BOSCH Condens 7000 WP Wall Mounted Gas Condensing Boilers Instruction Manual
- June 9, 2024
- Bosch
Table of Contents
Condens 7000 WP Wall Mounted Gas Condensing Boilers
Installation and Maintenance Instructions
Wall mounted gas condensing boilers Condens 7000 WP
GC7000WP 50 23, GC7000WP 65 23, GC7000WP 85 23, GC7000WP 100 23
6721841195 (2022/01) UK/IE
Table of contents
Table of contents
1 Explanation of symbols and safety instructions . . . . . . . . . . . 3 1.1 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . 3
2 Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 4
2.1 Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . .
4 2.2 Product data for energy consumption . . . . . . . . . . . . . . 4 2.3
About these instructions . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Appliance types . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 5 2.5 Type Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 5 2.6 Conversion of gas type. . . . . . . . . . . . . . . .
. . . . . . . . . . . 5 2.7 Accessories . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 5 2.8 Scope of delivery . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 5 2.9 Pump test. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 5 2.10 Frost protection . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.11 product
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.12
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 8 2.13 Minimum clearance from walls . . . . . . . . . . . . . . . . . . .
. 9 2.14 Flue gas temperature sensor . . . . . . . . . . . . . . . . . . . . .
. 9 2.15 Opening and closing the front panel of the
appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 10
3 Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.1 Notes on installation and operation . . . . . . . . . . . . . . . 10 3.2 Regulations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Flue gas routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Preconditions for installation. . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.1 Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.2 Important notices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.3 Water quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.3.1 Water conditioning and treatment . . . . . . . . . . . . . . . . 12 5.4 Maximum flow temperature. . . . . . . . . . . . . . . . . . . . . . 12
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.1 6.2 6.3 6.4 6.5 6.5.1 6.5.2 6.6
Unpacking the floor standing boiler . . . . . . . . . . . . . . . 12 Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Setting up the floor standing boiler. . . . . . . . . . . . . . . . 12 Connecting on the heating and gas side . . . . . . . . . . . . 14 Mounting the connection set (accessories) . . . . . . . . . 14 Installing the gas valve . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Mounting the connection set . . . . . . . . . . . . . . . . . . . . . 15 Mounting the siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.7 Connecting the condensate pipe . . . . . . . . . . . . . . . . . 16
6.8 Connecting heating pipes (without connection set) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.8.1 Connecting the gas valve . . . . . . . . . . . . . . . . . . . . . . . . 17
6.8.2 6.9 6.10 6.11
Installing the pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Installing the low loss header . . . . . . . . . . . . . . . . . . . . 17 Connecting an expansion vessel . . . . . . . . . . . . . . . . . . 18 Installing the insulation (accessory) . . . . . . . . . . . . . . . 18
7 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 7.1 Handling printed circuit boards. . . . . . . . . . . . . . . . . . . 18 7.2 Opening the top cover . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.3 Overview of plug-in strip . . . . . . . . . . . . . . . . . . . . . . . . 19 7.4 Connecting electrical components . . . . . . . . . . . . . . . . 20 7.5 Connecting the pump of the pump assembly. . . . . . . . 20 7.6 Connecting the 3-way valve 230 V (accessory). . . . . . 21 7.7 Mounting the function module (accessory) . . . . . . . . . 21 7.8 Fitting the plug (if not preassembled) . . . . . . . . . . . . . 21
8 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 8.1 Commissioning the floor standing boiler . . . . . . . . . . . 22 8.2 Setting the parameters . . . . . . . . . . . . . . . . . . . . . . . . . 22 8.3 Setting options for air/gas ratio control valve . . . . . . . 23 8.4 Measuring the gas standing pressure (static) . . . . . . . 23 8.5 Measuring the gas working pressure (dynamic) . . . . . 23 8.6 Measuring of CO2 and CO (full load) . . . . . . . . . . . . . . 24 8.7 Measuring the gas/air ratio (minimum load) . . . . . . . . 24 8.8 Reading off the ionisation current . . . . . . . . . . . . . . . . 24 8.9 Check the (flue) gas tightness . . . . . . . . . . . . . . . . . . . 25 8.10 Check the function of the floor standing boiler . . . . . . 25 8.11 Completion work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 8.12 Instructing the operator . . . . . . . . . . . . . . . . . . . . . . . . 25
9 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.1 Control panel overview . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.2 9.3 9.4 9.4.1 9.4.2 9.4.3
Switching on the device . . . . . . . . . . . . . . . . . . . . . . . . 25 Siphon filling program . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Settings in the service menu . . . . . . . . . . . . . . . . . . . . . 26 Operating the service menu . . . . . . . . . . . . . . . . . . . . . 26 Service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Thermal disinfection . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
10 Inspection and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 32 10.1 Important notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 10.2 General work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 10.3 Remove the gas-air unit . . . . . . . . . . . . . . . . . . . . . . . . . 33 10.4 Clean the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 10.5 Cleaning the heat exchanger . . . . . . . . . . . . . . . . . . . . . 34 10.6 Cleaning the siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 10.7 Cleaning the condensation catch pan . . . . . . . . . . . . . 35 10.8 Resetting the Maintenance type . . . . . . . . . . . . . . . . . . 35 10.9 Measuring the gas pressure . . . . . . . . . . . . . . . . . . . . . 35 10.10 Measuring of CO and CO2 . . . . . . . . . . . . . . . . . . . . . . . 35 10.11 Measuring the gas/air ratio . . . . . . . . . . . . . . . . . . . . . . 35 10.12 Measuring the ionisation current . . . . . . . . . . . . . . . . . 35 10.13 Check the flue gas backflow preventer. . . . . . . . . . . . . 35 10.14 Check the (flue) gas tightness . . . . . . . . . . . . . . . . . . . 35 10.15 Check for correct operation . . . . . . . . . . . . . . . . . . . . . 35 10.16 Replacing components . . . . . . . . . . . . . . . . . . . . . . . . . 36 10.16.1 Replacement interval for components . . . . . . . . . . . . 36 10.16.2 Inserting the igniter . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 10.16.3 Replacing the flue gas temperature sensor. . . . . . . . . 36 10.16.4 Replacing the coding plug . . . . . . . . . . . . . . . . . . . . . . 37 10.16.5 Replacing the air/gas ratio control valve . . . . . . . . . . . 37 10.17 Inspection and maintenance protocol (checklist) . . . . 38
11 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 11.1 Operating and fault displays . . . . . . . . . . . . . . . . . . . . . 39 11.1.1 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 11.1.2 Fault code table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2
Condens 7000 WP 6721841195 (2022/01)
11.1.3 Faults that are not displayed . . . . . . . . . . . . . . . . . . . .
.44 12 Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .45
12.1 Standard decommissioning . . . . . . . . . . . . . . . . . . . . . .45
12.2 Decommissioning when there is a risk of frost . . . . . . .45 13
Environmental protection and disposal . . . . . . . . . . . . . . . . .45
14 Data Protection Notice . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .45
15 Technical information and reports. . . . . . . . . . . . . . . . . . . . .
.46 15.1 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .46 15.2 Technical Specifications . . . . . . . . . . . . . . . . . .
. . . . . .47 15.3 Data relating to the gas. . . . . . . . . . . . . . . . . .
. . . . . . . .48 15.4 Hydraulic resistances . . . . . . . . . . . . . . . . .
. . . . . . . . . .49 15.5 Residual head of pumps . . . . . . . . . . . . . .
. . . . . . . . . . .49 15.6 Setting values for heating capacity . . . . . . .
. . . . . . . . .49 15.7 Commissioning report for the appliance. . . . . . . .
. . . .50
1 Explanation of symbols and safety instructions
1.1 Explanation of symbols Warnings In warnings, signal words at the beginning
of a warning are used to indicate the type and seriousness of the ensuing risk
if measures for minimizing danger are not taken. The following signal words
are defined and can be used in this document:
DANGER DANGER indicates that severe or life-threatening personal injury will
occur.
WARNING WARNING indicates that severe to life-threatening personal injury may
occur.
CAUTION CAUTION indicates that minor to medium personal injury may occur.
NOTICE NOTICE indicates that material damage may occur.
Important information
The info symbol indicates important information where there is no risk to
people or property.
1.2 General safety instructions
H Notices for the target group These installation instructions are intended
for gas, plumbing, heating and electrical contractors. All instructions must
be observed. Failure to comply with
Explanation of symbols and safety instructions
instructions may result in material damage and personal injury, including
danger to life. Read the installation, service and commissioning
instructions (heat source, heating controller, pumps, etc.) before
installation. Observe the safety instructions and warnings. Follow national
and regional regulations, technical regulations and guidelines. Record all
work carried out.
H Determined use The product may only be used for the heating of central
heating water in a sealed system and for DHW (Domestic Hot Water) heating in
closed-loop DHW and heating systems. Any other use is considered
inappropriate. Any damage that may result is excluded from liability.
H System malfunctions caused by third-party equipment
This heat source is designed for operation with our control units.
System malfunctions, malfunctions and defects of system components resulting
from the use of thirdparty equipment are excluded from liability.
Service work required to repair the damage will be invoiced.
H If you smell gas A gas leak could potentially cause an explosion. If you
smell gas, observe the following rules:
Prevent flames or sparks: Do not smoke, use a lighter or strike matches.
Do not operate any electrical switches or unplug any equipment. Do not use
the telephone or ring doorbells.
Turn off the gas at the meter or regulator. Open windows and doors. Warn your
neighbours and leave the building. Prevent anyone from entering the building.
Move well away from the building: call the National
Gas Emergency Service on 0800 111 999. L.P.G. boilers: Call the supplier’s
number on the
side of the gas tank.
H Danger to life from poisoning by flue gas There is a danger to life from
escaping flue gas.
Ensure that flues and gaskets are not damaged.
Condens 7000 WP 6721841195 (2022/01)
3
Product Information
H Danger of death from poisoning by flue gas due to inadequate combustion
Danger of death due to flue gas leak. If flues are damaged or leaking, or if
you smell flue gas, observe the following rules.
Close the fuel infeed. Open doors and windows. If necessary, warn all
residents and leave the
building. Prevent third parties from entering the building. Rectify any damage
to the flue gas pipe
immediately. Check the combustion air supply. Do not cover or reduce the size
of ventilation
openings in doors, windows and walls. Ensure that there is adequate combustion
air
supply, including for any appliances installed at a later date, e.g. extractor
fans, kitchen fans or air conditioning units that discharge air to the
outside. Never operate the device if there is insufficient combustion air
supply.
H Combustion/room air Keep the combustion/ambient air free of corrosive
substances (e.g. halogenated hydrocarbons that contain chlorine or fluorine
compounds). This will help to prevent corrosion. Keep the combustion air
supply free of dust.
H Installation, commissioning and maintenance Installation, commissioning and
maintenance may be performed only by an approved contractor.
In the case of open flue operation: ensure that the installation location
meets the ventilation requirements.
Do not repair, manipulate or deactivate safetyrelevant components.
Only install original spare parts. Check for gas tightness after working on
gas-
carrying components.
H Handover to the user When handing over, brief the owner in the operation of
the heating system and about the operating conditions.
Explain operation with particular emphasis on all safety-related actions.
Highlight the following points in particular: Point out that modifications
or repairs may be carried out only by an approved contractor. To ensure safe
and environmentally compatible operation, an annual inspection, and also
cleaning and maintenance as required, must be carried out within the specified
interval. Point out the possible consequences (material damage, personal
injury and possible danger to life) of not carrying out inspection, cleaning
and maintenance correctly, or omitting it altogether. Draw attention to the
dangers associated with carbon monoxide (CO) and recommend the use of CO
detectors. Hand over the installation and operating instructions to the user
for safekeeping.
H Inspection and maintenance interval To ensure the wall mounted gas
condensing boiler works correctly and safely, the following intervals must be
adhered to: · Inspection: annually, · Maintenance: every 2 years or following
a burner
runtime of 4000 hours (depending on which occurs first).
2 Product Information
2.1 Declaration of conformity The design and operating characteristics of this
product comply with the European and national requirements.
The CE marking declares that the product complies with all the applicable EU
legislation, which is stipulated by attaching this marking.
The complete text of the Declaration of Conformity is available on the
Internet: worcester-bosch.co.uk.
2.2 Product data for energy consumption The product data on energy consumption
can be found in the operating instructions for the user.
2.3 About these instructions
Figures used The figures in these instructions serve to provide general
notices regarding correct operation. The figures used serve to provide general
notices regarding correct operation. These figures may slightly deviate from
the actual situation.
Product types mentioned These instructions describe all product types of the
GC7000WP. Availability may vary depending on the country.
4
Condens 7000 WP 6721841195 (2022/01)
2.4 Appliance types
Appliance type: GC7000WP 50 23 GC7000WP 65 23 GC7000WP 85 23 GC7000WP 100 23 Table 1 Appliance types
Country UK, IE UK, IE UK, IE UK, IE
Part No. 7736 702 194 7736 702 195 7736 702 196 7736 702 197
The wall mounted boiler designation comprises the following:
· Condens 7000 WP: product name; · GC7000WP 50… GC7000WP 100: product type; ·
50 … 100: heating capacity in kW; · 23: gas type.
2.5 Type Plate
The data plate contains information on the appliance output, registration data
and serial number of the product. The data plate is on the underside of the
wall mounted boiler on the right next to the gas connection ( Fig. 1, p. 6).
2.6 Conversion of gas type This floor standing boiler is suitable for the gas
categories specified on the data plate.
If conversion of the floor standing boiler to a different gas category is
allowed, this is specified in the gas data ( § 15.3, p. 48).
2.7 Accessories A wide range of accessories is available for this appliance.
Contact the manufacturer for more information. You will find the relevant
addresses on the back of this document.
2.8 Scope of delivery A range of accessories is supplied with the GC7000WP.
Check the heating system is intact on delivery. Check that all package
contents are present.
Packaging unit 1 (boiler)
Component · Wall-mounted boiler
Packaging
Cardboard box
2 (accessories)
· Mounting rail
Cardboard
· Fixing materials
box
· Siphon
· Condensate drain hose
· Plug (if not pre-
assembled)
· Rotary joint + gasket (2x)
· Documentation
Table 2 Scope of delivery
2.9 Pump test.
The pump starts automatically for 10 seconds every 24 hours if it is not in
use for a longer period. This procedure prevents the pump from seizing.
Product Information
2.10 Frost protection
NOTICE Installation damage due to the effects of frost. The heating system
could freeze during a hard frost due to: mains voltage failure, insufficient
gas supply or appliance fault. Install the boiler in a frost-proof room. Drain
the entire heating system if it is to be shut down for a longer
period.
The boiler is equipped with integral frost protection. This means that an
external frost protection safeguard for the boiler does not have to be
installed. The frost protection switches the boiler on at a boiler temperature
of 7 °C and switches it off at a boiler temperature of 15 °C. This frost
protection does not protect the heating system against frost.
Condens 7000 WP 6721841195 (2022/01)
5
Product Information 2.11 product overview
14 13 12 11 10 9 8 7 6 5 4
3 2 1 38 37 28 36 35
Fig. 1 GC7000WP with connection set on frame
6
15 16 17 18
19 20 21
22 23 24 25 26
27 29 30 31 32 33 34
0010030188-002
Condens 7000 WP 6721841195 (2022/01)
Floor standing condensing boiler: [1] Pump assembly [2] Gas line [3] Drain pan [4] heat exchanger [5] Snap fastener [6] Automatic air vent valve [7] CO2 adjusting screw1) [8] Air intake pipe [9] Venturi nozzle [10] Air/gas ratio control valve [11] Remote control [12] On/off switch [13] Flue gas temperature sensor [14] Connector [15] Test point for flue gas routing [16] Test point for air supply [17] Appliance cover [18] Connection point for diagnosis tool [19] Fan [20] Burner cover [21] Igniter [22] Flow temperature sensor (93 °C) [23] Safety temperature monitor (105 °C) [24] High limit safety cut-out [25] Pressure sensor [26] return temperature sensor [27] Type Plate [28] Condensate trap Connection set and frame (accessories): [29] Pump [30] Gas isolator [31] Expansion vessel connection [32] Fill and drain valve [33] Service valve return [34] Base frame [35] Adjustment fixture [36] Service valve flow [37] Pressure gauge [38] Water pressure relief valve
- Reproduced: GC7000WP 100
Condens 7000 WP 6721841195 (2022/01)
Product Information 7
Product Information
2.12 Dimensions Floor standing boiler on frame
Floor standing boiler against the wall
64
53
115
520 115
521 200
115 520
115
260 300
53
457.5 136
202 198 199
138 198
1120
1690 ± 12
298 > 100
191
260
642,5 260
191
260
260
Fig. 2 Dimensions on base frame [mm]
0010030944-002
Fig. 3 Dimensions on the wall [mm]
0010031061-002
8
Condens 7000 WP 6721841195 (2022/01)
2.13 Minimum clearance from walls
With a horizontal flue gas connection, make sure the electronic components
inside the floor standing boiler at the top remain accessible when placing an
elbow directly on the flue outlet adapter. After fitting the flue bend, check
whether the top cover of the
appliance is easy to remove ( § 7.2, p. 18). There must be a clearance of at
least 100 mm directly above the bend
at the floor standing boiler.
23
1
100
B
A
K
5,2 % S
(52 mm/1 m)
136
Product Information
Flue gas routing
A [mm] B [mm]
Ø 110 mm Connection adapter with elbow, 165 A + 0.5*K
Ø 110/ 160 mm
horizontal flue outlet.
179 A + 0.5*K
Ø 110 mm Connection adapter, vertical –
0
Ø 110/ 160 mm
flue outlet
–
0
Table 4 Clearance A and B depending on flue outlet
Determine the minimum clearance above the floor standing boiler.
Add dimension B from Table 4 to the height of the top of the floor standing
boiler.
With a horizontal flue outlet: Add 52 mm to dimension B for every meter of
horizontal flue outlet. In this case also take the diameter of the collar
into consideration.
With a vertical flue outlet: Maintain a clearance of at least 100 mm above
the floor standing boiler to allow the electronic components to be accessed
and worked on.
Minimum space required for the floor standing boiler.
Provide an unobstructed space of at least 100 cm for the floor standing boiler
to allow maintenance and other work to be carried out.
Distance from walls at sides.
Maintain a clearance of at least 5 mm on the weather side of the floor standing boiler.
1120
5*
5*
C
0010040879-001
Fig. 4 Side view [mm] [1] Horizontal flue outlet [2] Collar [3] Vertical flue
outlet
A Clearance from top of floor standing boiler – hard borehole B Clearance from
top of floor standing boiler – upper side of
borehole C Depth of floor standing boiler: 365 mm K Diameter of borehole S
Wall thickness
Wall thickness S K [mm] for Ø flue outlet [mm]
Ø 110/160
Ø 110
15 – 24 cm
190
140
24 – 33 cm
195
145
33 – 42 cm
200
150
42 – 50 cm
205
155
Table 3 Diameter of borehole K
Condens 7000 WP 6721841195 (2022/01)
260 300
520
0010033512-001
Fig. 5 Front view [mm] 2.14 Flue gas temperature sensor The floor standing
boiler is manufactured with a flue outlet sensor as standard ( Fig. 1, p. 6).
The flue gas temperature sensor protects the floor standing boiler and flue
system from high flue gas temperatures by setting back the boiler load
(downward modulation).
9
Regulations 2.15 Opening and closing the front panel of the appliance The
floor standing boiler has a rotary lock. Use the designated tool when opening
and closing the front panel
(ideally a flat-bladed screwdriver). Opening the front panel Turn the locking
screw a quarter turn [1]. Tilt the front cover forwards and remove [2 + 3].
Closing the front panel Insert the locating pins on the front cover into the
centring holes [4] in the frame. Squeeze the front cover shut at the position
of the locking screw.
NOTICE
Risk of system damage due to differing operating conditions! Faults may arise
if the specified operating conditions are disregarded. Where there is serious
disregard for the stated operating conditions, individual components or the
boiler itself may be destroyed. Observe the binding information on the data
plate.
3.1 Notes on installation and operation
Use only genuine spare parts from the manufacturer. The manufacturer can
assume no liability for damage caused by spare parts not supplied by the
manufacturer.
When installing and operating the heating system, observe the following
requirements: · The local building regulations regarding installation
conditions. · The local building regulations regarding the supply and exhaust
air
systems, and the chimney connection. · Latest edition of the IEE Wiring
regulations governing electrical
connection to the mains power supply · Regulations and standards regarding the
safety equipment in water-
filled heating systems. For guidance see the ICOM water treatment guide for
commercial heating systems. · Make sure that the regional approvals required
for the flue system and condensate connection to the public sewage system have
been obtained.
3.2 Regulations In order to ensure installation and operation of the product
in accordance with the regulations, please observe all the applicable national
and regional regulations as well as all technical rules and guidelines. The
document 6720807972 contains information about the applicable regulations. You
can use the document search on our website to display this. You will find the
address of the website on the back of these instructions.
- 4
Fig. 6 Opening the front panel
4 Flue gas routing
A supplement for flue gas routing is included with this product. This document
describes the flue gas accessories, flue gas classifications and corresponding
flue lengths. Install the flue system as described in the supplied
documentation.
0010030538-001
3 Regulations
DANGER Failure to comply with instructions may result in material damage and
personal injury, including danger to life! Comply with all instructions.
10
Condens 7000 WP 6721841195 (2022/01)
5 Preconditions for installation
DANGER Danger to life from explosion! An increased and permanent ammonia
concentration may lead to stress corrosion cracking on brass (e.g.gas valves,
union nuts). As a result, there is a risk of explosion from gas escaping. Do
not use wall mounted gas boilers in rooms where there is an
increased or permanent ammoniac concentration (e.g. livestock stables or
storage room for fertilisers). If contact with ammonia is unavoidable, make
sure that there are no brass parts installed in the system.
CAUTION Personal injury due to lifting incorrectly. Due to the weight and
dimensions of the wall mounted boiler, take
adequate measures to transport the wall mounted boiler safely in the
installation room. The packaged floor standing boiler should ideally be
transported to the installation room on a sack truck or trolley.
NOTICE The appliance may be damaged if lifted incorrectly. Not all parts of
the boiler are suitable for lifting and carrying. To lift the floor standing
boiler correctly, handles are attached to the underside. Use these handles to
move the floor standing boiler [1]. Hold the boiler at the side and base and
not at the basic controller or
flue connection.
1
1
Preconditions for installation
5.1 Installation location
NOTICE
Frost damage! Install the heating system in a frost-free room.
DANGER Risk of fire through flammable materials or liquids. Never store
flammable materials or liquids in the immediate vicinity
of the boiler.
NOTICE
Boiler damage through contaminated combustion air or contaminated air in the
vicinity of the boiler! Never operate the boiler under dusty conditions or
where the
atmosphere is contaminated with corrosive substances. These might be, for
example, paint shops, hairdressing salons and agricultural operations
involving the production of manure. Never operate boilers in locations where
trichloroethene, halogenated hydrocarbons or other corrosive chemical
substances are used or stored. Certain adhesives, solvents, cleaning agents
and paints, for example, contain these substances. Choose or prepare a
suitable installation location.
5.2 Important notices The wall mounted boiler must not be operated in open
heating systems (oxygen permeation). The heating system must then be converted
to a sealed system according to EN12828 or a system separation must be
installed: Mount a separation (a plate heat exchanger for example) between the
floor standing boiler and the heating system.
When plastic pipes are used in the heating system If plastic pipes are used in
the heating system, in an underfloor heating system for example: Use plastic
pipes with oxygen diffusion resistance to DIN 4726/
4729 -or Mount a separation (a plate heat exchanger for example) between the
floor standing boiler and the heating system.
When using a room thermostat/room temperature-dependent controller Do not
mount thermostatic radiator valves in the reference room.
Surface temperature The maximum surface temperature of the appliance is below
85 °C. Therefore no special safety measures are required to protect flammable
materials and fitted furniture. Country-specific regulations must be observed.
Fig. 7 Position of handle recesses
0010034260-002
Condens 7000 WP 6721841195 (2022/01)
11
Installation
5.3 Water quality Unsuitable or contaminated heating and tap water can lead to
faults in the floor standing boiler and can damage the heat exchanger or DHW
supply among other things due to sludge formation, corrosion or calcification.
Please get in touch with the manufacturer if you require additional
information on the water quality. You will find the relevant addresses on the
back of this document. Using the supplied “Water quality operator’s log”
determine the water
volume Vmax: If the amount of fill and top-up water is already greater than
the calculated water volume Vmax: Use the water treatment as specified in the
“Water quality operator’s
log”. If the amount of fill and top-up water is less than the calculated water
volume Vmax: Purge and clean the heating system if required. Only use
untreated potable water. Do not use chemical additives (e.g. inhibitors or
agents that increase
or reduce the pH), apart from as specified in § 5.3.1.
5.3.1 Water conditioning and treatment
NOTICE
Damage to appliance due to sealing agent in the heating water. Addition of
sealing agent to the heating water is not permitted.
Conditioned water is water that has been softened or desalinated and to which no chemicals have been added. Treated water is unconditioned or conditioned water to which chemicals have been added.
The following water conditioning and water treatment measures have been approved for use by Bosch:
Application
Demineralisation
Inhibitor/antifreeze Antifreeze Table 5 Additives
Product name
Demineralisation/ desalination with mixed bed cartridges
Fernox Alphi 11 Noburst AL
Max. concentration [%] In accordance with the supplied “Manual for water
quality”
40
40
For information on concentrations and applications, contact the supplier of the additive.
5.4 Maximum flow temperature
NOTICE
Too much chloride in the heating water can damage the appliance.
If the chloride content in the heating water exceeds 150 ppm, the floor
standing boiler may be damaged if the heating water temperature is higher than
80 °C. If the maximum flow temperature is set higher than 80 °C, the water
treatment must be adapted in order to reduce the chloride content.
If the chloride content is more than 150 ppm, carry out a water treatment as
described in the supplied “Manual for water quality”.
The boiler is supplied with a set maximum flow temperature of 80 °C as standard. Under standard conditions, this maximum boiler temperature
is sufficient to cover the heating load and also guarantee the service life of
the floor standing boiler. A higher maximum flow temperature may however be
required for certain installations. In these cases, the chloride content of
the heating water must be checked and reduced if necessary. With the chloride
content of the heating water. If the chloride content is more than 150 ppm,
perform water
treatment as described in the supplied “Manual for water quality”. Set the
maximum flow temperature to the required value ( § 9.4.2,
p. 26). Contact the manufacturer for more information. You will find the
relevant addresses on the back of this document.
6 Installation
WARNING Risk of explosion Close the gas valve before working on gas-carrying
components. After completing the work, check the tightness of all gas-carrying
components.
6.1 Unpacking the floor standing boiler
The packaging material is fully recyclable. Dispose of the boiler packaging
after installing the floor standing
boiler at a recycling point.
Remove the outer packaging by setting the boiler upright and pulling it up and
off.
Avoid damaging the connections on the boiler at the top and bottom. Cover the
flue outlet adapter of the floor standing boiler during
assembly.
6.2 Checking the gas type Check whether the gas type to be connected to the
appliance
corresponds to the gas type specified on the data plate. ( § 2.11, p. 6 ).
6.3 Setting up the floor standing boiler The floor standing boiler can be
installed in two ways: · Installation on a frame (accessory). · Installation
on the wall. To make full use of the modular design of the system, it is
advisable to install the boiler in combination with the frame.
Installation on the frame (accessory)
WARNING Physical injury due to tipping of the boiler. The frame must be
securely attached to the floor or wall so that the boiler cannot tip over. Use
fixing materials that are suitable for the subsurface or wall and
offer a sufficient hold. Fasten the frame to the floor with the bracket
(included). If drilling in the floor is not permitted fasten the frame to the
wall.
Mount the cross bars [1] to the stands [2]. Secure the cross bars with the
brackets [3] (included). Place the frame at the required location in the
installation room.
12
Condens 7000 WP 6721841195 (2022/01)
Set up the frame so the marking [4] points forwards.
4
Installation
2
1 2
1 3
3
3
3
3
3
3 0010033904-001
Fig. 8 Installing the frame
[1] Cross bar [2] Stand [3] Angle [4] Marking
Fasten the brackets [1] to the frame. Fasten the brackets to the floor [3].
-or Fasten the frame to the wall [2]. As the boiler subsequently needs to be
adjusted, do not fully tighten
the screw.
0010039423-001
Fig. 9 Secure the frame to the wall or floor
Push the floor standing boiler onto the frame. The floor standing boiler is
secured to the frame at the rear. If it has been secured correctly a “click”
will be audible.
Align the floor standing in the frame using the adjustment option. [1]. Fully
tighten the grub screw in the frame.
Condens 7000 WP 6721841195 (2022/01)
1
1
Fig. 10 Align the floor standing boiler on the frame
0010030947-001
13
Installation
Assembly on the wall
NOTICE
If the boiler may be damaged if attached incorrectly.
Use suitable fixing materials for the condition of the masonry and weight of
the floor standing boiler. The fixing materials provided are only suitable for
installation on concrete walls.
Only use fixing materials that are suitable for the construction which will be
supporting the floor standing boiler.
Check whether the wall has sufficient load-bearing capacity based on the
dimensions and weight of the floor standing boiler. ( § 15.2, p. 47).
Mount a fastening structure if required.
Only use fixing materials that are suitable for the structure to which the
floor standing boiler is to be attached. ( Tab. 6).
Wall type Concrete Solid lime sandstone Others
Fixing materials See scope of delivery
Not included: to be decided by the installer.
Minimum load [N] 10001) Per fixing point.
- The load applies for tensile and shear loads.
Table 6 Specification of the fixing materials
Determine the position of the floor standing boiler on the wall. Mark the
boreholes using the enclosed mounting rail [1]. Install the mounting rail on
the wall using a spirit level to make sure it
is level [2 + 3 + 4].
Fig. 11 Installing the mounting rail on a concrete wall Hook the floor standing boiler into the mounting rail.
10011604-001
Align the floor standing boiler using a spirit level and adjusting screw on the rear.
Fig. 12 Aligning the floor standing boiler on the wall
0010030948-001
6.4 Connecting on the heating and gas side
The floor standing boiler can be connected on the heating and gas side in 2
ways: · using a connection set (accessory, § 6.5, p. 14), · without connection
set ( § 6.8, S. 16).
6.5 Mounting the connection set (accessories)
NOTICE
Installation damage due to incorrect excess pressure of the safety valve.
The connection set must be equipped with a safety valve.
Check whether the excess pressure of the safety valve is suitable for the
required operating pressure and the components in the heating system.
Replace the pre-installed safety valve with a safety valve with a suitable
excess pressure (accessory).
The following components have been incorporated into the connection set: · Gas
valve; · Service shut-off valves; · Pressure gauge · Safety valve; · Pump; ·
Fill and drain valve.
These components can be found in the overview drawing ( § 2.11, p. 6).
14
Condens 7000 WP 6721841195 (2022/01)
6.5.1 Installing the gas valve
WARNING If the sealing is not carried out correctly gas may escape. The thread
of the gas connection under the floor standing boiler must not be roughened.
This could cause gas to escape. Comply with the country-specific regulations
and standards in
relation to the sealing agent used.
NOTICE
Boiler damage due to dirt. Pollution in old gas lines, including rust, can
damage the air/gas ratio control valve or block the gas supply. Install a gas
filter in the gas line in accordance with the specifications
if required.
Seal the gas connection [1] using an approved sealing agent. Mount the
coupling (two parts) [2]. Install the gas valve [3]. Connect the gas line
without stress to the gas valve. Install a gas filer in the gas line if
required.
- Fig. 14 Mount the flow/return connection Screw down the bracket with the screws [1]. Fully tighten all rotary joints [2].
Installation
2. 3.
0010041394-001
1 2
2 2
2
3
0010033907-002
Fig. 13 Installing the gas valve [1] Gas connection [2] Two-part coupling [3]
Gas isolator 6.5.2 Mounting the connection set Mount the flow connection with
the flat gasket [1]. Mount the pump with the flat gasket [2]. Mount the return
connection with the flat gasket [3]. Tighten the rotary joints handtight.
1
0010041395-001
Fig. 15 Mount the brackets Connect the flow and return line to the connection
set, making sure
they are free of stress. The minimum diameter of the flow and return line must
be 1½” (Ø 35 mm).
Condens 7000 WP 6721841195 (2022/01)
15
Installation
6.6 Mounting the siphon Fill the boiler siphon with water. Mount the boiler
siphon [1] with gasket [2]. Check whether the neck of the siphon is properly
connected to the
condensation catch pan. Tighten the union nut hand tight [4].
4.
4
3.
1 2
2 2
1
0010033908-003
Fig. 16 Mounting the boiler siphon With pump assembly Mount the tee [1]
between the diaphragm safety valve and the
siphon. Connect the hose [2] from the automatic air vent valve to the tee [1].
Do not insert the hose into the tee by more than 10 cm. Shorten the hose if
required. Install the corrugated hose [3]. Without pump assembly Mount the
corrugated hose [3] directly on the siphon [4]. Connect the hose [2] from the
automatic air vent valve to the waste
water system.
3
Fig. 17 Mounting the air vent valve hose
[1] T-piece [2] Air vent valve hose [3] Corrugated hose [4] Condensate trap
6.7 Connecting the condensate pipe
0010033906-002
NOTICE
If the waste water pipe is blocked, this can damage the boiler.
A blockage in the waste water pipe can prevent the removal of condensate from
the boiler if the condensate drain line is permanently connected to the waste
water pipe.
Make sure that the connection between the condensate pipes of the floor
standing boiler and the waste water pipe connection is unobstructed.
Use a waste water pipe made of plastic material with a diameter of at least Ø
40 mm to remove the condensate.
Install a siphon in the waste water pipe. Install horizontal pipe sections so
they slope towards the downpipe.
The maximum length of the horizontal pipe section in this case is 5 m. Fill
siphon in the waste water pipe.
6.8 Connecting heating pipes (without connection set)
NOTICE
If the operating pressure is too high, this can damage the boiler. Install a
diaphragm safety valve between the floor standing boiler and
the service shut-off valve.
16
Condens 7000 WP 6721841195 (2022/01)
Installation
NOTICE
Damage to appliance due to incorrect connection of safety equipment. When
using service valves, all safety equipment must remain in operation when the
service valves are closed. Mount the connection for the expansion vessel and
safety valve
directly under the boiler and above the service valves. ( Fig. 18, p. 17).
NOTICE
Appliance fault due to insufficient cooling. If the boiler is installed on a
frame, the internal overtemperature protection of the pump may be triggered if
the cooling is insufficient when an On/Off pump was selected. When using
insulating parts, ensure sufficient ventilation by not
mounting the rear panel.
Connect the flow and return pipe without stress to the floor standing boiler.
The diameter of the flow and return pipe must be no less than 1 ½” (Ø 35 mm).
To make maintenance work easier: Install a service valve in the flow and
return pipe ( Fig. 18, p. 17).
6.8.1 Connecting the gas valve Connect the gas valve ( § 6.4, p. 14).
6.8.2 Installing the pump Select the pump using the specifications as the
basis ( Tab. 15.2,
p. 47). Take the required volumetric flow rate into consideration ( Tab.
15.4, p. 49). If a low loss header is not used: Select a pump with a residual
head of at least 200 mbar at the
required volumetric flow rate. Install the pump [6] in the return line [5].
1
5
7
2
46
8
3
3
9
3
3
0010018400-003
Fig. 18 Connection of heating water pipes
[1] Flow line [2] Water pressure relief valve [3] Service valve [4] Gas
isolator [5] Return line [6] Pump [7] Fill and drain valve [8] Expansion
Vessel [9] Dirt trap
6.9 Installing the low loss header If the remaining head is insufficient at
the required volumetric flow rate, a low loss header [1] must be set up.
Check the specifications to find out whether it is necessary to set up a low
loss header ( § 15.4, p. 49).
2
1
34
Condens 7000 WP 6721841195 (2022/01)
Fig. 19 Setup with low loss header
[1] Low-loss header [2] Expansion Vessel [3] Pump [4] Service valve [5]
Differential pressure regulator
5
4
0010018401-003
17
Electrical connection
6.10 Connecting an expansion vessel
For the boiler and the system to function correctly, the right expansion
vessel must be selected. Determine the size and pre-charge pressure of the
expansion vessel
by referring to EN 12828.
Remove the cap from the connection point [1]. Connect the connecting pipework
of the expansion vessel to the
connection point.
7.1 Handling printed circuit boards Printed circuit boards with control
electronics are very sensitive to electrostatic discharge (ESD). To prevent
damage to the components, exercise utmost caution.
CAUTION Damage due to electrostatic charge! Wear an earthed wristband when
handling unenclosed PCBs.
- 0010034327-001
Fig. 20 Connecting an expansion vessel
6.11 Installing the insulation (accessory) Insulating parts are available for the connection set of this floor standing boiler. If the floor standing boiler is placed on the base frame, the insulation consists of several panels. In the case of wall-mounted installation, the insulation consists of 1 piece which is fastened underneath the floor standing boiler. For more information, refer to worcester-bosch.co.uk or you will find
the relevant addresses on the rear of this document.
7 Electrical connection
CAUTION Electric shock. Disconnect the floor standing boiler from the power supply before
working on electrical parts.
NOTICE Electrical short circuit due to incorrect cabling. Only use original cables if they need to be replaced. All 230 VAC connections in the floor standing boiler must be
established using the cable type H05VV-F 3 x 0.75 mm2 or NYM-J 3 x 1.5 mm2. All 24 VAC connections in the floor standing boiler must be established using a 2-wire power cable with 0.4 0.8 mm2 crosssection.
6 720 614 366-24.1I
Fig. 21 Wrist strap The damage is not normally immediately apparent. A PCB may
function perfectly during commissioning and problems often only arise later
on. Charged objects are only a problem if they are in the vicinity of the
electronics. Before starting work, ensure a safe distance of at least 1 m from
foam rubber, protective film and other packaging materials, clothing made of
synthetic fibres (e.g. fleece pullovers) and similar items. An earthed wrist
strap offers good ESD protection when working with electronics. This wrist
strap must be worn when opening the screened metallic bag/packaging or prior
to exposing a fitted PCB. The wrist strap must be worn until the PCB has been
placed inside its screened packaging or has been connected inside the closed
control cabinet. Replaced PCBs that are returned must be handled in this way.
7.2 Opening the top cover The burner control unit and terminal strip for
electrical components are located under the top cover. Open the top cover by
unfastening the retaining screws [1].
1
2.
It must be possible to reach mains plug and therefore also the socket (230 V
AC, 50 Hz) at all times for commissioning of the floor standing boiler. The
socket must be earthed.
When establishing the electrical connection, also refer to the documentation
of the accessory to be connected and the wiring diagram (§ 15.1, p. 46).
18
Fig. 22 Opening the top cover
0010033907-002
Condens 7000 WP 6721841195 (2022/01)
7.3 Overview of plug-in strip
I1
BUS
I3
T1
TW1
T0
BUS
120/230 VAC
PW2
Electrical connection
120/230 VAC
PW1
Fig. 23 Overview of plug-in strip
Symbol
Function
Description
On/Off temperature control (volt free) Connect an On/Off temperature control. Request for heat via volt-free contact, closed = on, open = off.
0010034531-001
Modulation-controlled control unit and Connect modulating temperature controller (EMS bus).
BUS
EMS-BUS
21
External switching contact (volt free). This connection is short-circuited as standard.
If it is necessary to connect several safety components, e.g. a condensate pump and a thermal cut out for the underfloor heating system, they must be connected in series. If a break occurs due to one of the safety components, the heating load to the boiler is interrupted.
Remove short circuit.
Connect safety components (in series). Attention! 230 V components must only
be connected via a relay.
outside temperature sensor
Connect the outside temperature sensor.
Storage cylinder temperature sensor Connect cylinder temperature sensor.
BUS
120/230 VAC
PW2 120/230 VAC
PW1
Temperature sensor of low loss header Connect the temperature sensor of a low loss header. Set the use of the low loss header in the service menu: Settings
Hydraulics > Low-loss header.
Function modules
Connect the Bus cable of the function module. If installed in the boiler,
install the function module as described in the instructions ( §
7.7, p. 21).
Mains voltage
Circulating pump Mains voltage Cylinder primary pump
Connect the 230 V power supply for the function module. -or Connect the 3-way
valve according to the instructions ( § 7.6, p. 21). Attention! The total
power consumption of the connected components must not exceed 725 W. If a DHW
circulation line is used, a sanitary pump can be connected. Connect the 230 V
power supply for the sanitary pump.
Mains plug 230 VAC Connect the mains plug, if not pre-assembled ( § 7.8, p.
21).
Connect the cylinder pump. -or Connect the 3-way valve according to the
instructions ( § 7.6, p. 21).
Fine-wire fuse of the burner control unit There is a replacement fuse under the cover flap on the burner control unit.
Table 7 Plug-in strip symbols
Condens 7000 WP 6721841195 (2022/01)
19
Electrical connection
7.4 Connecting electrical components All cables from electrical components
outside the boiler that are connected to the plug-in strip must be routed to
the inside via the strain relief. Connect the connecting leads of the
components to the plug-in strip
without tension. Route the connecting lead through the strain relief. Position
the cable conduit [1].
Use the right screwdriver for this.
1
0010035234-002
Fig. 24 Positioning the connecting lead and cable conduit 7.5 Connecting the
pump of the pump assembly Open the pump terminal unit.
0010035232-002
Fig. 25 Opening the pump terminal unit
With pump assembly: Connect the 230 V mains cable [1] of the pump to the 3-pin
plug. Connect the PWM signal cable [2] of the pump to the 2-pin plug. Guide
both cables through the strain relief. Connect the pump terminal unit: fold
the pump terminal unit up and
press horizontally until it snaps into place.
Without pump assembly:
When using pump types other than those available from Bosch as accessories,
the PWM signal cannot be used. The PWM connection in the pump terminal unit is
then not used. On/Off operation applies for these pumps.
Connect the 230 V mains cable of the pump to the 3-pin plug [1]. Guide the 230
V mains voltage cable through the strain relief.
20
Condens 7000 WP 6721841195 (2022/01)
Close the pump terminal box: fold the pump terminal box up and press
horizontally until it snaps into place.
12
0010034673-001
Fig. 26 Connecting the pump [1] 230 V cable [2] PWM signal cable 7.6
Connecting the 3-way valve 230 V (accessory)
Electrical connection
7.7 Mounting the function module (accessory)
NOTICE EMC fault due to incorrect cable routing. If bus cables and power
cables are routed in parallel there is a risk of EMC faults occurring. Route
bus cables and power supply cables separately.
1 function module [3] can be installed in the floor standing boiler. Carefully
read the instructions for the function module when carrying
out the installation. Install the BUS cable on the plug [1] according to the
specified cable
routing. Install the 230 V power supply cable on the plug [2] according to the
specified cable routing.
1
BUS
120/230 VAC
2
A 3-way valve can only be connected to the plug-in strip of the floor standing
boiler if the output of the floor standing boiler is 100 kW.
An appropriate accessory 230 V 3-way valve can be connected to the plug-in
strip. Use the plug for the boiler pump for this [B]. Carefully read the
instructions for the 230 V 3-way valve. Connect the neutral wire (N) to the
plug [A]. Connect the phase wire (L), switching neutral wire (N) and earth
wire
to the plug [B].
A
120/230 VAC
PW2
120/230 VAC
PW1
B
3
0010036034-002
Fig. 28 Mounting the function module [1] BUS system connection EMS [2] 230 V
mains voltage cable [3] Function modules 7.8 Fitting the plug (if not
preassembled) Fit the plug to the power cable of the floor standing boiler.
65 43 211
M
Fig. 27 Connection diagram for 230 V 3-way valve [1] Phase cable L, continuous
230 V [2] Phase cable L, discontinuous 230 V [3] Neutral cable N
0010035147-001
1
2
3
Fig. 29 Fitting the plug [1] Neutral conductor N (blue) [2] Protective
conductor (green/yellow) [3] Phase L (brown)
0010018427-001
Condens 7000 WP 6721841195 (2022/01)
21
Commissioning
8 Commissioning
WARNING Escaping gas. After completing the work, check the tightness of all
gas-carrying
components.
CAUTION Flue gas spillage. Check the tightness of all flue gas routing parts
once the work is
complete.
Complete the commissioning report during the commissioning procedure ( § 15.7,
p. 50).
8.1 Commissioning the floor standing boiler
NOTICE
Risk of boiler damage due to unsuitable fill water. Check the chloride content
of the fill water, if the maximum heating
water temperature is set higher than 80 °C ( § 5.4, p. 12). Check whether the
fill water satisfies the water quality requirements
( § 5.3, p. 12).
The boiler starts as soon as the operating pressure exceeds 0.8 bar. If the
operating pressure is lower than 0.2 bar, the appliance no longer goes into
operation.
Open all radiator valves. Check whether the service shut-off valves of the
connection sets are
open. Use an appropriate filling method in line with Water Regulations. (
§ 2.11, p. 6). Fill the heating system to a pressure of 2 bar and close the
filling
valve. Vent the radiators. Fill the heating system again to a pressure of 2
bar. Open the gas cock. Venting the gas line. Operate the appliance. Start up
the floor standing boiler.
8.2 Setting the parameters Different parameters can be set in the settings
menu so the floor standing boiler can be adapted to the heating system. Go
through the parameters in the menu Settings ( § 9.4, p. 26). Adjust the
parameters if required. Make a note of which parameters have been modified in
the
commissioning report ( § 15.7, p. 50).
Setting Maintenance type With a maintenance period of 2 years, normal
operation is considered to be a maximum burner runtime of 4000 hours (every 2
years). During commissioning, the anticipated burner runtime must be estimated
in order to set the right Maintenance type. During the initial inspection or
maintenance the burner runtime can be read out via the service menu and the
burner runtime Maintenance type modified if required. Open the menu
Maintenance > Maintenance type. Based on the operation, estimate whether the
maximum burner
runtime of 4000 hours will be exceeded in 2 years.
If the maximum burner runtime of 4000 hours in 2 years is likely to be
exceeded:
Set Burner run time to 4000 hours.
If the maximum burner runtime is likely to be less than 4000 hours:
Set Boiler run time to 24 months. -or Set Service date: 24 months after
installation date.
Setting Maintenance Burner run
type
time
Standard operation 4000 hours
Boiler run time
24 months
Table 8 Maintenance interval parameters
Service date
Date: 24 months after installation
Setting Min. boiler outp. If the boiler is installed in a positive pressure
cascade system, the minimum load must be increased.
Open the menu Limit values > Min. boiler outp.. Increase the setting Min.
boiler outp. ( table 9).
Appliance type:
Factory [%]
Raised value with positive pressure
cascade
[%]
GC7000WP 50
28
36
GC7000WP 65
20
26
GC7000WP 85
24
28
GC7000WP 100
20
23
Table 9 Setting the Min. boiler outp. with positive pressure cascade systems
22
Condens 7000 WP 6721841195 (2022/01)
8.3 Setting options for air/gas ratio control valve Different air/gas ratio
control valves are used depending on the rating of the floor standing boiler.
The positions of the various test ports and adjusting screws vary accordingly.
Overview of air/gas ratio control valve GC7000WP 50, GC7000WP 65
2 34
1
0010034262-001
Fig. 30 Overview of test ports and adjusting screws 70 kW [1] Adjusting screw
CO2/O2 [2] Gas pre-charge pressure test port [3] Gas/air ratio test port [4]
Gas/air ratio adjusting screw Overview of air/gas ratio control valve GC7000WP
85, GC7000WP 100
2 34
5
1
0010034263-001
Fig. 31 Overview of test ports and adjusting screws 85 kW [1] Adjusting screw
CO2/O2 [2] Gas pre-charge pressure test port [3] Gas/air ratio test port [4]
Gas/air ratio adjusting screw [5] Without function 8.4 Measuring the gas
standing pressure (static) The gas standing pressure must be stable to
guarantee correct operation of the boiler. The measurement is carried out when
the floor standing boiler is switched off.
Commissioning
Switch off the appliance. Remove the front panel. Open the gas standing
pressure test port by turning the adjusting
screw through 2 revolutions ( § 8.3, p. 23). Set the pressure gauge to “0”.
Connect the pressure gauge to the test port. Measure the static gas standing
pressure. Make a note of the value in the commissioning report ( § 15.7,
p. 50). Close the inlet pressure test port.
8.5 Measuring the gas working pressure (dynamic) The gas working pressure must
be stable to guarantee correct operation of the boiler. The measurement is
performed at full load.
As the measurement is taken at the air/gas ratio control valve and not the gas
valve, the permissible gas working pressure may be reduced due to the pressure
drop between the gas valve and air/gas ratio control valve.
Example: GC7000WP 100 to natural gas H, G20. · Permissible gas pre-pressure:
min. 17 mbar max. 25 mbar (
Tab. 24, p. 48). · Pressure drop between gas valve and air/gas ratio control
valve is
2.7 mbar ( Tab. 10).
Permissible limit values on the air/gas ratio control valve:
Min. 17 mbar 2.7 mbar = 14.3 mbar. Max. 25 mbar 2.7 mbar = 22.3 mbar.
Max. pressure drop for each gas type [mbar]
Type
G20
G25 / G25.3
GC7000WP 50
1.5
2.0
GC7000WP 65
2.5
2.8
GC7000WP 85
2.6
3.3
GC7000WP 100
2.7
3.7
Table 10 Pressure drop between gas valve and air/gas ratio control valve
Calculate the permissible minimum and maximum gas pre-pressure. Switch off the
appliance. Remove the front panel. Open the gas inlet pressure test port by
turning the adjusting screw
through 2 revolutions ( § 8.3, S. 23). Set the pressure gauge to”0″. Connect
the pressure gauge to the test port. Make sure the heating system can release
its heat. Operate the appliance. Open the menu Function check > Burner. Start
the Function check by setting the value to 100%. Check whether the measured
value lies within the calculated limit
values.
If the measured value lies outside the calculated limit values, do not
commission the boiler. The cause must be established and the fault rectified.
If this is not possible, shut off the gas supply to the system and contact the
gas supplier.
Make a note of the measured value [mBar] after 1 minute in the commissioning
report ( § 15.7, p. 50).
Deactivate Function check. Close the working pressure test port.
Condens 7000 WP 6721841195 (2022/01)
23
Commissioning
8.6 Measuring of CO2 and CO (full load)
The CO content in the flue gases must be less than 250 ppm (0.025 % by volume)
during combustion without excess air. If the CO content exceeds 250 ppm, this
will be due to pollution of the burner, malfunction of the burner or
recirculation of the flue gases. Switch off the appliance. Remove the plug on
the test point for flue gas [1].
12
0010034264-002
Fig. 32 Remove the plug on the flue outlet
[1] Test point for flue gas [2] Test point for air supply
Make sure that the floor standing boiler can release its heat. Insert the
lance of the flue gas analyser 10 cm into the test point. Operate the
appliance. Open the menu Function check > Burner. Start the Function check by
setting the value to 100%. Measure the CO content. Determine and eliminate the
cause of the potentially high CO content. Make a note of the CO content in the
commissioning report ( §
15.7, p. 50). Measure the CO2 percentage. Check the measured value ( table 11,
p. 24). Only modify the CO2 level if the measurement is outside the specified
range. Make a note of the measured CO2 slevel in the commissioning report
( § 15.7, p. 50). Deactivate Function check. Remove the flue gas analyser. Fit
the plug on the test point for flue gas.
Setting data
Appliance type: Gas type
GC7000WP 50
Natural gas H (G20)
Natural gas L (G25)
Propane L (G31)
CO2 percentage
[%] 9.3 ± 0.3
9.1 ± 0.3
10.0 ± 0.3
Gas/air ratio [Pa] -5 ± 4
Appliance type: Gas type
GC7000WP 65 Natural gas H (G20)
Natural gas L (G25)
Propane L (G31)
GC7000WP 85 Natural gas H (G20)
Natural gas L (G25)
Propane L (G31)
GC7000WP 100 Natural gas H (G20)
Natural gas L (G25)
Propane L (G31)
Table 11 Setting data
CO2 percentage
[%] 9.3 ± 0.3 9.1 ± 0.3 10.0 ± 0.3 9.1 ± 0.3 9.1 ± 0.3 10.0 ± 0.3 9.1 ± 0.3
9.1 ± 0.3 10.0 ± 0.3
Gas/air ratio [Pa] -5 ± 4
-5 ± 4
-5 ± 4
8.7 Measuring the gas/air ratio (minimum load)
Switch off the appliance.
Make sure the heating system can release its heat.
Open the gas/air ratio test port by turning the adjusting screw through 2
revolutions ( § 8.3, p. 23).
Set the pressure gauge to “0”.
Connect the pressure gauge to the test port. Open the menu Function check >
Burner. Start Function check by setting the smallest possible value. Check the
measured value ( table 11, p. 24). Only modify the gas/air ratio if the
measurement is outside the
specified range. The gas/air ratio adjusting screw is underneath the cover.
Make a note of the measured value [Pa] in the commissioning report ( § 15.7,
p. 50).
Deactivate Function check. Close with the gas/air ratio test port.
8.8 Reading off the ionisation current Open the menu Function check > Burner.
Start Function check by setting the smallest possible value. Open the menu
Info > Ionisation current.
Reading off the ionisation current.
The ionisation current must be at least 2 A. If the value is lower, check the
gas/air ratio and the igniter.
Make a note of the value that has been read off [A] in the commissioning
report ( § 15.7, p. 50).
Deactivate Function check.
24
Condens 7000 WP 6721841195 (2022/01)
8.9 Check the (flue) gas tightness
NOTICE
Damage to wall mounted boiler due to short circuit. Cover plugs, cables and
components when using gas leak detection
spray.
Make sure that the floor standing boiler can release its heat. Operate the
appliance. Open the menu Function check > Burner. Start the Function check by
setting the value to 50%. Check all gas-carrying components using an approved
leak detecting
agent or device. Check the tightness and installation/brackets of the flue
system.
Operation
Draw attention to the dangers associated with carbon monoxide (CO) and
recommend the use of CO detectors.
Hand over the technical documents to the operator.
9 Operation
9.1 Control panel overview
9 1
8
2
7
3
0010034659-001
Fig. 33 Inspecting the gas path
Determine and rectify the cause of a possible leak. Deactivate Function check.
8.10 Check the function of the floor standing boiler Freeze the connected
control and check whether the floor standing
boiler starts burning after several minutes to support the boiler operation.
If applicable: open a DHW tap, check the DHW temperature and draw-off
quantity.
8.11 Completion work Mount the front cover. Complete the commissioning report
( § 15.7, p. 50).
8.12 Instructing the operator Familiarise the user with the heating system and
operation of the
floor standing boiler. Point out to the operator that if heating water
frequently needs to be
refilled this is a sign that the system is faulty and/or leaking (ensure
required water quality according to the operator’s log). Inform operator about
the required water quality and point out where the heating water must be
refilled. Inform the operator that he or she must not carry out any
modifications or repairs. Point out the possible consequences (material
damage, personal injury or danger to life) of not carrying out inspection,
cleaning and maintenance correctly, or omitting it altogether.
6
54
0010033251-001
Fig. 34 Control panel
[1] Display [2] and keys [3] Heating water pressure display [4] d key [5] OK key [6] Menu key [7] Hot water key [8] Heating key [9] Burner display
See the operating instructions for a description of the user menus.
9.2 Switching on the device Switch on the appliance at the On/Off switch (
Fig. 2.11, page 6). Set the language the first time the device is turned on.
To scroll through the languages, press the or key. To select the desired
language, press the OK key.
When the display shows Siphon fill. prog., the trap filling program is active.
The condensate trap in the appliance is filled ( Chapter 9.3,
page 26).
Condens 7000 WP 6721841195 (2022/01)
25
Operation
9.3 Siphon filling program The siphon filling program is activated
automatically, manually by the installer on the device or on the controller.
Before starting, fill the condensate siphon ( Page 16). The siphon filling
program is activated in the service menu under > Settings > Special function >
Siphon fill. prog.. While the siphon filling program is active, access to the
Hot water menu, the Heating menu and the service menu is possible. The siphon
filling program is activated automatically in the following cases: · The
device is switched on using the On/Off switch. · The burner was not in use for
at least 28 days. · After conversion from summer to winter mode. The next time
there is a heat demand for heating, the device is held at low thermal output
for 15 minutes. The siphon filling program remains active until the device has
completed 15 minutes of operation with increased min. capacity. During the
siphon filling program, Siphon fill. prog. appears on the display. The siphon
filling program is interrupted when the chimney sweep mode is called up.
9.4 Settings in the service menu Many device functions can be set and checked
in the service menu. It includes: · Info: viewing information · Settings:
general and device-specific settings · Function check: settings for function
checks and start of function
checks · Reset: restoring the factory settings, resetting the maintenance
intervals
9.4.1 Operating the service menu
Opening the service menu Press the DHW key and the Heating key simultaneously
until the
service menu appears.
Closing the service menu Press the DHW key or the Heating key. -or Press the d
key. Navigating through the menu To highlight a menu or a menu item, press the
key or the key. Press the OK key.
The menu or the menu item is displayed. To return to the next higher menu
level, press the d key. Changing the setting values Select the menu item with
the OK key. To select the desired value, press the or the key. Press the OK
key.
The new value is saved.
Exiting the menu item without saving values Press the d key.
The value is not saved.
9.4.2 Service menu
26
Condens 7000 WP 6721841195 (2022/01)
Overview of the service menu
Info
Current status Current fault Fault history Boiler
Max. heat output Flow temp. Set flow temp. Low-loss hdr.tmp Act.
burner mod. Burner output Ionisation current Pump mod. Outside temp.
Burner starts Hours run System pressure Hot water Max. output DHW
flow rate DHW act. temp. Hot water temp. Inlet temp. DHW set temp.
Autom. filling System pressure No. of refills Last refill dur.
Refilling active System Contr.device ver. Progr. unit ver. Code plug
no. Code plug ver. Solar Collector temp. Cyl.temp.bottom Collector
pump Solar fault
Settings
Hydraulics Low-loss header DHW configuration HC1 configuration Pump
config.
Heating Max. heat output Standby time Anticyc. temp. off Anticycle
temp. on
Hot water Max. DHW output DHW circ. pump Cycle circ. pump TD-
Temperature Start TD Stop TD
Condens 7000 WP 6721841195 (2022/01)
Pump Pump ctr. mode Min. output Pump overrun Min. Sys. Pres.
Target Sys. Pres.
Special function Ventilation func. Siphon fill. prog. 3-WV mid. pos.
Autom. filling System Fill Min. Sys. Pres. Target Sys. Pres. Max.
refill time Blocking time Max. refills Reset refilling
Maintenance Maintenance type Without Burner run time Boiler run time
Service date1)
Limit values Max. flow temp. Max. DHW temp. Min. boiler outp.
Heating curve Enable Htg. curve base Htg. curve end Summer mode
Frost prot. Frost temp. limit
Function check
Activate test Burner Ignition Fan Pump Cyl. prim. pump 3-way
valve HC1 pump DHW circ. pump Ionisat.oscill.
Reset
Default setting Service display Fault history
Demo mode
Yes No
- With heating controller
Operation 27
Operation
Menu Info
Meu item Current status Current fault Fault history Boiler
Max. heat output Flow temp. Set flow temp. HEx temperature Low-loss hdr.tmp
Return temp. Heating mod. Act. burner mod. Burner output Ionisation current
Pump mod. Outside temp. HC1 pump Burner starts Hours run System pressure Hot
water Max. output DHW act. temp. Act.DHWtmp.cyl. DHW set temp. System Progr.
unit ver. Contr.device ver. SW sub-ver. Code plug no. Code plug ver.
Table 12 Menu Info
Settings/adjustment range
Remark/restriction Tab. 11.1.2, page 39 Tab. 11.1.2, page 39
Internal appliance temperature
Temperature in low loss header Current return temperature in °C
Current burner modulation Current burner output in kW Current ionisation
current in A
Current outside temperature in °C Own pump installed downstream of low loss
header Number of burner starts since commissioning Run time of the system
since commissioning Current operating pressure in bar
Current water temperature in the cylinder DHW temperature setting value
Software version of the control unit Software version of the control device
Software subversion of the control device Coding plug number Coding plug
version
28
Condens 7000 WP 6721841195 (2022/01)
Settings menu
Operation
The factory settings are highlighted in the following table.
Meu item Hydraulics
Low-loss header
DHW configuration
HC1 configuration Pump config. Heating Max. heat output
Settings/adjustment range
· Off · NTC on device
· NTC on module
· NTC off
· Not installed · 3-way valve installed · Cyl. prim. pump inst. after low loss
hdr. · Cyl. primary pump installed · Not installed · Dedicated pump inst.
after low loss hdr. · Heating pump
· 50 100%
Standby time
Anticyc. temp. off Anticycle temp. on Hot water Max. DHW output DHW circ. pump
Cycle circ. pump
TD-Temperature Start TD Stop TD Pump Pump ctr. mode
· 5 … 10 … 60 min
· 2 … 6 … 15 K
· -15 -6 … 2 K
· 50 100% · Off · On · 1 x 3 minutes/h · 2 x 3 minutes/h · 3 x 3 minutes/h · 4
x 3 minutes/h · 5 x 3 minutes/h · 6 x 3 minutes/h · Permanent · 60 70 … 80 °C
· Start now? · Cancel now?
· Energy saving · Heat demand
Min. output
· 10 … 100 %
Remark/restriction
Connection of temperature sensor on the low loss header · Low loss header not
installed in the system · Low loss header installed, temperature sensor
connected to wall mounted boiler · Low loss header installed, temperature
sensor
connected to heating circuit module · Low loss header installed, but no
temperature sensor
connected
Maximum released heat output [%]. On natural gas devices: Measure the gas
rate. Compare the measurement obtained with the setting
tables ( Chapter 15.6, page 49). Correct deviations. The time interval
specifies the minimum waiting time between switching on the burner and
switching it on again. The difference between the current flow temperature and
the set flow temperature until the burner is switched off. The difference
between the current flow temperature and the set flow temperature until the
burner is switched on.
Maximum approved DHW output [%].
The DHW circulation pump goes into operation 1 … 6 times per hour for 3
minutes, or into continuous operation.
DHW temperature during thermal disinfection. Start thermal disinfection.
Cancel thermal disinfection.
· Save energy: intelligent shutdown of heat pump for heating systems with
weather-compensated controller. The heating pump is only switched on if
required.
· With heat demand: the flow temperature controller switches the heating pump.
If there is heat energy demand, the heating pump starts up with the burner.
Pump output at minimum heat output. Only available if Pump range map is set to
0.
Condens 7000 WP 6721841195 (2022/01)
29
Operation Meu item
Max. output Pump block time Pump overrun Ventilation func.
Siphon fill. prog.
3-WV mid. pos. Min. Sys. Pres. Target Sys. Pres. Maintenance Maintenance type
Limit values Max. flow temp. Max. DHW temp. Min. boiler outp.
Heating curve Enable
Htg. curve base Htg. curve end
30
Settings/adjustment range · 10 … 100 % · 0 … 24 × 10 seconds · 1 2 … 60 min,
24 h · Off · Auto · On · Off (only permitted when maintenance is in
progress) · On, boiler min. · On, heating min.
· No · Yes · 0.6 0.8 bar · 1.0 … 1.3 … 1.7 bar
Remark/restriction
Pump output at maximum heat output. Only available if Pump range map is set to
0.
The internal pump is locked until the external 3-way valve has reached its end
position.
Overrun time of the heating pump: pump overrun begins when heat demand ends.
The venting function can be switched on after maintenance work.
During ventilation, the following appears in the info area of the standard
display Ventilation func.
The siphon filling program is activated in the following cases: · Once the
device is switched on using the On/Off
switch · Once the burner was not in operation for at least
28 days · Once the operating mode is switched from summer to
winter mode · Once the factory settings of the device have been
restored
The next time there is a heat demand for heating, the appliance is held at low
heat output for 15 minutes. The siphon filling program remains active until
the device was in operation with low heat output for 15 minutes.
When the trap filling program is running, the following appears in the info
area of the standard display Siphon fill. prog.
The function ensures that the system is fully drained and that the motor can
be easily removed. The 3-way valve remains at the middle position for approx.
15 minutes.
· Without
· Burner run time: 1000 … 6000 h · Service date1)
· Boiler run time: 1 … 72 months
· 30 … 85 °C
Limits the adjustment range for the flow temperature.
· 35 … 60 … 80 °C · 14 … 50%
Limits the adjustment range for the domestic hot water temperature.
Minimum heat output. Minimum setting value may vary depending on appliance
output.
· Yes · No
· 20 … 90 °C
· 20 … 90 °C
When connecting a weather-compensated control unit, no adjustment at the
device is required. The system control unit optimises this setting. This
service function activates a simple, weather-compensated controller with a
linear heating curve. Depending on the on/off input, the heating is switched
on or off.
This is only displayed if the control unit was activated. This can be used to
set the base point of the heating curve, which corresponds to an outside
temperature of +20 °C.
This is only displayed if the control unit was activated. This can be used to
set the base point of the heating curve, which corresponds to an outside
temperature of 10 °C.
Condens 7000 WP 6721841195 (2022/01)
Meu item Summer mode
Frost prot. Frost temp. limit
Settings/adjustment range · 0 … 16 … 30 °C
· Yes · No · 0 … 5 … 10 °C
- With heating controller
Table 13 Settings menu Menu Function check Meu item Activate test
Burner
Ignition
Settings/adjustment range
· Off …100 %
· On · Off
Fan
Pump Cyl. prim. pump 3-way valve HC1 pump DHW circ. pump Ionisat.oscill. Table
14 Menu Function check Menu Reset Meu item Default setting
Service display Fault history
· On · Off · On · Off · On · Off · Heating · Hot water · On · Off · On · Off ·
On · Off
Settings/adjustment range Restore?
Reset? Delete?
Table 15 Menu Reset Menu Demo mode Menu item Demo mode
Table 16 Menu Demo mode
Settings/adjustment range · Yes · No
Condens 7000 WP 6721841195 (2022/01)
Operation
Remark/restriction This is only displayed if the control unit was activated.
This can be used to set the outside temperature threshold at which the heating
system switches to summer mode.
Temperature value for the system frost protection. This service function is
only available if the frost protection function was activated. If the outside
temperature does not exceed the frost threshold temperature, then the heating
pump in the heating circuit switches on.
Remark/restriction
This service function enables you to test the burner by adjusting the
appliance output. Permanent ignition. Testing the ignition by means of
permanent ignition without gas supply. To prevent damage to the ignition
transformer: leave
the function switched on for a maximum of 2 minutes. Permanent ignition. Fan
running without gas supply or ignition. Permanent pump run (internal or
external pumps).
Permanent pump operation of cylinder primary pump
Permanent position of the 3-way valve.
Permanent HC1 pumpoperation (downstream of low loss header), if HC1 pump is
installed. Permanent DHW circulation pump.
Check the ionisation measurement function at the flame.
Remark/restriction All settings of the heat source, and the control unit if
applicable, are reset to the respective default setting. The system needs to
be re-commissioned following this reset. Resetting the maintenance Reset the
maintenance first. The fault history of the heat generator, and control unit
if applicable, is deleted. If currently a fault is present, it is immediately
entered again.
Remark/restriction To exit Demo mode: switch the device off and back on
at the ON/OFF switch.
31
Inspection and maintenance
9.4.3 Thermal disinfection To prevent hot water from becoming contaminated by
bacteria such as legionella, we recommend thermal disinfection after long
downtimes.
CAUTION Risk of scalding. During thermal disinfection, discharging unmixed hot
water can cause serious scalding. Only use the maximum adjustable hot water
temperature for thermal
disinfection. Inform occupants of the premises of the risk of scalding.
Perform thermal disinfection outside of the normal operating times. Do not
discharge DHW unmixed.
Proper thermal disinfection involves the DHW system including the draw-off
points. Set the thermal disinfection in the hot water program of the heating
controller ( heating controller operating instructions). Close DHW draw-off
points. Set any DHW circulation pump to continuous operation. Wait until the
maximum temperature is reached. Open all DHW draw-off points, from the nearest
to the one furthest
away, and draw off hot water until hot water at a minimum of 70 °C has flown
from all draw-off points for at least 3 minutes. Restore the original
settings.
10 Inspection and maintenance
WARNING Risk of explosion Close the gas valve before working on gas-carrying
components. After completing the work, check the tightness of all gas-carrying
components.
CAUTION Flue gas poisoning Check the tightness of all flue gas routing parts
once the work is
complete.
CAUTION Electric shock Avoid contact with the burner control unit, fan or pump
when
measuring and adjusting the floor standing boiler. These are 230 V parts.
Switch off the floor standing boiler before working on electrical parts.
CAUTION Malfunctioning safety sensors The function of the safety sensors in
the installation room (such as CO, CO2, and gas detectors) must be regularly
checked. Check the function of relevant safety sensors during inspection or
maintenance. You can read about how to perform the check in the instructions
for
the safety sensor. Defects at relevant safety sensors must be rectified
immediately.
10.1 Important notices You will need the following measuring devices and
tools:
· Pressure gauge with a measurement accuracy of 0.01 mbar. · Flue gas analysis
measurement device. · Cleaning brush with plastic bristles.
Only install original spare parts. Replace all loose gaskets when carrying out
the work.
Inspection and maintenance interval To ensure the wall mounted gas condensing
boiler works correctly and safely, the following intervals must be adhered to:
· Inspection: annually, · Maintenance: every 2 years or following a burner
runtime of 4000
hours (depending on which occurs first).
The following tasks must be performed when carrying out an inspection or
maintenance:
General work
Cleaning
Check measurements
§ 10.2 § 10.3 to § 10.8 § 10.9 to § 10.15
Inspection
–
Maintenan ce
Table 17 Work to be carried out
10.2 General work The following work is not described in any further detail in
this document. It must, nevertheless, still be carried out:
Check the general condition of the heating system. Visual inspection and
function check of the heating system. Check the supply air and flue gas
routing for function and safety. Check all gas and water pipes for signs of
corrosion. Replace any corroded pipes. Check the pre-charge pressure of the
expansion vessel. Check the concentration of any antifreeze/additives that may
be used
in the system fill/top-up water annually. If necessary, check installed water
treatment cartridges
(in the backfeed section) to ensure they are functioning correctly and for
wear. During commissioning and the annual inspection, check all regulating,
control and safety equipment for correct function and, where applicable, for
correct settings.
Reading out Hours run The number of Hours run that have elapsed since initial
commissioning is displayed in the menu. The number of Hours run specifies
whether:
· Components need to be replaced as a preventative measure. · The Maintenance
type needs to be modified.
Open the menu Info > Boiler > Hours run. Read out the number of Hours run.
Check based on the value read out whether components need to be
replaced ( § 10.16.1, p. 36). Make a note of the value in the maintenance
protocol ( § 10.17, p.
38). Establish the difference between the value most recently read out
and the previous value from the maintenance protocol. Check the setting
Maintenance type based on this difference and
adjust if required ( § 8.2, p. 22).
32
Condens 7000 WP 6721841195 (2022/01)
Reading out Burner starts The number of Burner starts that have elapsed since
initial commissioning is displayed in the menu. The number of Burner starts
specifies whether:
· Components need to be replaced as a preventative measure.
Open the menu Info > Boiler > Burner starts. Read out the number of Burner
starts. Check based on the value read out whether components need to be
replaced ( § 10.16.1, p. 36). Make a note of the value in the maintenance
protocol ( § 10.17, p.
38).
10.3 Remove the gas-air unit Remove the plug from the fan. Remove the gas hose
between the air/gas ratio control valve venturi
nozzle.
Inspection and maintenance
Open the 4 snap fasteners on the burner cover. Attention! The snap fasteners
are under tension.
0010028689-001
Fig. 37 Open the snap fasteners Remove the gas-air unit together with the
burner cover.
70 kW
Fig. 35 Remove the gas hose 85 kW Remove the air intake pipe from the venturi
nozzle.
0010028685-001
0010031062-001
Fig. 38 Remove the gas-air unit together with the burner cover.
Fig. 36 Removing the air intake pipe
0010029890-001
Condens 7000 WP 6721841195 (2022/01)
33
Inspection and maintenance
10.4 Clean the burner Removing the burner gasket.
Purge the heat exchanger with water [2].
2. 1.
Fig. 39 Removing the burner gasket Removing the burner.
0010035719-001
0010035230-001
Fig. 41 Cleaning the heat exchanger 10.6 Cleaning the siphon Remove the
flexible hose, and possibly the tee, from the siphon. Unscrew the union nut of
the siphon in the floor standing boiler and
completely screw open [1]. Remove siphon [2].
0010035717-001
Fig. 40 Removing the burner Check the burner and gas distributor plate for
pollution and cracking. Clean the burner with compressed air or a soft brush
if necessary.
10.5 Cleaning the heat exchanger
NOTICE Risk of damage to the heat exchanger due to improper cleaning. Do not
use chemical agents to clean the heat exchanger. Only use one brush with
plastic bristles for cleaning.
Cover ignition unit [1]. Remove loose dirt with a vacuum cleaner. Loosen any
other dirt with a brush and remove it with a vacuum
cleaner.
0010040938-001
Fig. 42 Remove the boiler siphon
Flush the siphon. Fill the siphon completely with water. Reattach the siphon.
Check whether the neck of the siphon is properly connected to the
condensation catch pan. Tighten the union nut hand tight.
34
Condens 7000 WP 6721841195 (2022/01)
10.7 Cleaning the condensation catch pan If the siphon is soiled, check and
clean the condensation catch pan as necessary. Open the 2 quick-release
fasteners.
2.
- 0010035238-001
Fig. 43 Open the snap fasteners of the condensation catch pan Remove the condensation catch pan.
0010035239-001
Fig. 44 Remove the condensation catch pan. Clean the condensation catch pan. Insert new gasket in the condensation catch pan. Place the condensation catch pan under the heat exchanger. Push the condensation catch pan so it rests seamlessly against the
exchanger. Close the snap fasteners. Reassemble all parts in reverse order. Start up the floor standing boiler. 10.8 Resetting the Maintenance type Resetting the set Maintenance type starts the new maintenance interval. Open the menu Reset ( table 15, p. 31). Reset the parameter Service display. 10.9 Measuring the gas pressure Measure the gas working pressure ( § 8.5, p. 23).
Inspection and maintenance
Make a note of the value in the maintenance protocol ( § 10.17, p. 38).
10.10 Measuring of CO and CO2 Measure the CO content and the CO2 percentage (
§ 8.6, p. 24). Make a note of the values in the maintenance protocol ( §
10.17,
p. 38).
10.11 Measuring the gas/air ratio Measure the gas/air ratio ( § 8.7, p. 24).
Make a note of the value in the maintenance protocol ( § 10.17, p.
38).
10.12 Measuring the ionisation current Read off the ionisation current on the
display ( § 8.8, p. 24). Make a note of the value in the maintenance protocol
( § 10.17, p.
38). -or If the value is less than 2 A: replace the ignition and flame sense
electrode ( § 10.16.2, p. 36).
10.13 Check the flue gas backflow preventer If a positive pressure cascade
system has been mounted on the floor standing boiler, the backflow preventer
must be checked.
Open the inspection aperture via the backflow preventer. Check the backflow
preventer for wear, damage or pollution and
replace if necessary. Fill the backflow preventer with water if necessary.
Close the inspection aperture of the backflow preventer.
10.14 Check the (flue) gas tightness Check the tightness of all gas-carrying
components ( § 8.9, p.
25). Visually inspect the supply air and flue gas routing and check for
tightness and correct installation/brackets. Check whether the siphon is
filled with water and fill if required ( §
10.6, p. 34).
10.15 Check for correct operation Check the tightness of all couplings. Check
the operating pressure and top up if required.
In doing so, take the water quality into consideration ( § 5.3, p. 12). Check
the settings of the floor standing boiler ( § 9.4.2, p. 26). Complete the
inspection and maintenance protocol ( § 10.17, p. 38). Close the front panel.
Condens 7000 WP 6721841195 (2022/01)
35
Inspection and maintenance
10.16 Replacing components
10.16.1 Replacement interval for components
The following components must be replaced after expiry of the specified
service life.
Replace according to specification, depending on what occurs first.
Service life
Burner Burner starts runtime
Component
[Year] [Hours] [Number]
Gaskets and O-rings Remove gaskets and always replace O-rings.
Ignition and flame sense electrode
2
4000
25,000
Burner gasket
2
4000
—
Gasket of condensate
2
4000
—
catch pan
Air/gas ratio control
10
—
500,000
valve
Gas hose
10
20,000
–1)
- When replacing the air/gas ratio control valve it is advisable also to replace the gas hose.
Table 18 Replacement interval for each component
Document replacement of components in the maintenance protocol ( § 15.7, p. 50).
10.16.2 Inserting the igniter
NOTICE
Damage to the appliance by applying an excessively high torque when tightening
the screws.
The threaded bolts of the ignition unit are mounted in an aluminium heat
exchanger. Using a graphite seal ensures tightness when tightening the
threaded bolts hand-tight (using hand tools). Tighten both threaded bolts of
the igniter (3 Nm).
Take the replacement interval of the air/gas ratio control valve into account.
Replace the igniter, depending on the service life ( Tab. 18, p.
36).
Switch off the appliance. Undo both threaded bolts [1] of the igniter.
Remove igniter [3] and seal [2].
3 Nm 1
3 2
0010034708-002
Fig. 45 Inserting the igniter Detach connections from the igniter. Clean the
contact surface on the heat exchanger. Position the new seal and igniter.
Tighten both threaded bolts of the igniter (3 Nm). Mount the plug of the
igniter. Start up the floor standing boiler. Check the flue gas tightness of
the removed parts. Carry out a check by measuring the ionisation current ( §
8.8, p.
24). 10.16.3 Replacing the flue gas temperature sensor The flue gas
temperature sensor is equipped with a bayonet connection. Switch off the
appliance. Turn the flue gas temperature sensor anticlockwise by a quarter
turn. Take the flue gas temperature sensor out of the flue pipe. Detach the
plug from the flue gas temperature sensor. Fit the new O-ring on the new flue
gas temperature sensor before
inserting it. Connect the plug at the new sensor. Insert the flue gas
temperature sensor with the cam [1] pointing to
the right in the flue pipe. Turn the flue gas temperature sensor clockwise by
a quarter turn.
36
Condens 7000 WP 6721841195 (2022/01)
Operate the appliance.
Inspection and maintenance
Mount the burner control unit again by following the above steps in reverse
order.
Screw down the bracket of the burner control unit. Close and secure the top
panel. Operate the appliance. 10.16.5 Replacing the air/gas ratio control
valve
1
Fig. 46 Replacing the flue gas temperature sensor 10.16.4 Replacing the coding plug
0010036539-001
NOTICE
Damage due to electrostatic charge Printed circuit boards in electronic
components are susceptible to electrostatic charge (ESD).
Wear an earthed wrist strap when working on electronic components ( § 7.1, p.
18).
Switch off the appliance. Open the top appliance cover ( § 7.2, p. 18). Detach
the bracket of the burner control unit [1]. Push the burner control unit to
the left [2]. Lift the front of the burner control unit so the coding plug is
easily
accessible [3]. Remove the coding plug [4]. Attach new coding plug.
Take the replacement interval of the air/gas ratio control valve into account.
If the air/gas ratio control valve is defective or depending on the service
life, replace it ( table 18, page 36).
Switch off the appliance. Close gas isolator. Follow the replacement
instructions provided when replacing the air/
gas ratio control valve. Open the gas cock. Operate the appliance. Check the
tightness of all gas-carrying components.
Fig. 47 Replacing the coding plug
0010035231-001
Condens 7000 WP 6721841195 (2022/01)
37
Inspection and maintenance
10.17 Inspection and maintenance protocol (checklist) Date
1
Call up the last fault saved in the service menu.
2
Call up the burner starts in the service
menu.
3
Call up the operating hours in the service
menu.
4
Inspect the flue system visually to make sure it has been
installed correctly. If there are any noticeable problems,
ensure tightness and mechanical stability.
5
Check the gas supply pressure.
mbar
6
Check the gas/air ratio.
Pa
7
Check CO content.
ppm
8
Check CO2 content.
%
9
Check tightness on the gas and water side.
10 Check the electrodes.
11 Check the burner.
12 Check the heating block.
13 Check ionisation current.
A
14 Clean dirt trap.
15 Check non-return valve.
16 Check the pre-charge pressure of the
bar
expansion vessel for the static head of the
heating system.
17 Check the heating system pressure.
bar
18 Check the sacrificial anode of the cylinder. mA
19 Check the electrical wiring for damage.
20 Check settings of the heating control.
21
Reset maintenance.
Table 19 Inspection and maintenance record
38
Condens 7000 WP 6721841195 (2022/01)
11 Troubleshooting
11.1 Operating and fault displays
11.1.1 General information · Fault code: indicates which fault is present. ·
Fault category: indicates what kind of fault is present and its effects.
Fault category O (operating code) Operating codes indicate the operating
conditions in normal operation.
Fault category B (blocking faults) Blocking faults result in the heating
system being shut down temporarily. The heating system restarts automatically
as soon as the blocking fault is removed.
11.1.2 Fault code table
Fault text on the display, description Remedy
Troubleshooting
Fault category V (locking faults) Locking faults result in the heating system
being shut down, and the system can only be restarted after a reset. Press the
and keys, until Reset is displayed.
The appliance resumes operation. If a fault persists: Rectify the fault
according to 10.1.2 Fault code table
Fault category W (service displays) Service displays indicate that a
maintenance or repair has to be carried out. The device is still in operation.
If the service display has been caused by a defect, under certain
circumstances, it may continue running with restricted functions.
Fault code Fault category
200 O 201 O 202 O 203 O 204 O 208 O 214 V 224 V
227 V
228 V
Boiler in heating mode Boiler in hot water mode Boiler in anti-cycle mode
Boiler in standby, no heat energy demand Current prim. water temp. higher than
set val. Chimney sweep demand Fan shut down during safety time Maximal flue
gas thermostat or heat exchanger maximal thermostat has activated
No flame signal after ignition
Flame signal without flame present
1. Check the plug on the fan. 2. Check the connecting lead to the fan.
Heating circuit:
1. Check that the heating water is circulating correctly. 2. Open the closed
valve in the heating circuit. 3. Top up water until the preset pressure is
reached. 4. Connect the plug to the heating block temperature limiter
correctly. 5. Check heating block temperature limiter, replace if required.
Potable water circuit:
Check that the potable water in the cylinder circuit is circulating correctly.
- Open the main shut-off valve. 2. Open the device shut-off valve. 3. Interrupt the power supply of the appliance and check the gas line. 4. Check the supply pressure of the gas line. 5. Check that the burner is working correctly, adjust burner if necessary. 6. Check CO2 content of combustion air, adjust if necessary. 7. Establish protective conductor connection (PE) in the control device. 8. Carry out function check for ignition. 9. Carry out function check for ionisation. 10.Connect the plug for the ionisation and ignition sections correctly. 11.Connect the plug for the air/gas ratio control valve correctly. 12.Check condensate pipes. 13. Check flue gas side of heat exchanger for pollution. 14.Check flame sense electrode, replace if necessary. 15.Check ignition electrode, replace if necessary. 16.Check ignition electrode connecting lead, replace if necessary. 17.Check flame sense electrode connecting lead, replace if necessary. 18.Check air/gas ratio control valve, replace if necessary. 19.Check control device/burner control unit, replace if necessary. 1. Check ionisation cable, replace if necessary. 2. Check electrode set, replace if necessary. 3. Replace the control device.
Condens 7000 WP 6721841195 (2022/01)
39
Troubleshooting Fault text on the display, description Remedy
Fault code Fault category
229 B
232 B
233 V 234 V 235 V 237 V 238 V 242 – V 263 265 O 268 O 269 V 273 B 281 B 306 V
316 V 317 V 318 V
Flame failed during burner operation
1. Open the main shut-off valve.
2. Open the device shut-off valve.
3. Shut down the device and check the gas line.
4. Signal evaluation on printed circuit board defective.
5. Replace flame sense electrode.
6. Establish protective conductor connection (PE) in the control device.
7. Replace ignition cable.
8. Replace the connecting lead to the flame sense electrode.
9. Replace air/gas ratio control valve.
10.Set the burner correctly or replace the burner nozzles.
11.Set the burner at minimum rated load.
12.Convert the flue system.
13.The interconnected combustion air supply is too low or the ventilation opening is too small.
14. Clean the heating block on the flue gas side.
15.Replace control device/burner control unit.
Boiler locked by external switching contact 1. Connect the plug for the external switching contact.
2. Install jumper/check condensate pump according to manufacturer’s specifications.
3. Adapt switching point of the external temperature switch to the system.
4. Replace connecting lead to the external temperature switch.
5. Replace external temperature switch.
Boiler identification module or device electronics faulty
1. Install boiler identification module/coding plug. 2. Connect plug to boiler identification module/coding plug.
3. Replace boiler identification module/coding plug (Bosch contact customer service).
Gas valve electrical fault
1. Replace connecting lead and reset once replacement is complete.
2. Replace air/gas ratio control valve and reset once replacement is complete.
Conflicting versions of boiler electr. and 1. Check boiler identification module/coding plug.
boiler identification
2. Install valid combination of control device/burner control unit.
System fault
1. Replace boiler identification module/coding plug.
2. Replace control device/burner control unit.
Boiler electronics faulty
Replace control device.
System fault boiler electronics / basic controller
1. Remedy contact problem. 2. If necessary, replace control device or boiler
identification module/coding plug (Bosch
contact customer service).
Heat demand lower than energy supplied
Component test activated
Flame monitoring
Replace control device/burner control unit.
Operation interrupted following 24 hours of The fan and burner start automatically after the safety check. continuous operation
Pump stuck or running in air
1. Check whether the pump is blocked, unblock or replace if necessary.
2. Ensure that the heating water can circulate correctly.
3. Vent the pump.
Flame signal after closing the fuel supply 1. Replace the air/gas ratio control valve.
2. Replace the ionisation cable.
3. Replace the control device/burner control unit.
Flue gas temp. too high during sensor test 1. Replace flue gas temperature sensor.
2. Replace the connecting lead to the flue gas temperature sensor.
3. Replace the control device/burner control unit.
Short-circuit at flue gas temp. sensor
1. Replace flue gas temperature sensor.
2. Replace the connecting lead to the flue gas temperature sensor.
3. Replace the control device/burner control unit.
Flue gas temperature sensor interrupted 1. Connect the plug to the flue gas temperature sensor.
2. Check the connecting lead to the flue gas temperature sensor.
3. Replace flue gas temperature sensor.
4. Replace the control device/burner control unit.
40
Condens 7000 WP 6721841195 (2022/01)
Fault code Fault category
Fault text on the display, description Remedy
Troubleshooting
349 B
357 O 358 O 360 V 362 V 363 V 811 A
815 W 1010 O 1013 W 1017 W 1018 W 1019 W 1022 W
1023 1025 W
1037 W
1065 W
Difference between flow and return temperature too high
1. Open the shut-off valves. 2. If the water pressure is too low, top up with water and vent the system.
3. Open a thermostat valve.
4. Replace flow or return sensor if required.
5. Replace the pump if required.
Ventilation program
Anti-seizing functn. active
System fault boiler electronics / basic controller
1. Install boiler identification module/coding plug. 2. Connect plug to boiler identification module/coding plug.
3. Replace boiler identification module/coding plug (Bosch contact customer service).
Boiler identification module or boiler electronics faulty
Replace boiler identification module/coding plug (Bosch contact customer service).
System fault boiler electronics / basic controller
Replace control device/burner control unit.
Hot water heating: thermal disinfection failed
1. If water is being drawn constantly, take action to stop this. 2. Position the DHW temperature sensor correctly.
3. Check that there is contact between the DHW cylinder temperature sensor and the cylinder.
4. Vent the cylinder circuit.
5. Set DHW heating to “priority”.
6. Check plate heat exchanger for calcification.
7. Check sizing of DHW circulation line and heat loss.
Low loss header temp. sensor faulty
1. Check hydraulic configuration, correct if necessary.
2. Check sensor for breaks or short circuits, replace if necessary.
No communication via EMS BUS connection 1. Rectify wiring fault and switch the control unit off and on again.
2. Repair the BUS cable or replace it.
3. Replace faulty EMS-BUS node.
Max. combustion point reached
1. Carry out maintenance.
2. Reset service display.
System pressure too low
1. Top up water and vent the system.
2. Check the pressure sensor, replace if necessary.
Maintenance interval expired
1. Carry out maintenance.
2. Reset service display.
Incorrect pump type detected
1. Check pump cabling.
2. Check that the correct heating pump type is in the appliance, replace if necessary.
Cylinder temp. sensor faulty or contact problems
1. Connect the plug to the temperature sensor correctly. 2. Connect the plug to the control device correctly.
3. Check the temperature sensor, replace if necessary.
4. Check temperature sensor connecting lead, replace if necessary.
Maximum run time including standby time 1. Carry out maintenance.
reached
2. Reset service display.
Return temp. sensor is faulty
1. Connect the plug to the return temperature sensor correctly.
2. Replace return temperature sensor.
3. Replace connecting lead to return temperature sensor.
4. Replace control device.
Outside temp. sensor faulty – heating back- 1. If an outside temperature sensor is not desired. Select the room temperature-
up operation active
dependent configuration in the control device.
2. If there is no continuity, rectify the fault.
3. Clean corroded terminals in the outside sensor housing.
4. If values do not match, replace the sensor.
5. If the sensor values matched, but the voltage values do not match, replace the control unit.
System pressure sensor faulty or not connected
1. Connect the plug to the pressure sensor correctly. 2. Check pressure sensor connecting lead, replace if necessary.
3. Check the pressure sensor, replace if necessary.
Condens 7000 WP 6721841195 (2022/01)
41
Troubleshooting Fault text on the display, description Remedy
Fault code Fault category
1068 W
1070 1071 1072 1074 1075 W 1076 W 2085 V 2908 V 2910 V 2914 – V 2916 2920 V
2923- V 2926 2927 B
2928 V 2931 V 2940 V
Outside temp. sensor or lambda probe faulty.
1. Connect the plug to the temperature sensor correctly. 2. Connect the plug to the control device correctly.
3. Attach the temperature sensor correctly.
4. Check the temperature sensor, replace if necessary.
5. Check temperature sensor connecting lead, replace if necessary.
Maintenance is due on <dd.mm.yyyy>
please call your service engineer
Maintenance is now due please call your service engineer
Maintenance is overdue please call your service engineer
No signal from flow temperature sensor
Heat exchanger temp sensor short circuit 1. Connect the plug to the temperature sensor correctly.
2. Check the temperature sensor, replace if necessary.
3. Check temperature sensor connecting lead, replace if necessary.
Heat exchanger temp sensor disconnected 1. Connect the plug to the temperature sensor correctly.
2. Check the temperature sensor, replace if necessary.
3. Check temperature sensor connecting lead, replace if necessary.
Internal fault
1. Unlock.
2. Disconnect power from the system for 30 seconds.
3. Replace the burner control unit.
System fault boiler electronics / basic controller
If the fault persists following a reset, the burner control unit is faulty and must be replaced.
Fault in flue system
1. Install the flue system.
2. Remove any deposits from the flue system.
Boiler electr. system fault
If the fault persists following a reset, the control device is faulty and must be replaced.
Fault in flame monitoring Boiler electr. system fault No flame detected after
ignition
Internal fault System fault boiler electronics / basic controller System fault
burner control unit
Check control device, replace if necessary. 1. Check air/gas ratio control
valve cabling. 2. Check air/gas ratio control valve.
If the fault persists following a reset, the control device or the air/gas
ratio control valve is faulty and must be replaced. 1. Open the main shut-off
valve. 2. Open the device shut-off valve. 3. Interrupt the power supply of the
appliance and check the gas line. 4. Carry out function check for ignition. 5.
Carry out function check for ionisation. 6. Connect the plug for the
ionisation and ignition sections correctly. 7. Establish protective conductor
connection (PE) in the control device. 8. Check flame sense electrode, replace
if necessary. 9. Check ignition electrode, replace if necessary. 10.Check
ignition electrode connecting lead, replace if necessary. 11.Replace the
connecting lead to the flame sense electrode. 12.Set the burner
correctly/replace the burner nozzles. 13.Set the burner at minimum rated load.
14.Check air/gas ratio control valve, replace if necessary. 15.Check the flue
system and repair if necessary. 16.The interconnected room air supply is too
small or the size of the ventilation opening
is too small. 17.Clean the heating block on the flue gas side. 18.Check
control device/burner control unit, replace if necessary. 1. Perform reset. 2.
Replace control device/burner control unit. 1. Perform reset. 2. Replace
control device/burner control unit. 1. Perform reset. 2. Replace control
device/burner control unit.
42
Condens 7000 WP 6721841195 (2022/01)
Fault code Fault category
Fault text on the display, description Remedy
Troubleshooting
2946 V 2948 B 2949 B 2950 B 2951 V
2952 V 2955 B
2956 O 2957 V 2961 V 2962 2963 B
2964 2965 B
Incorrect code plug detected No flame signal with low output
No flame signal with high output
Replace boiler identification module/coding plug (Bosch contact customer
service).
Burner starts automatically after purging. If this fault occurs frequently,
check CO2 setting. The burner is automatically restarted following purging.
1. Check burner gaskets, replace if required.
2. Reduce output.
No flame signal following starting procedure Burner starts automatically after purging. Set gas/air ratio correctly.
Loss of flame too many times
1. Open the main shut-off valve.
2. Open the device shut-off valve.
3. Interrupt the power supply of the appliance and check the gas line.
4. Carry out function check for ionisation.
5. Connect the plug for the ionisation and ignition sections correctly.
6. Establish protective conductor connection (PE) in the control device.
7. Check flame sense electrode, replace if necessary.
8. Check ignition electrode, replace if necessary.
9. Check ignition electrode connecting lead, replace if necessary.
10.Check flame sense electrode connecting lead, replace if necessary.
11.Set the burner correctly/replace the burner nozzles.
12.Set the burner at minimum rated load.
13.Check air/gas ratio control valve, replace if necessary.
14.Check the flue system and repair if necessary.
15.The interconnected room air supply is too small or the size of the ventilation opening is too small.
16.Clean the heating block on the flue gas side.
17.Check control device/burner control unit, replace if necessary.
Internal fault when testing the ionisation 1. Perform reset.
signal
2. Replace control device/burner control unit.
Boiler does not support the parameters set Check hydraulic settings, change if necessary.
for the hydraulic configuration
· Low-loss header
· Internal DHW circuit (cylinder charging circuit)
· Heating circuit 1
· Heating pump in appliance
Hydraulic configuration at the boiler
activated
Boiler electr. system fault
1. Reset control device / burner control unit.
2. Reconnect electrical connections at control device / burner control unit correctly.
3. Replace the control device/burner control unit.
No fan signal available
1. Check fan and connecting lead.
2. Check mains voltage.
The heat exchanger sensor or both supply and heat exchanger sensors are defect
Flow rate in heat exchanger too low Flow temperature too high
1. Connect the plug to the temperature sensor correctly. 2. Connect the plug to the control device correctly. 3. Attach the temperature sensor correctly. 4. Check the temperature sensor, replace if necessary. 5. Check temperature sensor connecting lead, replace if necessary. 1. Ensure that the heating circulation is working correctly. 2. Check pump setting, adjust to match heating system if necessary. 3. Connect the plug to the temperature sensor correctly. 4. Connect the plug to the control device correctly. 5. Attach the temperature sensor correctly. 6. Check the temperature sensor, replace if necessary. 7. Check temperature sensor connecting lead, replace if necessary.
Condens 7000 WP 6721841195 (2022/01)
43
Troubleshooting Fault text on the display, description Remedy
Fault code Fault category
2966 B
Flow temperature rise in heat exchanger too 1. Ensure that the heating circulation is working correctly.
rapid
2. Check pump setting, adjust to match heating system if necessary.
3. Connect the plug to the temperature sensor correctly.
4. Connect the plug to the control device correctly.
5. Attach the temperature sensor correctly.
6. Check the temperature sensor, replace if necessary.
7. Check temperature sensor connecting lead, replace if necessary.
2967
The temperature difference between supply temperature sensor and temperature sensor at heat exchanger is too large
2968
Refilling system pressure
2970
Pressure drop in heating system too rapid
2971 B System pressure too low
1. Vent the heating system.
2. Check the heating system for tightness.
3. Top up water until the target pressure is reached.
4. Check the pressure sensor, replace if necessary.
5. Check the pressure sensor cable, replace if necessary.
2972
Mains voltage too low
1. Establish supply voltage of at least 196 VAC.
2. Replace burner control unit.
3071
No communication with remote control 1. Check configuration.
2. Check cabling.
Table 20 Indicators and fault displays
11.1.3 Faults that are not displayed
Device faults Combustion noises too loud, rumbling noises
Flow noises Heat-up takes too long. Flue gas values incorrect, CO content too
high.
Violent ignition, poor ignition.
No function, the display remains dark. Table 21 Faults that are not shown on
the display
Remedy Check the gas type. Check the gas supply pressure. Check the flue
system, clean or repair as necessary. Check the gas/air ratio. Check the
air/gas ratio control valve, replace if required.
Set the pump rate or pump characteristic map correctly and match to the
maximum output.
Set the pump rate or pump characteristic map correctly and match to the
maximum output.
Check the gas type. Check the gas supply pressure. Check the flue system,
clean or repair as necessary. Check the gas/air ratio. Check the air/gas ratio
control valve, replace if required.
Check the ignition transformer with service function t01 for misfiring,
replace if required.
Check the gas type. Check the gas supply pressure. Check the power supply.
Check the electrodes with cable, replace if required. Check the flue system,
clean or repair as necessary. Check the gas/air ratio. For natural gas: check
the external gas flow monitor, replace if required. Check the burner, replace
if required. Check the air/gas ratio control valve, replace if required.
Check the electrical wiring for damage. Replace defective cables. Check the
fuse, replace if required.
Fault display: System pressure too low
If the system pressure in the heating system falls below the minimum pressure
that has been set, the display shows the message LoPr => L0.X
bar. The system pressure is too low. Fill the heating system.
44
Condens 7000 WP 6721841195 (2022/01)
If the system pressure in the heating system drops below 0.3 bar, the display
shows the message LoPr alternating with the operating pressure. The heating
system is then blocked. Fill the heating system.
12 Shutdown
12.1 Standard decommissioning Switch off the floor standing boiler via the
on/off switch ( § 2.11,
p. 6). Close gas isolator. Close the service valves.
12.2 Decommissioning when there is a risk of frost If the floor standing
boiler remains switched off. Set the pump overrun time to 24 hours ( § , p.
29). Make sure that a sufficient flow rate is possible at all radiators.
If the floor standing boiler is switched off: Switch off the floor standing
boiler via the on/off switch ( § 2.11,
p. 6). Drain the entire heating system. If installed, drain the entire potable
water system.
13 Environmental protection and disposal
Environmental protection is a fundamental corporate strategy of the Bosch
Group. The quality of our products, their economy and environmental safety are
all of equal importance to us and all environmental protection legislation and
regulations are strictly observed. We use the best possible technology and
materials for protecting the environment taking account of economic
considerations.
Packaging Where packaging is concerned, we participate in country-specific
recycling processes that ensure optimum recycling. All of our packaging
materials are environmentally compatible and can be recycled.
Used appliances Used appliances contain valuable materials that can be
recycled. The various assemblies can be easily dismantled. Synthetic materials
are marked accordingly. Assemblies can therefore be sorted by composition and
passed on for recycling or disposal.
Old electrical and electronic appliances This symbol means that the product
must not be disposed of with other waste, and instead must be taken to the
waste collection points for treatment, collection, recycling and disposal.
The symbol is valid in countries where waste electrical and electronic
equipment regulations apply, e.g. “European Directive 2012/ 19/EC on old
electronic and electrical appliances”. These regulations define the framework
for the return and recycling of old electronic appliances that apply in each
country.
As electronic devices may contain hazardous substances, it needs to be
recycled responsibly in order to minimize any potential harm to the
environment and human health. Furthermore, recycling of electronic scrap helps
preserve natural resources.
For additional information on the environmentally compatible disposal of old
electrical and electronic appliances, please contact the relevant local
authorities, your household waste disposal service or the retailer where you
purchased the product.
You can find more information here: www.weee.bosch-thermotechnology.com/
Shutdown
14 Data Protection Notice
We, Bosch Thermotechnology Ltd., Cotswold Way, Warndon, Worcester WR4 9SW,
United Kingdom process product and installation information, technical and
connection data, communication data, product registration and client history
data to provide product functionality (art. 6 (1) sentence 1 (b) GDPR), to
fulfil our duty of product surveillance and for product safety and security
reasons (art. 6 (1) sentence 1 (f) GDPR), to safeguard our rights in
connection with warranty and product registration questions (art. 6 (1)
sentence 1 (f) GDPR) and to analyze the distribution of our products and to
provide individualized information and offers related to the product (art. 6
(1) sentence 1 (f) GDPR). To provide services such as sales and marketing
services, contract management, payment handling, programming, data hosting and
hotline services we can commission and transfer data to external service
providers and/or Bosch affiliated enterprises. In some cases, but only if
appropriate data protection is ensured, personal data might be transferred to
recipients located outside of the European Economic Area. Further information
are provided on request. You can contact our Data Protection Officer under:
Data Protection Officer, Information Security and Privacy (C/ISP), Robert
Bosch GmbH, Postfach 30 02 20, 70442 Stuttgart, GERMANY.
You have the right to object, on grounds relating to your particular situation
or where personal data are processed for direct marketing purposes, at any
time to processing of your personal data which is based on art. 6 (1) sentence
1 (f) GDPR. To exercise your rights, please contact us via
privacy.ttgb@bosch.com To find further information, please follow the QR-Code.
Condens 7000 WP 6721841195 (2022/01)
45
Technical information and reports
15 Technical information and reports
15.1 Wiring Diagram
2
3 45
P
C13 C12 C11 C7 C6 C5 C4 C3 C2 C1
1
HMI
A8 A7 A6 A5 A4 A3 A2 A1
6 7 8 9 10 11
D17 D14 D16 D14 D13
PE D11 D4 D14 D1 D2
12
PE 13 14
PE
2(N) 1(L)
E7 E6 E5 P1 P2 E2 E1
PE
NL
PE
F6 F5
A B 1 8 8
1 17
C
1 17
D
1
7
E
16
F
1
27
5678 1234 R4 R3 R2 R1
R1 4
G HJ K
L M NP
Q
1
8
1
41
41
61
41
61
41
5
1
4
J4 J3 J2 J1 K2 K1 K6 K5
J
L3 L4 L2 L1
J1 J2
12 3 4 5 6 7 8
I1
BUS
I3
T1
9 10 11 12 13 14 15 16
TW1
T0
BUS
P
P1 P2 M3 M4
PE
PE
PM
P4 P5 M1M2
PE
PE
Q1Q2Q3Q4
120/230 VAC
PW2
120/230 VAC
PW1
1234
26 25 24 23
22 21 20
Fig. 48 Wiring Diagram
[1] Control panel, HMI 700 [2] PWM signal, pump [3] Pressure sensor [4] Return
temperature sensor [5] Flue gas temperature sensor [6] Safety temperature
sensor [7] flow temperature sensor [8] High limit safety cut-out STB, heat
exchanger [9] Maximum temperature limiter STB [10] Monitoring electrode [11]
Air/gas ratio control valve [12] Fan [13] Ignition and flame sense electrode
[14] Boiler circulation pump 230Vac [15] On/off switch [16] Cylinder primary
pump 230VAC
46
19 18
16
15
17
0010034254-002
[17] Mains plug 230VAC [18] DHW circulation pump 230VAC [19] Mains voltage
230VAC [20] EMS-bus
[21] Temperature sensor of low loss header
[22] Storage cylinder temperature sensor
[23] Outdoor ambient temperature sensor
[24] External switching contact, volt free
[25] EMS-bus
[26] Volt-free contact
[27] Coding plug
Condens 7000 WP 6721841195 (2022/01)
Technical information and reports
15.2 Technical Specifications
Condens 7000 WP GC7000WP
General information Rated heat output (50/30 °C) [Pn cond] Rated heat output
(80/60 °C) [Pn] Rated thermal load G20, G25, G25.3 (UW) [Qn (Hi)] Rated
thermal load G31 (UW) [Qn (Hi)] Efficiency (37/30 °C) partial load 30% in
accordance with EN 15502 Efficiency (80/60 °C) full load Standby loss in
accordance with EN 15502. Standard efficiency of heating curve (75/60 °C)
Standard efficiency of heating curve (40/30 °C) Pump overrun IP classification
[IP rating] Appliance class in accordance with EN 15502. Product ID no.
Temperature classification in accordance with EN 14471. Appliance fuse Mains
voltage, frequency [U] Power input (without pump),
standby / partial load / full load Maximum possible installation altitude of
boiler Permissible ambient temperature Maximum flow temperature [Tmax] Maximum
permissible water pressure [PMS] Maximum condensate accumulation rate
Connections Flue gas connection/concentric air supply Heating flow/return pipe
(wall mounted gas condensing boiler) Gas connection (wall mounted gas
condensing boiler) Condensate drain (flexible drain hose) Emission values in
accordance with EN 13384 CO2 content with natural gas G20, partial load/full
load CO2 content with natural gas G25, partial load/full load CO2 content with
natural gas G25.3, partial load/full load CO2 content with propane G31,
partial load/full load O2 content with natural gas G25.3, partial load/full
load O2 content with propane G31, partial load/full load CO output G20 at full
load (n = 1) Standard emission factor (EN15502) CO Standard emission factor
(EN15502) NOx G20 (average) NOx class Flue gas mass flow rate at min./max.
rated heat output Flue gas temperature at 80/60 °C, partial load/full load
Flue gas temperature at 50/30 °C, partial load/full load Differential pressure
gas/air (with partial load) Flue gas class for LAS (Germany only) Fan
discharge pressure Residual head of fan (pmax) DN110/185, B23p, partial
load/full load DN110/185, with overpressure flap, B23p, partial load/full load
DN110/160, Cx3x, partial load/full load DN110-110, Cx3x, partial load/full
load Dimensions and weight
GC7000WP 50 GC7000WP 65 GC7000WP 85 GC7000WP 100
Unit
kW
14.3 49.9 14.3 69.5 20.8 84.5 20.8 99.5
kW
13.0 46.5 13.0 62.6 18.9 80.0 19.0 94.5
kW
13.3 47.5 13.3 64.3 19.3 82.0 19.3 96.5
kW
13.3 47.5 13.3 64.3 19.3 82.0 19.3 96.5
%
108.4
108.7
109.1
108.7
%
98.5
98.9
98.7
98.6
%
0.24
0.18
0.14
0.12
%
106.0
106.9
106.7
106.8
%
109.7
110.4
110.2
110.3
min
2
IP X0D
B23(p), B53(p), C13(x), C33(x), C43(x), C53(x), C63(x), C83(x), C93(x) CE- 0085DL0480
T120
230 V, 5AF
230 V, 50 Hz
W
2 / 8 / 31
2 / 8 / 65
2 / 10 / 88 2 / 10 / 133
m
°C
°C
bar
l/h
6.0
1200
0 – 40
85
6
7.6
9.3
11.0
mm
110/160
inch
G1½
inch
R1
mm
24
% % % % % % ppm mg/m3 mg/kWh
8.4 / 9.3 8.3 / 9.1 8.4 / 9.1 9.5 / 10.0 5.7 / 4.4 6.5 / 5.7
31 2.7 25
g/s
6.5/21.6
°C
56 / 59
°C
32 / 39
Pa
8.4 / 9.3
8.2 / 9.1
8.4 / 9.1
8.2 / 9.1
8.4 / 9.1
8.2 / 9.1
9.5 / 10.0
9.1 / 10.0
5.7 / 4.4
6.1 / 4.4
6.5 / 5.7
7.1 / 5.7
63
70
10.8
17.2
34
34
6
6.5/29.2
9.8/38.0
56 / 61
56 / 66
32 / 43
34 / 50
-5
G61
8.1 / 9.1 8.1 / 9.1 8.1 / 9.1 9.0 / 10.0 6.3 / 4.4 7.3 / 5.7
81 23.4 38
9.8/44.7 56 / 73 34 / 53
Pa
71
130
162
226
Pa
50 / 83
50 / 148
50 / 177
50 / 241
Pa
41 / 41
50 / 100
50 / 108
50 / 148
Pa
50 / 71
50 / 130
50 / 162
50 / 226
Pa
50 / 71
50 / 130
50 / 162
50 / 226
Condens 7000 WP 6721841195 (2022/01)
47
Technical information and reports
Condens 7000 WP GC7000WP
Height x Width x Length
mm
Weight
kg
Connection set
Heating flow pipe
inch
Heating return pipe
inch
Gas line
inch
Power input Wilo-Para STG 25/8, min./max.
W
Power input Wilo-Stratos Para 25/1-8,
W
min./max.
Table 22 Technical Specifications
15.3 Data relating to the gas Gas consumption
Maximum gas consumption [ m³/h]
Gas type
GC7000 GC7000 GC7000 GC7000 WP 50 WP 65 WP 85 WP 100
Natural gas E, H, Es (G20)
5.03 6.80 8.68 10.21
Natural gas LL, L, Ei, (G25)
5.85 7.91 10.09 11.88
Natural gas K (G25.3)
XX
XX
XX
XX
Propane 3P (G31)
1.94 2.62 3.34 3.93
Table 23 Gas consumption
Gasaansluitdruk
Land
Gasfamilie Gasaansluitdruk [mbar] Min.1) Nom. Max.
AT, AU, AZ, BA, BG, BY, CH, Aardgas H, 17 20 25
CZ, DK, EE, ES, GB, GR, HR,
G20
IE, IT, KZ, LT, LV, MD, NO, PT,
RO, RS, RU, SE, SI, SK, TR, UA
HU
Aardgas H, 17 20 25
G20
DE, LU, NL, PL
Aardgas E, 17 20 25 G20
FR
Bereik Es 17 20 25
Aardgas E
(G20)
FR
Bereik Ei 20 25 30
Aardgas E
(G20)
BE
Bereik Es 20 25 30
Aardgas E
(G25)
NL
Aardgas K, 20 25 30
G25.3
DE
Aardgas LL, 18 20 25
G25
DK, NL, NO, SE
Propaan L, 25 30 35 G31
AZ, BA, BE, BG, CH, CZ, ES, Propaan L, 25 37 45 FR, GB, GR, IE, PT, IT, MD, PL, G31 RO, RS, TR, PL, SK
AT, AU, BG, CH, DE, ES, EE, Propaan L, 42,5 50 57,5 HR, HU, LT, LV, LU, NL, SI, SK, G31 RS, UA
GC7000WP 50 GC7000WP 65 GC7000WP 85
1120 x 520 x 457 74
GC7000WP 100
4 / 74
G1½ G1½ G 1
27 / 138
- De minimale gasvoordruk gemeten op het gasregelblok waarbij de maximale belasting van het cv-toestel gewaarborgd blijft is 10 mbar.
Table 24 Gasaansluitdrukken
Natural gas
Country
Standard Gas Gas type gas category
pressure [mbar]
DE
20
2ELL 2E, G20
DE
25
2ELL 2LL, G25
AT, AU AZ, BA, BG, BY, 20 CH, CZ, DK, EE, ES, GB, GR, HR, IE, IT, KZ, LT, LV, MD, NO, PT, RO, RS, RU, SE, SI, SK, TR, UA
2H 2H, G20
FR
20/25
2Es 2Es, G20
FR
20/26
2EI 2Ei, G20
BE
20/25 2E
2Es,
G20/G25
LU, PL
20
2E 2E, G20
NL
20
2E 2E, G20
HU
25
2H 2H, G20
NL
25
2K
2K,
G25.3
Table 25 Natural gas
Default setting [mbar] 20 25 20
20 -20
20 -25 25
Propane
Country
Standard Gas Gas Conversion gas category type required
pressure [mbar]
DK, NO, SE
30
3P G31
Yes
AZ, BA, BE, FR, GB, GR, 37 IE, IT, MD, PL, PT, RO, TR
3P G31
Yes
AT, DE, EE, HR, HU, LT, 50 LU, LV, RS, SI, UA
3P G31
Yes
NL
30, 50 3P G31
Yes
BG, CH, CZ, ES, RS, SK 37, 50 3P G31
Yes
Table 26 Propane
48
Condens 7000 WP 6721841195 (2022/01)
15.4 Hydraulic resistances
Unité GC7000 GC7000 GC7000 GC7000 WP 50 WP 65 WP 85 WP 100
Required
l/h 2200 3000 3600 4300
volumetric flow
rate at T = 20 K
Max. volumetric l/h flow rate
5000
Resistance of floor standing boiler
mbar 75 130 170 240
Table 27 Hydraulic resistances
15.5 Residual head of pumps
Changing the pump output The standard setting for the pump output is
sufficient under normal conditions or with the heating circuit distributor.
With a measured T of more than 20 K an adjustment of the pump output is
desirable.
Increase the pump output until T is 20 K ( § 9.4, 26). -or Reduce the
installation resistance by installing a low loss header.
[mbar]
800
1
4
700
5
600
2
6
500
400
300
200
3 100
00
500 1000 1500 2000 2500 3000 3500 4000 4500 5000
[l/h]
0010039392-001
Fig. 49 Residual head of pump GC7000WP 100
Legend next to pump graphics:
[1] Maximum adjustable discharge head of pump [2] Standard setting of
discharge head [3] Minimum pump discharge head [4] Resistance of heat
exchanger + connection + non-return valve [5] Resistance of heat exchanger +
connection set [6] Resistance of heat exchanger
[mbar]
800
1
4
700
5
600
6
500
400
2
300
200
3 100
00
500 1000 1500 2000 2500 3000 3500 4000 4500 5000
[l/h]
0010039391-001
Fig. 50 Residual head of pump GC7000WP 85
Technical information and reports
[mbar]
800
4
700
5
600
6
500 400
21
300
200
3 100
00
500 1000 1500 2000 2500 3000 3500 4000 4500 5000
[l/h]
0010039390-001
Fig. 51 Residual head of pump GC7000WP 65
[mbar]
800
4
700
5
600
6
500
1
400
300
2
200
3 100
00
500 1000 1500 2000 2500 3000 3500 4000 4500 5000
[l/h]
0010039389-001
Fig. 52 Residual head of pump GC7000WP 50
15.6 Setting values for heating capacity
Power
Display
Display
Display
Display
GC7000WP GC7000WP GC7000WP GC7000WP
50
65
85
100
[kW] [%] [%] [%] [%]
13
28
20
—
—
20
40
28
24
20
25
50
36
29
25
30
60
43
35
30
35
70
50
41
35
40
80
57
47
40
45
90
64
53
45
50
100
71
59
50
55
—
79
65
55
60
—
86
71
60
65
—
93
76
65
70
—
100
82
70
75
—
—
88
75
80
—
—
94
80
85
—
90
—
95
—
100
—
—
100
85
—
—
90
—
—
95
—
—
100
Table 28 Setting values for heating capacity
Condens 7000 WP 6721841195 (2022/01)
49
Technical information and reports
15.7 Commissioning report for the appliance Customer/system user: Surname,
first name Telephone/fax System installer:
Street, house number Postcode, town
Order number:
Appliance type:
(Complete a separate report for every appliance!)
Serial number:
Date of commissioning:
Individual appliance | Cascade, number of devices: ……
Installation location: Cellar | Attic | Other:
Ventilation apertures: Number: ……, Size: approx.
cm2
Flue gas routing:
Twin pipe system | LAS | Duct | Separate pipe routing
Plastic | Aluminium | Stainless steel
Total length: approx. …… m | Elbow 87°: …… pce | Elbow 15 – 45°: …… pce
Leak check of the flue with a countercurrent: Yes | No
CO2 value in the combustion air at maximum rated output:
%
O2 value in the combustion air at maximum rated output:
%
Notes regarding underpressure or overpressure operation:
Gas setting and flue gas test: Set gas type: Gas supply pressure: Set maximum
rated output: Gas flow rate at maximum rated output: Net calorific value HiB:
CO2 at maximum rated output: O2 at maximum rated output: CO at maximum rated
output:
Flue gas temperature at maximum rated output: Maximum measured flow
temperature: System Hydraulic: Low loss header, type: Heating pump:
mbar kW l/min
kWh/m3 % % ppm mg/kWh °C
°C
DHW cylinder/type/number/heating surface output: System hydraulics checked, Notes:
Gas static supply pressure: Set minimum rated output: Gas flow rate at minimum
rated output:
CO2 at minimum rated output: O2 at minimum rated output: CO at minimum rated
output:
Flue gas temperature at minimum rated output: Minimum measured flow
temperature:
mbar kW l/min
% % ppm mg/kWh °C
°C
Additional expansion vessel Size/pre-charge pressure: Automatic air vent valve present? Yes | No
50
Condens 7000 WP 6721841195 (2022/01)
Changed service functions Read off the changed service functions and enter the values here.
Technical information and reports
Label with “settings in the service menu” filled out and affixed.
Heating controls:
Weather-compensated control
Room temperature-dependent control
Remote control × …… pce., heating circuit(s) coding:
Room temperature-dependent control × …… pce., heating circuit(s) coding:
Module × …… pce., heating circuit(s) coding:
Miscellaneous:
Heating controls set, Notes:
Changed settings for the heating controls documented in the operating/installation instructions for the control unit
The following work has been carried out:
Electrical connections checked, Notes:
Condensate trap filled
Carry out a combustion air/flue gas test
Function check carried out
Leak test carried out on the gas and water sides
Commissioning includes checking the setting values, a visual leak test on the appliance and a function check of both the device and its control. The system installer conducts a test of the heating system.
The system named above has been checked to the extent described.
The documents have been handed over to the user. The user has been made aware of the safety instructions and operation of the abovementioned wall mounted boiler, including accessories. Attention has been drawn to the requirement for regular maintenance of the above-mentioned heating system.
___ Name of service engineer
__ Date, user’s signature Affix the test report here.
____ Date, system
installer’s signature
Table 29 Commissioning report
Condens 7000 WP 6721841195 (2022/01)
51
Bosch Thermotechnik GmbH Junkersstrasse 20-24 D-73249 Wernau
www.bosch-thermotechnology.com
References
- New Boilers | Worcester Bosch
- Home | Bosch Home Comfort
- WEEE Electronic Waste | Bosch Home Comfort Group
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>