NOTIFIER R-10T Multi Voltage Conventional Relay Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NOTIFIER R-10T Multi Voltage Conventional Relay Owner’s Manual
R-10E(A)/ R-14E(A)/R-20E(A)/ R-24E(A)
- Operating Voltage Range: 18-35 VDC,. 18-35 VAC, 115 VAC, 230 VAC.
- Operating Current: 23 mA DC max. @ 24 V, 59 mA @ 24 VAC, 150mA @ 120 VAC, 180 mA @ 240 VAC [R-10E(A)/ R-14E(A)]. -40 mA DC max. @ 24 VDC, 24 VAC, 115 VAC, 230 VAC (R20E/R-24E).
- Humidity Range: 10% to 93% (non-condensing).
- Dimensions: R-10E(A)/R-20E(A): 5.1”L x
- 3.75”W x 2.5”H.
- R-14E(A)/R-24E(A): 11”L x
- 5.3”W x 2.5”H
- Operating Temperature: -40° F to 158° F (-40° C to 70° C)
- Contact Ratings: 24 VDC: 7 A with L/R = 5mS.
- 120 VAC: 10 A.
- 120 VAC: 1/6 HP.
- 230 VAC: 7 A.
- Operating Voltage Range: 18-35 VDC, 18-35 VAC, 120 VAC.
- Operating Current: 15 mA DC max. @ 24 VDC, 24 VAC,120VAC.
- Humidity Range: 10% to 93% RH.
- Dimensions: 0.87” H x 2.01” W x 1.42” D.
- Operating Temperature: -40° F to 158° F (-40° C to 70° C).
- Contact Ratings: 24 VDC: 7 A with LR = 5 mS.
- 120 VAC: 7 A max. (0.35 PF).
- 250 VAC: 10 A resistive.
- 30 VDC: 10 A resistive.
- Wire Length: 8” minimum.
General
Notifier’s multi-voltage conventional relays are used for highcurrent switching applications such as fan and damper assembly control, door control, air handling unit controls, and other types of system interfacing. The R-10T(A)/20T(A) and R-14T(A)/R-24T(A) models are multi-voltage relays with terminal strip field wiring connections, mounting track and hardware. The R-10T(A) is a single FORM-C (SPDT) relay with a red activation LED, and the R-14T(A) is a 4-gang 1 FORM-C (SPDT) relay with 4 red activation LEDs. The R 20T(A) is a single 2 FORM-C (DPDT) relay with red activation LED, and the R-24T(A) is a 4-gang 2 FORM-C (DPDT) relay with 4 red activation LEDs. The R-10E(A)/R-20E(A) and R-14E(A)/R-24E(A) are similar to the T series track mount relays, but they are mounted into a steel enclosure. The enclosure has a removable front cover that provides easy access and a LED viewing hole on the top of the cover. PR-1(A)/PR-2(A)/PR-3(A) are epoxy encapsulated multi- voltage relays. They are single pole double throw relays that use a red LED as a visible indication of relay coil energization. PR-3 is identical to PR-2 except it has an extra pair of wires for redundant power input. Model EOLR-1(A) is an epoxy encapsulated single pole single throw, normally open relay that can be used as an end of line device in fire alarm systems, e.g. to supervise power supplies.
Specifications
R-10T(A)/R-14T(A)/R-20T(A)/ R-24(A)T
-
Operating Voltage Range: 18-35 VDC, 18-35 VAC, 115 VAC, 230 VAC.
Operating Current: 23 mA @ 24 VDC , 59 mA @- 24 VAC,150 mA @ 120 VAC,
- 180 mA @ 240 VAC [R-10T(A)/
- R-14T(A)].
- 40 mA DC max. @ 24 VDC, 24
- VAC, 92 mA @ 24 VAC, 220
- mA @ 120 VAC, 260 mA @
- 240 VAC [R-20T(A)/R-24T(A)]
-
Humidity Range: 10% to 93% (non-condensing).
-
Dimensions: R-10T(A)/ R-20T(A): 2.5”L x
- 3.35”W x 1.2”H.
- R-14T(A)/R-24T(A): 10”L x
- 3.35”W x 1.2”H.
-
Operating Temperature: -40° F to 158° F (-40°C to 70°C)
-
Contact Ratings: 24 VDC: 7A with L/R = 5 mS.
- 120 VAC: 10 A.
- 120 VAC: 1/6 HP.
- 230 VAC: 7 A.
PR-2(A)/PR-3(A)
- Operating Voltage Range: 10 to 40 VDC.
- Operating Current: 30 mA DC max.
- Humidity Range: 10% to 93% RH.
- Dimensions: 0.91” H x 1.65” W x 1.22” D.
- Operating Temperature: -40° F to 158° F (-40° C to 70° C).
- Contact Ratings: 120 VAC: 10 A (resistive load).
- 120 VAC: 7 A max. (0.35 PF).
- 250 VAC: 10 A max. (resistive load).
- 30 VDC: 10 A max. (resistive load).
- Wire Length: 8” minimum.
EOLR-1(A)
- Operating Voltage Range: 9 to 40 VDC.
- Operating Current : 20 mA DC max.
- Humidity Range: 10% to 93% RH.
- Operating Temperature: -22° F to 140° F (-30° C to 60° C).
- Contact Ratings: 120 VAC: 0.5 A max. (resistive load).
- 30 VDC: 3 A max. (resistive load)
- Wire Length: 8” minimum.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL/ULC Listed: S3705
- ULC Listed: CS669
- MEA: 419-04-E
- CSFM: 7300-1653:173
PRODUCT LINE INFORMATION
NOTE: “A” suffix indicates ULC listed model.
PR-1(A): Epoxy encapsulated single pull double throw (SPDT) relay. It
also uses a red LED as a visible indication of relay coil energization with
pigtails.
PR-2(A): Epoxy encapsulated single pull double throw (SPDT) activated by
10 to 40 VDC. It uses a red LED as a visible indication of relay coil
energization with pigtails.
PR-3(A): Epxoy encapsulated single pull double throw (SPDT) activated by
10 to 40 VDC. It contains an additional black and red wire for redundant power
input with pigtails.
EOLR-1(A): Epoxy encapsulated single pull single throw (SPST) normally
open relay that is activated by 9 to 40 VDC. This relay can be used as an end
of line device in fire alarm systems, e.g., to supervise power supplies.
R-10T(A): Single (SPDT) relay with a red activation LED.
R-14T(A): 4-gang (SPDT) relay with 4 red activation LEDs.
R-20T(A): Single (DPDT) relay with a red activation LED.
R-24T(A): 4-gang (DPDT) relay with 4 red activation LEDs.
The R-10E(A)/R-20E(A) and R-14E(A)/R-24E(A) are similar to the T series track mount relays, but they are mounted into a steel enclosure. The enclosure has a removable front cover that provides easy access and a LED viewing hole on the top of the cover
R-10E(A): Single (SPDT) relay mounted into a steel enclosure, 1 red
activation LED.
R-14E(A): 4-gang (SPDT) relay mounted into a steel enclosure, 4 red
activation LEDs.
R-20E(A): Single (DPDT) relay mounted into a steel enclosure, 1 red
activation LED.
R-24E(A): 4-gang (DPDT) relay mounted into a steel enclosure, 4 red
activation LEDs.
©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact Noti fier. Phone: 203-484-7161, FAX: 203-484-7118. www.notifier.com
Page 4 of 4 — DN-7015: A2 7/30/13
References
- Fire Alarm Resources | Download fire alarm documents
- Home (USA) | NOTIFIER by Honeywell | Engineered Fire Alarm System.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>