Honeywell SS2 Fire Sentry Fire and Flame Detectors Owner’s Manual

June 9, 2024
Honeywell

Fire Sentry SS2 Fire and Flame Detectors

SS2 UV/IR Flame Detector
Fire and Flame Detector

Features

  • Multi-Spectrum senses energy in the UV, Vis and Wide Band IR™
  • False alarm immunity
  • Detects hydrocarbon and non-hydrocarbon fires
  • Microprocessor based algorithms: Fire Pic™ and Tri-Mode Plot™
  • Wide field of view and solar blind
  • Wide temperature range of operation
  • Explosion-proof housing
  • FS2000TM System compatible or standalone operation
  • Compatible with approved fire alarm panels

SS2-A & SS2-AN UV/IR Digital Fire and Flame Detector

  • Oil, Gas & Petrochemical Facilities
  • Gas Turbines
  • Compressor Stations
  • Power Plants
  • Silane & Hydrogen Gas Storage
  • Aircraft Hangers
  • Warehouses

SS2-AM & SS2-AML UV/IR 
Ultra-High Speed Digital Fire and Flame Detector

  • Munitions production
  • Explosives production
  • Manufacture of other explosive material
  • Silane & Hydrogen gas storage
  • SS2-AH & SS2-AHD UV/IR

Ultra-High Speed Digital Fire and Flame Detector

  • Sodium Azide propellant manufacture
  • Automotive Air Bag manufacture

SS2-A & SS2-AN Multi-Spectrum
Digital Electro-Optical Fire Detector

Fire Sentry SS2-A and Fire Sentry SS2-AN
The Fire Sentry SS2-A, (latching Fire Alarm relay), and Fire Sentry SS2-AN (nonmatching Fire Alarm relay), represent the world´s pre-eminent UV/IR technology for Electro-Optical fire and flame detectors, with thousands successfully operating in a multitude of installations worldwide. This detector senses radiant energy in the Ultraviolet (UV), Visible and Wide Band IR™ spectrum. The radiant energy from all types of flaming fires will alert the detector to their presence.
The field-of-view is the widest in the industry with a 120° cone of vision. This means each detector can cover more hazard area. Greater sensitivity also increases the volume of coverage by the detector, up to four times more than some other detectors.

Fire Sentry SS2-AM and Fire Sentry SS2-AML
The Fire Sentry SS2-AM, (latching Fire Alarm relay), and Fire Sentry SS2AML (non-latching Fire Alarm relay), represent the world´s pre-eminent Ultra High Speed UV/IR technology for Electro-Optical fire and flame detectors, successfully operating in a multitude of installations worldwide. This detector senses radiant energy in the Ultraviolet (UV), Visible and Wide Band IRTM spectrum. The radiant energy from all types of flaming fires will alert the detector to their presence.

The field-of-view is the widest in the industry with a 120° cone of vision. This means each detector can cover more hazardous area.

The field of view for the Fire Sentry SS4 detectors is the widest in the industry with a 120° cone of vision. This means more hazard area can be covered by each detector. Greater sensitivity also increases the volume covered by each detector, up to four times more than some other detectors.
Using sophisticated microprocessor signal processing algorithms, false alarm rejection is maximized ­ with virtual immunity to false alarms from arc welding, corona discharge and other common non-fire sources.

Operation

The SS2 operates from standard 24 Volt DC power and interfaces to approved fire alarm panels or standard PLC’s. When power is applied, an internal self test is performed and the fault relay resets to show no faults. The detector is then in normal operation.
The front LEDs flash every ten seconds to indicate power is on. The continuous spectral data stream of information from the sensor array is analyzed by the microprocessor. On Alarm, the detector activates the alarm relay and stores all of the pre-fire spectral data from the sensor array in nonvolatile memory for retrieval and evaluation. This Fire Pic™ data can be used to postulate the cause of the fire.
As part of the FS2000™ System, the the lens and complete optical path can be checked using COP-i™ Test Sources in the system. Connection into the FS2000™ System is by the four wire RS-485 FireBus™.

Tri-Mode Plot Shown on Computer Display

| |
---|---|---

SPECIFICATIONS

Response Time| 2-5 seconds to 1 sq. ft. of gasoline pan
Fire at 60 ft.
---|---
Field-of-View| 120 degrees cone of vision (60 degrees from on axis).
Spectral Sensitivity| Ultraviolet:| 185 to 260 nanometers
Wide Band Infrared:| 0.7 to 3.5 micrometers
Visible:| 400 to 700 nanometers
Input Power| 24 VDC nominal (20.4 to 34 VDC)
Power| 56 mA normal operation, typical
Consumption| 75 mA alarm condition, typical
Relay Outputs| Fire Alarm Relay:| NO & NC contacts
Latching /Non-Latching, factory set Normally de-energized
Fault Relay| NO & NC contacts
Normally energized
Relay contact ratings: 0.5 A at 120 VAC, 1.0 A at 24 VDC
Operating Temperature| -40to + 185°F
– 40 to + 85° C
Humidity Range| 10 to 90% RH, non-condensing
Weight| 4 pounds – Aluminum
7.5 pounds – Stainless Steel
Housing| Copper-free aluminum (less than 0.4%) powder coated NEMA4 IP66, tamper resistant with integral dual 3/4” NPT conduit openings Stainless steel housing available
Electrical| Explosion-Proof
Classification| Class I, Div. 1 & 2, Groups B, C, & D
Class II, Div. 1 & 2, Groups E, F, & G
Class III.
Mounting| Swivel bracket assembly
Warranty| Two years from factory shipping date Extended warranty available.

ORDERING INFORMATION

SS2-A Electro-Optical Detector, latching
SS2-AN Electro-Optical Detector, non-latching
SM4 Stainless Steel Swivel Mount
FT-2145 Explosion-proof Test Lamp
CM1-A Wall-mount Controller

Customer business centre
Korea: +82-2-69090300
Singapore: +65-65803776
Australia: +61-3-94642770
Taiwan: +886-3-5169284
China: +86-21-28943293| Technical Services
AP: ha.ap.service@honeywell.com
EMEA: ha.emea.service@honeywell.com
US: ha.us.service@honeywell.com
www.honeywell.com
---|---

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or  missions. Data may change, as well as  legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract.

DS01144_v1 06/12
© 2012 Honeywell Analytics
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals