NOTIFIER 100 Series Low Profile Plug In Smoke Detector Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
DN-7049:B1
100 Series
100 Series Low-Profile Plug-In Smoke Detectors
Conventional Initiating Devices
General
100 Series Plug-in Smoke Detectors offer superb performance and reliability in
a profile which is just 2″ (5.1 cm) deep. Model 2151 (photoelectric sensor)
and model 2151T (photoelectric sensor with thermal) can be used with a variety
of different adapter bases in several wiring configurations and voltages.
Other features include: low current draw, stable performance in high air
velocities, built-in tamper resistant base design, remote LED option,
removable cover, and built-in test switch.
The 100 Series is designed to meet the performance criteria designated by UL.
Its sensing chambers are sealed against back pressure air flow, dirt, and
insects. This chamber is protected by a fine mesh screen which can be cleaned
or replaced. Additional key features include a variety of mounting bases and a
full line of accessories.
All 100 Series photoelectric smoke detectors contain a unique optical sensing
chamber designed to sense smoke particles produced by a wide range of
combustion sources. A custom integrated circuit incorporates signal processing
to reduce false alarms.
Model 2151(A) photoelectric detector’s unique optical sensing chamber is
engineered to sense smoke by a wide range of combustion sources. Dual
electronic thermistors add 135°F fixed temperature thermal sensing on model
2151T.
Specifications
Operating Voltage/Alarm Current:| See Adapter Base Selection Guide (see
page 2).
---|---
Standby Current:| 120A Standby.
Sensitivity:| 1 – 3.18%/ft.
Height:| 2.0” in B401.
Diameter:| 4.1” installed in B401; 6.2” installed in B110LP.
Shipping Weight:| 5.2 oz.
Construction:| Flame retardant thermoplastic.
Temperature:| – Photo: 32°F to 120°F (0°C to 49°C).
– Photo/Thermal: 32°F to 100°F (0° to 38°C)
UL Listed Velocity Range:| Photo: 0–3000 fpm (0–15.2 m/s).
Humidity Range:| 10%–93% RH non-condensing.
Smoke Detector Spacing:| On smooth ceilings (as defined in NFPA 72),
spacing of 30 feet (900 sq. ft.) may be used as a guide. Other spacing may be
used depending on ceiling height, high air movements, and other conditions or
response requirements.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL Listed: S911.
- ULC Listed: CS308.
- CSFM: 7272-1653:0122.
- FM Approved.
- MEA Approved: 205-94-E.
- Maryland State Fire Marshal : #2180.
Product Line Information
NOTE: “A” suffix indicates ULC listed model. 2151(A): Low-profile
photoelectric detector. Must be mounted to one of the B100 Series or B400
Series bases listed in the Adapter Base Selection Guide.
2151T: Low-profile photoelectric detector with thermal. Must be mounted
to one of the B100 Series or B400 Series bases listed in the Adapter Base
Selection Guide.
F110: Retrofit replacement flange for B400 Series flanged bases.
RA100Z: Remote annunciator for 2 or 4 wire systems, 3-32V. Fits standard
single gang electrical box.
SENS-RDR: Hand-held sensitivity reader.
SMK400E: Surface mounting kit provides for entry of surface wiring
conduit. For use with B401 or B401R mounting bases only.
EOLR-1: End of line relay for power supervision, 12/24 VDC systems.
M02-04-00: Test magnet.
M02-09-00: Test magnet with 32° telescoping handle.
XR2B: Detector removal tool. Allows installation and/or removal of 100
Series detector heads from base in high ceiling installations when used with
XP-4.
XP-4: Extension pole for XR2B. Comes in three 5 ft. sections.
C58-227-01: Replacement dust cover for 100 Series smoke detectors.
RMK400: Recessed mounting kit (B401 sold separately).
Adapter Base Selection Guide
Base Model Number| Loop Type| Current Limit Resistor|
Contact Type| Nominal Voltage| Current Draw on
Alarm (mA)
---|---|---|---|---|---
B110LP| 2-wire*| No| —| 12/24 VDC| 10-130
B11ORLP/B401BRt| 2-wire| Yes| —| 24 VDC| 10-62
B112LP/B402t| 4-wire| Yes| Form A & C| 24 VDC| 17-36
B114LP/B404t| 4-wire| Yes| Form A & C + A Supervisory| 120 VAC| 75 mA AC
maximum
B116LP/B406t| 2-wire| No| Form C| 24 VDC| 20-100
B401t| 2-wire*| No| —| 12/24 VDC| 10-130**
- Functionality contingent on panel compatibility.
** Must be limited by control panel.
† Flangeless base.
Relay Contact Ratings: Resistive or inductive (60% power factor) load.
Form A: 2.0 A at 30 VAC/DC
Form C: 0.6 A at 110VDC, 2.0 A at 30 VDC
1.0 A at 125VAC, 2.0 A at 30 VAC
Junction Box Selection Guide*
Base Model
Number| Single
Gang| 3-1/2″
Octagon| 4″
Octagon| 4″ Square| 50 mm| 60 mm| 75 mm
---|---|---|---|---|---|---|---
B401| No| No| No| No| Yes| Yes| No
B110LP/RLP| Yes| Yes| Yes| Yes| No| No| No
B112LP/B116LP| Yes| Yes| Yes| Yes| Yes| Yes| Yes
B114LP| No| No| Yes| Yes| No| No| No
- Box depth contingent on base and wire size. Refer to National Electrical Code or local applicable codes for appropriate recommendations.
NOTIFIER® is a registered trademark of Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
| This document is not intended to be used for installation purposes. We try
to keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice.
For more information, contact
Notifier. Phone: 203-484-7161, FAX:
203-484-7118.
www.notifier.com|
---|---|---