CERBERUS PYROTRONICS Thermal Fire Detectors Explosion Proof Models Owner’s Manual

June 9, 2024
CERBERUS PYROTRONICS

CERBERUS PYROTRONICS Thermal Fire Detectors Explosion Proof Models

CERBERUS-PYROTRONICS-Thermal-Fire-Detectors-Explosion-Proof-Models-
PRODUCT

ENGINEER AND ARCHITECT SPECIFICATIONS

DETECT-A-FIRE MODELS

  • Explosion Proof
  • Self-Restoring Detector Element
  • Models Available in both Normally Open and Normally Closed Contacts in a Wide Range of Temperature Settings
  • Factory Set and Hermetically Sealed in Stainless Steel Shell
  • Listed and FM Approved as Fenwal Model Series 27120 and 27121 Manufactured for Cerberus Pyrotronics by Fenwal

Introduction

Detect-A-Fire explosion proof detectors are of the rate compensated type and are designed for use with either standard Cerberus Pyrotronics systems or other commercially available fire alarm systems. The detector element in all models is self-restoring after operation. The Detect- A-Fire explosion proof models can be supplied with normally closed contacts at 140, 160, 190, 210, 225, 275, 325, 360 or 450°F settings or with normally open contacts at 140, 160, 190, 210, 275, 325, 360, 450, 500, 600, or 725°F settings. These detectors are only explosion proof when mounted in an approved explosion proof junction box.

Principle of Operation

Detect-A-Fire units have met with wide acceptance because they are designed with rate compensation. This provides a unique advantage over both standard fixed temperature and rate-of-rise types of detectors because only the Detect-A-Fire unit accurately senses the surrounding air temperature regardless of the fire growth rate. At precisely the predetermined danger point the system is activated. The secret of the unit’s sensitivity is in the design. The outer shell is made of a rapidly expanding alloy that closely follows changes in surrounding air temperature. The inner struts are made of a lower expanding alloy.

Designed to resist thermal energy absorption and sealed inside the shell, the struts follow temperature changes more slowly. A slow rate fire will heat the shell and struts together. At the “set point” the unit will trigger, actuating the alarm or releasing the extinguishant. A transient rush of warm air up to 40°F/min. may expand the shell, but not enough to trigger the unit. In ignoring transient warm air excursions, the Detect-A-Fire unit virtually eliminates false alarms prevalent with rate-of-rise devices. If a fast rate fire starts, then the shell will expand rapidly. The struts will close, actuating the alarm or releasing the agent. The faster the fire rate of growth, the sooner the alarm.

Engineer and Architect Specifications

The explosion proof thermal fire detector shall be a Detect- A-Fire explosion proof model, Fenwal ( MODEL ), also for purchasing purposes referred to as Cerberus Pyrotronics ( MODEL ), and shall be of the rate compensated type. The explosion proof detector shall have a self-restoring element and shall be factory set and hermetically sealed in stainless steel. These detectors shall be mounted in an approved explosion-proof junction box. The explosion proof detectors must be UL listed and FM approved.

Model Cross-Reference Chart



°F

Setting

| ****


°F

Tolerance

| ****


Color Coding

| Normally Open Contact| Normally Closed Contact
---|---|---|---|---
Fenwal Model| Cerberus Pyrotronics Model| Fenwal Model| Cerberus Pyrotronics Model
140| (+7,-8)| Yellow| 27121-140| DT-140EP| 27120-140|
160| (+7,-8)| Yellow| 27121-160| DT-160EP| 27120-160|

190| (+7,-8)| White| 27121-190| DT-190EP| 27120-190|
210| (+7,-8)| White| 27121-210| DT-210EP| 27120-210|

225| (+7,-8)| White| 27121-225| DT-225EP| 27120-225|
275| (+/-10)| Blue| 27121-275| DT-275EP| 27120-275|

325| (+/-10)| Red| 27121-325| DT-325EP| 27120-325|
360| (+/-10)| Red| 27121-360| DT-360EP| 27120-360|

450| (+/-15)| Green| 27121-450| DT-450EP| 27120-450| *
500| (+/-15)| Orange| 27121-500| DT-500EP|  |
600

725

| (+/-20)

(+/-25)

| Orange

Orange

| 27121-600

27121-725

| DT-600EP

DT-725EP

|  |

Normally Closed Contact Detectors do not operate with any Cerberus Pyrotronics Control Panels. These Normally Closed Contact Detectors are offered for special applications only.

Ordering Information

Refer to the chart above. When placing a purchase order refer to the Cerberus Pyrotronics model number. The format of the model number is: DT- (the temperature setting desired) EP. For example, if you wish to order a normally open 140°F detector, you would order model numbers DT-140EP. The Cerberus Pyrotronics model numbers DT-140EP and DT-190EP (both normally open) are stocked items. All other models are special orders. Contact Cerberus Pyrotronics Customer Service Department for assistance. Shipping weight for these items is approximately one pound.

Dimensions

Hazardous Locations Applications| Detector Model Series| Fitting Required for UL & ULC Listings and FM Approval
---|---|---
Class I, Groups B,| 27120| Mount the detector to a
C and D;|  | suitably listed fitting in accordance with the
 |  | National Electric Code and/or local authority having jurisdiction
Class II, Groups E, F and G;| 27121

Mounting and Installation Information

The explosion proof (EP) models attach to the threaded hub cover of listed explosion proof junction boxes such as Killark Series, UL or equal. The EP models should not be installed in outdoor or other wet locations.

CERBERUS-PYROTRONICS-Thermal-Fire-Detectors-Explosion-Proof-Models-
FIG-2

CONSTRUCTION: Units have a stainless steel sensing shell and a brass mounting head.

Fenwal Model No.| Contacts| **Electrical Rating (Resistive Only)
---|---|---
27120 Series| Normally Closed| 5 Amps., 125 VAC

0.5 Amps., 125 VDC

27121 Series| Normally Open| 5 Amps., 125 VAC

0.5 Amps., 125 VDC

2.0 Amps., 24 VDC

1.0 Amps., 48 VDC

CONTACTS

Cerberus Pyrotronics

Cerberus Pyrotronics

4/97
5M CPY-IG
Printed in U.S.A

April 1997
Supersedes sheet dated 1/95

firealarmresources.com