NOTIFIER N-ANN-LED Annunciator Module
General
The N-ANN-LED annunciator module provides LED annuncia-tion of general system
faults and input zones/points when used with a compatible Fire Alarm Control
Panel (FACP). The N-ANN-LED module provides alarm (red), trouble (yellow) and
supervi-sory (yellow) indication for up to ten input zones or addressable
points. N-ANN-RLED has red LEDs only for alarm communica-tion of up to 30
addressable points.
The N-ANN-LED is supplied standard with Canadian Firewar-den FACPs as required
by ULC. The Canadian part number are designated below with a (C).
The N-ANN-LED and the FACP communicate over a two-wire serial interface
employing the ANN-BUS communication format. An additional two wires are used
for 24-volt DC power. A single four-conductor unshielded cable may be used for
both power and data communications.
Up to eight ANN-BUS devices may be connected to the ANN-BUS of each FACP.
Features
- N-ANN-LED connects to the ANN-BUS terminal on the FACP and requires minimal programming.
- Includes three LEDs for each zone: Alarm, Trouble and Supervisory. N-ANNRLED includes all red LEDs for alarm only annunciation.
- Compatible with the NFW-50(C), NFW2-100(C), SFP-5UD(C), SFP-10UD(C), RP-2001(C), RP-2002(C).
- Can be remotely located up to 6,000 feet (1,829 m) from the panel.
- May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC).
Specifications
- Maximum ANN-BUS Voltage: 24 VDC
- Maximum Current: Alarm: 68 mA Standby: 28 mA
- Maximum wiring distance from FACP: 6,000 ft. (1,829 m.)
- Ambient Temperature: 32ºF to 120ºF (0ºC to 49ºC)
- Relative Humidity: 93% ± 2% RH (noncondensing) at 32ºC ± 2ºC (90ºF ± 3ºF)
- For use indoors in a dry location
- Connections to FACP are power-limited and supervised.
- 5.160″ (13.11 cm.) high x 10.043″ ( 25.51 cm.) wide x 1.77″ (4.5 cm.) deep.
Agency Listings and Approvals
The listings and approvals below apply to the N-ANN-LED. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL: S635
- ULC: S635 (N-ANN-LED only)
- FM approved
- CSFM: 7120-0028:0259
- MEA: 333-07-E
- Fire Dept of NY: COA #6177
The ANN-BUS
POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY
ANN-BUS devices can be powered by an auxiliary power supply when available
panel power is exceeded. See FACP manual for information.
ANN-BUS DEVICE ADDRESSING
Each ANN-BUS device requires a unique address (ID Number) in order to
communicate with the FACP. A maximum of eight devices can be connected to the
FACP ANN-BUS communica-tion circuit. See the FACP manual for more information.
WIRE REQUIREMENTS
The N-ANN-LED connects to the FACP ANN-BUS communica-tions circuit. To
determine the type of wire and the maximum wir-ing distance, calculate the
total worst case current draw for all modules on a single 4-conductor bus. Use
the table on the fol-lowing page to determine the maximum distance the modules
can be located from the FACP. In general, the wire length is lim-ited by
resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can
never be more than 6,000 feet (1,800 m), regardless of gauge used.
Refer to the appropriate FACP manual for wiring details and proper settings.
Ordering Information
- N-ANN-LED: annunciator module with alarm (red), trouble (yel-low) and supervisory (yellow) indication for up to ten input zones or addressable points, includes module mounting bracket, metal cover and clear plastic screen, rubber display/label holder, screws for securing the metal cover and the backbox, black enclosure.
- N-ANN-LED-R: same as above, with red enclosure.
- N-ANN-RLED: annunciator module with alarm (red) indicators for up to 30 input zones or addressable points, includes black enclosure.
- N-ANN-RLED-R: annunciator module with alarm (red) indica-tors for up to 30 input zones or addressable points, includes red enclosure.
Communication Pair Wiring Distance: FACP to last ANN-BUS Module
Communication Pair Wiring Distance: FACP to last ANN-BUS Module
Total Worst Case Current Draw (amps)| 22 Gauge| 18 Gauge| 16
Gauge| 14 Gauge
0.100| 1,852 ft. (565 m)| 4,688 ft. (1,429 m)| 6,000 ft. (1,829 m)| 6,000
ft. (1,829 m)
0.200| 926 ft. (282 m)| 2,344 ft. (715 m)| 3,731 ft. (1,137 m)| 5,906 ft.
(1,800 m)
0.300| 617 ft. (188 m)| 1,563 ft. (476 m)| 2,488 ft. (758 m)| 3,937 ft. (1,200
m)
0.400| 463 ft. (141 m)| 1,172 ft. (357m)| 1,866 ft. (569 m)| 2,953 ft. (900 m)
0.500| 370 ft. (113 m)| 938 ft. (286 m)| 1,493 ft. (455 m)| 2,362 ft. (720 m)
0.600| 309 ft. (94 m)| 781 ft. (238 m)| 1,244 ft. (379 m)| 1,969 ft. (600 m)
0.700| 265 ft. (81 m)| 670 ft. (204 m)| 1,066 ft. (325 m)| 1,687 ft. (514 m)
0.800| 231 ft. (70 m)| 586 ft. (179 m)| 933 ft. (284 m)| 1,476 ft. (450 m)
0.900| 206 ft. (63 m)| 521 ft. (159 m)| 829 ft. (253 m)| 1,312 ft. (400 m)
1.000 (max.)| 185 ft. (56 m)| 469 ft. (143 m)| 746 ft. (227 m)| 1,181 ft. (360
m)
NOTIFIER® is a registered trademark of Honeywell International Inc.
©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.