Blue Heaven Technologies Logo ASHRAE Standard 52.2-2017
Test Report
Date: 19-Apr-23
TEST NO. 23-191-1
ASHRAE Standard 52.2-2017
TEST REPORT
Initial Efficiency / Resistance

Filter Description

Manufacturer BNX
Filter Model 1″ Pleat
Part Number MERV 8
Generic Filter Type Pleated
Nominal Dimensions (H x W x D) 20″ x 20″ x 1″
Pocket / Pleat Quantity 23 Pleats
Media Type Synthetic
Est. Gross Media Area 5.62 Ft²
Adhesive Type N A

Blue Heaven Technologies MERV 8 TruFilter 20x20x1 Air Filter -
Fig

Test Conditions

Loading Dust Type NA
Barometric Pressure (In. Hg.) 29.38
   Test Air Temp (degrees F.) 82
   Relative Humidity (%) 40

Test Results

Airflow Rate (CFM) 819
Nominal Face Velocity (fpm) 295
Initial Resistance (in WG) 0.12
E1 (%) Initial Efficiency 0.30 – 1.0 um 5
E2 (%) Initial Efficiency 1.0  – 3.0 um 31
E3 (%) Initial Efficiency 3.0 – 10.0 um 72

Estimated Minimum Efficiency Reporting Value (MERV) If initial data is minimum| MERV 8 @ 819 CFM

Comments Tested For: BNX

Test Performed by: RAS
Approved By:
Page 1 of 3
Manager
Important Note: Please be advised that the ASHRAE committee SSPC 52.2. in March 2016, has published “addendum e” relative to the 52.2-2012 test protocol. This addendum restricts the use of the acronym “MERV” as only applicable to a test report that has been completed using the “entire procedure prescribed by the standard”. This report is a modified version of the procedure and therefore, subject to that ruling.In the best interest of our customers, Blue Heaven Technologies has elected to delay this action until further assessment can be made at committee level. Where applicable, the qualified use of the term “MERV” will continue to be part of our reported data.

Blue Heaven Technologies MERV 8 TruFilter 20x20x1 Air Filter -
Resistance

Data – Initial Resistance

Airflow (CFM) Resistance (in WG)
0 0
205 0.01
410 0.04
614 0.08
819 0.12
1024 0.17

Data – Particle Removal Efficiency

Particle Size Range (urn)| Geometric Mean Diam (um)| Initial Particle Removal Efficiency (%)
---|---|---
0.30-0.40| 0.35| 1.
0.40-0.55| 0.47| 3.
0.55 0.70| 0.62| 5.
0.70 1.00| 0.84| 9.0
1.00 1.30| 1.| 16.
1.30 1.60| 1.| 25.
1.60 2.20| 2.| 34.
2.20 3.00| 3.| 50.
3.00 4.00| 3.| 65.
4.00 5.50| 5.| 72.
5.50 7.00| 6.20| 75.
7.00 – 10.00| 8.| 76.

Blue Heaven Technologies
2820 S. English Station Rd. Louisville, KY
502 357 0132
2820 S. English Station Road – Louisville, KY 40299
Tel:502-357-0132
Fax502-267-8379