NOTIFIER 302 Series Rate Anticipation Heat Detector Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
dn-1271:A1 • I-307
302 Series
Rate-Anticipation Heat Detectors
Conventional Initiating Devices
General
The Thermotech 302 Series rate-anticipation heat detectors operate within a
controlled range of two to three degrees of their set points, regardless of
the speed or rate of temperature rise. These detectors are available in either
135°F (57.2°C) or 194°F (90°C) ratings.
The 302 Series are normally-open devices designed especially for fire
detection and alarm systems.
Features
- Immediate response. The 302 Series activate whenever ambient air temperature reaches a detector’s setting, eliminating the thermal time lag inherent in conventional heat detectors.
- Eliminates false alarms. The 302 Series do not respond to momentary temperature fluctuations below the selected temperature.
- Universal application. The 302 Series can be used in all areas for any type of occupancy.
- Self-restoring.
- Hermetically sealed. Shock resistant, corrosion resistant, and tamper-proof.
Principles Of Operation
The 302 Series rate-anticipation heat detectors respond and activate the fire alarm immediately whenever the ambient temperature reaches the preset temperature setting. Under rapid heat rise conditions, the rate-anticipation feature enables the detector to respond one to three degrees ahead of the setting. At the same time, however, it does not respond to momentary temperature fluctuations below the selected protection level, thus eliminating false alarms. When temperature drops back down below the protection level, the detector automatically resets itself.
Dimensions (Model 302)
Total overall length: 4-1/8″ (10.48 cm).
Base diameter: 2″ (5.08 cm).
Electrical Ratings
Voltage | Current |
---|---|
6 – 125 VDC | 5 amps |
6 – 25 VDC | 1 amp |
125 VDC | 0.5 amp |
Application Information
302 Series detector have a smooth ceiling UL rating of 50′ x 50′ (15.24 x 15.24 meters) and are the only type of heat detectors having such a rating on both fixed temperature and rate anticipation.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL Listed: S539 (302-AW-135/-194; 302-ET-135/-194; 302-135-194)
- FM Approved: (302-AW-135/-194; 302-ET-135/-194; 302-135/-194)
- CSFM: 7270-0021:001
Cut-Away View
Thermotech Model 302 Series Rate-Anticipation Heat Detectors
Model Number | Description | Refer To |
---|---|---|
302-194 | 135°F Interior Vertical Mounting | Note 1 below |
302-135 | 194°F Interior Vertical Mounting | |
302-AW-135 | 135°F All-Weather Vertical Mounting | Note 2 below |
302-AW-194 | 194°F All-Weather Vertical Mounting | |
302-ET-135 | 135°F All-Weather Vertical Mounting | Note 3 below |
302-ET-194 | 194°F All-Weather Vertical Mounting | |
302-EPM-135 | 135°F Explosion Proof Mounting | Note 4 below |
302-EPM-194 | 194°F Explosion Proof Mounting | |
AP-P | Decorative white plastic adaptor plate for mounting 302 and 302-AW to 4” | |
outlet box. |
NOTE 1: For interior mounting in any atmosphere that is compatible with
terminal-screw-type connections. UL rating 50′ x 50′ (15.24 x 15.24 meters).
NOTE 2: Hermetically sealed for moisture-proof or dust-proof
installations. Requires no special backbox when the all-weather leads are
properly spliced to “THW” or equivalent type wire.
NOTE 3: Hermetically sealed for moisture-proof or dust-proof
installations. Requires no special backbox. Has plastic hexagonal wrench grip
bushing with 1/2″ (1.27 cm) conduit threads for attachment to threaded hub
cover, or any outlet box.
NOTE 4: Explosion-proof for installation in hazardous locations. Has
hexagonal wrench-grip bushing with 1/2″ (1.27 cm) conduit threads for
attachment to threaded hub cover of Series JL fixture fitting as manufactured
by Killark Electric Co., or equal.
NOTIFIER® is a registered trademark of Honeywell International Inc.
©2008 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
| This document is not intended to be used for installation purposes. We try
to keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Notifier.
Phone: 203-484-7161, FAX:
203-484-7118.