SIEMENS NCCXP Series FireFinder Network Command Center Instruction Manual
- June 9, 2024
- SIEMENS
Table of Contents
FireFinder
Network Command Center
Graphics
Software Installation Manual
Introduction
This manual describes the installation for Siemens NCC – Network Command
Center
The Network Command Center Graphics product family comprises of two system
series:
- The NCC-G Series, which includes the NCC-GL, NCC-1G, NCC-2G, NCC-3G and NCC-4G software packages.
- The NCCWAN Series, which includes the NCCWAN1G, NCCWAN2G, NCCWAN3G, NCCWAN4G, NCCWAN5G and NCCWAN6G, NCCWAN7G software packages.
These software packages, when operating in the appropriate UL 864 listed
computer, form the FireFinder Network Command Center Graphics system (NCC-G).
For new installations, the NCC-G and NCCWAN software package includes the
FireFinder CD-ROM program, software key, keyboard templates, the NCC manual,
and this software installation manual.
Minimum PC Requirements
UL 864 9th Edition Listed Industrial Computer Requirements
Model | NCCXP Series |
---|---|
CPU | Pentium 4 2.8 GHz |
0/S | Windows XP ® Professional |
RAM | 1 GB |
Hard Disk | 80 GB |
Floppy | 1.44M Bytes |
SVGA LCD Monitor | 22″ or 42″ {55.8 cm. -or- 106.7 cm.} |
Touch Screen | 22″ or 42″ {55.8 cm. -or- 106.7 cm.} |
Serial Ports | 2 |
Parallel Ports | 2 |
Printer | PAL-1 ( UL 864 9th Edition Listed parallel printer) |
CD-ROM | R / W, DVD-ROM |
USB | 4 ports |
Ethernet | (10110OBT & Gigabit LAN) |
UL 864 9th Edition Listed Industrial Computer Requirements
Model | NCCW7I7 Series |
---|---|
0/S | Windows® 7; 64-bit software |
0/S Processor | Intel 7 |
RAM | 8GB DDR3 |
Hard Disk | 250 GB SSD, 2 TB SATA |
Floppy | 1.44M Bytes |
SVGA LCD Monitor | 22″ or 42″ {55.8 cm. -or- 106.7 cm.} |
Touch Screen | 22″ or 42″ {55.8 cm. -or- 106.7 cm.} |
Serial Ports | Six (6) RS-232; COM1-6 |
Parallel Ports | LPT1 |
Printer | PAL-1 ( UL 864 9th Edition Listed parallel printer) |
CD-ROM | DVD-RJW |
USB | Two (2) ports (located behind locked door) |
Graphics Card | On-board CPU card, Multi-monitor capable |
Ethernet | (101100BT & Gigabit LAN) |
Dimensions | 16.8″ [W] —x- 17.6″ [D] —x- 7″ [H] 42.6 cm. [w] —x- 44.7 cm. [o] |
-x- 17.7 cm. [H)
Weight| 17.4 Lbs. (7893g.)
Software Installation
All SIEMENS FireFinder Network Command Center computers are preloaded with the NCC-G software in SIEMENS computer models SCD550, SCD550T, and NCCW7I7. Complete the following procedure to:
- re-install the software when necessary
- upgrade a system
- install the system on a computer that is not preconfigured from SIEMENS
-
Install the NCC-2F card driver in the PC (refer to Section 3.1).
-
Insert the CD into the CD drive. The installation will start with the Preparing to Install dialog. If the installation does not start automatically, click Run Setup in the AutoPlay window.
-
The NCC will start with the installation for PostgreSQL and Acrobat Reader to the computer.
-
After the PostgreSQL and Acrobat Reader installation is completed, for Windows XP™ first time installation, the Microsoft IIS installation will start with the following screen. Note that this step may not show if IIS is available on the hard disk or if you are installing on Windows 7.
-
Remove the NCC CD from the CD-ROM drive and insert the Windows XP™ CD. Browse the Windows XP™ CD and select the I386 folder. Click OK.
-
If the Welcome to Microsoft Windows XP™ screen appears, click Exit to close the window.
-
After the IIS installation is completed, the NCC installation will start with the following screen:
-
Click Next> to continue the installation process. The Setup Type screen will appear.
-
Select NCC Management Station with full options to install the complete NCC Management Station software to the computer. Select Generic computer for Demo/Design to install the NCC demo to a laptop for offline editing, configuration, or demonstration. A confirmation dialog will appear.
-
The option for the complete installation will change the logon and security settings of the computer. Select the Continue, I am installing a full workstation option to confirm the choice for the full installation. Select Get me out of here or click Back to change the installation choice.
-
Select the type of NCC system to be installed. Click Next> to continue.
-
The installer will install the NCC software to the computer. By default, the NCC files will be installed in a folder named NCC2 when installation is completed.
-
A reboot is required to complete the installation. Select Yes, I want to restart my computer now. Click Finish to restart the PC.
-
After the computer reboots, at the Windows logon dialog, enter the following to log on to Windows and start the NCC:
Username: firefinder
Password: firefinder -
If this is a first time NCC installation, a prompt for NCC Database Initialization will be displayed. This is fine because there is currently no NCC configuration in the PC. Click OK to continue.
-
If the NCC key is not installed prior to the software installation, a prompt for Software Key Missing will be displayed. Plug in your Software Key. You will have five chances to install the Software Key before continuing with the NCC installation. If the installation is for testing purposes, click OK to continue and choose the default type of operation. Without the NCC key, the software will run in Emergency Mode and a warning will appear until a valid NCC key is installed.
-
If the NCC Software Key has been installed, the installation will proceed with the site configuration setup.18. Click Next>> to continue with the site setup.
-
The Use NIM Interface option is used with the NIM-1W/R to extend the NCC-GL topography. This option allows the NCC-GL to be used on a system with multiple nodes, however, the NCC-GL will only monitor and control one node. In order for this option to operate, a NIM-1W/R card must be installed in the node which the NCC-GL will be monitoring and controlling. The proper module and node number for the NIM-1R must agree with the programming in the MMB for the NCC-GL module.
Enter the Node Number assignment for the NCC-G/GL system and a Node Button label. These values can be changed later in the system dialog box. -
If you do not complete this information, the following dialog box appears (as applicable) and you cannot continue with the installation.
-
Once the node number assignment and label have been accepted, the following screen appears.
-
Press NEXT>> to continue with the basic system configuration. The following screen appears.System Identification: Enter the name of the installed site (up to 52 characters long). This is a required field. If System Identification is left blank, the following dialog box appears:→ Serial #: The number displayed is the version of the NCC-G software.
→ Select the correct UL system configuration.
o UL System: Select the NFPA 72 mode of operation. The possible selections are:
• NFPA 72 Local – Campus
• NFPA 72 Local – Highrise
• NFPA 72 Proprietary
o NOTE: All NCCs on a network system need to be set to the same UL system setting.
→ Command Seq #: The number displayed is the number of commands executed since the system was installed.
→ Foreign Language Support: The default country and language setting is USA and English. If the site location is in Canada, select the check box to Enable Support for Foreign Country support and change the country and language. -
After clicking DONE in the site information section, the following screen appears, as applicable.
-
If you want to review your entries, click <<Prev. Click Finish if you want to save your entries. This completes the NCC software installation.
3.1 NCC-2F Driver Installation
Refer to Section 4 for detailed steps on NCC-2F driver installation
instruction. An error will be displayed if the NCC-2F driver has not been
installed.
3.2 Un-configured NCC-2F Cards
- On a new installation, or if the NCC-2F card is replaced, the Configure Network Hardware setup screen will be displayed during boot up.
- Select a port and click Find to assign a network to this port. Notice, at the back of the PC, the flashing activity LEDs on the selected card. Click Edit to display or change the card’s assigned network type (XNET or HNET) properties.
- The Network field will select between XNET_1 and HNET_1. When the desired type is showing, click Set and then click Done to complete the operation. You will be asked to confirm your selection. If it is desired to un-configure a port, click Clear and then click Done.
- After all the required hardware is assigned, the Network Hardware screen should resemble the following.
- Now click Done and the normal boot process will continue. If a change is required in the future, this setup dialog can be accessed by navigating to More > Setup > Network > Net Hardware.
3.3 Printer Installation
- For printer installation, refer to page 2-26 in the FireFinder Network Command Center Graphics Operation, Installation, and Maintenance Manual.
NCC-2F Driver Installation
The NCC-2F is a PCI-compliant network card used with the NCC and NCC WAN
systems.
The NCC-2F allows the user to interface MXL and XLS systems over XNET and to
connect to WAN components using HNET. The NCC-2F provides the NCC with an
RS-485 supervised network.
The module fits in any available PCI 5V-compliant slot. The card is keyed so
that it will only fit in the appropriate PCI slot. The module comes
preinstalled in the NCC. When a PC with an NCC-2F card is first started, the
card will be detected in Windows, and the user will be prompted to install the
drivers. The drivers are on the Firefinder NT (P/N 316-099108) and the
Firefinder NCC NT WAN (P/N 316-048853) installation disks. Load the
appropriate disk (both disks have the same drivers) in the CD-ROM drive, and
follow the instructions for installing the drivers. Each card will
automatically prompt the user for drivers. There are three drivers to install:
one for the PCI card UART, and two for the PCI communication ports. The
outlined installation steps are repeated three times.
After the first card is installed, the next card will prompt the user for its
drivers. Repeat the following steps for the second card. When all is complete,
refer to the Device Manger to check the COM port designations, and view any
installation issues. Use the following step to perform the procedure.
4.1 Installing NCC-2F Driver on Windows XP
-
When the NCC-2F is first installed, Windows will detect the new hardware. At this point, select the No, not at this time option and click Next>.
-
Select Install from a list or specific location (Advanced) and then click Next>.
-
Select Browse and navigate to the CD-ROM and locate the
OXUART_v512_DRIVERS folder. On the Firefinder NCC, this location is:
D:\drivers\NCC2F_DRIVERS\OXUART_v512_Drivers.
NOTE: If the CD-ROM drive is not D, substitute the proper drive letter for your PC. -
After you highlight the folder, click OK to proceed. Now that the path is populated, click Next>. Windows will install the appropriate drivers.
-
When you see the following Hardware Installation warning, click Continue Anyway.
-
The Windows XP Hardware Wizard will install the drivers as shown in the following image.
-
Once the drivers are successfully installed, the following message will be displayed. Click Finish.
NOTE: Windows will prompt the user to install the drivers for the serial port. -
On the Welcome to the Found New Hardware Wizard window, select Install from a specific location [Advance].
NOTE: Windows will use the first available COM port for communication. -
Select Next> and search for the CD-ROM drive where the
OXUART_v512_DRIVERS folder is located. On the Firefinder NCC, this location is:
D:\drivers\NCC2F_DRIVERS\OXUART_v512_Drivers
NOTE: If the CD-ROM is not D, substitute the proper driver letter for your PC. -
After you highlight the folder, click OK to proceed. Now that the path is populated, click Next>. Windows will install the appropriate drivers.
-
When you see the following Hardware Installation warning, click Continue Anyway.
-
Once the drivers are successfully installed, the following message will be displayed.
-
Click Finish.
NOTE: Windows will prompt the user to install the drivers for the additional PCI Communications Port. -
Select Install from a list or specific location [Advance].
-
Select Next> and search for the CD-ROM driver where the OXUART_v512_DRIVERS folder is located. On the Firefinder NCC Install CD, this location is:
D:\drivers\NCC2F_DRIVERS\OXUART_v512_Drivers
NOTE: If the drive is not D, substitute the proper drive letter for your PC. -
Highlight the folder and click OK to proceed. Once the path is populated in the field, click Next>. Windows will install the appropriate drivers.
-
On the Hardware Installation warning message, click Continue Anyway.
-
Once the drivers are successfully installed, the following message will be displayed. Click Finish.
-
To verify which COM ports were installed and to check that there are no issues, right click on My Computer on the desktop and select Properties.
-
Then click the Hardware tab.
-
Click Device Manager.
-
Click the + sign next to Ports (COM & LPT) to expand.
-
The following example displays two NCC-2F cards installed. They are configured in pairs, for example, COM 3 and COM 4 are the first NCC-2F and COM 5 and COM 6 are the second NCC-2F. The NCC will use COM 3 for the first card and COM 5 for the second card.
4.2 Installing NCC-2F Driver on Windows 7
After installing the NCC-2F card on the PC, Windows 7 will attempt to install
a driver for the NCC2F card.
The installation should fail with the following message: ‘Device driver
software was not successfully installed’, click Close.
To install Windows 7 drivers:
-
Insert the NCC-2F CD card driver software in the CD drive on the computer.
-
On the Windows desktop, right click on the Computer icon and select Properties from the drop-down menu.
-
Select Device Manager from the Properties menu.
-
On the message box, Do you want to allow the following program to make changes to this computer, select Yes.
-
From the Device Manager list, select PCI Serial Port (XP) or 16c95x Serial Port (Win7) under Other Devices from the list.
NOTE: You may need to observe and choose the serial port name as appropriate.
Depending on the computer and the operating system, there may be other names for the serial port device. -
Highlight PCI Serial Port and right-click on it, then select Update Driver Software from the drop-down menu.
-
Click Browse my computer from driver software from the message box.
-
Click on Browse and navigate to the CD-ROM drive and locate the SP45463>X86 folder.
-
Highlight the folder x86 and click OK to proceed.
D:\drivers\NCC2F_DRIVERS\OxDriver_V70
NOTE: D = the CD Driver -
Select the folder amd64 for 64bit PC or the folder x86 for 32bit PC.
-
On the Update Driver Software-PCI Serial Port window, the path will automatically be populated in the field. Verify the path and select Next.
-
Windows will prompt a Successful message once the install is completed. Click Close.
-
To verify that the new COM Ports are ready to be used, refresh the Device Manager tree (F5) under Ports (COM & LPT). Enhanced Communication Port (COM3) and Enhanced Communication Port (COM4) will be displayed.
-
If additional cards are required, follow the procedure from Step 1 of section Installing NCC-2F Driver on Windows 7 to install additional cards.
-
Process is complete.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ