GENERAL
Electronic MIZ-Mini Horns are designed to produce high sound output with
minimal current requirements. They are UL Listed under Standard UL 464 for
Audible Signal Appliances and ULC Listed under first draft Standard ULC-S525
dated August 1997 Audible Signal Appliances For Fire Alarm Systems. All inputs
are polarized for compatibility with standard reverse polarity supervision of
circuit wiring by a Fire Alarm Control Panel (FACP). MIZ-Mini Horns are
recommended for alarm signaling for individual rooms in apartments, motels,
hotels and offices. These appliances are attractive in appearance and reliable
performers. They mount to standard backboxes to reduce the cost of
installation. All models are Listed for indoor use with the backboxes
specified in these instructions (See Mounting Options).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All
warnings are printed in bold capital letters.
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER
APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
SPECIFICATIONS
Table 1: UL and ULC Listed Models and Ranges
Model| Voltage| Current| Reverberant dBA Per UL 464 At 10 Feet| Anechoic
dBA Per ULC-S525-99 At 10 Feet| Mounting Options
Continuous| Code 3| Continuous| Code 3
DC| RMS| dBA| dBA| dBA| dBA
* MIZ-TC12| 8.0| .011| .017| 77.8| 73.3| 82.8| 82.7| ** A,B
12.0| .016| .025| 80.9| 76.8| 86.3| 85.9
17.5| .023| .035| 83.9| 79.8| 89.9| 89.7
** MIZ-TC24| 16.0| .012| .027| 79.7| 75.5| 84.8| 84.7| ** A,B
24.0| .017| .038| 83.2| 78.8| 87.9| 87.9
33.0| .024| .043| 85.8| 81.3| 90.6| 89.7
WARNING: OPERATING THE SERIES MIZ-TC12 UL VERSION, SET ON “CODE 3 TONE”
dBA AT MINIMUM VOLTAGE (8.0VDC) WILL NOT MEET THE 75 dBA MINIMUM UL
REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION SERVICE
(NOTED BY * IN TABLE 1). MODELS WITH SETTINGS THAT PRODUCE LESS THAN 75 dBA
MAY NOT BE HEARD. THIS SETTING IS ACCEPTABLE ONLY FOR GENERAL SIGNALING (NON-
FIRE ALARM) USE.
WARNING: OPERATING THE MIZ-TC12 AND MIZ-TC24 AT MINIMUM VOLTAGE (8.0VDC
FOR 12 VOLT MODEL AND 16.0 FOR 24VDC MODEL) WILL NOT MEET THE 85 dBA MINIMUM
ULC ANECHOIC SOUND LEVEL REQUIRED FOR FIRE PROTECTION SERVICE (NOTED BY IN
TABLE 1). MODELS WITH SETTINGS THAT PRODUCE LESS THAN 85 dBA MAY NOT BE HEARD.
THIS SETTING IS ACCEPTABLE ONLY FOR GENERAL SIGNALING (NON-FIRE ALARM) USE.
The UL Listed “Regulated Voltage” range is shown in Table 1 using either
filtered (DC) or unfiltered full-wave-rectified (FWR) voltage. Check the
minimum and maximum output of the power supply and standby battery and
subtract the voltage drop from the circuit wiring resistance to determine the
applied voltage to the signaling appliance.
NOTE:**
- Anechoic dBA is measured in anechoic chamber with peak meter response.
- Reverberant dBA is rated per UL standard 464.
- As per ULC requirement, the -3dB off-axis is 15° and the -6dB off-axis is 30°.
Copyright 1999, 2000 Wheelock, Inc. All rights reserved.
WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BY ALL APPLIANCES THAT
ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES AND
SIGNALING CIRCUITS DOES NOT EXCEED THEIR RATED CURRENT. OVERLOADING THESE
SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN
EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
When calculating the total current: use Table 1 to determine the highest value
of “Rated Average Current” for an individual horn (across the expected
operating voltage range of the device); then multiply this value by the total
number of devices; be sure to add the current for any other devices powered by
the same source and include any required safety factors.
WARNING: MAKE SURE THAT ALL FUSES USED ON SIGNALING CIRCUITS ARE RATED TO
HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE
CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE SIGNALING
CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.
CAUTION: This product is not designed to be used with the SM or DSM Sync
Modules.
WIRING INFORMATION
- Appliances have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
- Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision shown in Figure 2. The polarity shown in the wiring diagrams is for the operation of the appliances. The polarity is reversed by the FACP during supervision.
NOTE: Code 3 (shorted) Continuous (open)
Unit is shipped from factory with Code 3 selected (jumper to right). Installer
can select continuous audible signal by moving the factory installed jumper to
the left one position. The jumper will be placed only on the left pin, leaving
the circuit open to select Continuous.
MOUNTING OPTIONS
CAUTION: The following figures show the maximum number of field wires
(conductors) that can enter the backbox used with each mounting option. If
these limits are exceeded, there may be insufficient space in the backbox to
accommodate the field wires and stresses from the wires could damage the
product.
Although the limits shown for each mounting option comply with the National
Electrical Code (NEC), Wheelock recommends use of the largest backbox option
shown and the use of approved stranded field wires, whenever possible, to
provide additional wiring room for easy installation and minimum stress on the
product from wiring.
MOUNTING PROCEDURES
CAUTION: Check that the installed product will have sufficient clearance and
wiring room prior to installing backboxes and
conduit, especially if sheathed multiconductor cable or 3/4″ conduit fittings
are used.
- Mounting hardware for each mounting option is supplied.
- Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. When extension rings are required, conduit should enter through the backbox, not the extension ring. Use Steel City #53151 (1-1/2″ deep) or #53171 (2-1/8″ deep) extension rings (as noted in the mounting options) or equal with the same cut-out area.
- When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling appliance.
- Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
- Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance.
- For Fire Alarm applications using white MIZ-Mini Horns, a red “Fire” Label is provided. Affix this label to the front of the mounting plate to identify the function of the alarm appliance.
- All models are UL Listed for indoor use with a temperature range of +32°F to +120°F (0°C to +49°C) and maximum humidity of 85% RH.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER
DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS,
OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION,
OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND
WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
IMPORTANT: READ SEPARATE “GENERAL INFORMATION” SHEET FOR INFORMATION ON
THE PLACEMENT, LIMITATIONS, INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING
OF NOTIFICATION APPLIANCES.
CAUTION: Check the installation instructions of the manufacturers of
other equipment used in the system for any guidelines or restrictions on
wiring and/or locating Notification Appliance Circuits (NAC) and notification
appliances. Some system communication circuits and/or audio circuits, for
example, may require special precautions to assure electrical noise immunity
(e.g. audio crosstalk).
If this appliance is required to produce a distinctive three-pulse Temporal
Pattern Fire alarm Evacuation Signal (for total evacuation) in accordance with
NFPA 72, 1999 Edition, the appliance must be used with a fire alarm control
unit that can generate the temporal pattern signal. Refer to manufacturer’s
installation manual for details.
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna,
- Increase the separation between the equipment and receiver,
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and
- Consult the dealer or an experienced radio/TV technician for help.
Limited Warranty
Wheelock products must be used within their published specifications and must
be PROPERLY specified, applied, installed, operated, maintained and
operationally tested in accordance with these instructions at the time of
installation and at least twice a year or more often and in accordance with
local, state and federal codes, regulations and laws. Specification,
application, installation, operation, maintenance and testing must be
performed by qualified personnel for proper operation in accordance with all
of the latest National Fire Protection Association (NFPA), Underwriters’
Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National
Electrical Code (NEC), Occupational Safety and Health Administration (OSHA),
local, state, county, province, district, federal and other applicable
building and fire standards, guidelines, regulations, laws and codes
including, but not limited to, all appendices and amendments and the
requirements of the local authority having jurisdiction (AHJ). Wheelock
products when properly specified, applied, installed, operated, maintained and
operationally tested as provided above are warranted against mechanical and
electrical defects for a period of three years from date of manufacture (as
determined by date code). Correction of defects by repair or replacement shall
be at Wheelock’s sole discretion and shall constitute fulfillment of all
obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL
IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS
INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES
ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK
MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR
STATUTORY WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR
ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR
THE USER’S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER’S INTENDED RESULTS.
THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER
SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK’S
CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS,
WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE
UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD
OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET
THE USER’S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS,
BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN
THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS
USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE
EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND
UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE.
WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR
REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE
WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR
CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE
PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK’S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A
PRODUCT.
Limitation of Liability
WHEELOCK’S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND
BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR
CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE,
REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE
PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM.
WHEELOCK’S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE
INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT
SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT
OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING
IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL
OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION
OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT
APPLY TO ALL PURCHASERS. 6/00
273 Branchport Avenue
Long Branch, N.J. 07740
800-631-2148 – US
800-397-5777
Canadawww.wheeelockinc.com
www.PDF-Zoo.com
firealarmresources.com
P83946 E
Sheet 5 of 4
Documents / Resources
|
NOTIFIER Wheelock MIZ-MINI Fire Alarm
Horn
[pdf] Instruction Manual
MIZ-MINI, Wheelock MIZ-MINI Fire Alarm Horn, MIZ-MINI Fire Alarm Horn, Fire
Alarm Horn, Alarm Horn, Horn
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>