SIEMENS FDBZ492 Air Duct Monitoring Housing Instruction Manual
- June 9, 2024
- SIEMENS
Table of Contents
SIEMENS FDBZ492 Air Duct Monitoring Housing
INTRODUCTION
Models FDBZ492, FDBZ492-R and FDBZ492-HR from Siemens Industry, Inc., are air duct monitoring housings containing sampling tubes. When used with a compatible smoke detector, smoke and combustion products are detected for shutdown of the duct system and/or operation of supplementary equipment as provided by the system control panel. See the following chart for usage.
TECHNICAL DATA
AIR DUCT CONDITIONS
Temperature Range:
PE-11/-11C, FP-11/-11C, HFP-11, HFPO-11, SFP-11, SFPO-11, 8854, 8710,
8713,FDOOTC441, OOHC941, 32OF (0OC) – 100OF (38OC) per UL 268 OP121, FDOOT441,
OOH941, FDO421, OP921, 32OF (0OC) – 120OF (49OC) per UL 268
Altitude Range:
FDBZ492, FDBZ492-R and FDBZ492-HR—No altitude limitations
Relative Humidity Range:
0-95% (non-condensing/non-freezing)
Air Duct Velocity Range:
100-4000 ft/min – FDBZ492, FDBZ492-R and FDBZ492-HR
Sampling Tube Pressure Range of Differences:
Greater than 0.01 and less than 1.2 inches of water column
These air duct detectors are designed for detection and control of products of
combustion in a duct system. They are not to be used for open area protection.
DO NOT USE air duct detectors with Alarm Verification.
The SFP-11 and SFPO-11 are approved for use in Canada only.
ASSEMBLY
This detector has a cover tamper (removal) switches. Care should be taken when
installing the cover. Squarely place the cover on the unit to aviod possible
damage to the switches.
DO NOT SLIDE COVER INTO POSITION.
APPLICATION
The duct smoke detectors provide early detection of smoke and products of
combustion present in air moving through an HVAC duct supply, return, or both.
These devices are designed to prevent the recirculation of smoke in areas by
the air handling system’s fans and blowers. Complete systems may be shut down
in the event of smoke detection.
For the correct installation of a duct smoke unit please refer to NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard for Installation of Air Conditioning and Ventilation Systems) and NFPA 92A (Recommended Practice for Smoke Control Systems).
OPERATION
When the Models FDBZ492, FDBZ492-R and FDBZ492-HR are operating, a sample of
air is drawn from the duct and passed through the sampling chamber by means of
the input sampling tube. The air sample passes through the smoke detector
mounted in the duct housing and is exhausted back into the duct through the
outlet tube.
This detector is equipped with cover removal switches (SW1, SW2) that
instantly provides a trouble condition upon removal of the clear cover. For
all testing and inspection with the cover removed, the cover removal switches
(designated as SW1,SW2 on PCB) must be manually depressed to simulate normal
operation.
LED Indicator
The FDBZ492, FDBZ492-R and FDBZ492-HR contain an LED indicator (located on the smoke detector) capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the microprocessor based detector checks the following:
- for smoke in its sensing chamber
- that its critical smoke sensing electronics are operating.
Based on the results of these checks, the LED indicator flashes as follows:
Flash Color | Condition | Flash Interval (Seconds) |
---|
PE-11/ PE-11C-
/8854
| FP-11/FP-11C/ HFP-11/HFPO-11/ SFP-11/SFPO-11/ 8710/8713|
OP121| FDO421/OP921| FDOOT441/ FDOOTC441/- OOH941/ OOHC941
Green| Normal supervisory operation.| 7| 4| 10| 8| 10
Yellow| Detector requires service (cleaning or repair) or is operating beyond
its environmental specifications.*| 7-30| 4| 5| 4| 4
Red| Alarm| 2½| 4| 2½| 1| 1
No Flashes| Detector is not powered, or requires repair/replacement.| –| –| –|
–| –
Note: OP121, FDO421, OP921, FDOOT441, FDOOTC441, OOH941, OOHC941 detectors are not serviceable and need replacement.
MOUNTING THE AIR DUCT HOUSING
Location on Duct System
This guideline contains general information on duct smoke detector installation, but does not preclude the NFPA documents listed. Siemens Industry, Inc. assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for a duct smoke detector, the following factors must be considered.
-
A uniform non-turbulent (laminar) airflow between 100 ft/min. to 4,000 ft/ min. must be present in the HVAC duct. To determine duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP velocity meter (or equivalent).
-
To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of velocity and pressure differential within specifications is required.
The pressure differential between the input sampling (high pressure) tube and outlet (low pressure) tube for the smoke duct detector should be greater than 0.01 inches of water and less than 1.2 inches of water. -
Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access for viewing and serviceability.
-
When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside “fresh” air.
-
When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in the supply air side may monitor upstream equipment and/or filters.
-
Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers.
-
To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high humidity exists,
or in areas where the duct may contain gases or excessive dust.
Duct Preparation
The Air Duct Housings come with an installation kit that contains the
following items:
- Short return (outlet) sampling tube
- Stopper
- Two #12 x 3/4” sheet metal screws
- Mounting template (packaged separately)
Remove mounting template from the installation kit. Remove paper backing from the mounting template and affix it to the duct at the desired location. Using the template as a guide, drill (2) mounting holes, 3/32″ (2.5mm) for the #12 X 3/4” sheet metal screws packaged in the installation kit. Drill or punch (2) 1¼” (32mm) holes for input sampling and outlet tubes, using the template as a guide. Clean all holes.
Sampling Tube Installation
The duct smoke detectors use a specially notched sampling tube, which may be ordered separately in one of four standard lengths.
- ST-10 For duct widths of 6″ to 1.0’
- ST-25 For duct widths of 1.0’ to 3.0’
- ST-50 For duct widths of 3.0’ to 5.0’ (requires support)
- ST-100* For duct widths of 5.0’ to 10.0’ (requires support)
This model is supplied as two 5 ft. sections with a coupling.
Assembly is required for installation.
Each model is manufactured with a different number and size of sampling holes.
Only the specific tube must be used for the specified duct width.
Standard sampling tubes are steel tubes with air intake holes drilled the
entire length of the tube. These tubes can be cut to length and must span at
least 80% the width of the duct. Sampling tubes over 3.0’ must be supported on
the opposite side of the duct. To ensure the correct operation, the red
stopper (stopper in installation kit) must be inserted in the end of the air
input sampling tube. If the input tube protrudes through the opposite side of
the duct, the opening around the tube must be sealed.
For custom duct widths, always use the next longest standard size and cut down
to the exact requirement.
NOTE: Mountings shown are typical. Detectors can be installed side, bottom or top of duct as long as proper tube operation and flow/pressure performance is maintained.
Once the airflow direction has been determined (refer to Figure 3), insert the input and outlet tubes into the duct housing.
- Remove the cover from the housing.
- Loosen the screw and rotate the tube retainer until the input tube is inserted and oriented properly. Ensure that the notched end of the tube is inside the housing and that the air input sampling tube is positioned so that the input holes are directly facing the airflow.
- Once the tube is installed, rotate the retainer back into place and tighten screw.
- Install the outlet tube in the remaining position. Once the tube is installed, rotate the retainer back into place and tighten screw.
Mounting
After securing the input and outlet tubes to the duct smoke unit, (or
initially placing
the tubes through the 1¼” holes drilled or punched in the HVAC duct to accept
the input and outlet tubes and then attaching them to the duct unit), hold the
duct unit assembly in position and use (2) # 12 X 3/4” sheet metal screws
(packaged in the installation kit) to secure the duct smoke detector to the
HVAC duct sheet metal.
Air Duct Sampling Tube Pressure Measurement
The Model PDM-3 Pressure Differential Measuring device should be used to
ensure that the sampling tube pressure differential is within the specified
limits. The differential pressure between the two tubes should be greater than
0.01 inches of water and less than 1.2 inches of water. Qualified personnel
should take measurements in accordance with the PDM-3 instructions, P/N
315-085535.
WIRING
Conduit Knockouts
Determine knockout size required based upon installation wiring. Refer to
Figure 4.
Select knockout and remove by placing screwdriver at center of knockout and
tap with a hammer until the knockout breaks out. Clean the hole before
installing conduit.
Wiring The FDBZ492, FDBZ492-R and FDBZ492-HR should be connected as shown in Figures 5, 6, 7, 8, and 9. Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit.
The FDBZ492 is used with the 8854, PE-11/PE-11C, FP-11/FP-11C and OP121. It is also used with the HFP-11/HFPO-11, 8710, 8713 detector in the FireFinder- XLS/Desigo Fire Safety Modular/Cerberus PRO Modular, FS-250 or MPC6000, 7000 System. The FDBZ492 is also used with the SFP-11/SFPO-11 detector in the FS- 250C System. The FDBZ492 is also used with the FDO421, FDOOT441, FDOOTC441, OP921, OOH941,OOHC941 detector in the Desigo and Cerberus Fire Alarm Systems. The FDBZ492- HR must be used for the relay version. Also, all optional accessories in the same loop must be compatible with the detector series being used. These devices should be interconnected as shown in Figure 8 and wired to the DLC, FS-DLC or FDLC. (Refer to the DLC Installation Instructions, P/N 315-033090, or the FS-250, P/N 315-049353,or the FS-250C Manual, P/N 315-049589C, or the MPC-6000/MPC-7000 Manual, P/N 315-447309, as applicable.) The HFP-11, HFPO-11, SFP-11, SFPO-11, 8710, 8713,FDO421, FDOOT441, FDOOTC441, OP921, OOH941, and OOHC941 are polarity insensitive detectors. Line 1 and Line 2 can be either line of the loop. Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit.
When replacing a detector with a different model, be aware that existing detector accessories connected to the base or air duct housing that were compatible with the old detector may not be compatible with the new detector. Always read the Installation Instructions accompanying the detector to determine detector and accessory compatibility.
Installation Of Smoke Detectors
To Install:
- Remove cover by loosening the four screws. Take off the cover and set it aside.
- Align detector with base and insert detector.
- Rotate detector clockwise while gently pressing on it until the detector drops fully into base.
- Then rotate the detector clockwise until it stops and snaps in place.
- Replace cover and tighten the four screws.
To Remove:
- Rotate the detector counterclockwise until stop is reached.
- Pull detector out of base.
TESTING
Only qualified service personnel should test these units. To assure proper
operation
of the detector and control panel, both the Sensitivity and the Functional
tests should be conducted. The minimum test schedule may be found in the
current edition of NFPA 72 for installations in the U.S. and CAN/ULC-S537, The
Verification of Fire Alarm Systems, for installation in Canada.
Sensitivity Test
The PE-11/-11C, 8854, OP121 detector monitors its smoke sensitivity
automatically and requires no test equipment. A green flash of the detector
LED indicates that the smoke sensitivity is within its listed limits.
The following detector models are analog types that must be programmed for the
air duct application using the control unit configuration tool; that is,
CSG-M, Zeus,FS-CT2, Desigo Programming Tool or Cerberus Programming Tool, as
applicable.
To test the FP-11/-11C detector refer to its installation instructions. See
Table 7.
To test the HFP-11/HFPO-11/SFP-11/SFPO-11 detector refer to its installation
instructions.
See Table 7.
These tests ensure that the detector is within its listed and marked
sensitivity range.
For additional instructions on applying the Sensitivities mode, refer to the
FireFinder-XLS Manual, P/N 315-033744, the Desigo Fire Safety Modular Manual,
Document ID A6V11231620, the Cerberus PRO Modular Manual, Document ID
A6V11231627, the DPU Manual, P/N 315-033260 or the SDPU Manual, P/N
315-033260C.
Functional Test Smoke Testing
Using P/N 500-649750 TG-11 smoke test canister with testing nozzle model AD-
TGN P/N 500-649717 (purchased separately) available from Siemens Industry,
Inc., insert the test gas nozzle into the hole in the red plug in the unit
cover. Press can against cover for about 1/2 second to release gas into the
chamber.
DO NOT SPRAY GAS FOR MORE THAN ½ SECOND. OVERUSE OF TEST GAS MAY RESULT IN DETECTOR CONTAMINATION.
After 15 to 20 seconds the detector will go into alarm, illuminating the detector LED and causing the duct unit functions to operate; alarm relays will change state, and the alarm related remote accessories, if attached, will function.
If no test gas is available to conduct functional testing, remove cover and, while holding down the cover removal switch, blow smoke from a smoldering cotton wick or punk directly at the head to cause an alarm. The alarm indicator on the detector should illuminate within one minute.
NOTES:
- Up to 30 air duct housings can be installed on one initiating circuit, except as noted in Note 2.
- When an FDBZ492-R is used to control a fire safety function, the FDBZ492-R must be the ONLY device on the initiating circuit.
- Do not use looped wire under base terminal.
- Break wire run to provide supervision of connection.
- The green grounding screw in the wiring compartment of the air duct housing is not used.
- Please follow Pin designation in Tables 1 and 2.
If the relay contacts are being used to control 120 VAC-operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes.
Figure 6
Typical Connections for the FDBZ492 / FDBZ492-R Using OP121 Detectors in Line
Isolation Mode
TB1 – Pin
Designations
| ****
Polarity Insensitive
| ****
Line Isolation
---|---|---
7| Not Used| Not Used
6| Device Loop + / Remote +| Device Loop +
5| Device Loop +| Remote TB1
4| Not Used| Remote TB3
3| Remote Control| Device Loop –
2| Device Loop-| Device Loop –
1| Device Loop – / Remote –| Remote TB2
TABLE 2
TB1 – Pin
Designations
| ****
Polarity Insensitive / Line Isolation
---|---
1| Device Loop +
2| Not Used
3| Device Loop –
4| Device Loop/Rem –
5| Remote Control
6| Device Loop – / Remote +
7| Relay Normally Closed Contact (NC)
8| Relay Common Contact (COM)
9| Relay Normally Open Contact (NO)
MULTIPLE REMOTE DEVICES
If remote devices are supported by the initiating circuit, each detector/base may have up to 2 remote devices with the following configurations and restrictions only:
NOTES:
- The relay contacts are shown after a reset pulse, which represents the non-alarm condition.
- The green grounding screw in the wiring compartment of the air duct housing is not used.
- Please follow the pin designation on Tables 3 and 4.
If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes.
Figure 7
Typical Connections for the FDBZ492 / FDBZ492-HR Using FP-11 / FP-11C
Detectors
TABLE 3
TB1 – Pin
Designations
| ****
Description
---|---
7| Not Used
6| Not Used
5| Remote +
4| Remote –
3| Device Loop –
2| Device Loop +
1| Not Used
TABLE 4
TB1 – Pin
Designations
| ****
Description
---|---
1| Not Used
2| Not Used
3| Remote +
4| Remote –
5| Device Loop –
6| Device Loop +
7| Not Used
8| Relay Normally Closed Contact (NC)
9| Relay Common Contact (COM)
10| Relay Normally Open Contact (NO)
11| Not Used
12| Not Used
13| Not Used
NOTES:
- The relay contacts are shown after a reset pulse, which represents the non-alarm condition.
- Refer to the RL-HW / RL-HC Installation Instructions, P/N 315-033230.
- The green grounding screw in the wiring compartment of the air duct housing is not used.
- Please follow the pin designation on Tables 5 and 6.
- For connection to FDBZ492-RTL only. This allows manual control of the relay output of FDBZ492-HR for testing purposes only. The LED on the FDBZ492-RTL indicates the status of the relay: GRN in supervisory state; RED in alarm state.
- When using relay housing with the FDO421, FDOOT441, FDOOTC441, OP921, OOH941, or OOHC941 devices and remote lamp, the RL HW/RL-HC cannot be used. Instead, use the ILED-H series programmed to Active Mode. Refer to the ILED-HC/ILED-HW Installation Instructions, P/N 315-048637 for details.
If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes.
Figure 8
Typical Connections for the FDBZ492 / FBDZ492-HR Using Compatible Addressable
Detectors in Polarity Insensitive Topology
Figure 9
Typical Connections for the FDBZ492 / FBDZ492-HR Using Compatible Addressable
Detectors in Line Isolation Mode
TABLE 5
TB1 – Pin
Designations
| Polarity Insensitive| ****
Line Isolation
---|---|---
7| Not Used| Not Used
6| Not Used| Device Loop +
5| Remote TB1| Remote TB1
4| Remote TB3| Remote TB3
3| Line 1| Device Loop –
2| Line 2| Device Loop –
1| Remote TB2| Remote TB2
TABLE 6
TB1 – Pin
Designations
| __
Polarity Insensitive
| __
Line Isolation
---|---|---
1| Not Used| Not Used
2| Not Used| Device Loop +
3| Remote TB1| Remote TB1
4| Remote TB3| Remote TB3
5| Line 1| Device Loop –
6| Line 2| Device Loop –
7| Remote TB2| Remote TB2
8| Relay Normally Closed Contact (NC)| Relay Normally Closed Contact (NC)
9| Relay Common Contact (COM)| Relay Common Contact (COM)
10| Relay Normally Open Contact (NO)| Relay Normally Open Contact (NO)
11| Connection to + Power terminal of FDBZ492-RTL| Connection to + Power
terminal of FDBZ492-RTL
12| Connection to the Control terminal of FDBZ492-RTL| Connection to the
Control terminal of FDBZ492-RTL
13| Connection to – Power terminal of FDBZ492-RTL| Connection to – Power
terminal of FDBZ492-RTL
Refer to the following Installation Instructions for additional information on testing each of these detectors:
TABLE 7
Detector | Installation Instruction |
---|---|
PE-11 | 315-094198 |
PE-11C | 315-095626 |
FP-11/-11C | 315-095921 |
HFP-11 | 315-033290 |
HFPO-11 | 315-034800 |
SFP-11 | 315-033290C |
SFPO-11 | 315-033290C |
FDO421 | A6V10323926 |
FDOOT441 | A6V10324655 |
FDOOTC441 | A6V10324657 |
8854 | 315-094198FA |
OP121 | A6V10281367 |
8710 | 315-033290FA |
8713 | 315-033290FA |
OP921 | A6V10323928 |
OOH941 | A6V10324659 |
OOHC941 | A6V10324661 |
The FP-11, HFP-11, SFP-11, HFPO-11, SPFO-11, 8710, 8713, FDO421, FDOOT441,FDOOTC441, OP921, OOH941, and OOHC941 detectors can also be tested individually using the DPU. Refer to the DPU Manual, P/N 315-033260. The SFP-11 and SFPO-11 detectors can be tested individually using the SDPU. Refer to the SDPU Manual,P/N 315-033260C.
MAINTENANCE
The performance of the air duct detector unit may be adversely affected by
dirt or foreign matter on the sampling tubes or detector. If the air holes in
the input sampling tube become restricted, the unit cannot receive a proper
air sample, and performance is impaired. It is recommended that the sampling
tubes be checked and cleaned periodically. The detector maintenance program
should consist of periodic cleaning of dust from the detector head by using a
vacuum cleaner. For cleaning Models PE-11, PE-11C, FP-11, FP-11C, HFP-11,
HFPO-11, SFP-11 or SFPO-11, refer to the detector’s Installation Instructions
(See Table 7).
The cleaning and test program is recommended for 6 month intervals, or more
frequently, if needed, depending on the individual detector environment.
Consult your local code and AHJ requirements for required maintenance
schedules.
Under no circumstances is the detector portion of the unit to be disassembled
by anyone other than an authorized Siemens Industry, Inc. Systems Technician.
For service, contact your nearest authorized Siemens Industry, Inc. Service
Representative.
If the fire alarm system is connected to a central station or fire department,
or operates external devices such as fans, extinguishers, etc., connected,
notify appropriate personnel and disconnect the external devices until all
tests are completed. After testing, reset the system, reconnect the devices,
and notify the personnel that the system is operating again.
COMPATIBLE CONTROL EQUIPMENT
FDBZ492 AND FDBZ492-R USING PE-11/-11C/8854/OP121 DETECTOR
Module Equipment Compatibility Identifier| Module Installation/ Wiring
Instructions
---|---
CDC-4 (FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular)| P/N
315-034100-8
CP-35 (SYSTEM 3)| P/N 315-084902-22
CZM-1B6 (MXL, MXL-IQ)| P/N 315-095355-9
CZM-4 (MXL, MXL-IQ)| P/N 315-090826-10
HZM (FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular, FS-250,
FC2050, FC2025, FC2005, FC922, FC924, FC901)| P/N 315-034850-6
SXL-EX| P/N 315-095997-8
SZE-4X (SXL-EX)| P/N 315-096018-8
SZE-8AX (SXL-EX)| P/N 315-096022-8
SZM (FS-250C)| P/N 315-034850C-4
ZU-35 (SYSTEM 3)| P/N 315-083222-18
8705 (MPC-6000/MPC-7000)| P/N 315-447309-8
FDBZ492 AND FDBZ492-R USING FP-11/-11C DETECTOR
Module Equipment Compatibility Identifier| Module Installation/ Wiring
Instructions
---|---
ALD-2I (MXL, MXL-IQ)| P/N 315-091464-13
MMB-2 (MXL)| P/N 315-095097-8
MMB-3 (MXL)| P/N 315-048860-7
SMB-2 (MXL-IQ)| P/N 315-095931-7
FDBZ492 AND FDBZ492-HR USING HFP-11, HFPO-11, 8710, 8713 DETECTOR
Module Equipment Compatibility Identifier| Module Installation/ Wiring
Instructions
---|---
DLC (FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular)| ****
P/N 315-033090-10
XDLC (Desigo Fire Safety Modular/Cerberus PRO Modular)| P/N A6V101040156
FS-DLC (FS-250)| P/N 315-049353-10
FDLC (MPC-6000/MPC-7000)| P/N 315-447309-8
FC2050, FC2025| P/N A6V10337045
FC2005| P/N A6V10333722
FC922, FC924| P/N A6V10356958
FC901| P/N A6V10336754
FDBZ492 AND FDBZ492-HR USING FDO421, FDOOT441, FDOOTC441,OP921, OOH941, OOHC941 DETECTOR
Module Equipment Compatibility Identifier| Module Installation/ Wiring
Instructions
---|---
FC2050, FC2025| P/N A6V10337045
FC2005| P/N A6V10333722
FC924, FC922| P/N A6V10356958
FC901| P/N A6V10336754
FDBZ492 AND FDBZ492-HR USING SFP-11 OR SFPO-11 DETECTOR
Module Equipment Compatibility Identifier| Module Installation/ Wiring
Instructions
---|---
FDLC (FS-250C)| P/N 315-049589C-1
The detector model number is the compatibility identifier.
Control equipment does not support remote accessories; e.g., lamps or relays.
ELECTRICAL RATINGS FOR PE-11/-11C, 8854, OP121
Voltage | 16-27 VDC |
---|---|
Ripple | 3V peak-to-peak |
Supervisory Current | 110 uA max. |
Start-up Time | 50 seconds max. |
PE-11/-11C
Detector
|
PE-11/-11C Detector + Remote Device
---|---|---
Alarm Current| 33 – 50mA| 50 – 70mA
ELECTRICAL RATINGS FOR HFP-11, HFPO-11, SFP-11, SFPO-11, 8710, 8713, FDO421, FDOOT441, FDOOTC441,OP921, OOH941, OOHC941
Electrical ratings are not provided here for these detectors. Guidance for detector loop loading, along with loop wire electrical specifications are provided in the applicable control unit instructions given in the above Compatible Control Equipment tables.
CYBER SECURITY DISCLAIMER
Siemens provides a portfolio of products, solutions, systems and services that
includes security functions that support the secure operation of plants,
systems, machines and networks. In the field of Building Technologies, this
includes building automation and control, fire safety, security management as
well as physical security systems.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a
holistic, state-of-the-art security concept. Siemens’ portfolio only forms one
element of such a concept.
You are responsible for preventing unauthorized access to your plants,
systems, machines and networks which should only be connected to an enterprise
network or the internet if and to the extent such a connection is necessary
and only when appropriate security measures (e.g. firewalls and/or network
segmentation) are in place. Additionally, Siemens’ guidance on appropriate
security measures should be taken into account.
For additional information, please contact your Siemens sales representative
or visit https://www.siemens.com/global/en/home/company/topicareas/future-of-
manufacturing/industrialsecurity.html.
Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats. Siemens strongly recommends to comply with security advisories on the latest security threats, patches and other related measures, published, among others, under https://www.siemens.com/cert/en/cert-security- advisories.htm.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada
P/N A5Q00053166
Document ID A6V10336866_en–_e
References
- Fire Alarm Resources | Download fire alarm documents
- CERT Services - Services - Siemens Global Website
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>