NOTIFIER SD-651 Low Profile Photoelectronic Plug In Smoke Detector User Guide
- June 9, 2024
- NOTIFIER
Table of Contents
SD-651 Low Profile Photoelectronic Plug-in Smoke Detector
Installation and Maintenance Instructions
Before installing detectors, please thoroughly read, System Smoke Detector Application Guide, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from Notifier.
GENERAL DESCRIPTION
The Model SD-651 low profile, photoelectronic detector uses a state-of-the-art
optical sensing chamber. This detector is designed to provide open area
protection and to be used with compatible UL-listed control panels only. The
capability of plugging this detector into a variety of special bases makes it
more versatile than equivalent direct-wired models.
Two LEDs on the detector light to provide a local 360° visible alarm
indication. They flash every 10 seconds to indicate power is applied and the
detector is working properly. The LEDs latch on in alarm. Remote LED
annunciator capability is standard and may be implemented through an optional
accessory RA400Z. The alarm can be reset only by a momentary power
interruption. This detector may be tested by activating the internal reed
switch with a magnet.
SPECIFICATIONS
Size: Height | 1.7 inches (43 mm) |
---|---|
Diameter | 4.0 inches (101 mm) |
Weight: | 3.6 oz. (102 g) |
Operating Temperature Range | -10° to 60°C (14° to 140°F) |
Note: Do not install in locations where normal ambient temperature range
extends beyond
0° to 49°C (32° to 120°F)
Operating Humidity Range| 10% to 93% Relative Humidity noncondensing
Latching Alarm| Reset by momentary power interruption.
BASE SELECTION AND WIRING GUIDE
Refer to the installation instructions for the Plug-in Detector Bases for base selection and wiring instructions. Notifier has a variety of detector zr base manual for testing procedure.)
WARNING
Remove power from initiating-device circuits before installing detectors.
-
Install detectors:
a. Place the detector into the detector base
b. Turn the detector clockwise until the detector drops into place.
c. Continue turning detector clockwise to lock it in place. -
Tamper Resistance: The detector bases can be made tamper resistant. When capability is enabled, detectors cannot removed from the base without the use of a tool. See the detector base installation manual of the detector base for details in using this capability.
-
After all detectors have been installed, apply power to the control unit.
-
Test the detector using the magnet as described under TESTING.
-
Reset the detector at the system control panel.
-
Notify the proper authorities that the system is back on line.
CAUTION
Dust covers can be used to help limit dust entry into the smoke detector, but
they are not a substitute for removing the detector during building
construction.
Remove any dust covers before placing the system in service.
TESTING
Before testing notify the proper authorities that the smoke detector system is
undergoing maintenance and will temporarily be out of service. Disable the
zone or system undergoing maintenance to prevent unwanted alarms. Detectors
must be tested after installation and as part of periodic maintenance. Test
the SD-651 as follows:
NOTE: Before testing the detector, check to ensure the LEDs blink. If
they do not, the detector has lost power (check the wiring) or it is defective
(return it for repair).
A. Test Magnet (Model no. M02-04-01)
- Place the magnet against the cover in the location designated by the raised mark to activate the test feature (see Figure 1).
- The LEDs should latch ON within 5 seconds indicating alarm and annunciating the panel.
B. Test Module ( MOD400R).
Use the MOD400R with a DMM or voltmeter to check the detector sensitivity as
described in the MOD400R manual.
C. Aerosol Generator (Gemini 501)
Set the generator to represent 4% to 5%/Ft. obscuration as described in the
Gemini 501 Manual. Using the bowl shaped applicator, apply aerosol until unit
alarms.
Notify the proper authorities that the system is back on line. Detectors that
fail these tests should becleaned as described under MAINTENANCE and
retested. If the detectors still fail these tests they should be returned for
repair.
MAINTENANCE
It is recommended that the detector be removed from its mounting base to
facilitate cleaning. The detector is cleaned as follows:
NOTE: Before removing the detector, notify the proper authorities that
the smoke detector system is undergoing maintenance and will be temporarily
out of service. Disable the zone or system undergoing maintenance to prevent
unwanted alarms.
- Remove the detector cover by prying away the four side tabs with a small-bladed screwdriver, and then pulling the cover from the base.
- Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 3, otherwise skip to Step 8.
- Remove the screen assembly by pulling it straight out (see Figure 2).
- Remove the sensing chamber cover by pulling it straight out.
- Clean the vaned chamber piece by vacuuming or blowing out dust and particles.
- Replace the sensing chamber cover, aligning the arrow on the top with arrow on the printed circuit board.
- To replace the screen, place it over the chamber assembly, turning it until it snaps into place.
- Replace the cover using the test module socket and LEDs to align the cover and then gently pushing it until it locks into place.
- Reinstall the detector.
- Test the detector as described in TESTING.
- Reconnect disabled circuits.
- Notify the proper authorities that the system is back on line.
Please refer to insert for the Limitations of Fire Alarm Systems
N500-20-00
I56-651-08R