device may react with a delay. Ì In devices with IMP/IMM inputs, the power supply for the evaluation electronics is separate from the power supply for the guard locking solenoid. If different power supplies are used, they must have the same reference potential. Ì For device variants with two connecting cables, both cables must be laid in the same cable duct.
Important!
EN If the device does not appear to function when the operating voltage is applied (e.g. STATE LED does
not flash), the safety switch must be returned to the manufacturer.

MAN20001531-01-09/22 (translation of the original operating instructions)

17

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

9.1.

Notes about
Important!
Ì This device is intended to be used with a Class 2 power source in accordance to UL1310. As an alternative an LV/C (Limited Voltage/Current) power source with the following properties can be used: This device shall be used with a suitable isolating source in conjunction with a fuse in accordance to UL248. The fuse shall be rated max. 3.3 A and be installed in the max. 30 V DC power supply to the device in order to limit the available current to comply with the UL requirements. Please note possibly lower connection ratings for your device (refer to the technical data).
Ì For use and application as per the requirements of UL 1) a connecting cable listed under the UL category code CYJV/7, min. 24 AWG, min. 80 °C, must be used.

  1. Note on the scope of the UL approval: the devices have been tested as per the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock and fire).

9.2. Safety in case of faults
Ì The operating voltage UB and the solenoid operating voltage UIMP are reverse polarity protected. Ì The safety outputs FO1A/FO1B are short circuit-proof. Ì A short circuit between the safety outputs is detected on starting or when the safety outputs are activated by the device. Ì A short circuit in the cable can be excluded by laying the cable with protection.

9.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of switches and the current required for the outputs. The following rules apply:

Max. current consumption of an individual switch Imax Imax UB = IUB_1 + IFO1A+FO1B + IOX1 + IOX2

IUB_1 = Switch operating current (max. 50 mA)

IOX

= Load current of monitoring output (max. 20 mA per monitoring output)

IFO1A+FO1B = Load current of safety outputs FO1A + FO1B (2 x max. 80 mA)

Imax IMP = Solenoid operating current (max. 500 mA)

Max. current consumption of a switch chain Imax UB Imax UB = IFO1A+FO1B + n x (IUB_2 + IOX1 + IOX2)

n

= Number of connected switches

IUB_2 = Switch operating current (max. 80 mA)

Important! If there are further monitoring outputs, their load current must be taken into account.

18

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

9.4.

Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables. Ì Use connection components and connecting cables from EUCHNER. Ì On the use of other connection components, the requirements in the following table apply. EUCHNER
provides no warranty for safe function in case of failure to comply with these requirements.

Observe the following requirements with respect to the connecting cables:

For safety switches CTS-…-VAB-… with plug connector 2 x M12

Parameter Conductor cross-section, min. R max. C max. L max. Recommended cable type

Value 0.25 80 120 0.65 LIYY 8 x 0.25 mm² or 5 x 0.34 mm²

For safety switches CTS-…-VSA-… with plug connector M12, 8-pin

Parameter Conductor cross-section, min. R max. C max. L max. Recommended cable type

Value 0.25 80 120 0.65 LIYY 8 x 0.34 mm²

Unit mm² W/km nF/km mH/km
Unit mm² W/km nF/km mH/km

9.5. Connector assignment of safety switches CTS-…-VAB-… with plug connector 2 x M12

Plug connector (view of connection side)

2 x M12

X1.2 X1.3
X1.4
X2.5 X2.2 X2.3

X1.1 X1.7 X1.6 X1.5 X1.8
X2.1
X2.4

Pin X1.1 X1.2
X1.3
X1.4
X1.5 X1.6 X1.7 X1.8

Designation FI1B UB
FO1A
FO1B
OX1 2) FI1A 0VUB

Function

Conductor coloring of connecting cable 1)

Enable input, channel B

WH

Electronics operating voltage, 24 V DC

BN

Safety output, channel A

Active monitoring of the guard locking for process protection:

ON, if door is closed and locked.

GN

Optional monitoring of the guard locking for process protec-

tion:

ON, if door is closed.

Safety output, channel B

Active monitoring of the guard locking for process protection:

ON, if door is closed and locked.

YE

Optional monitoring of the guard locking for process protec-

tion:

ON, if door is closed.

Door monitoring output 1

GY

Enable input, channel A

PK

Electronics operating voltage, 0 V DC

BU

n.c.

RD

EN

X2.1

IMM

Solenoid operating voltage, 0 V DC

BN

X2.2

OX2 2)

Door monitoring output 2

WH

X2.3

n.c.

BU

X2.4

IMP

Solenoid operating voltage, 24 V DC

BK

X2.5

n.c.

GY

  1. Only for standard EUCHNER connecting cable 2) The function of the monitoring output OX is determined by the actuator taught-in. You will find more detailed information in the data sheet 2153710 or
    at www.euchner.com.

MAN20001531-01-09/22 (translation of the original operating instructions)

19

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

9.6. Connector assignment of safety switches CTS-…-VSA-… with plug connector M12, 8-pin

Plug connector (view of connection side)

1 x M12

2 3
4

1 7 6 5 8

Pin

Designation

Function

Conductor coloring of connecting cable 1)

1

IMP

Solenoid operating voltage, 24 V DC

WH

2

UB

Electronics operating voltage, 24 V DC

BN

Safety output, channel A

Active monitoring of the guard locking for process protection:

3

FO1A

ON, if door is closed and locked.

GN

Optional monitoring of the guard locking for process protec-

tion:

ON, if door is closed.

Safety output, channel B

Active monitoring of the guard locking for process protection:

4

FO1B

ON, if door is closed and locked.

YE

Optional monitoring of the guard locking for process protec-

tion:

ON, if door is closed.

5

OX1 2)

Door monitoring output 1

GY

6

OX2 2)

Door monitoring output 2

PK

7

0VUB

Electronics operating voltage, 0 V DC

BU

8

IMM

Solenoid operating voltage, 0 V DC

RD

  1. Only for standard EUCHNER connecting cable 2) The function of the monitoring output OX is determined by the actuator taught-in. You will find more detailed information in the data sheet 2153710 or
    at www.euchner.com.

20

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
9.7. Notes on operation with safe control systems
Observe the following guidelines for connection to safe control systems: Ì Use a common power supply for the control system and the connected safety switches. Ì A pulsed power supply must not be used for UB. Tap the supply voltage directly from the power supply unit. If the power
supply is connected to a terminal of a safe control system, this output must provide sufficient electrical current. Ì The safety outputs FO1A and FO1B can be connected to the safe inputs of a control system. Prerequisite: the input must be
suitable for pulsed safety signals (OSSD signals, e.g. from light grids). The control system must tolerate test pulses on the input signals. This normally can be set up by parameter assignment in the control system. Observe the notes of the control system manufacturer. For the test pulse duration of your safety switch, refer to chapter 16. Technical data on page 38. Ì With series connection: always connect inputs FI1A and FI1B directly to a power supply unit or to outputs FO1A and FO1B of another EUCHNER BR device. Pulsed signals must not be present at inputs FI1A and FI1B. A detailed example of connecting and setting the parameters of the control system is available for many devices at www.euchner.com, in the area Downloads/Applications/CTS. The features of the respective device are dealt with there in greater detail.
9.8. Connection without and with IO-Link communication
9.8.1. Connection without IO-Link communication Only the safety and monitoring outputs are switched with this connection method. With a series connection, the safety signals are looped through from device to device.
9.8.2. Connection with IO-Link communication If, in addition to the safety function, detailed monitoring and diagnostic data are to be processed, a BR /IO-Link Gateway is required. To poll the communication data from the connected device, communication connection C is routed to the BR/ IO-Link Gateway. You will find further information in the operating instructions for your BR/IO-Link Gateway.

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
21

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

10. Connection of a single CTS-C2-BP/BR-CC-FLX (separate operation)
WARNING
In the event of a fault, loss of the safety function due to incorrect connection. Ì To ensure safety, both safety outputs FO1A and FO1B must always be evaluated.

Important!
The example shows only an excerpt that is relevant for the connection of the CTS system. The example illustrated here does not show complete system planning. The user is responsible for safe integration into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter the order number of your switch in the search box. You will find all available connection examples for the device in Downloads.

24V DC 0 V

1

1

-F1

-F2

2

2

13

-S1

14

24V DC 0 V

-B1

Actuator config L+HC

IMP

UB

Actuator EUC.167919

1

2

Read Head

Locking active

Monitoring Outputs
Door Monitoring

Safety Outputs

EUC.169051

8

7

CTS-C2-BP-CC-FLX-AP-VSA-169051

0 V

IMM

UB

5
OL/C

6
OD

3
FO1A

4
FO1B

Connected load

Fig. 5: Connection example, separate operation

22

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
11. Connection of several devices in a chain (series connection)
WARNING
In the event of a fault, loss of the safety function due to incorrect connection. Ì To ensure safety, both safety outputs FO1A and FO1B must always be evaluated.
Important!
Ì A BR chain may contain a maximum of 20 safety switches. Ì The BR chain is not permitted to be changed during operation. Ì The example shows only an excerpt that is relevant for the connection of the CTS system. The
example illustrated here does not show complete system planning. The user is responsible for safe integration into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter the order number of your switch in the search box. You will find all available connection examples for the device in Downloads. Ì Make sure you use the correct Y-distributors. See chapter 11.2.3. Connector assignment of Y-distributor for series connection without IO-Link communication on page 25 and chapter 11.2.4. Connector assignment of Y-distributor for series connection with IO-Link communication on page 27.
11.1. Series connection with wiring in the control cabinet
The series connection can be realized via additional terminals in a control cabinet.
Important!
In case of series connection with IO-Link communication: Ì The safety outputs are permanently assigned to the respective safety inputs of the downstream
switch. FO1A must be routed to FI1A and FO1B to FI1B. Ì If the connections are interchanged (e.g. FO1A to FI1B), the downstream device will enter the fault state.
11.2. Series connection with Y-distributors
The series connection is shown here based on the example of the version with plug connector M12. The switches are connected one behind the other with the aid of pre-assembled connecting cables and Y-distributors. If a safety door is opened or if a fault occurs on one of the switches, the system shuts down the machine.

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
23

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

11.2.1. Maximum cable lengths with BR switch chains
Important!
The maximum number of switches in a BR switch chain depends on many factors, including the cable length. This case example shows a standard application. You will find further connection examples at www.euchner.com.

l1
umin = 24 V

lmax =200 m l2
ln<100 m

SPS

iout

PLC

5 x 0,34 mm2

5 x 0,34 mm2

5 x 0,34 mm2

CTS # n

CTS # n-1

CTS # 1

11.2.2. Determining cable lengths using the example table

n Max. number of switches depending on the cable
length 5
6
10

IFO1A/FO1B (mA)
Possible output current per channel FO1A/FO1B
10 25 50 80 10 25 50 80 10 25 50 80

l1 (m)
Max. cable length from the last switch to the control system 150 100 80 50 120 90 70 50 70 60 50 40

24

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

11.2.3. Connector assignment of Y-distributor for series connection without IO-Link communication (Only for BR version with plug connectors 2 x M12)
Important!
Ì The switch chain must always be terminated with strapping plug 097645. Ì A higher-level control system cannot detect which safety door is open or on which switch a fault has occurred
with this connection technology.

Plug connector X1

Y-distributor

Plug connector X2 / X3

Pin X1.1 X1.2 X1.3 X1.4 X1.5 X1.6 X1.7 X1.8

X1 Function FI1B UB FO1A FO1B n.c. FI1A 0VUB *

X1 Socket

6

5

7

8

1

4 3 2

097627
X2 X1
X3

X1 Socket

5

6

8

7

4

1

3

2

111696 112395
X2 X1
X3
With connecting cable

  • Function and compatibility are dependent on the connector assignment of the device connected.

X2

Plug

4

1

3

5

2

5

2

1

3

4

X3

Socket

X2

Plug

4

3

5

1 2

1

2

3

4

5

X3

Socket

Pin X2.1 X2.2 X2.3 X2.4 X2.5

X2 Function UB FO1A 0 V FO1B *

Pin X3.1 X3.2 X3.3 X3.4 X3.5

X3 Function UB FI1A 0 V FI1B *

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
25

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

24V DC 0 V 1
-F1
2 13
-S1
14
-B1

Actuator config L+HC
Actuator EUC.167919

IMP
X2:4

Read Head

EUC.169613
CTS-C2-BR-CC-FLX-AP-VAB-169613

X2:1
IMM

UB
X1:2

n.c

n.c.

n.c.

X1:8 X2:3 X2:5

Monitoring Outputs

Locking active

Door Monitoring

X1:7
0 V UB

X1:5
OL/C

X2:2
OD

1
-F2
2

24V DC 0 V

FI1A

FI1B

X1:6

X1:1

Safety Inputs

Safety Outputs

X1:3
FO1A

X1:4
FO1B

-B2

Actuator config L+HC

IMP

Actuator EUC.167919

X2:4

Read Head

EUC.169613
CTS-C2-BR-CC-FLX-AP-VAB-169613

X2:1
IMM

UB
X1:2

n.c

n.c.

n.c.

X1:8 X2:3 X2:5

Monitoring Outputs

Locking active

Door Monitoring

X1:7
0 V UB

X1:5
OL/C

X2:2
OD

FI1A

FI1B

X1:6

X1:1

Safety Inputs

Safety Outputs

X1:3
FO1A

X1:4
FO1B

-B3

Actuator config L+HC

IMP

Actuator EUC.167919

X2:4

Read Head

EUC.169613
CTS-C2-BR-CC-FLX-AP-VAB-169613

X2:1
IMM

UB
X1:2

n.c

n.c.

n.c.

X1:8 X2:3 X2:5

Monitoring Outputs

Locking active

Door Monitoring

X1:7
0 V UB

X1:5
OL/C

X2:2
OD

FI1A

FI1B

X1:6

X1:1

Safety Inputs

Safety Outputs

X1:3
FO1A

X1:4
FO1B

Connected load

Fig. 6: Connection example for series connection

26

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

11.2.4. Connector assignment of Y-distributor for series connection with IO- Link communication (Only for BR version with plug connectors 2 x M12)
Important! Ì These Y-distributors can be used only with device variants that control guard locking via IO-Link communication. Ì The switch chain must always be terminated with strapping plug 097645.

Plug connector X1

Y-distributor

Plug connector X2 / X3

Pin X1.1 X1.2 X1.3 X1.4 X1.5 X1.6 X1.7 X1.8

X1 Function FI1B UB FO1A FO1B C FI1A 0VUB n.c.

X1 Socket

6

5

7

8

1

4 3 2

157913
X2 X1
X3

X2

Plug

4

1

3

5

2

5

2

1

3

4

X3

Socket

X1 Socket

5

6

8

7

4

1

3

2

158192 158193
X2 X1
X3
With connecting cable

X2

Plug

4

5

1

3

2

2

1

3

4

5

X3

Socket

Pin X2.1 X2.2 X2.3 X2.4 X2.5

X2 Function UB FO1A 0 V FO1B C

Pin X3.1 X3.2 X3.3 X3.4 X3.5

X3 Function UB FI1A 0 V FI1B C

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
27

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
12. Using communication data
A BR/IO-Link Gateway is required to use the device’s communication data and forward them to a higher-level bus system. The following devices are suitable: Ì GWY-CB-1-BR-IO (BR/IO-Link Gateway) Ì ESM-CB (safety relay with integrated BR/IO-Link Gateway)
12.1. Connection to a BR/IO-Link Gateway GWY-CB
The Gateway is an IO-Link device. Communication via IO-Link offers cyclical (process data) and acyclical (device data and events) data exchange (see chapter 12.3. Overview of the communication data on page 29). The communication connection C on the device allows the diagnostic line to be connected to the Gateway. The Ox/C connection represents a non-safety-related communication channel between the Gateway and the connected devices. IO-Link communication can be used for the following functions as well: Ì Reset for acknowledging error messages
You will find further information in the operating instructions for your BR /IO-Link Gateway.
12.2. Connection to a safety relay ESM-CB
The safety relay ESM-CB features an integrated BR/IO-Link Gateway. In addition to functioning as an IO-Link device (see chapter 12.1. Connection to a BR/IO- Link Gateway GWY-CB on page 28), the device can be used for connecting two monitored single- or dual-channel sensor circuits. The sensor circuits evaluate various signaling devices: Ì Sensor circuit S1 with short circuit detection; suitable for single- or dual-channel safety sensors Ì Sensor circuit S2, suitable for OSSD signals; short circuit detection by signaling device
When at least one sensor circuit is interrupted, the safety relay initiates the safe state. Different relay starting behaviors and various monitoring functions are possible. The device’s safety outputs FO1A and FO1B are routed to the OSSD inputs of the safety relay. The Ox/C connection of the device allows the diagnostic line to be connected to the Gateway. You will find further information in the operating instructions for your safety relay with integrated BR/IO-Link Gateway.

28

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

12.3. Overview of the communication data
The switch transmits both process data that are continuously transmitted to the evaluation unit (cyclical data) and data that can be polled specifically as needed (acyclical data). For further information on connection and on the communication data, refer to the operating instructions for your BR/IO-Link Gateway.

12.3.1. Cyclical data (process data)

Table 2: Cyclical data (process data)

Byte 1 Byte 2

Bit 7 OI –

Bit 6 –

Bit 5 OER

Bit 4 –

Bit 3 OM OLS

Bit 2 –

Bit 1 OL

Bit 0 OD OT

Bit

Signal

Message

OI

Diagnostics

There is a fault, see chapter 15.3. Error messages on page 36.

OM

Status

The safety outputs of the device are switched.

OD

Door position 1

A valid actuator is detected in the actuating range, and the guard is closed.

OER

Escape release

The device has been unlocked manually.

OT

Door position 2

The actuator is inserted in the switch head and the guard locking can be activated.

OLS

Locking element

The locking element is stuck, see chapter 15.3. Error messages on page 36.

OL

Guard locking

Guard locking is active.

12.3.2. Acyclical data (device data and events)
After one of the commands listed below is sent, the requested data are provided via the IO-Link Gateway. The reply message always consists of 8 bytes in big endian format.

Example 1: Reply message in response to the command Send device ID number/serial number: 06 02 68 E0 00 01 17 00 In this example, the device’s ID number is 157920 and its serial number is 279.

Byte number Reply in hex Description Reply in dec.

Byte 0

Byte 1

06

02

User data length in bytes

6 bytes

Byte 2 68

Byte 3 E0

Device ID number

157920

Byte 4 00

Byte 5 01

Byte 6 17

Serial number

279

Byte 7 00 Padding data ­

Example 2: Reply message for the command Send current device configuration: 02 01 08 00 00 00 00 00 In this example, the device has the high coding level and guard locking monitoring is active.

Byte number Reply in hex Description
Reply in dec.

Byte 0

Byte 1

02

01

User data length in bytes

Coding level

2 bytes

High coding level

Byte 2 08 Guard lock monitoring
Active

Byte 3 00
­

Byte 4 00
­

Byte 5 00

Byte 6 00

Padding data

­

­

Byte 7 00
­

EN

MAN20001531-01-09/22 (translation of the original operating instructions)

29

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

Command

HEX

Meaning

2

Send device ID number/serial number

3

Send version number of the device

5

Send number of devices in series connection

8

Send number of starting processes

12

Send current error code

13

Send most recently saved error code

14

Send size of log file

15

Send entry from log file with index

16

Send current actuator code

17

Send taught-in actuator code

18

Send disabled actuator code

19

Send applied voltage in mV

0B

Send current device configuration

0F

Send number of teach-in operations, factory resets and resets for

acknowledging error messages

1A

Send current temperature in °C

1B

Send number of switching cycles

1D

Reset for acknowledging error messages 1)

1E

Factory reset

Number of bytes
6
5
1 3 1 1 1 1 5 5 5 2 2
3
1 3 1

Bytes 1 – 3 Bytes 4 – 6 Byte 1 Bytes 2 – 4

Reply Bit sequences
(big endian format) Device ID number Serial number {V} Version number

Bytes 3 – 4 Bytes 3 – 4 Bytes 3 – 4

Byte 1
Byte 2
Byte 1 Byte 2 Byte 3

0x00 – Coding level not configured 0x01 – High coding level 0x02 – Low coding level 0x00 – Guard lock monitoring not configured 0x05 – Guard lock monitoring optional 0x08 – Guard lock monitoring active Number of teach-in operations Number of factory resets Number of resets for acknowledging error messages

0x1E ­ Factory reset performed

  1. Each BR device must be addressed individually in a chain.

For more information on these and other acyclical data, refer to the operating instructions for your BR/IO-Link Gateway.

30

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

13. Setup
13.1. Configuring device and teaching-in actuator for the first time
The device must be configured and the actuator must be allocated to the safety switch before the system forms a functional unit. During configuration, with the aid of a function actuator, the monitoring of the guard locking for process protection is specified as permanently active or available as an additional option. The coding level is also defined. As such the selection of the actuator determines the function of the device.
Configuration and the teach-in operation occur simultaneously in the delivery state or after a factory reset.

Actuator A-FLX-D-0C-167919 A-FLX-D-0D-169044 A-FLX-D-0E-169045 A-FLX-D-0F-169046

Monitoring of the guard locking for process protection Active
Optional
Active
Optional

Coding level High coding level High coding level Low coding level Low coding level

WARNING
Danger to life due to improper use Ì During the initial configuration or reconfiguration after a factory reset, ensure that all risk assessment
measures for the selected function are performed.

Important!
Ì If the actuator to be taught-in is in the actuating range for less than 30 s, the device will not be configured and the actuator will not be taught-in.

Prerequisite: Ì The device is in the delivery state. A factory reset must be performed before a preconfigured device can be reconfigured
(see chapter 14. Factory reset on page 34). Ì The device is isolated from the operating voltage.

1. Apply operating voltage. ¨ The STATE LED flashes white quickly. The device is carrying out a self-test. ¨ The STATE LED illuminates white. The device is in unlimited teach-in standby. 2. Insert an actuator. ¨ The teach-in operation begins. The STATE LED flashes alternately white/violet slowly. ¨ The teach-in operation ends after approx. 30 s. The STATE LED flashes alternately green/blue quickly (approx. 3 Hz). 3. Switch off operating voltage for at least 3 s. ¨ The code of the actuator taught-in is activated in the safety switch. The actuator is valid. 4. Switch on operating voltage. ¨ The device operates normally.

EN

MAN20001531-01-09/22 (translation of the original operating instructions)

31

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
13.2. Teaching-in new actuator (only for evaluation of the actuator with a high coding level)
Tip!
Prior to switching on the operating voltage, close the guard on which the actuator to be taught-in is installed. The teach-in operation starts immediately after switching on. This feature simplifies above all teach-in with series connections and on large installations.
Important! Ì During a teach-in operation, the safety outputs are switched off, i.e. the system is in the safe state. Ì The safety switch disables the code of the preceding device if teach-in is carried out for a new actuator.
Teach-in is not possible again immediately for this device if a new teach-in operation is carried out. The disabled code is released again in the safety switch only after a third code has been taught-in. Ì The safety switch can be operated only with the last actuator taught-in. Ì The number of teach-in operations is unlimited. Ì If the actuator to be taught-in is within the actuating range for less than 30 s, it will not be activated and the most recently taught-in actuator will remain saved. The device indicates an error (see chapter 15.3. Error messages on page 36).
Prerequisite: Ì The device is isolated from the operating voltage.
1. Make sure there is no actuator in the actuating range. 2. Apply operating voltage. ¨ The STATE LED flashes white quickly (5 Hz). The device is carrying out a self-test. ¨ The device is in teach-in standby for up to 3 minutes. The STATE LED flashes green. 4. Insert an actuator that has not been taught-in. ¨ The teach-in operation begins. The STATE LED flashes alternately white/violet slowly. ¨ The teach-in operation ends after approx. 30 s. The STATE LED flashes alternately green/blue quickly (approx. 3 Hz). 5. Switch off operating voltage for at least 3 s. ¨ The code of the new actuator taught-in is activated in the safety switch. The actuator is valid. 6. Switch on operating voltage. ¨ The device operates normally.

32

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

13.3. Functional check
WARNING
Danger of fatal injury as a result of faults in installation and functional check. Ì Before carrying out the functional check, make sure that there are no persons in the danger zone. Ì Observe the valid accident prevention regulations.

13.3.1. Mechanical function test The actuator must slide easily into the switch. Close the guard several times to check the function.

13.3.2. Electrical function test After installation and after any fault, the safety function must be fully checked. Proceed as follows:
If monitoring of the guard locking for process protection is active: 1. Switch on operating voltage. ¨ The machine must not start automatically. ¨ The safety switch carries out a self-test. The STATE LED then flashes green slowly. 2. Close all guards. In case of guard locking by solenoid force: activate guard locking. ¨ The machine must not start automatically. It must not be possible to open the guard. ¨ The STATE LED illuminates green, the LOCK LED illuminates orange. 3. Enable operation in the control system. ¨ It must not be possible to deactivate guard locking as long as operation is enabled. 4. Unlock guard locking if necessary and open guard. ¨ The machine must switch off and it must not be possible to start it as long as the guard is open. Repeat steps 2 – 4 for each guard.

If monitoring of the guard locking for process protection is optional:

1. Switch on operating voltage.

¨ The machine must not start automatically.

¨ The safety switch carries out a self-test. The STATE LED then flashes green slowly.

2. Close all guards. As soon as the actuator is inserted into the switch, the safety outputs are switched on independent of the state of the guard locking.

¨ The machine must not start automatically.

¨ The STATE LED illuminates green. In addition, depending on the state of the guard locking, the LOCK LED illuminates orange permanently or with a short interruption.

3. Enable operation in the control system.

4. Unlock guard locking if necessary and open guard.

¨ The machine must switch off and it must not be possible to start it as long as the guard is open. Repeat steps 2 – 4 for each guard.

EN

MAN20001531-01-09/22 (translation of the original operating instructions)

33

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

14. Factory reset
A factory reset deletes the configuration and restores the device’s factory settings.
To perform a factory reset, connect the two outputs FO1A and FO1B to 0 V before switching on or send the command Ox1E via IO-Link communication (see chapter 12.3.2. Acyclical data (device data and events) on page 29).

15. Status and error messages

15.1. LED displays

LED STATE LOCK DIA

Color RGB Orange Red

Key to symbols

2x LED STATE LOCK DIA
Important!
If you do not find the displayed device status in the following tables, this indicates an internal device fault. Contact the manufacturer.

quickly slowly ¨ X

LED not illuminated LED illuminated LED flashes quickly (3 Hz) LED flashes slowly (0.6 Hz) LED flashes alternately Any state

34

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

15.2. Status messages

Operating mode

LED indicator

STATE RGB

LOCK Orange

Safety outputs FO1A / FO1B

Guard locking signal OL

Door position 1 signal
OD

Status

Self-test

Normal operation

white quickly 5 Hz
(CTS-BP: 2 s; CTS-BR: 5 s)

Self-test after operating voltage is switched on.

off

off

off

green quickly

No communication with the BR/IO-Link Gateway.

green

on

on

on

If guard locking monitoring is active: door is closed and locked. The safety outputs of the preceding device in a series connection are switched on.

green

on

off

on

slowly

If guard locking monitoring is optional: door is closed. The safety outputs of the preceding device in a series connection are switched on.

slowly

off slowly

on

on

Door is closed and not locked. The safety outputs of the preceding device in a series connection are switched off.

slowly

off

off

off

Door is open.

off

off

off

Door is open and ready for locking.

slowly

quickly

¨

white/orange slowly

slowly

off

off

X

The escape release has been actuated.

white

off

on

Device is in teach-in standby (see chapter 13.1. Configuring device and teaching-in actuator for the first time on page 31).

¨
white/violet slowly

off

X

off

Teach-in operation. Door is closed.

¨
green/blue quickly

X

X

Positive acknowledgment after successful teach-in operation.

¨
white/blue quickly

off

off

off

Factory reset

depending on the error

depending on the error

off

depending on the error Error message (see chapter 15.3. Error messages on page 36).

Teach-in operation

Factory reset

Error

EN

MAN20001531-01-09/22 (translation of the original operating instructions)

35

Error code via IO-Link Open/close door
Reset

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
15.3. Error messages
LED indicator

STATE RGB

LOCK

DIA

Orange

Red

Error

Troubleshooting

Acknowledging errors

Teach-in error

¨

0x1F

white/red slowly

0x25

blue quickly

0x42

blue slowly

0x45 blue
Input error
0x2E

0x30

0x31 0x32

violet slowly

0x36 0x37

Transponder/read error

0x44

blue slowly

0x46 blue

-0x47 0x48 0x89

blue quickly ¨
white/blue slowly ¨
blue/red quickly

Actuator removed from the actuating range prior to the end of the teach-in operation.

Check whether the actuator is outside the actuating range or in the limit range.

Disabled actuator detected during the teach-in operation: The actuator was taught-in during the penultimate teach-in operation and is disabled for the current teach-in operation.
Invalid actuator detected: The actuator is not intended for the current device configuration.
Faulty or incompatible actuator detected: The actuator’s data structure cannot be read. The actuator is faulty or is not suitable for the device.

Repeat the teach-in operation with a new actuator (see chapter 13.2. Teaching- in new actuator (only for evaluation of the actuator with a high coding level) on page 32).
Ì Perform the teach-in operation with an actuator intended for the current device configuration.
Ì If the device is to be reconfigured, observe chapter 13.1. Configuring device and teaching-in actuator for the first time on page 31.
Repeat teach-in operation with new actuator.

Different signal states at the safety inputs FI1A and FI1B during operation.

Different signal states at the safety inputs FI1A and FI1B during the self- test.
Test pulses not detected at safety input FI1A or FI1B during operation.

Ì Check wiring. Ì Check preceding device in the switch chain.

Test pulses at safety input FI1A or FI1B not detected during self-test.

Invalid actuator detected during operation: The actuator is not intended for the current device configuration.

Faulty or incompatible actuator detected during operation: The actuator’s data structure cannot be read. The actuator is faulty or is not suitable for the device.
Disabled actuator detected during operation: The actuator is not the currently valid actuator.

Use a valid actuator.

Actuator not taught-in detected during operation.

Ì Use the currently valid actuator. Ì Teach-in actuator.

Possibly mechanically damaged actuator detected during operation.

Ì Check actuator for any damage. If necessary, replace actuator.
Ì Check whether the actuator is outside the actuating range or in the limit range.

36

(translation of the original operating instructions) MAN20001531-01-09/22

LED indicator

STATE RGB

LOCK

DIA

Orange

Red

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

Error

Troubleshooting

Acknowledging errors

Error code via IO-Link Open/close door
Reset

Output error 0x4C 0x4D
0x54 violet quickly

Environment error

0x60

¨

0x61 0x62

orange/red slowly
¨

0x63 Internal erroorraqnugicek/lyred

0x01 red

A HIGH signal is detected at safety output FO1A or FO1B during the self-test.
The voltage level at safety outputs FO1A and FO1B during operation does not meet the requirements. External voltage might be present.

Check wiring.

Supply voltage too high. Supply voltage too low.
Device temperature too high. Device temperature too low.

Decrease supply voltage. Ì Increase supply voltage. Ì Check system configuration: cable length, number
of devices in the switch chain.
Observe the specified temperature range (see chapter 16. Technical data on page 38).

Internal device error

Restart the device. On repeated occurrence, contact the manufacturer.

15.4. Acknowledging error messages
If the DIA LED flashes inversely once, the error message can be acknowledged by opening and closing the guard. If the error is still displayed afterward, a reset must be performed. If the LED DIA is permanently illuminated, the error message can be acknowledged only by a reset. The reset can be performed as follows.

Reset

Centrally for all switches in
a chain

Each switch must be addressed indi-
vidually

Further information

By briefly disconnecting the power supply (at least 3 s)

Via the cyclical data of IO-Link communication

See operating instructions for the IO-Link Gateway

Via the acyclical data of IO-Link communication

See chapter 12.3.2. Acyclical data (device data and events) on page 29

Resetting to acknowledge error messages does not delete the configuration.

Important!

EN

Contact the manufacturer if the fault display is not reset after briefly disconnecting the power supply.

MAN20001531-01-09/22 (translation of the original operating instructions)

37

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

16. Technical data
NOTICE If a data sheet is available for the product, the information on the data sheet applies.

16.1. Technical data for safety switch CTS-C2-BP/BR-CC-FLX

Parameter
General Material – Switch head – Switch housing Installation orientation Degree of protection Safety class acc. to EN IEC 61140 Degree of contamination (external, acc. to EN 60947-1) Mechanical life Ambient temperature at UB = 24 V Actuator approach speed max. Actuating/extraction/retention force Locking force Fmax Locking force FZh Weight Connection (depending on version) Operating voltage UB (reverse polarity protected, regulated, residual ripple < 5%) Current consumption IUB at UB = 24 V The following applies to the approval acc. to UL Switching load acc. to UL External fuse (operating voltage UB) External fuse (solenoid operating voltage UIMP) Rated insulation voltage Ui Rated impulse withstand voltage Uimp Rated conditional short-circuit current Shock and vibration resistance EMC protection requirements Ready delay Risk time for single device Risk time extension per device Turn-on time Discrepancy time between both safety outputs acc. to EN 60947-5-3 Test pulse duration Test pulse interval Safety outputs FO1A/FO1B Output voltage UFO1A/UFO1B 1) – HIGH UFO1A/UFO1B – LOW UFO1A/UFO1B Switching current per safety output Utilization category acc. to EN 60947-5-2
Switching frequency Monitoring outputs Ox/C Output voltage Max. load Solenoid Solenoid operating voltage UIMP (reverse polarity protected, regulated, residual ripple < 5%) Solenoid current consumption IIMP Connection rating at max. switching frequency Duty cycle Reliability values acc. to EN ISO 13849-1 2) Category Performance Level (PL) PFHD Mission time

min.

Value typ.

max.

Die-cast zinc

Reinforced thermoplastic

Any

IP65/IP67/IP69/IP69K

III

3

1 x 106 operating cycles

-20

+55

20

Device dependent, see www.euchner.com

3900

3000

0.34

2 plug connectors M12, 5- and 8-pin / 1 plug connector M12, 8-pin

24 -15% / +20% (SELV)

50

Operation only with UL Class 2 power supply or equivalent measures

DC 24 V, class 2

1

8

1

8

32

0.5

100

Acc. to EN 60947-5-3

Acc. to EN 60947-5-3

1

200

10

400

10

0.3

96

Semiconductor outputs, p-switching, short circuit-proof

UB – 2

UB

0

1

1

80

DC-13 24 V 80 mA

Caution: outputs must be protected with a free-wheeling diode in case of inductive loads

0.2

p-switching, short circuit-proof

0.8 x UB

UB

20

24 V DC ± 20 %

500

9

100

Monitoring of the guard position

4

e

6.44 x 10-9/h

20

  1. Values at a switching current of 50 mA without taking into account the cable lengths 2) Refer to the declaration of conformity in chapter 20 for the issue date.

Unit
°C m/min
N N N kg
V DC mA
A A V kV A
s ms ms ms ms ms ms
V DC mA
Hz V DC mA
V DC mA W %
years

38

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16.1.1. Typical system times Refer to the technical data for the exact values. Ready delay: After switching on, the device carries out a self-test. The system is ready for operation only after this time. Turn-on time of safety outputs: The max. reaction time ton is the time from the moment when the guard is locked to the moment when the safety outputs switch on. Risk time according to EN 60947-5-3: The risk time is the maximum time until at least one of the safety outputs FO1A or FO1B switches off safely when the actuator is removed from the actuating range. This also applies if an internal or external fault occurs at this moment.
For optional guard locking monitoring for process protection the following applies: if an actuator moves outside the actuating range, the safety outputs FO1A and FO1B are switched off after the risk time at the latest. If several devices are operated in a series connection, the risk time of the overall device chain will increase with each device added. Use the following calculation formula: tr = tr, e + (n x tl) tr = Total risk time tr, e = Risk time for single device (see technical data) tl = Risk time extension per device n = Number of additional devices (total number -1) Discrepancy time: The safety outputs FO1A and FO1B switch with a slight delay in relation to each other. They have the same signal state no later than after the discrepancy time. Test pulses at the safety outputs: The device generates its own test pulses on the safety outputs FO1A and FO1B. A downstream control system must tolerate these test pulses. This can usually be set up in the control systems by parameter assignment. If parameter assignment is not possible for your control system or if shorter test pulses are required, contact our support organization. The test pulses are output only if the safety outputs are switched on.
EN

MAN20001531-01-09/22 (translation of the original operating instructions)

39

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

16.2. Radio frequency approvals

FCC ID: 2AJ58-18

IC:

22052-18

FCC/IC-Requirements
This device complies with part 15 of the FCC Rules and with Industry Canada’s licence-exempt RSSs. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.
    Changes or modifications not expressly approved by the party responsible for compliance could void the user`s authority
    to operate the equipment.
    NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
    Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
    Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes :
    (1) l’appareil ne doit pas produire de brouillage, et
    (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.

Supplier`s Declaration of Conformity 47 CFR § 2.1077 Compliance Information
Unique Identifier: CTS-C1-BP Series CTS-C1-BR Series CTS-C2-BP Series CTS-C2-BR Series
Responsible Party ­ U.S. Contact Information EUCHNER USA Inc. 1860 Jarvis Avenue Elk Grove Village, Illinois 60007
info(at)euchner-usa.com http://www.euchner-usa.com

40

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX
16.3. Dimension drawing of safety switch CTS

MAN20001531-01-09/22 (translation of the original operating instructions)

EN
41

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

16.4. Technical data for actuator A-FLX-D-0.-…

Parameter
Material – Mounting – Cover – Actuating element – Housing Weight Ambient temperature Degree of protection Mechanical life Locking force, max. Locking force FZh Installation orientation Overtravel Power supply

min.

Value typ.

Unit max.

Safety screws, galvanized steel 8.8

NBR

Stainless steel

fiber reinforced plastic, black

0.06

kg

-20

+55

°C

IP65/IP67/IP69/IP69K

1 x 106

3900

N

3000

N

Any

4

mm

Inductive via read head

16.4.1. Dimension drawing for actuatorA-FLX-D-0.-…

42

(translation of the original operating instructions) MAN20001531-01-09/22

Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX

17. Ordering information and accessories
Tip!
Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed in Accessories.

18. Inspection and service
WARNING
Danger of severe injuries due to the loss of the safety function. Ì If damage or wear is found, the complete switch and actuator assembly must be replaced. Replace-
ment of individual parts or assemblies is not permitted. Ì Check the device for proper function at regular intervals and after every fault. For information about
possible time intervals, refer to EN ISO 14119:2013, section 8.2.
Regular inspection of the following is necessary to ensure trouble-free long- term operation: Ì Check the switching function (see chapter 13.3. Functional check on page 33) Check all additional functions (e.g. escape
release, lockout bar, etc.) Ì Check the secure mounting of the devices and the connections Ì Check for contamination
No servicing is required. Repairs to the device are only allowed to be made by the manufacturer.
NOTICE
The year of manufacture is given in the laser marking at the bottom right corner. The current version number in the format (V X.X.X) can also be found on the device.

19. Service
If servicing is required, please contact:

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen Germany

Service telephone:

+49 711 7597-500

E-mail:

[email protected]

Internet:

www.euchner.com

20. Declaration of conformity

EN

The declaration of conformity is part of the operating instructions.

The complete EU declaration of conformity can also be found at www.euchner.com. Enter the order number of your device in the search box. The document is available under Downloads.

MAN20001531-01-09/22 (translation of the original operating instructions)

43

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen Germany [email protected] www.euchner.com
Edition: MAN20001531-01-09/22 Title: Operating Instructions Transponder-Coded Safety Switch CTS-C2-BP/BR-CC-FLX (translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 09/2022
Subject to technical modifications; no responsibility is accepted for the accuracy of this information.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EUCHNER User Manuals

Related Manuals