NOTIFIER NION-232B Fire Alarm Module Installation Guide

June 9, 2024
NOTIFIER

NOTIFIER -logo NION-232B-FS90
Product Installation Document

This document covers the procedures and specifications for installing the above listed unit and when appropriate, information regarding configuration on the monitored device. For more detailed configuration and operation information, refer to Network Installation Manual, Echelon Local Area Server Manual, or BCI 3 Manual as appropriate.

Description of the Serial NION-232B

The Serial NION-232B (Network Input Output Node) is the EIA-232 interface used with the network. All of the system components are based on LonWorks™ (Local Operating Network) technologies. The Serial NION-232B provides transparent or interpreted communications between the workstation and control panels. Unless otherwise
noted, full control capabilities are available for each interface. Check specific connections for details.
The NION connects a LonWorks™ FT-10 or FO-10 network, and the RS-232 port of control panels. It provides a single, two-way communication channel for RS-232 serial data when connected to a control panel. NIONs are specific to the type of network to which they connect (FT-10 or FO-10). The transceiver type must be specified and ordered separately when ordering the NION.
The NION can be powered by any 24VDC power limited source with battery backup which is UL listed for use with fire protective signaling units.
The NION mounts in an enclosure (NIS CAB-1 or CHS-4L in CAB-3 series enclosure) with conduit knockout.

Site Requirements

The NION-232B can be installed in the following environmental conditions:

  • Temperature range of 0ºC to 49ºC (32°F – 120°F).
  • 93% humidity non-condensing at 30ºC (86°F).

Mounting

The NION-232B is designed to be installed on a wall within 20 feet of the control panel in the same room. The type of hardware used is at the discretion of the installer, but must be in accordance with local code requirements.

NOTIFIER NION 232B Fire Alarm Module-

Serial Communication Description

The baud rate, parity and data bits of the NION-232B must be equal to those of the RS-232 serial port of the control panel. The NION-232B comes from the factory preset for the application it was ordered to fill. These settings are made on switch S2.
If it becomes necessary to change any of these settings use the chart below:

   Baud Rate   Switch Position 4   Switch Position 5   Switch Position 6
600 Off On On
1200 On Off On
* 2400 Off Off            On
4800 On On Off
9600 Off On Off
  • All Notifier equipment operates at 2400 baud.
   Parity Switch Position 2 Switch Position 3
      None On On
      Odd On Off
      Even Off Off
  Data Bits Switch Position 1
8 On
7 Off

NOTE: If the device connected to the NION calls for 9 data bits then the NION must be set to 8 data bits with either Even or Odd parity.

Switch S2 Settings for the NION-232B RS-232 Configuration

NION Power Requirements

The NION-232B requires 24 VDC @ 0.080 A nominal and battery backup in accordance with local code requirements. It can be powered by any power limited source with battery backup which is UL listed for use with fire protective signaling units.

NOTES: It is recommended that the installer conform to local code requirements when installing all wiring . All power connections must be non- resettable. Refer to the current Notifier catalog for specific part numbers and ordering information for each NION. Always remove power from the NION before making any changes to switch settings and removing or installing option modules, SMX network modules and software upgrade chips or damage may result. Always observe ESD protection procedures.

Serial Connections with the FS90 Control Panel
The NION-FS90 must be connected to the Serial Printer port of the LH Interface board installed with the FS90 Control panel. RS-232 settings are: Baud Rate – 9600, Data Bits – 8, Stop Bits – 1, Parity – None.
NOTE: This interface does not provide direct reset, acknowledge or silence/unsilence control.

Powering the NION
The NION-FS90 can be powered from any power limited source UL or ULC listed, as appropriate for your area, for use with fire protective signaling units, providing +24VDC +/- 10% @ 0.080 A.
Device Addressing for the FS90 Control Panel
FS90 device addresses contain a seven digit individual device address.

< Address> AAAAAAA
Example: The panel reports 01.01.110
The NION reports 0101110 to the WKS.
NOTE: Use only wire for power limited systems. Power limited wire runs use type FPLR, FPLP, FPL or equivalent cabling per NEC 760.

NOTIFIER NION 232B Fire Alarm Module-Wiring Diagram

Document 51222 NION-232B-FS90 Installation Rev. A 6/22/99