TRANE WSHP-PRC029C-EN Water Source Heat Pump Axiom User Guide

June 9, 2024
Trane

TRANE WSHP-PRC029C-EN Water Source Heat Pump Axiom

TRANE-WSHP-PRC029C-EN-Water-Source-Heat-Pump-Axiom-
PRODUCT

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

  • Updated GEHG006-0024 and 030-060 models general data tables.
  • Updated ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance – 0.5 to 5 tons table.
  • Updated Clearances GEHG 0.5 to 5 tons.

List of options

Factory Installed Options Field Installed Options
1-inch or 2-inch Ducted Filter Rack 2-inch or 4-inch Ducted Filter Rack
Air-Fi® Wireless Communications Ducted Panel
Deluxe 24V, UC400B Controls Hose Kits (or ship separate hoses and valves)
Factory-mounted Isolation Valve Low, Medium and High Electric Heat
Hot Gas Reheat Pump Module
Matte or Foil Face Insulation Pump Module Hose Kit
MERV 8 or 13 Filters Thermostats or Zone Sensors
Polymer or Stainless Steel IAQ Drain Pan Waterside Economizer
Recessed Unit Mounted Disconnect Switch

Standard or Deluxe Sound Package

General data

models: GEHG006-024

Model GEHG 006 009 012 015 018 024
Unit size width x depth x height (in.) 23 x 41 x 15.75 23 x 41 x 15.75 23 x
41 x 15.75 25.5 x 46 x 17.75 25.5 x 46 x 17.75 25.5 x 49 x 18.75
Compressor type Rotary Rotary Rotary Rotary Rotary Scroll
Net weight (lbs.) 165 165 165 173 173 269
Ship weight (lbs.) 255 255 255 297 297 393
Filter size nominal (in.) 14 x 16 14 x 16 14 x 16 16 x 19 16 x 19 17 x

20
Water in/out size (FPT)| 0.5| 0.5| 0.5| 0.5| 0.5| 0.75
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 9 x 6| 9 x 6| 9 x 6| 9 x 8| 9 x 8| 10 x 8

models: GEHG030-060

Model GEHG 030 036 042 048 060
Unit size width x depth x height (in.) 25.5 x 49 x 18.75 25.5 x 55 x 19.75
25.5 x 55 x 19.75 28 x 68 x 21.75 28 x 68 x 21.75
Compressor type Scroll Scroll Scroll Scroll Scroll
Net weight (lbs.) 269 313 313 381 394
Ship weight (lbs.) 393 437 437 526 539
Filter size nominal (in.) 17 x 20 18 x 23 18 x 23 20 x 30 20 x 30
Water in/out size (FPT) 0.75 0.75 0.75 1.00 1.00
Condensate size (NPTI) 0.75 0.75 0.75 0.75 0.75
Blower wheel Size (in.) 10 x 8 10 x 9 10 x 9 11 x 11 11 x 11

models: GEVG006-024

Model GEVG 006 009 012 015 018 024
Unit size width x depth x height (in.) 19 x 19 x 30 19 x 19 x 30 19 x 19 x
30 21.5 x 21.5 x 34 21.5 x 21.5 x 34 21.5 x 23 x 36
Compressor type Rotary Rotary Rotary Rotary Rotary Scroll
Net weight (lbs.) 149 149 149 155 157 210
Ship weight (lbs.) 201 201 201 210 212 268
Filter size nominal (in.) 14 x 16 14 x 16 14 x 16 16 x 19 16 x 19 16 x

19
Model GEVG| 006| 009| 012| 015| 018| 024
---|---|---|---|---|---|---
Water in/out size (FPT)| 0.5| 0.5| 0.5| 0.5| 0.5| 0.75
Condensate size (NPTI)| 0.75| 0.75| 0.75| 0.75| 0.75| 0.75
Blower wheel Size (in.)| 9 x 6| 9 x 6| 9 x 6| 9 x 8| 9 x 8| 10 x 8

models: GEVG030-060

Model GEVG 030 036 042 048 060
Unit size width x depth x height (in.) 21.5 x 23 x 36 21.5 x 26 x 38 21.5 x
26 x 38 24 x 32.5 x 42 24 x 32.5 x 42
Compressor type Scroll Scroll Scroll Scroll Scroll
Net weight (lbs.) 214 220 252 280 285
Ship weight (lbs.) 272 280 312 343 348
Filter size nominal (in.) 16 x 19 18 x 23 18 x 23 20 x 30 20 x 30
Water in/out size (FPT) 0.75 0.75 0.75 1.00 1.00
Condensate size (NPTI) 0.75 0.75 0.75 0.75 0.75
Blower wheel Size (in.) 10 x 8 10 x 9 10 x 9 11 x 11 11 x 11

ANSI/AHRI/ASHRAE/ISO13256-1

WLHP, GWHP and GLHP performance – 0.5 to 5 Tons

Model

|

Rated GPM

|

Rated CFM

| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat Pump
---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating 50°F| Full Cool 77°F| Full Heat 32°F
Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

GEH/VG006| 1.50| 190| 7,000| 13.70| 9,300| 4.70| 8,100| 21.30| 7,500| 4.10| 7,400| 16.00| 5,600| 3.30
GEH/VG009| 2.25| 285| 8,700| 15.50| 11,200| 5.50| 9,600| 23.80| 9,100| 4.70| 8,900| 17.80| 6,700| 3.70
GEH/VG012| 3.00| 380| 11,400| 14.90| 15,300| 5.30| 13,300| 24.20| 12,400| 4.60| 12,100| 17.60| 9,400| 3.70
GEH/VG015| 3.75| 475| 14900| 15.3| 18700| 5.10| 16600| 23.00| 15400| 4.30| 15500| 17.40| 12300| 3.60
GEH/VG018| 4.50| 570| 17400| 15.6| 22200| 5.00| 19300| 23.50| 18400| 4.40| 18100| 17.70| 14300| 3.60
GEH/VG024| 6.00| 760| 23,900| 16.10| 31,100| 5.30| 26,600| 24.40| 25,300| 4.60| 24,800| 18.50| 19,600| 3.80

Model

|

Rated GPM

|

Rated CFM

| Water Loop Heat Pump| Ground Water Heat Pump| Ground Loop Heat Pump
---|---|---|---|---|---
Cooling 86°F| Heating 68°F| Cooling 59°F| Heating 50°F| Full Cool 77°F| Full Heat 32°F
Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

| Capacity Btuh|

EER

| Capacity Btuh|

COP

GEH/VG030| 7.50| 950| 29,000| 15.40| 37,900| 5.10| 32,300| 23.00| 30,800| 4.50| 30,200| 17.70| 23,300| 3.70
GEH/VG036| 9.00| 1140| 36,000| 15.40| 45,100| 5.00| 39,900| 22.60| 36,900| 4.40| 37,300| 17.60| 28,700| 3.60
GEH/VG042| 10.50| 1330| 40,900| 14.90| 55,600| 4.70| 45,500| 22.00| 45,600| 4.20| 42,600| 17.10| 35,300| 3.50
GEH/VG048| 12.00| 1520| 49,500| 15.10| 62,600| 4.90| 55,700| 22.80| 50,000| 4.20| 51,800| 17.40| 37,600| 3.30
GEH/VG060| 15.00| 1900| 55,200| 14.50| 75,400| 4.60| 61,700| 21.30| 61,200| 4.10| 57,300| 16.50| 47,000| 3.50

Notes

  1. Rated in accordance with ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68F DB/59°F WB EAT in heating.
  2. Models with capacities greater than 135,000 Btuh are not included in the ANSI/AHRI/ASHRAE/ISO13256-1 water-to-air and brine-to-air heat pump certification program.

Electrical data

*ECM motors – GE 0.5 to 5 tons**

Model No.| Unit Volts| Blower Motor HP| Minimum Circuit Ampacity| Maximum Overcurrent Protective Device
---|---|---|---|---
GEH/GEV006| 208-230/60/1| 1/3| 5/5| 15/15
GEH/GEV006| 265/60/1| 1/3| 5| 15
GEH/GEV009| 208-230/60/1| 1/3| 6/6| 15/15
GEH/GEV009| 265/60/1| 1/3| 5| 15
GEH/GEV012| 208-230/60/1| 1/3| 9/9| 15/15
GEH/GEV012| 265/60/1| 1/3| 7| 15
GEH/GEV015| 208-230/60/1| 1/3| 10/10| 15/15
GEH/GEV015| 265/60/1| 1/3| 7| 15
GEH/GEV018| 208-230/60/1| 1/3| 12/12| 20/20
GEH/GEV018| 265/60/1| 1/3| 10| 15
GEH/GEV024| 208-230/60/1| 1/2| 19/19| 30/30
GEH/GEV024| 265/60/1| 1/2| 13| 20
GEH/GEV024| 208-230/60/3| 1/2| 11/11| 15/15
---|---|---|---|---
GEH/GEV024| 460/60/3| 1/2| 6| 15
GEH/GEV030| 208-230/60/1| 3/4| 20/20| 30/30
GEH/GEV030| 208-230/60/3| 3/4| 13/13| 20/20
GEH/GEV030| 265/60/1| 3/4| 16| 25
GEH/GEV030| 460/60/3| 3/4| 7| 15
GEH/GEV036| 208-230/60/1| 3/4| 24/24| 40/40
GEH/GEV036| 265/60/1| 3/4| 20| 30
GEH/GEV036| 208-230/60/3| 3/4| 16/16| 25/25
GEH/GEV036| 460/60/3| 3/4| 9| 15
GEH/GEV042| 208-230/60/1| 3/4| 26/26| 40/40
GEH/GEV042| 208-230/60/3| 3/4| 21/21| 30/30
GEH/GEV042| 460/60/3| 1| 10| 15
GEH/GEV048| 208-230/60/1| 1| 31/31| 50/50
GEH/GEV048| 208-230/60/3| 1| 23/23| 35/35
GEH/GEV048| 460/60/3| 1| 10| 15
GEH/GEV060| 208-230/60/1| 1| 38/38| 60/60
GEH/GEV060| 208-230/60/3| 1| 25/25| 40/40
GEH/GEV060| 460/60/3| 1| 13| 20

Clearances

GEHG 0.5 to 5 tonsTRANE-WSHP-PRC029C-EN-Water-Source-Heat-Pump-Axiom-
FIG-1

A minimum 14–inch clearance for servicing the unit is required for all 0.5 to 5 tons configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. The optimum clearance required is 20 inches.

TRANE-WSHP-PRC029C-EN-Water-Source-Heat-Pump-Axiom-
FIG-2

  • A 24-inch clearance from other mechanical and electrical equipment (where shown) is recommended for most unit configurations. This will enable panel removal from
    the unit for service/maintenance.

  • The 24-inch side clearance on GEVG 0.5-5T models is for optimal access only. Side clearance is not a requirement as most components can be accessed from the
    front of the unit.

  • A 1-inch minimum clearance between the filter rack and any obstacle is required for units in a free return application to provide proper air flow to the air-to-refrigerant
    coil. A 12-inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork.

  • The 1-inch dimension shown in the back of the unit represents the supply duct collar for the back supply option. This clearance is needed to clear these flanges.

Trane:  by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

WSHP-PRC029C-EN 01 Mar 2023
Supersedes WSHP-PRC029B-EN (Oct 2021)

©2023 Trane

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals