LG ThermaV12 Air to Water Heat Pump Instruction Manual
- June 9, 2024
- LG
Table of Contents
ThermaV12 Air to Water Heat Pump
ENGLISH ITALIANO PORTUGUÊS MAGYAR
ESPAÑOL
FRANÇAIS SRPSKI
INSTALLATION MANUAL
AIR-TO-WATER HEAT PUMP
DEUTSCH HRVATSKI
SLOVENSCINA
CESTINA DANSK
NEDERLANDS
POLSKI
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only. Please retain this installation manual
for future reference after reading it thoroughly.
Original instruction
MFL68026607 Rev.14_020922
www.lg.com
Copyright © 2018 – 2022 LG Electronics Inc. All Rights Reserved.
LIMBA ROMÂN
ENGLISH
2 TABLE OF CONTENTS
TABLE OF CONTENTS
5 PREFACE 6 SAFETY INSTRUCTIONS 14 INSTALLATION PART 15 GENERAL INFORMATION
15 Model Information 17 Model name and related information 18 Parts and
Dimensions 24 Control Parts 26 Remote Controller 27 Typical Installation
Example 33 Cycle Diagram 36 Water cycle
39 INSTALLATION
39 Transporting the Unit 40 Installation places 41 Seasonal Wind and Cautions
in Winter 42 Foundation for Installation 43 Electrical Wiring 53 Wiring of
main power supply and equipment capacity 54 Water Piping and Water Circuit
Connection 56 Water Charging 56 Pipe Insulation 57 Water pump Capacity 57
Pressure Drop 58 Performance curve 59 Water Quality 59 Frost protection by
antifreeze 60 Frost protection by antifreeze valve 62 Water Volume and
Expansion Vessel Pressure
63 ACCESSORIES INSTALLATION
63 Accessories supported by LG Electronics 65 Accessories supported by 3rd
party Companies 66 Before Installation 66 Thermostat 70 2nd Circuit 75 3rd
Party Boiler 76 3rd Party Controller 77 Meter Interface 78 Central Controller
79 Remote Controller 82 DHW Tank 87 DHW Tank Kit 89 Solar Thermal Kit 91 Dry
Contact 93 External Controller – Setting up programmable digital input
operation 94 Remote Temperature Sensor 97 Solar pump 98 External pump 99 Wi-fi
Modem 100 Energy State 101 Digital Input for energy saving (ESS, Smart Grid)
102 2Way Valve 104 3Way Valve(A) 105 3Way Valve(B)
106 Electric Heater 112 Final check
113 CONFIGURATION
113 DIP Switch Setting
123 SERVICE SETTING
123 How to enter service setting 123 Service setting 124 Service Contact 125
Model Information 126 RMC Version lnformation 127 Open Source License
128 INSTALLER SETTING
128 How to enter installer setting 129 Installer setting (For 3 Series) 131 3
Minutes Delay 132 Select Temperature Sensor 133 Dry Contact Mode 134 Central
Control Address 135 Pump test run 136 Air cooling set temp 137 Water cooling
set temp 138 Air heating set temp 139 Water heating set temp 140 DHW set temp
141 Screed drying 143 Heater on temperature 145 Water supply off temp. during
cooling 147 Tank disinfection setting 1, 2 148 Tank setting 1 149 Tank setting
2 151 Heater priority 152 DHW time setting 153 TH on/off Variable, heating air
154 TH on/off Variable, heating water 155 TH on/off Variable, cooling air 156
TH on/off Variable, cooling water 157 Heating temp. setting 158 Cooling temp.
setting 159 Pump setting in heating 160 Pump setting. in cooling 161 Forced
operation 162 CN_CC 163 Pump Capacity 164 Seasonal auto temp 166 Modbus
Address 167 CN_EXT 168 Anti-freezing Temperature 169 Add Zone 170 Use External
Pump 171 3rd Party Boiler 172 Meter Interface 173 Pump Prerun/Overrun 174
Solar Thermal System 176 Energy state 177 Data logging 178 Password
Initialization 179 Overview settings (For 3 Series) 181 Installer setting (For
4 Series) 184 Select Temperature Sensor 185 Use Heating Tank Heater
TABLE OF CONTENTS 3
ENGLISH
ENGLISH
4 TABLE OF CONTENTS
186 Mixing Circuit 187 Use External Pump 188 RMC master/slave 189 LG Therma V
Configuration 190 Forced operation 191 Pump Prerun/Overrun 192 Water Flow
Control 193 Energy Monitoring 194 Anti-Freezing Option 1 (For 4 Series) 195
Password Reset 196 Screed drying 198 Heater on temperature 200 Air heating set
temp. 201 Water heating set temp. 202 Hysteresis Room Air(Heating) 203
Hysteresis Heating Water 204 Heating temp. setting 205 Pump setting in heating
206 Air cooling set temp. 207 Water cooling set temp. 208 Water supply off
temp. during cooling 210 Hysteresis Room Air(Cooling) 211 Hysteresis Cooling
Water 212 Cooling temp. setting 213 Pump setting in cooling 214 Seasonal auto
temp. 217 Heater priority 218 DHW set temp. 219 Tank disinfection setting 1, 2
220 Tank setting 1 221 Tank setting 2 223 DHW time setting 224 Recirculation
time 225 Solar Thermal System 227 Pump test run 228 Frost Protection Temp. 229
Dry Contact Mode 230 Central Control Address 231 CN_CC 232 LG Therma V
Configuration 233 Pump frequency setting (RPM) 234 Smart Grid(SG) 235 Power
Supply Blockage (Smart Grid) 236 Energy state 237 Thermostat control type 238
Pump operation time 239 IDU operation time 240 Modbus Address 241 Modbus
gateway memory map 244 CN_EXT 245 3rd Party Boiler 246 Meter Interface 247
Current flow rate 248 Data logging 249 Overview settings (For 4 Series)
252 COMMISSIONING
252 Check List before Starting Operation 253 Starting Operation 254 Starting
Operation flow chart 254 Airborne Noise Emission 255 Vacuum & Charge of
Refrigerant 257 How to drain remaining water in the product 258
Troubleshooting
PREFACE 5
ENGLISH
PREFACE
This installation manual is to present information and guide about understanding, installing,
and checking
.
Your careful reading before installation is highly appreciated to make no mistake and to prevent
potential risks. The manual is divided into nine chapters. These chapters are classified according
to installation procedure. See the table below to get summarized information.
Chapters Chapter 1 Chapter 2 Chapter 3
Chapter 4
Chapter 5 Chapter 6 Chapter 7
Contents
· Warning and Caution concerned with safety. · This chapter is directly
related with human safety. We strongly recommend reading
this chapter carefully.
· Items Inside product Box · Before starting installation, please make it sure
that all parts are found inside the
product box.
· Fundamental knowledge about · Model identification, accessories information,
refrigerant and water cycle diagram,
parts and dimensions, electrical wiring diagrams, etc. · This chapter is
important to understand
· Installation about the unit. · Installation location, constraints on
installation site, etc · Electrical wiring at the unit. · System set-up and
configuration. · Information about water pump
· Information about supported accessories · Specification, Constraints, and
wiring are described. · Before purchasing accessories, please find supported
specification to buy proper
one.
· Information about DIP switch setting
· check and input service contact · information about model and open source
license
Chapter 8
· Information on the installer setup mode that sets the detailed functions of
the remote control
· Incorrectly setting the installer setup mode may result in product failure,
personal injury, or property loss, so this chapter requires a deeper
understanding
Chapter 9
· Check points before starting operation are explained. · Troubleshooting,
maintenance, and error code list are presented to correct
problems
6 SAFETY INSTRUCTIONS
ENGLISH
SAFETY INSTRUCTIONS
Read the precautions in this manual carefully before operating the unit.
This symbol indicates that the Operation Manual should be read carefully.
This appliance is filled with flammable refrigerant (for R32)
This symbol indicates that a service personnel should be handling this
equipment with reference to the Installation Manual.
The following safety guidelines are intended to prevent unforeseen risks or
damage from unsafe or incorrect operation of the appliance. The guidelines are
separated into WARNING’ and
CAUTION’ as described below.
! This symbol is displayed to indicate matters and operations that can cause
risk. Read the part with this symbol carefully and follow the instructions in
order to avoid risk.
! WARNING
This indicates that the failure to follow the instructions can cause serious
injury or death.
! CAUTION
This indicates that the failure to follow the instructions can cause the minor
injury or damage to the product.
! WARNING
Installation
· Do not use a defective or underrated circuit breaker. Use this appliance on
a dedicated circuit. – There is risk of fire or electric shock.
· For electrical work, contact the dealer, seller, a qualified electrician, or
an Authorized Service Center. – There is risk of fire or electric shock.
ENGLISH
SAFETY INSTRUCTIONS 7
· Always ground the unit. – There is risk of fire or electric shock.
· Install the panel and the cover of control box securely. – There is risk of
fire or electric shock.
· Always install a dedicated circuit and breaker. – Improper wiring or
installation may cause fire or electric shock
· Use the correctly rated breaker or fuse. – There is risk of fire or electric
· Do not modify or extend the power cable. – There is risk of fire or electric
shock.
· Do not install, remove, or reinstall the unit by yourself (customer). –
There is risk of fire, electric shock, explosion, or injury
· For antifreeze, always contact the dealer or an authorized service center. –
Almost the antifreeze is a toxic product.
· For installation, always contact the dealer or an authorized Service Center.
– There is risk of fire, electric shock, explosion, or injury.
· Do not install the unit on a defective installation stand. – It may cause
injury, accident, or damage to the unit.
· Be sure the installation area does not deteriorate with age. – If the base
collapses, the unit could fall with it, causing property damage, unit failure,
and personal injury.
· Do not install the water pipe system as Open loop type. – It may cause
failure of unit.
· Use a vacuum pump or inert (nitrogen) gas when doing leakage test or purging
air. Do not compress air or oxygen and do not use flammable gases. – There is
the risk of death, injury, fire or explosion.
· Make sure the connected condition of connector in product after maintenance.
– Otherwise, it may cause product damage
ENGLISH
8 SAFETY INSTRUCTIONS
· Do not touch leaked refrigerant directly. – There is risk of frostbite.
· Compliance with national gas regulations shall be observed.
· Refrigerant tubing shall be protected or enclosed to avoid damage.
· The installation of pipe-work shall be kept to a minimum.
· A brazed, welded, or mechanical connection shall be made before opening the
valves to permit refrigerant to flow between the refrigerating system parts. A
vacuum valve shall be provided to evacuate the interconnecting pipe and/or any
uncharged refrigerating system part.
· Any person who is involved with working on or breaking into a refrigerant
circuit should hold a current valid certificate from an industry-accredited
assessment authority, which authorizes their competence to handle refrigerants
safely in accordance with an industry recognized assessment specification.
· Pipe-work shall be protected from physical damage and shall not be installed
in an unventilated space, if that space is smaller than 1) The minimum floor
area : 49.4 m2 2) The maximum refrigerant charge amount : 2.4 kg
· Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
· Do not pierce or burn.
· Be aware that refrigerants may not contain an odour.
· Dismantling the unit, treatment of the refrigerant oil and eventual parts
should be done in accordance with local and national standards.
· Ducts connected to an appliance shall not contain an ignition source.
· Copper in contact with refrigerants shall be oxygen-free or deoxidized, for
example Cu-DHP as specified in EN 12735-1 and EN 12735-2.
ENGLISH
SAFETY INSTRUCTIONS 9
Operation
· Take care to ensure that power cable could not be pulled out or damaged
during operation. – There is risk of fire or electric shock.
· Do not place anything on the power cable. – There is risk of fire or
electric shock.
· Do not plug or unplug the power supply plug during operation. – There is
risk of fire or electric shock.
· Do not touch (operate) the unit with wet hands. – There is risk of fire or
electric shock.
· Do not place a heater or other appliances near the power cable. – There is
risk of fire or electric shock.
· Do not allow water to run into electric parts. – There is risk of fire,
failure of the unit, or electric shock.
· Do not store or use flammable gas or combustibles near the unit. – There is
risk of fire or failure of unit.
· Do not use the unit in a tightly closed space for a long time. – It may
cause damage to the unit.
· When flammable gas leaks, turn off the gas and open a window for ventilation
before turning the unit on. – There is risk of explosion or fire.
· If strange sounds or smell or smoke comes from unit, turn the breaker off or
disconnect the power supply cable. – There is risk of electric shock or fire.
· Stop operation and close the window in storm or hurricane. If possible,
remove the unit from the window before the hurricane arrives. – There is risk
of property damage, failure of unit, or electric shock.
· Do not open the front cover of the unit while operation. (Do not touch the
electrostatic filter, if the unit is so equipped.) – There is risk of physical
injury, electric shock, or unit failure.
ENGLISH
10 SAFETY INSTRUCTIONS
· Do not touch any electric part with wet hands. you should be power off
before touching electric part. – There is risk of electric shock or fire.
· Do not touch refrigerant pipe and water pipe or any internal parts while the
unit is operating or immediately after operation. – There is risk of burns or
frostbite, personal injury.
· If you touch the pipe or internal parts, you should be wear protection or
wait time to return to normal temperature. – Otherwise , it may cause burns or
frostbite, personal injury.
· Turn the main power on 6 hours ago before the product starting operation. –
Otherwise, it may cause compressor damage.
· Do not touch electric parts for 10 minutes after main power off. – There is
risk of physical injury, electric shock.
· The inside heater of product may operate during stop mode. It is intended to
protect the product.
· Be careful that some part of the control box are hot. – There is risk of
physical injury or burns.
· When the unit is soaked (flooded or submerged), contact an Authorized
Service Center. – There is risk of fire or electric shock.
· Be cautious that water could not be poured to the unit directly. – There is
risk of fire, electric shock, or unit damage.
· Ventilate the unit from time to time when operating it together with a
stove, etc. – There is risk of fire or electric shock.
· Turn the main power off when cleaning or maintaining the unit. – There is
risk of electric shock.
· Take care to ensure that nobody could step on or fall onto the unit. – This
could result in personal injury and unit damage.
· For installation, always contact the dealer or an Authorized Service Center.
– There is risk of fire, electric shock, explosion, or injury.
ENGLISH
SAFETY INSTRUCTIONS 11
· If the unit is not used for long time, we strongly recommend not to switch
off the power supply to the unit. – There is risk of water freezing.
· The appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specified for operation.
· The appliance shall be stored in a room without continuously operating open
flames (for example an operating gas appliance) and ignition sources (for
example an operating electric heater).
· The appliance shall be stored so as to prevent mechanical damage from
occurring.
· Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person competent
in the use of flammable refrigerants.
· When mechanical connectors are reused indoors, sealing parts shall be
renewed. When flared joints are reused indoors, the flare part shall be re-
fabricated.
· Be aware that refrigerants may not contain an odor. · Periodic(more than
once/year) cleaning of the dust or salt
particles stuck on the heat exchangers by using water. · Keep any required
ventilation openings clear of obstruction.
! CAUTION
Installation
· Always check for gas (refrigerant) leakage after installation or repair of
unit. – Low refrigerant levels may cause failure of unit.
· Keep level even when installing the unit. – To avoid vibration or water
leakage.
· Use two or more people to lift and transport the unit. – Avoid personal
injury.
· Do not install the unit in potentially explosive atmospheres.
ENGLISH
12 SAFETY INSTRUCTIONS
· Connect the water for filling or refilling the heating system as specified
by EN 1717/EN 61770 to avoid contamination of drinking water by return flow.
Operation
· Do not use the unit for special purposes, such as preserving foods, works of
art, etc. – There is risk of damage or loss of property.
· Use a soft cloth to clean. Do not use harsh detergents, solvents, etc. –
There is risk of fire, electric shock, or damage to the plastic parts of the
unit.
· Do not step on or put anything on the unit. – There is risk of personal
injury and failure of unit.
· Use a firm stool or ladder when cleaning or maintaining the unit. – Be
careful and avoid personal injury.
· Do not turn on the breaker or power under condition that front panel
cabinet, top cover, control box cover are removed or opened. – Otherwise it
may cause fire, electric shock, explosion or death.
· The appliance shall be disconnected from its power source during service and
when replacing parts.
· Means for disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules.
· The Installation kit supplied with the appliance are to be used and that old
Installation kit should not be reused.
· If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
· In order to avoid a hazard due to inadvertent resetting of the thermal cut-
out, this appliance must not be supplied through an external switching device,
such as a timer, or connected to a circuit that is regularly switched on and
off by the utility.
ENGLISH
SAFETY INSTRUCTIONS 13
· This equipment shall be provided with a supply conductor complying with the
national regulation.
· The instructions for service to be done by specialized personnel, mandated
by the manufacturer or the authorized representative may be supplied in only
one Community language which the specialized personnel understand.
· This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
ENGLISH
14 INSTALLATION PART
INSTALLATION PART
Thank you for choosing LG Electronics Air-to-Water Heat Pump Before starting
installation, please make it sure that all parts are found inside the product
box.
Item
Image
Installation Manual
Outdoor Unit UN36A Chassis (Product heating capacity :
5, 7, 9 kW)
Outdoor Unit UN60A Chassis (Product heating capacity : 9, 12, 14, 16 kW)
Remote Controller
Remote Controller Cable Damper Drain Cap
Drain Nipple
GENERAL INFORMATION 15
ENGLISH
GENERAL INFORMATION
With advanced inverter technology,
is suitable for applications like under floor
heating, under floor cooling, and hot water generation. By Interfacing to various accessories user
can customize the range of the application.
In this chapter, general information of
is presented to identify the installation
procedure. Before beginning installation, read this chapter carefully and find helpful information
on installation.
Model Information
Factory Model Name
Model
No. 1234567
Monobloc ZH B W 09 6 A 0
No.
Signification
1 Air-to-Water-Heat Pump for R32
2
Classification – B : Monobloc
3
Model Type – W : Inverter Heat Pump
4
Heating Capacity – E.g) 9 kW ’09’
Electrical ratings 5 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz
6
Function – A : General heating heat pump
7 Series Number
Buyer Model Name
– For 3 Series
Refrigerant
No.
123457 8
R32 H M 09 1 M U3 3
No.
Signification
1 Air-to-Water-Heat Pump
2
Classification – M : Monobloc
3
Heating Capacity – E.g) 9 kW ’09’
Electrical ratings 4 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz
5
Leaving Water Combination – M : Middle Temperature
Chassis Name 6 – U3 : UN60A Chassis
– U4 : UN36A Chassis
7 Series Number
16 GENERAL INFORMATION
ENGLISH
– For 3 Series
Refrigerant 123
R32 H M 09
No. 456 1MR
789 S U3 3
No.
Signification
1 Air-to-Water-Heat Pump
2
Classification – M : Monobloc
3
Heating Capacity – E.g) 9 kW ’09’
Electrical ratings 4 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz
5
Leaving Water Combination – M : Middle Temperature
6
Refrigerant – R : R32
7
Function – S : Silent
Chassis Name 8 – U3 : UN60A Chassis
– U4 : UN36A Chassis
9 Series Number
– Additional Information : Serial number refers to the barcode on the product.
– Max allowable pressure High side : 4.32 MPa / Low side : 2.4 MPa
[Operating condition] – Maximum operating temperature of water : 65 °C –
Minimum operating temperature of water : 15 °C – Maximum inlet water pressure
: 0.3 MPa – Minimum inlet water pressure : 0.03 MPa
– For 4 Series
Refrigerant
No.
12345678
R32 H M 09 1 M R U3 4
No.
Signification
1 Air-to-Water-Heat Pump
2
Classification – M : Monobloc
3
Heating Capacity – E.g) 9 kW ’09’
Electrical ratings 4 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz
5
Leaving Water Combination – M : Middle Temperature
6
Refrigerant – R : R32
Chassis Name 7 – U3 : UN60A Chassis
– U4 : UN36A Chassis
8 Series Number
Check the model information based on the buyer model series number.
(e.g., geometry, cycle, etc.)
GENERAL INFORMATION 17
ENGLISH
Model name and related information
Chassis UN36A
UN60A
Model Name Phase(Ø) 1
1
3
Capacity(kW) 5 7 9 9 12 14 16 12 14 16
Capacity (kW)
Heating1)
Cooling2)
5.5
5.5
7
7
9
9
9
9
12
12
14
14
16
16
12
12
14
14
16
16
Power Source (Unit)
220-240 V~ 50 Hz
380-415 V 3N~ 50 Hz
1 : tested under EN14511 (water temperature 30 °C ¡ 35 °C at outdoor ambient
temperature 7 °C / 6 °C)
2 : tested under EN14511 (water temperature 23 °C ¡ 18 °C at outdoor ambient
temperature 35 °C / 24 °C)
C All appliances were tested at atmospheric pressure.
ENGLISH
18 GENERAL INFORMATION
Parts and Dimensions
– For 3 Series
4
UN36A (5, 7, 9 kW)
5
4
5
9
2
6
7
8
10
3
1
C The shape may differ depending on the model.
Description
No
Name
1 Entering water pipe
2 Leaving water pipe
3 Strainer
4 Top cover
5 Control Box
6 Plate Heat Exchanger
7 Water Pump
8 Pressure Gage
9 Safety valve
10 compressor
Remarks Male PT 1 inch Male PT 1 inch Filtering and stacking particles inside circulating water PCB and terminal blocks Heat exchanger between refrigerant and water Circulating the water Indicates circulating water pressure Open at water pressure 3 bar –
ENGLISH
GENERAL INFORMATION 19 UN60A (9, 12, 14, 16 kW)
C The shape may differ depending on the model.
20 GENERAL INFORMATION
ENGLISH
Description
No
Name
Remarks
1 Entering water pipe
Male PT 1 inch
2 Leaving water pipe
Male PT 1 inch
3 Strainer
Filtering and stacking particles inside circulating water
4 Top cover
–
5 Front Panel
–
6 Side Panel
–
7 Signal A
Network Kit cables
8 Signal B
Network Kit cables
9 Signal C
–
10 Outdoor Entry Power Cable –
11 Water Pump
Circulating the water
12 Plate Heat Exchanger
Heat exchanger between refrigerant and water
13 Pressure Gage
Indicates circulating water pressure
14 Safety valve
Open at Water pressure 3 bar
15 Heater Control Box
Heater PCB and terminal blocks
16 Outdoor Control Box
Outdoor PCB and terminal blocks
ENGLISH
– For 4 Series
GENERAL INFORMATION 21 UN36A (5, 7, 9 kW)
C The shape may differ depending on the model.
ENGLISH
22 GENERAL INFORMATION
UN60A (12, 14, 16 kW)
C The shape may differ depending on the model.
Description
No
Name
1
Entering water pipe
2
Leaving water pipe
3
Strainer
4
Top cover
5
Front Panel
6
Side Panel
7
Low Voltage
8
UNIT Power
9
Water Pump
10
Plate Heat Exchanger
11
Compressor shield panel
12
Safety valve
13
Indoor Control Box
14
Outdoor Control Box
15
Flow sensor
16
Pressure Sensor
GENERAL INFORMATION 23
Remarks Male PT 1 Inch Male PT 1 Inch Filtering and stacking porticles inside
circulating water
Communication Cable Hole Power Cable Hole Heat exchange between refrigerant
and water Open at water pressure 3 bar PCB and terminal blocks PCB and
terminal blocks SIKA VVX20 5-80 LPM SENSATA 2HMP3-05W 02-MPa
ENGLISH
ENGLISH
24 GENERAL INFORMATION
Control Parts
– For 3 Series
Control box before structural change (Until August, 2020)
UN36A (5, 7, 9 kW)
UN60A (9, 12, 14, 16 kW)
2 2
1 1
Control box after structural change (From September, 2020)
2
1
C The shape may differ depending on the model. Refer to “Exploded View” in SVC
Manual.
Description
No
Name
1 Terminal blocks
2 Main PCB
Remark The terminal blocks allow easy connection of field wiring
The main PCB(Printed Circuit Board) controls the functioning of the unit
ENGLISH
– For 4 Series
Control box
GENERAL INFORMATION 25
2 1
C The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual.
Description
No
Name
1 Terminal blocks
2 Main PCB
Remark The terminal blocks allow easy connection of field wiring
The main PCB(Printed Circuit Board) controls the functioning of the unit
ENGLISH
26 GENERAL INFORMATION
Remote Controller
Operation display window
Back button
OK
Up/Down/Left/Right Button
On/Off Button OK Button
Operation display window Back button Up/down/left/right button OK button On/Off button
Operation and Settings status display When you move to the previous stage from the menu’s setting stage When you change the menu’s setting value When you save the menu’s setting value When you turn ON/OFF the Unit
ENGLISH
GENERAL INFORMATION 27
Typical Installation Example
! CAUTION
If
is installed with pre-existing boiler, the boiler and
should not be
operated together. If entering water temperature of
is above 55 °C, the system
will stop operation to prevent mechanical damage of the product. For detailed electric wiring
and water piping, please contact authorized installer.
Some installation scenes are presented for example. As these scenes are conceptual
figures, installer should optimize the installation scene according to the installation
conditions. Note that buffer tank should be installed.
CASE 1: Connecting Heat Emitters for Heating and Cooling
(Under floor loop, Fan Coil Unit, and Radiator)
Outdoor Indoor
R T
M / F
Buffer Tank
NOTE
Fan coil unit Floor heating loop Radiator
· Room thermostat – Type of thermostat and specification should be complied with chapter 4 and chapter 7 of installation manual.
· 2way valve
– It is important to install 2way valve to prevent dew condensation on the floor and radiator
while cooling mode.
– Type of 2way control valve and specification should be complied with chapter 4 and
chapter 7 of
installation manual.
– 2way valve should be installed at the supply side of the collector.
· By-pass valve – To secure enough water flow rate, by-pass valve should be installed at the collector. – By-pass valve should guarantee minimum water flow rate in any case. Minimum water flow rate is described in water pump characteristics curve.
High Temperature Low Temperature M / F Magnetic Filter (Mandatory)
Room Thermostat (Field supply)
2way valve (Field supply)
Shut-off valve By-pass valve(Field supply) R Remote controller
ENGLISH
28 GENERAL INFORMATION
CASE 2: Connecting DHW Tank
Outdoor Indoor R T
M / F
Buffer Tank
Hot water
City water
DHW tank
Fan coil unit Floor heating loop Radiator
NOTE
· DHW tank – It should be equipped with internal electric heater to generate
sufficient heat energy in very cold season. – DHW : Domestic Hot Water
· 3way valve – Type of 3way valve and specification should be complied with
chapter 4 and chapter 7 of installation manual.
High Temperature Low Temperature Shut-off valve M / F Magnetic Filter (Mandatory)
Room Thermostat(Field supply)
2way valve (Field supply) By-pass valve(Field supply)
R Remote controller
3way valve (Field supply)
ENGLISH
CASE 3: Connecting Solar thermal system
Outdoor Indoor R T
M / F
Buffer Tank
GENERAL INFORMATION 29
Solar heat source
Hot water
DHW tank
Fan coil unit Floor heating loop Radiator
City water
NOTE
· DHW tank – It should be equipped with internal electric heater to generate
sufficient heat energy in very cold season. – DHW : Domestic Hot Water
· Pump – Maximum power consumption of pump should be less than 0.25 kW.
High Temperature Low Temperature Shut-off valve M / F Magnetic Filter (Mandatory)
Room Thermostat(Field supply)
2way valve (Field supply) By-pass valve(Field supply)
R Remote controller
3way valve (Field supply) Pump(Field supply)
ENGLISH
30 GENERAL INFORMATION
CASE 4: Connecting 2nd Circuit
Outdoor Indoor
R T
M / F
Buffer Tank
[Room A] Main Zone zone (Low Temp.)
Mix
2nd circuit temp. sensor
Mix Kit
Floor heating loop Floor heating loop
[Room B] Additional zone (High Temp.)
Radiator
Radiator
NOTE
· Mix Kit – You can install it when you want to set the temperature of two
rooms individually – When heating, Main Zone can not be higher than Add Zone.
– When cooling, Main Zone can not be lower than Add Zone. – The types and
specifications of the Mix Kit are to comply with Chapters 4 and 7 of the
Installation Manual.
High Temperature
Low Temperature
Shut-off valve M / F Magnetic Filter (Mandatory)
Pressure Regulation valve (Field supply)
Room Thermostat (Field supply) 2way valve (Field supply)
By-pass valve(Field supply)
Air vent (Field supply)
3way valve (Field supply) Pump(Field supply)
Mix Kit (Field supply)
ENGLISH
CASE 5: Connecting 3rd Party
Outdoor Indoor
R T
M / F
3 Way V/V direction Boiler On : Boiler Off :
Buffer Tank
Boiler
GENERAL INFORMATION 31
Floor
Floor
Floor
heating loop heating loop heating loop
NOTE
· DHW tank – 3rd Party Boiler – You can control the boiler automatically and
manually by comparing the outside temperature and the set temperature.
· 3way valve – It is a valve for DHW use. – Not installed when installing
Buffer Tank – Type of 3way valve and specification should be complied with
chapter 4 and chapter 7 of installation manual.
High Temperature Low Temperature Shut-off valve M / F Magnetic Filter (Mandatory) Reverse check valve
Room Thermostat(Field supply) 2way valve (Field supply) By-pass valve(Field supply) Air vent (Field supply)
3way valve (Field supply) Pump(Field supply)
Aquastat V/V
ENGLISH
32 GENERAL INFORMATION
CASE 6 : Connecting backup heater
Outdoor Indoor R T
M/F
Buffer Tank
Floor heating Floor heating Floor heating
loop
loop
loop
NOTE
· Backup heater(Accessory) – You can retain sufficient capacity even though
ambient temperature will be decreased in winter.
High Temperature Low Temperature M / F Magnetic Filter (Mandatory)
Room Thermostat (Field supply) 3way valve (Field supply)
R Remote controller
Shut-off valve
By-pass valve (Field supply)
ENGLISH
Cycle Diagram
– For 3 Series UN60A (12, 14, 16 kW)
GENERAL INFORMATION 33
S6 S2
Pressure
Switch
S5
Muffler Accumulator
S4
S3
Inv. Comp
S8
EEV1
EEV2
EEV3 (Inj.EEV) IHEX
S7
High Pressure Sensor S1
S9
:: HCoeaotliinngg S13
S12
Relief
Water
valve
Out Pressure
Gage
Backup Heater Accessory Expansion Tank
Air Vent
S10 [PHE] Water Flow W/Pump Strainer S11 In Switch
UN36A (5, 7, 9 kW)
S6 S2
High
Pressure
Pressure
Sensor
S5
Switch Muffler
S1
Accumulator
S4 EEV1
S7
EEV3 S8 (Inj.EEV)
Inv. Comp
S3
S9 EEV2
: Cooling : Heating
Air Vent
S13
S12
Relief
Water
valve
Out Pressure
Gage
Backup Heater Accessory Expansion Tank Air Vent
IHEX
S10
[PHE]
Water In
Flow W/Pump Switch
Strainer S11
Inv. Comp ENGLISH
34 GENERAL INFORMATION
UN60A (1Ø : 9 kW)
: Cooling
S6
High Pressure
Air Vent
: Heating S13
S2
Pressure
Sensor
S5
Switch
Muffler S1
Accumulator
S12
Backup Heater Accessory
EEV1
S4
S3
Water
Relief valve
Expansion Tank
Out Pressure
EEV3
S9
Gage
Air Vent
(Inj.EEV)
S10
[PHE]WIanter
Flow W/Pump Strainer S11 Switch
Description
Category Symbol
Meaning
Indoor Unit
Water Side
S1 High pressure sensor S2 Condenser middle temperature sensor S3 Compressor- discharge pipe temperature sensor S4 Compressor-suction pipe temperature sensor S5 Condenser temperature sensor S6 Outdoor air temperature sensor S7 Inlet IHEX temperature sensor S8 Outlet IHEX temperature sensor S9 PHEX gas temp. sensor S10 PHEX liquid temp. sensor S11 Entering water temperature sensor S12 Leaving water temperature sensor S13 Electric backup heater outlet (Accessory kit)
-S9, S10, S5 : Description is expressed based on Cooling mode.
PCB Connector CN_H_PRESS CN_MID CN_DISCHA CN_SUCTION CN_C_PIPE
CN_AIR CN_VI_IN CN_VI_OUT CN_PIPE_OUT CN_PIPE_IN
CN_TH3
ENGLISH Inv. Comp
GENERAL INFORMATION 35
– For 4 Series
UN36A (5, 7, 9 kW) UN60A (12, 14, 16 kW)
S6 S2
S5
EEV1
EEV3 (Inj.EEV)
Pressure Switch
Accumulator
S4
S3
S7
Pressure Sensor
Air Vent
S13 Backup Heater Accessory
: Cooling : Heating
S10 [PHE]
Expansion Tank
Relief Water valve Out
S12 Air Vent
S11
Water In
A1
S17 Strainer S19
Flow Sensor
Pressure Sensor
Description
Category Symbol
Meaning
Refrigerant side
S1 S2 S3 S4 S5 S6 S7 EEV1 EEV2
PHEX liquid temperature sensor Outdoor-HEX middle temperature sensor Compressor-discharge pipe temperature sensor Compressor-suction pipe temperature sensor Outdoor-HEX temperature sensor Outdoor air temperature sensor Compressor-injection pipe temperature sensor Electronic Expansion Valve (Heating/Cooling) Electronic Expansion Valve (Injection)
S12 Outlet water temperature sensor
S11 Inlet water temperature sensor S13 Backup heater outlet sensor S17 Flow sensor Water Side S19 Water pressure sensor
A1 Main Water Pump
A8 Electric backup heater(1Ø, Optional accessory) A9 Electric backup heater(3Ø, Optional accessory)
PCB Connector
CN_PIPE_IN CN_MID
CN_DISCHARGE CN_SUCTION CN_C_PIPE CN_AIR CN_VI_IN CN_EEV1 CN_EEV_MAIN
CN_WATER_OUT CN_WATER_IN
CN_TH3 CN_F_SENSOR CN_H20_PRESS CN_PUMP_A1 CN_MOTOR1 CN_HEATER_PCB
HEATER1
ENGLISH
36 GENERAL INFORMATION
Water cycle
– For 3 Series
Remote Room Temp. Sensor
S14
3WAY V/V_1
Shower
B/HT
S15 City Water
DHW Tank
3WAY V/V_2
S16
Solar Thermal Componets
Solor Panel
W/PUMP_2
SOLAR THERMAL SYSTEM
Ref Out Ref In
S9 S10
Unit
F/S
2WAY V/V_1
S12
W/PUMP_1
EXP/TANK
S11 M/F
Fan Coil Unit
Underfloor Heating
Radiator
Indoor Unit (Hydro-Kit)
Magnetic Filter (Mandatory)
Basic installation
DHW Tank is Installed
(DHW tank is necessary)
Solar thermal system is connected
(Solar thermal kit is necessary)
– For 4 Series
Remote Room Temp. Sensor
S14
3WAY V/V_1
Shower
B/HT
S15 City Water
DHW Tank
3WAY V/V_2
S16
Solar Thermal Componets
Solor Panel
W/PUMP_2
SOLAR THERMAL SYSTEM
GENERAL INFORMATION 37
Ref Out Ref In
S10
Unit
F/S
2WAY V/V_1
S12
W/PUMP_1
EXP/TANK
S11 M/F
Fan Coil Unit
Underfloor Heating
Radiator
Indoor Unit (Hydro-Kit)
Magnetic Filter (Mandatory)
Basic installation
DHW Tank is Installed
(DHW tank is necessary)
Solar thermal system is connected
(Solar thermal kit is necessary)
ENGLISH
38 GENERAL INFORMATION
ENGLISH
Description
Category
Symbol S9 S10 S11 S12
F/S
Meaning Refrigerant temperature sensor (Gas side) Refrigerant temperature
sensor (Liquid side) Water temperature sensor (Water In) Water temperature
sensor (Water Out)
Flow Switch
E/HT Electric Heater
Unit W_PUMP1 Internal Water Pump EXP/TANK Expansion Tank S14 Remote Air
temperature sensor CTR/PNL Remote Controller 2WAY V/V_1 To control water flow
for Fan Coil Unit
M / F Magnetic Filter
W/TANK DHW Tank
B/HT Booster heater(in DHW tank)
Water Heating
– Flow control for water which is leaving from unit. 3WAY V/V_1 – Flow
direction switching between underfloor and
water tank
CITY WATER
Water to be heated by Indoor unit and B/HT of W/TANK
SHOWER Water supplied to end-user
S15 W/TANK water temperature sensor
S16 Solar-heated water temperature sensor
3WAY V/V_2
– Flow control for water which is heated and circulated by SOLAR THERMAL SYSTEM. – Flow direction switching between SOLAR THERMAL SYSTEM and W/TANK
PCB Connector CN_PIPE_OUT CN_PIPE_IN
Water _IN Water _OUT CN_FLOW1
CN_E/HEAT(A) CN_E/HEAT(B)
CN_MOTOR1 (no connector)
CN_ROOM CN_REMO CN_2WAY(A)
(No connector)
(no connector)
CN_B/HEAT(A)
CN_3WAY(A)
(no connector) (no connector)
CN_TH4
CN_3WAY(B)
Remarks
– Meaning is expressed based on Cooling mode.
– Optional accessory (sold separately) – Model : HA**1A E1 – Heating capacity
is divided into two level : partial capacity by E/HEAT(A) and full capacity by
E/HEAT(A) + E/HEAT(B). – Operating power(220-240 V~ 50 Hz) of E/HEAT(A) and
E/HEAT(B) are supplied by external power source via relay connector and ELB. –
Water Pump is connected at CN_MOTOR1 – Absorb volume change of heated water, –
Optional accessory (sold separately) – Model : PQRSTA0
– 3rd party accessory and Field installation (sold separately) – 2 wire NO or
NC type 2way valve is supported. – 3rd party accessory and Field installation
(sold separately) – It is Mandatory to install an additional filter on the
heating water circuit. – 3rd party accessory and Field installation (sold
separately) – Generating and storing DHW by AWHP or built-in electric heater –
3rd party accessory and Field installation (usually built-in at W/TANK) –
Supplying additional water heating capacity. – 3rd party accessory and Field
installation (sold separately) – SPDT type 3way valve is supported.
– Field installation
– Field installation – S15 and S16 are connected at 4 pin type connector
CN_TH4. – S15 is a part of DHW tank kit.(Model : PHLTB) – S16 is a part of
solar thermal kit (Model:PHLLA)
– 3rd party accessory and Field installation (sold separately) – SPDT type
3way valve is supported.
Solar Heating
W_PUMP/2 External Water Pump
CN_W/PUMP(B)
– 3rd party accessory and Field installation (sold separately) – If water pump of SOLAR THERMAL SYSTEM is incapable of circulation,external water pump can be used.
SOLAR THERMAL SYSTEM
– This system can include following components :
Solar panel, Sensors, Thermostats, Interim heat
exchanger, Water pump, etc.
(no connector)
– To utilized hot water heated by SOLAR THERMAL
SYSTEM, end-user must by LG AWHP Solar-Kit.
– 3rd party accessory and Field installation (sold separately)
ENGLISH
INSTALLATION 39
INSTALLATION
Transporting the Unit
· When carrying the suspended unit, pass the ropes between legs of base panel
under the unit. · Always lift the unit with ropes attached at four points so
that impact is not applied to the unit. · Attach the ropes to the unit at an
angle of 40° or less. · Use only accessories and parts which are of the
designated specification when installing. · Forklift trucks are not available
without a palette. · Be careful not to damage the product when moving the
forklift.
Sub line
40º or less
Air outlet grille
Corner Handle
Intake hole
Always hold the unit by the corners, as holding it by the side intake holes on the casing may cause them to deform.
Forklift
ENGLISH
40 INSTALLATION
Installation places
– If an awning is built over the unit to prevent direct sunlight or rain
exposure, make sure that heat radiation from the condenser is not restricted.
– Ensure that the spaces indicated by arrows around front, back and side of
the unit. – Do not place animals and plants in the path of the warm air. –
Take the Unit weight into account and select a place where noise and vibration
are minimum. – Select a place so that the warm air and noise from the air
conditioner do not disturb neighbors. – Place that can sufficiently endure the
weight and vibration of the outdoor unit and where even
installation is possible – Place that has no direct influence of snow or rain
– Place with no danger of snowfall or icicle drop – Place without weak floor
or base such as decrepit part of the building or with a lot of snow
accumulation
More than 300
Awning
- : Please secure the space to Maintain the shut-off valve and strainer.
oFbesntcaecloers
*Minimum 300
More than 600 More than 700
Unit : mm
! CAUTION
Be very careful while carrying the product.
· Do not have only one person carry product if it is more than 20 kg.
· PP bands are used to pack some products. Do not use them as a mean for
transportation because they are dangerous.
· Do not touch heat exchanger fins with your bare hands. Otherwise you may get
a cut in your hands.
· Tear plastic packaging bag and scrap it so that children cannot play with
it. Otherwise plastic packaging bag may suffocate children to death.
· When carrying in Unit, be sure to support it at four points. Carrying in and
lifting with 3-point support may make Outdoor Unit unstable, resulting in a
fall.
· Use 2 belts of at least 8 m long.
· Place extra cloth or boards in the locations where the casing comes in
contact with the sling to prevent damage.
· Hoist the unit making sure it is being lifted at its center of gravity.
ENGLISH
INSTALLATION 41
Installation at Seaside
! CAUTION
· Unit should not be installed in areas where corrosive gases, such as acid or
alkaline gas, are produced.
· Do not install the unit where it could be exposed to sea wind (salty wind)
directly. It can result corrosion on the unit. Corrosion, particularly on the
condenser and evaporator fins, could cause unit malfunc-tion or inefficient
performance.
· If unit is installed close to the seaside, it should avoid direct exposure
to the sea wind. Otherwise it needs additional anticorrosion treatment on the
heat exchanger.
Selecting the location
· If the unit is to be installed close to the seaside, direct exposure to the
sea wind should be avoided. Install the unit on the opposite side of the sea
wind direction.
Sea wind
Sea wind
· In case, to install the unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak Sea wind
– It should be strong enough like concrete to prevent the sea wind from the
sea.
– The height and width should be more than 150 % of the unit.
– It should be keep more than 700 mm of space between unit and the windbreak
for easy air flow.
· Select a well-drained place.
– If you can’t meet above guide line in the seaside installation, please
contact your supplier for the additional anticorrosion treatment.
– Periodic ( more than once/year ) cleaning of the dust or salt particles
stuck on the heat exchanger by using water
Seasonal Wind and Cautions in Winter
· Sufficient measures are required in a snow area or severe cold area in
winter so that unit can be operated well.
· Get ready for seasonal wind or snow in winter even in other areas. · Install
a suction and discharge duct not to let in snow or rain. · Install the unit
not to come in contact with snow directly. If snow piles up and freezes on the
air
suction hole, the system may malfunction. If it is installed at snowy area,
attach the hood to the system. · Install the unit at the higher installation
console by 500 mm than the average snowfall (annual average snowfall) if it is
installed at the area with much snowfall. · Where snow accumulated on the
upper part of the unit by more than 100 mm, always remove snow for operation.
– The height of H frame must be more than 2 times the snowfall and its width
shall not exceed
the width of the unit. (If width of the frame is wider than that of the unit,
snow may accumulate.) – Don’t install the suction hole and discharge hole of
the unit facing the seasonal wind.
ENGLISH
42 INSTALLATION
Foundation for Installation
· Check the strength and level of the installation ground so that the unit
will not cause any operating vibration or noise after installation.
· Fix the unit securely by means of the foundation bolts. (Prepare 6sets of
M12 foundation bolts, nuts and washers each which are available on the
market.)
· It is best to screw in the foundation bolts until their length are 20 mm
from the foundation surface.
· When installing the unit on the ground, install a separate pedestal with
enough height to install the drain nipple.
620
293
100 75
200 75
200 361
Spring washer
Frame
Nut
H-Beam
Anti-vibration materials
Concrete base
Six bolt are required 3 thread ridges
Foundation bolt executing method
[Unit:mm]
! WARNING
· Be sure to remove the Pallet(Wood Support) of the bottom side of the unit
Base Pan before fixing the bolt. It may cause the unstable state of the unit
settlement, and may cause freezing of the heat exchanger resulting in abnormal
operations.
· Be sure to remove the Pallet(Wood Support) of the bottom side of the unit
before welding. Not removing Pallet(Wood Support) causes hazard of fire during
welding.
Pallet(Wood Support) – Remove before Installation
ENGLISH
INSTALLATION 43
Electrical Wiring
· Follow ordinance of your governmental organization for technical standard
related to electrical equipment, wiring regulations and guidance of each
electric power company.
! WARNING
· Be sure to have authorized electrical engineers do the electric work using
special circuits in accordance with regulations and this installation manual.
If power supply circuit has a lack of capacity or electric work deficiency, it
may cause an electric shock or fire.
· Install the Unit transmission line away from the power source wiring so that
it is not affected by electric noise from the power source. (Do not run it
through the same conduit.)
· Be sure to provide designated grounding work to Unit.
! CAUTION
· Be sure to correct the unit to earth. Do not connect earth line to any gas
pipe, liquid pipe, lightening rod or telephone earth line. If earth is
incomplete, it may cause an electric shock.
· Give some allowance to wiring for electrical part box of Units, because the
box is sometimes removed at the time of service work.
· Never connect the main power source to terminal block of transmission line.
If connected, electrical parts will be burnt out.
· Only the transmission line specified should be connected to the terminal
block for Unit transmission.
! CAUTION
· This product have reversed phase protection detector that only works when
the power is turned on. If there exists black out or the power goes on and off
which the product is operating, attach a reversed phase protection circuit
locally. running the product in reversed phase may break the compressor and
other parts.
· Use the 2-core shield cables for communication lines. Never use them
together with power lines.
· The conductive shielding layer of cable should be grounded to the metal part
of both units. · Never use multi-core cable · As this unit is equipped with an
inverter, to install a phase leading capacitor not only will
deteriorate power factor improvement effect, but also may cause capacitor
abnormal heating. Therefore, never install a phase leading capacitor. · Make
sure that the power unbalance ratio is not greater than 2 %. If it is greater,
the unit’s lifespan will be reduced. · Introducing with a missing N-phase or
with a mistaken N-phase will break the equipment
44 INSTALLATION
ENGLISH
! CAUTION
The power cable connected to the unit should be complied with IEC 60245 or HD
22.4 S4 (This equipment shall be provided with a cable set complying with the
national regulation. Pipes and wires should be purchased separately for
installation of the product.)
Select a circuit breaker and power cable suitable for the current
specification.
Factory Model Name ZHBW056A0 ZHBW076A0 ZHBW096A0 ZHBW096S0 ZHBW126A0 ZHBW146A0 ZHBW166A0 ZHBW128A0 ZHBW148A0 ZHBW168A0 ZHBW056A1 ZHBW076A1 ZHBW096A1 ZHBW126A1 ZHBW146A1 ZHBW166A1 ZHBW128A1 ZHBW148A1 ZHBW168A1
Buyer Model Name HM051M U43 HM071M U43 HM091M U43
HM091MRS U33 HM121M U33 HM141M U33 HM161M U33 HM123M U33 HM143M U33 HM163M U33
HM051MR U44 HM071MR U44 HM091MR U44 HM121MR U34 HM141MR U34 HM161MR U34
HM123MR U34 HM143MR U34 HM163MR U34
Phase[Ø] 1 1 3 1 1 3
Capacity [kW] 5 7 9 9 12 14 16 12 14 16 5 7 9 12 14 16 12 14 16
ELCB 16 A 20 A 25 A 16 A 40 A 40 A 40 A 16 A 16 A 16 A 16 A 20 A 25 A 40 A 40 A 40 A 16 A 16 A 16 A
Power cable (Type : H07RNF)
Current [A] Area [mm2] [A] 0.2 Tinsel cord a
0.2< [A] 3
0.5 a
3< [A] 6
0.75
6< [A] 10 1.0 (0.75)b
10< [A] 16 1.5 (1.0)b
16< [A] 25
2.5
25< [A] 32
4
32< [A] 40
6
40< [A] 63
10
a These cords may only be used if their length does not exceed 2 m between the
point where the cord or cord guard enters the appliance and the entry to the
plug.
b Cords having the cross-sectional areas indicated in the parentheses may be
used for portable appliances if their length does not exceed 2 m.
10±3 mm 35±5 mm
10±3 mm 35±5 mm
GN/YL 20 mm
For the 1-Phase
GN/YL 20 mm
For the 3-Phase
ENGLISH
INSTALLATION 45
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power wire
When none are available, follow the instructions below. – Do not connect
wiring of different thicknesses to the power terminal block. (Slack in the
power
wiring may cause abnormal heat.) – When connecting wiring which is the same
thickness, do as shown in the figure below.
Connect same thickness wiring to both sides.
It is forbidden to connect two to one side.
It is forbidden to connect wiring of different thicknesses.
– For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal block.
– Use an appropriate screwdriver for tightening the terminal screws. A
screwdriver with a small head will strip the head and make proper tightening
impossible.
– Over-tightening the terminal screws may break them.
! WARNING
· Make sure that the screws of the terminal are free from looseness.
ENGLISH
46 INSTALLATION
Point for attention regarding quality of the public electric power supply (For
3 Series)
– European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply systems
for equipment with rated current 75 A.
– European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with
input current 16 A of > 75 A per phase.
For 1 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents
emission limits corresponding Rsce = 33.
– This equipment complies with reference impedance for IEC (EN) 61000-3-3.
For 3 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 provided that the short-
circuit power Ssc is greater than or equal to 2067 kVA at the interface point
between the user’s supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to 2067
kVA.
– This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (5,7, 9 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents
emission limits corresponding Rsce = 33.
– This equipment complies with IEC (EN) 61000-3-3.
ENGLISH
INSTALLATION 47
Point for attention regarding quality of the public electric power supply (For
4 Series)
– European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply systems
for equipment with rated current 75 A.
– European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with
input current 16 A of > 75 A per phase.
For 1 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents
emission limits corresponding Rsce = 33.
– This equipment complies with reference impedance for IEC (EN) 61000-3-11.
For 3 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 provided that the short-
circuit power Ssc is greater than or equal to 2672 kVA at the interface point
between the user’s supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to 2672
kVA.
– This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (5,7 kW)
– This equipment complies with IEC (EN) 61000-3-2. – This equipment complies
with IEC (EN) 61000-3-3.
For 1 Phase (9 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents
emission limits corresponding Rsce = 33.
– This equipment complies with IEC (EN) 61000-3-3.
ENGLISH
48 INSTALLATION
Circuit Breaker Specification
Perform the electrical wiring work according to the electrical wiring
connection. · All wiring must comply with local requirements. · Select a power
source that is capable of supplying the current required by the appliance. ·
Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power
source and the
unit. A disconnection device to adequately disconnect all supply lines must be
fitted. · Model of circuit breaker recommended by authorized personnel Only. ·
Select a circuit breaker suitable for the current specification.
Unit
Backup
Live Signal for Backup Heater
Heater
(A+B)
CB
Live Signal for DHW Tank kit
CB ELCB
Switch Box
DHW Tank
CB DHW Tank kit
Power source Sensor Signal
CB : Circuit Breaker ELCB : Electric Leakage Circuit Breaker
ENGLISH
INSTALLATION 49
Wiring procedure for power cable
This cable is generally connected between external power source (such as main
electric power distribution panel of user’s house) and the unit. Before
starting wiring, check if wire specification is suitable and read following
directions and cautions VERY carefully.
! CAUTION
After checking and confirming following conditions, start wiring work. ·
Secure dedicated power source for the Air-to-Water heat pump. The wiring
diagram
(attached inside the control box of the unit) is presenting related
information. · Provide a circuit breaker switch between power source and the
outdoor unit. · Although it is very rare case, sometimes the screws used to
fasten internal wires can be
loosen due to the vibration while product transportation. Check these screws
and make it sure if they are all fastened tightly. If not tightened, burn-out
of the wire can be occurred. · Check the specification of power source such as
phase, voltage, frequency, etc. · Confirm that electrical capacity is
sufficient. · Be sure that the starting voltage is maintained at more than 90
percent of the rated voltage marked on the name plate. · Confirm that the
cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.) · Provide
an ELB(electric leakage breaker) when the installation place is wet or moist.
· The following troubles would be caused by abnormal voltage supply such as
sudden voltage increasing or voltage drop-down. – Chattering of a magnetic
switch (frequent on and off operation) – Physical damage of parts where
magnetic switch is contacted – Break of fuse – Malfunction of overload
protection parts or related control algorithms. – Failure of compressor start
up – Ground wire to ground outdoor unit to prevent electrical shock.
Step 1. Disassemble side panel and front panel from the unit by loosing
screws.
UN36A (5, 7, 9 kW)
UN60A(1Ø : 9, 12, 14, 16 kW)
UN60A (3Ø : 12, 14, 16 kW)
- The feature may be vary according to the type of model.
ENGLISH
50 INSTALLATION
Step 2. Connect power cable to main power terminal See below figure for
detailed information. When connecting earth cable, the diameter of cable
should be refer to the below table. The earth cable is connected to the
Control box case where earth symbol is marked.
Step 3. Use cable clamps (or cord clamps) to prevent unintended move of power
cable. Step 4. Reassemble the side panel to the unit by fastening screws.
CODE CLAMP
UNIT POWER
UN36A (5, 7, 9 kW)
CODE CLAMP
CODE CLAMP
UNIT POWER
UN60A(1Ø : 9, 12, 14, 16 kW)
UNIT POWER
UN60A (3Ø : 12, 14, 16 kW)
Failure to do these instruction can result in fire, electric shock or death. · Make sure the power cable do not touch to copper tube. · Make sure to fix [cord clamp] firmly to sustain the connection of terminal. · Make sure to connect unit power & heater power separately.
- The feature may be vary according to the type of model.
ENGLISH
INSTALLATION 51
Terminal Block Information
– For 3 Series Symbols used below pictures are as follows : – L, L1, L2 : Live
(220-240 V~) – N : Neutral (220-240 V~) – BR : Brown, WH : White, BL : Blue,
BK : Black
Case 1
Terminal Block 1
Energizing water pump for solar thermal system
1
2
3
L1 L2 N
MIXING VALVE
45 LN
MIX PUMP
67
LN
WATER PUMP
(B)
8 9 10 L L1 N
3WAY VALVE (B)
Power supply for 2nd heating kit
Water flow switching between using solar thermal heating and skipping solar thermal heating
Opening or closing water flow for FCU cooling
11 12 13
L L1 N
3WAY VALVE (B)
14 15 16 L L1 N
2WAY VALVE (A)
17 18 19 20 L N L1 L2
THERMOSTAT (Default : 230 V AC)
Water flow switching between under floor heating and DHW tank heating
Connection for thermostat (230 V AC)
Supporting type : Heating only or Heating/Cooling
Case 2
Terminal Block 1
Energizing water pump for solar thermal system
Water flow switching between under floor heating and DHW tank heating
1
2
3
L L1 N
3WAY VALVE (B)
45
LN
WATER PUMP
(B)
67
LN
WATER TANK HEATER
8 9 10 L L1 N
3WAY VALVE (A)
Water flow switching between using Turn on or off DHW
solar thermal heating and skipping
tank heater
solar thermal heating
Terminal Block 2
Power supply for 2nd heating kit
11 12 13 14
ABL N
3rd PARTY CONTROLLER
MIX PUMP
15 16 17 18 19 20 L1 L2 N L L1 N
MIXING VALVE 2WAY VALVE(A)
Connection for 3rd PARTY CONTROLLER
Opening or closing water flow for FCU cooling
Terminal Block 2 Terminal Block 3
21
22
L1
L2
WATER TANK HEATER
Turn on or off DHW tank heater
Turn on or off backup heater
23 24 LN
HEATER (B)
25 26 27 28 LNAB
HEATER 3rd PARTY (A) CONTROLLER
Connection for 3rd PARTY CONTROLLER
Terminal Block 4
Terminal Block 3
Connection for thermostat (230 V AC)
Supporting type : Heating only or Heating/Cooling
21 22 23 24 25 26 27 28 29 30
L N L N L N L1 L2
HEATER (A)
HEATER (B)
THERMOSTAT (Default : 230 V AC)
Turn on or off backup heater
Terminal Block 4
29
30
L1
L2
E/HEATER OUT SENSOR (5 V DC)
Connection for E/HEATER OUT SENSOR
31
32
L1
L2
E/HEATER OUT SENSOR (5 V DC)
Connection for E/HEATER OUT SENSOR
Terminal Terminal Block 1 Block 2
Terminal Terminal Block 3 Block 4
(Accessory)
Terminal Block 4
Terminal Terminal Terminal Block 1 Block 3 Block 2
(Accessory)
C Refer to Terminal Block Information according to the C/Box shape.
ENGLISH
52 INSTALLATION
– For 4 Series Symbols used below pictures are as follows : – L, L1, L2 : Live
(220-240 V~) – N : Neutral (220-240 V~) – BR : Brown, WH : White, BL : Blue,
BK : Black
Terminal Block 1
1
23
L L1 N
MIXING VALVE
45 6 L L1 N
2WAY VALVE (A)
7
89
L L1 N
3WAY VALVE (A)
Power supply for 2nd heating kit
Water flow switching between using solar thermal heating and skipping solar thermal heating
Energizing water pump for solar thermal system
10 11 12 13 14 L L1 N L N
3WAY VALVE WATER TANK
(B)
HEATER
15 16 LN
WATER PUMP(B)
17 18 LN
MIX PUMP
19 20 LN
WATER PUMP(C)
Water flow switching between under floor heating and DHW tank heating
Power supply for 2nd heating kit
Terminal Block 2 Terminal Block 3
21 22 23 24 25 26 27
L
N L1 L2 L3 A B
THERMOSTAT (Default : 230 V AC)
3rd PARTY CONTROLLER
(5V DC)
Connection for thermostat (230 V AC)
Supporting type : Heating only or Heating/Cooling
Connection for 3rd PARTY CONTROLLER
Terminal Block 1
Terminal Terminal Terminal Block 2 Block 3 Block 4
(Accessory)
Terminal Block 4
28
29
L1
L2
E/HEATER OUT SENSOR (5 V DC)
Connection for E/HEATER OUT SENSOR
C Refer to Terminal Block Information according to the C/Box shape.
ENGLISH
INSTALLATION 53
Wiring of main power supply and equipment capacity
1. Use a separate unit power and heater power. 2. Bear in mind ambient
conditions (ambient temperature,direct sunlight, rain water,etc.) when
proceeding with the wiring and connections. 3. The wire size is the minimum
value for metal conduit wiring. The power cord size should be 1
rank thicker taking into account the line voltage drops. Make sure the power-
supply voltage does not drop more than 10 %. 4. Specific wiring requirements
should adhere to the wiring regulations of the region. 5. Power supply cords
of parts of appliances for unit use should not be lighter than polychloroprene
sheathed flexible cord. 6. Don’t install an individual switch or electrical
outlet to disconnect each of unit separately from the power supply.
! WARNING
· Follow ordinance of your governmental organization for technical standard
related to electrical equipment, wiring regulations and guidance of each
electric power company.
· Make sure to use specified wires for connections so that no external force
is imparted to terminal connections. If connections are not fixed firmly, it
may cause heating or fire.
· Make sure to use the appropriate type of overcurrent protection switch. Note
that generated overcurrent may include some amount of direct current.
! CAUTION
· Some installation site may require attachment of an earth leakage breaker.
If no earth leakage breaker is installed, it may cause an electric shock.
· Do not use anything other than breaker and fuse with correct capacity. Using
fuse and wire or copper wire with too large capacity may cause a malfunction
of unit or fire.
ENGLISH
54 INSTALLATION
Water Piping and Water Circuit Connection
! CAUTION
Followings are should be considered before beginning water circuit connection.
· Service space should be secured. · Water pipes and connections should be
cleaned using water. · Space for installing external water pump should be
provided if internal water pump
capacity is not enough for installation field. · Never connect electric power
while proceeding water charging.
Definition of terms are as follow : · Water piping : Installing pipes where
water is flowing inside the pipe. · Water circuit connecting : Making
connection between the unit and water pipes or between
pipes and pipes. Connecting valves or elbows are, for example, in this
category.
Configuration of water circuit is shown in “Installation Scenes”. All
connections should be complied with presented diagram.
While installing water pipes, followings should be considered : · While
inserting or putting water pipes, close the end of the pipe with pipe cap to
avoid dust
entering. · When cutting or welding the pipe, always be careful that inner
section of the pipe should not be
defective. For example, no weldments or no burrs are found inside the pipe. ·
Drain piping should be provided in case of water discharge by the operation of
the safety valve.
This situation can be happened when the internal pressure is over 3.0 bar and
water inside the unit will be discharged to drain hose. · Pipe fittings (e.g.
L-shape elbow, T-shape tee, diameter reducer, etc) should be tightened
strongly to be free from water leakage. · Connected sections should be
leakage-proof treatment by applying tefron tape, rubber bushing, sealant
solution, etc. · Appropriate tools and tooling methods should be applied to
prevent mechanical breakage of the connections. · Operation time of flow
valve(e.g. 3way valve or 2way valve) should be less than 90 seconds. · While
supplying water, pressure of supplying water should be 2.0 bar approximately.
· Pipe is insulated to prevent heat loss to external environment and to
prevent dew generation on the surface of the pipe in cooling operation. ·
Maximum allowable Torque at the water piping connection is 50 N·m
ENGLISH
INSTALLATION 55
When the water pipes are connected. It must be tightened the nut with two
wrench. Otherwise pipes can be deformed.
Water Out
Union Water In
- The feature may be vary according to the type of model.
! WARNING
Installing shut-off valve · While assembling two shut-off valves, pop sound will be heard when valve is open or
close by rotating handles. It is normal condition because the sound is due to leakage of charged nitrogen gas inside the valve. The nitrogen gas is applied to secure quality assurance. · Before starting water charging, these two shut- off valves should be assembled with water inlet and outlet pipe of the unit.
Water condensation on the floor While cooling operation, it is very important to keep leaving water temperature higher than 16 °C. Otherwise, dew condensation can be occurred on the floor. If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator While cooling operation, cold water may not flow to the radiator. If cold water enters to the radiator, dew generation on the surface of the radiator can be occurred.
Water Pipe Insulation Purpose of water pipe insulation is : To prevent heat loss to external environment. To prevent dew generation on the surface of the pipe in cooling operation. To prevent pipe breakage by freeze at winter season, Must be insulation at exterior water pipe between product and building.
ENGLISH
56 INSTALLATION
Water Charging
For water charging, please follow below procedures.
Step 1. Open all valves of whole water circuit. Supplied water should be
charged not only inside the unit, but also in the under floor water circuit,
DHW water tank circuit, FCU water circuit, and any other water circuits
controlled by the product.
Step 2. Connect supply water into drain valve and fill valve located at the
side of the shut-off valve.
! CAUTION
No water-leakage permitted at the drain and fill valve. Leakage-proof
treatment which is described in previous section should be applied.
Step 3. Start to supply water. While supplying water, following should be
kept. – Pressure of supplying water should be 2.0 bar approximately. – For
supplying water pressure, time to be taken from 0 bar to 2.0 bar should be
more than 1 minute. Sudden water supply can yield water drain through safety
valve. – Fully open the cap of air vent to assure air purging. If air is exist
inside the water circuit, then performance degrade, noise at the water pipe,
mechanical damage at the surface of electric heater coil. – Open both the air
vent in the water pipe and the air vent in the pump.
Step 4. Stop water supplying when the pressure gage located in front of the
control panel indicates 2.0 bar.
Step 5. Close drain valve and fill valve. Then wait for 20~30 seconds to
observe water pressure being stabilized.
Step 6. If following conditions are satisfactory, then go to Next process(Pipe
Insulation). Otherwise, go to step 3. – Pressure gage indicates 2.0 bar. Note
that sometimes pressure in decreased after step 5 due to water charging inside
expansion vessel. – No air purging sound is heard or no water drop are popping
out from air vent.
! CAUTION
Keep the air vent of the water pipe open and keep the air vent of the pump
closed. Otherwise, the pump may make noise.
Pipe Insulation
Purpose of water pipe insulation is : · To prevent heat loss to external
environment · To prevent dew generation on the surface of the pipe in cooling
operation
ENGLISH
INSTALLATION 57
Water pump Capacity
The water pump us variable type which is capable to change flow rate, so it
may be required to change default water pump capacity in case of noise by
water flow. In most case, however, it is strongly recommended to set capacity
as Maximum.
NOTE
· To secure enough water flow rate, do not set water pump capacity as Minimum.
It can lead unexpected flow rate error CH14.
Pressure Drop
NOTE
When installing the product, install additional pump in consideration of the
pressure loss and pump performance. If flow rate is low, overloading of
product can occur
Capacity [kW] 16 14 12 9 7 5
Rated flow-rate [LPM(m3/h)]
Pump Head [m] (At rated flow rate)
Product pressure
drop [m] Serviceable Head
(Plate heat
[m]
exchanger)
46.0 (2.8)
9.0
1.4
7.6
40.25 (2.4)
9.3
1.1
8.2
34.5 (2.1)
9.8
0.8
9.0
25.87 (1.5)
6.1
0.4
5.7
20.12 (1.2)
7.3
0.3
7.0
14.37 (0.9)
7.5
0.2
7.3
ENGLISH
58 INSTALLATION
Performance curve
MGQ62321901 : UPML GEO 20 – 105 CHBL UN60A (12, 14, 16 kW)
MGQ62321902 : UPM3K GEO 20 – 75 CHBL UN36A (5, 7, 9 kW), UN60A (9 kW)
Performance test based on standard ISO 9906 with pre-pressure 2.0 bar and
liquid temperature 20 °C.
! WARNING
· Selecting a water flowrate outside the curves can cause damage to or
malfunction of the unit.
ENGLISH
INSTALLATION 59
Water Quality
Water quality should be complied with EN 98/83 EC Directives. Detailed water
quality condition can be found in EN 98/83 EC Directives.
! CAUTION
· If the product is installed at existing hydraulic water loop, it is
important to clean hydraulic pipes to remove sludge and scale.
· Installing sludge strainer in the water loop is very important to prevent
performance degrade.
· Chemical treatment to prevent rust should be performed by installer. · It is
strongly recommended to install an additional filter on the heating water
circuit.
Especially to remove metallic particles from the heating piping, it is advised
to use a magnetic or cyclone filter, which can remove small particles. Small
particles may damage the unit and will NOT be removed by the standard filter
of the heat pump system.
Frost protection by antifreeze
In areas of the country where entering water temperatures drop below 0 °C, the
water pipe must be protected by using an approved antifreeze solution. Consult
your AWHP unit supplier for locally approved solutions in your area. Calculate
the approximate volume of water in the system. (Except the AWHP unit.) And add
six liters to this total volume to allow for the water contained in AWHP unit.
Antifreeze type
Ethylene glycol Propylene glycol
Methanol
Antifreeze mixing ratio
0 °C
-5 °C
-10 °C -15 °C -20 °C -25 °C
0 %
12 %
20 %
30 %
–
–
0 %
17 %
25 %
33 %
–
–
0 %
6 %
12 %
16 %
24 %
30 %
If you use frost protection function, change DIP switch setting and input the
temperature condition in Installation mode of remote controller. Refer to
CONFIGURATION > DIP Switch Setting > DIP Switch Information > Option Switch 3
and INSTALLER SETTING > Antifreezing Temperature
.
! CAUTION
· Use only one of the above antifreeze. · If a antifreeze is used, pressure
drop and capability degradation of the system can be
occurred. · If one of antifreezes is used, corrosion can be occurred. So
please add corrosion inhibitor. · Please check the concentration of the
antifreeze periodically to keep same concentration. · When the antifreeze is
used (for installation or operation), take care to ensure that
antifreeze must not be touched. · Ensure to respect all laws and norms of your
country about Anti-freeze usage.
ENGLISH
60 INSTALLATION
Frost protection by antifreeze valve
About antifreeze valve This is a valve to prevent freeze in winter. When no
antifreeze is added to the water, you can use antifreeze valves at all lowest
points of the field piping to drain the water from the system before it can
freeze
To install antifreeze valve To protect the field piping against freezing,
install the following parts:
Outdoor Indoor
a C
b C
b
a Automatic air intake b Antifreeze valve (Optional field supply) c Normally closed valves (recommended field supply)
Part
Description
An automatic air intake (for air supply) should be installed at the highest point.
a
For example, an automatic air purge.
Protection for the field piping. The antifreeze valve must be installed:
· Vertically to allow water to flow out properly and free from obstructions.
b
· At all lowest points of the field piping.
· In the coldest part and away from heat sources.
Isolation of water inside the house when there is a power interruption.
Normally closed valves (located indoors near the piping entry/exit points) can
prevent that all water from indoor piping is drained when the antifreeze valve
open.
s
· When there is a power interruption: The normally closed valves close and
c
isolate the water inside the house. If the antifreeze valve open, only the
water outside the house is drained.
· In other circumstances (example: when there is a pump failure): The normally closed valves remain open. If the antifreeze valve open, the water from inside the house is also drained.
ENGLISH
INSTALLATION 61
NOTE
· Do not make any trap connections. If the shape of the connection pipe has
the potential to create a trap effect, part of the pipe will not be able to
drain and frost protection will no longer be guaranteed.
· Leave at least 15 cm clearance from the ground to prevent ice from blocking
the water exit.
· Keep a distance of at least 10 cm between the antifreeze valves.
· The valve must be free of insulation for the system to work properly.
· When antifreeze valves are installed, do NOT select a minimum cooling
setpoint lower than 7 °C. If lower, antifreeze valves can open during cooling
operation.
· When installed outdoors, the antifreeze valve must be protected from rain,
snow and direct sunlight.
Outdoor Indoor
10 cm
b b
15 cm
62 INSTALLATION
ENGLISH
Water Volume and Expansion Vessel Pressure
Inside expansion vessel is included which is 8 liter capacity with 1 bar pre-
pressure. That means, according to the volume-pressure graph, total water
volume of 230 liter is supported as default. If total water volume is changed
because of installation condition, the pre-pressure should be adjusted to
secure proper operation.
– Minimum total water volume is 20 liter. – Pre-pressure is adjusted by the
total water volume. If the indoor is located at the highest
position of the water circuit, adjustment is not required. – To adjust pre-
pressure, use nitrogen gas by certificated installer.
2.4
Pre-pressure in Expansion vessel (bar)
2.1
1.7
1.4
1.0
0.7
0.3
20
60
100 140
180 220 260 300 340
Maximum total water volume (liter)
Adjusting pre-pressure of expansion vessel is as following :
Step 1. Refer “Volume-Height” table. If installation scene is belong to Case
A, go to Step 2. Otherwise, if it is Case B, do nothing. (pre-pressure
adjustment is not required.) Otherwise, if it is Case C, go to Step 3.
Step 2. Adjust pre-pressure by following equation. Pre-pressure [bar] = (0.1 x
H + 0.3) [bar] where H : difference between unit and the highest water pipe
0.3 : minimum water pressure to secure product operation
Step 3. Volume of expansion vessel is less than installation scene. Please
install additional expansion vessel at the external water circuit.
Volume-Height Table
H < 7 m H7m
V < 230 liter V 230 liter
Case B
Case A
Case A
Case C
H : difference between unit and the highest water pipe V : total water volume of installation scene
ACCESSORIES INSTALLATION 63
ENGLISH
ACCESSORIES INSTALLATION
can interface to various accessories to extend its functionality and to improve user
convenience. In this chapter, specifications about supported 3rd party accessories and how to
connect to
is introduced.
It is noted that this chapter only deal with 3rd party accessories. For accessories supported by LG Electronics, please refer to installation manual of each accessories.
Accessories supported by LG Electronics
Item DHW Tank Install Kit Thermistor for DHW Tank Remote Temperature Sensor
Dry Contact
Solar thermal Kit Meter Interface
Central Controller
Backup heater
Wi-Fi Modem Thermistor for 2nd Circuit Extension wire
PI485
ESS
Purpose
To operate with DHW tank
To control hot water temperature of DHW tank
PHLTB
Model
PHRSTA0
To control by air temperature
PQRSTA0
To receive on & off external signal Dry Contact For Thermostat
PDRYCB000 PDRYCB300
To operate with solar heating system
PHLLA(Limit temperature : 96 °C)
To measure production / consumption power
PENKTH000
Multiple installed products into one central control
AC EZ Touch (PACEZA000) AC Smart IV (PACS4B000) AC Smart 5 (PACS5A000) ACP 5 (PACP5A000) AC Manager 5 (PACM5A000)
To supplement insufficient capacity
HA031M E1 / HA061M E1 / HA063M E1
To enable remote system operation from smartphone
PWFMDD200
To interlock with 2nd circuit operation and control temperature of main zone.
PRSTAT5K10
To connect remote controller with Indoor PCB for communication
PZCWRC1
To communicate and control through For 3 Series: PMNFP14A1
the central controller
For 4 Series: PP485A00T
To control the operation mode according to the energy storage state
HOME 8 (PCS) : D008KE1N211 HOME10(PCS) : D010KE1N211 HB7H(Battery) : BLGRESU7H HB10H(Battery) : BLGRESU10H
64 ACCESSORIES INSTALLATION
ENGLISH
Item
Purpose
Model
DHW Tank
To generate and store hot water
OSHW-200F : 200 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-300F : 300 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-500F : 500 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-300F : 300 L, Double Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater
Cloud Gateway To use Becon cloud
PWFMDB200
Wi-Fi Modem
To enable remote system operation from smartphone
PWFMDD200
Extension cable for Wi-Fi Modem
To connect with Wi-Fi modem to the USB cable
PWYREW000
Thermistor for 2nd Circuit or E/Heater
To interlock with 2nd circuit
operation and control temperature
of main zone or To interlock with 3rd party E/Heater and control
PRSTAT5K10
temperature of water out 3rd
party E/Heater.
RS3 remote controller
To control unit with 2 remote controllers
PREMTW101
2-Remo Control Wire
The wire for 2 remo control
PZCWRC2
ACCESSORIES INSTALLATION 65
ENGLISH
Accessories supported by 3rd party Companies
Item Solar Heating System
Purpose
To generate auxiliary heating energy for water tank
Specification
· Solar collector · 3way valve(B)
Mix Kit 3rd Party Boiler 3rd Party Controller
To use 2nd Circuit
To use auxiliary boiler. To connect external controller using modbus protocol
· Mixing valve · Mix pump
Thermostat
To control by air temperature
Heating-Only type (230 V AC) Cooling/Heating type (230 V AC with Mode selection switch)
3way valve and actuator
(A) : To control water flow for hot water heating or floor heating / To
control water flow when installing 3rd party boiler
(B) : To control close/open mode of solar circuit
3 wire, SPDT (Single Pole Double Throw) type, 230 V AC
To control water flow for Fan Coil 2way valve and actuator Unit / To serve as
3way valve when
installing backup heater
2 wire, SPST (Single Pole Sing Throw) type, 230 V AC
External Pump
To retain sufficient capacity using additional pump
Smart Grid
To control operation mode depending on input signal from provider
3rd Party ESS
To control the operation mode according to the energy storage state
(For 4 Series)
3rd party Backup heater To supplement in sufficient capacity (For 4 Series)
Antifreeze valve
To protect the pipes against freezing
DHW Recirculation Pump
To control the water flow of DHW recirculation pump
(For 4 Series)
ENGLISH
66 ACCESSORIES INSTALLATION
Before Installation
! WARNING
Followings should be kept before installation · Main power must be turned off
during installing 3rd party accessories. · 3rd party accessories should be
comply with supported specification. · Proper tools should be chosen for
installation. · Never do installation with wet hands.
Thermostat
Thermostat is generally used to control the product by air temperature. When
thermostat is connected to the product, the product operation is controlled by
the thermostat.
Installation condition
! CAUTION
· USE 220-240 V~ Thermostat · Some electro-mechanical type thermostat has
internal delay time to protect compressor. In
that case, mode change can takes time more than user’s expectation. Please
read thermostat manual carefully if the unit does not response quickly. ·
Setting temperature range by thermostat can be different with that of the
unit. The heating or cooling set temperature should be chosen within the
setting temperature range of the unit. · It is highly recommended that the
thermostat should be installed where space heating is mainly applied.
Following location should be avoid to secure proper operation : · Height from
floor is approximately 1.5 m. · Thermostat can not be located where the area
may be hidden when door is open. · Thermostat can not be located where
external thermal influence may be applied. (such as
above heating radiator or open window)
Direct Sun ray contact area
yes
no
no
1.5 m
no
ENGLISH
ACCESSORIES INSTALLATION 67
General Information
The Heat Pump supports following thermostats.
Type Mechanical
(1)
Electrical (2)
Power 230 V~
230 V~
Operating Mode Heating Only (3) Heating / Cooling (4) Heating / Cooling / DHW Heating (5) Heating Only (3) Heating / Cooling (4) Heating / Cooling / DHW Heating (5)
Supported Yes Yes Yes Yes Yes Yes
(1) There is no electric circuit inside the thermostat and electric power
supply to the thermostat is not required.
(2) Electric circuit such as display, LED, buzzer, etc is included in the
thermostat and electric power supply is required.
(3) Thermostat generates “Heating ON or Heating OFF” signal according to
user”s heating target temperature.
(4) Thermostat generates both “Heating ON or Heating OFF” and “Cooling ON or
Cooling OFF” signal according to user”s heating and cooling target
temperature.
(5) Thermostat generates “Heating ON or Heating OFF”, “Cooling ON or Cooling
OFF”, “DHW Heating ON or DHW Heating OFF” signal according to user’s heating,
cooling and DHW heating target temperature. (For Split Indoor unit 5 Series,
For Hydrosplit)
! CAUTION
Choosing heating / cooling thermostat · Heating / cooling thermostat must have
“Mode Selection” feature to distinguish operation
mode. · Heating / cooling thermostat must be able to assign heating target
temperature and
cooling target temperature differently. · If above conditions are not kept,
the unit can not operation properly. · Heating / cooling thermostat must send
cooling or heating signal immediately when
temperature condition is satisfied. No delay time while sending cooling or
heating signal is permitted.
68 ACCESSORIES INSTALLATION
ENGLISH
How to wire thermostat
Follow below procedures Step 1 ~ Step 5. Step 1. Uncover front cover of the
unit and open the control box. Step 2. Identify the power specification of the
thermostat. If it is 220-240 V~, go to Step 3. Step 3. If it is Heating only
thermostat, go to step 4. Otherwise, if it is Heating / cooling
thermostat, go to step 5. Step 4. Find terminal block and connect wire as
below.
27 28 29 30
L
N L1 L2
THERMOSTAT (Default : 230 V AC)
(L)
(N)
(H)
Thermostat
! WARNING
Mechanical type thermostat Do not connect wire (N) as mechanical type
thermostat does not require electric power supply.
! CAUTION
Do not connect external electric loads. Wire (L) and (N) should be used only
for operation electric type thermostat. Never connect external electric loads
such as valves, fan coil units, etc. If connected, Main PCB (Heater) can be
seriously damaged.
(L) : Live signal from PCB to thermostat (N) : Neutral signal from PCB to
thermostat (H) : Heating signal from thermostat to PCB
C The terminal block connection number may differ depending on the model.
Refer to the “Wiring Diagram” in the SVC Manual.
Step 5. Find terminal block and connect wire as below.
27 28 29 30 L N L1 L2
THERMOSTAT (Default : 230 V AC)
! WARNING
Mechanical type thermostat Do not connect wire (N) as mechanical type
thermostat does not require electric power supply.
(L) (N) (C) (H) Thermostat
! CAUTION
Do not connect external electric loads.
Wire (L) and (N) should be used only for operation Electric type thermostat.
Never connect external electric loads such as valves, fan coil units, etc. If
connected, Main PCB (Heater) can be seriously damaged.
(L) : Live signal from PCB to thermostat (N) : Neutral signal from PCB to thermostat (C) : Cooling signal from thermostat to PCB (H) : Heating signal from thermostat to PCB
ENGLISH
ACCESSORIES INSTALLATION 69
How to wire Heating / Cooling / DHW Heating thermostat (For 4 Series)
Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the
unit and open the control box. Step 2. Identify the power specification of the
thermostat. If it is 220-240 V~, go to Step 3. Step 3. Find terminal block and
connect wire as below.
23 24 25 26 27 L N L1 L2 L3
THERMOSTAT (Default : 230 V AC) (L) (N) (C) (H) (D)
Thermostat
! WARNING
Mechanical type thermostat. Do not connect wire (N) as mechanical type
thermostat does not require electric power supply.
! CAUTION
Do not connect external electric loads. Wire (L) and (N) should be used only
for operation electric type thermostat. Never connect external electric loads
such as valves, fan coil units, etc. If connected, Main PCB (Heater) can be
seriously damaged.
(L) : Live signal from PCB to thermostat (N) : Neutral signal from PCB to
thermostat (C) : Cooling signal from thermostat to PCB (H) : Heating signal
from thermostat to PCB (D) : DHW Heating signal from thermostat to PCB
ENGLISH
70 ACCESSORIES INSTALLATION
Final check
· DIP switch setting : Set DIP switch No. 8 to ON’. Otherwise, the unit can not recognize the thermostat. · Remote Controller : –
Thermostat’ text is displayed on the remote
controller. – Button input is prohibited. – In case of Heating / Cooling / DHW
Heating thermostat, select `Heat&Cool / DHW’ as the Thermostat Control Type in
the remote controller installer settings.
2nd Circuit
The 2nd circuit is generally used to control the temperature of 2 rooms
differently. To use the 2nd Circuit, you need to prepare a separate Mix Kit.
The mix kit must be installed in the main zone. – Main Zone : zone where the
water temperature is lowest when heating. – Add. Zone : The other zone
– For 3 Series [Install Guide 2nd Circuit Heating]
Main Zone Add. Zone
Floor (35 °C)
Convector (FCU, 45 °C)
Radiator (45 °C) Radiator (55 °C)
Floor (35 °C)
Convector (FCU, 45 °C)
X
Radiator (45 °C)
X
Radiator (55 °C)
X X
[Install Guide 2nd Circuit Cooling]
Main Zone Add. Zone
Floor (18 °C)
Floor (18 °C)
Radiator(18 °C)
Convector (FCU, 5 °C)
X
Radiator(18 °C) X
Convector (FCU, 5 °C)
X
X
C To use a floor combination during cooling operation, the flow through the floor of the flow must be blocked by the 2 way valve.
ACCESSORIES INSTALLATION 71
ENGLISH
– For 4 Series [Install Guide 2nd Circuit Heating]
Circuit 2 Circuit 1
Floor (35 °C)
Convector (FCU, 45 °C)
Radiator (45 °C) Radiator (55 °C)
Floor (35°C)
Convector (FCU, 45 °C)
Radiator (45 °C)
Radiator (55 °C)
[Install Guide 2nd Circuit Cooling]
Circuit 2 Circuit 1
Floor (18 °C) Convector (FCU, 5 °C)
Floor (18 °C)
Convector (FCU, 5 °C)
C To use a floor combination during cooling operation, the flow through the floor of the flow must be blocked by the 2 way valve.
NOTE
Circuit 1 = Direct circuit : Zone where the water temperature is lowest when
heating Circuit 2 = Mixing circuit : The other zone
ENGLISH
72 ACCESSORIES INSTALLATION
How to Wire 2nd Circuit
– For 3 Series Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front
cover of the unit. Step 2. Find terminal block and connect wire as below
13 14 15 16 17 L N L1 L2 N
MIX PUMP
MIXING VALVE
(L) (N) (L1) (L2) (N1)
(L) : Live signal from PCB to mix pump
(N) : Neutral signal from PCB to mix pump
(L1) : Live signal (for Normal* Closed type) from PCB to mixing valve
(L2) : Live signal (for Normal Open type) from PCB to mixing valve
(N1) : Neutral signal from PCB to mixing valve
MIX PUMP
MIXING VALVE
*Closed = NOT Mixed
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.
Step 3. Insert the temperature sensor to ‘CN_MIX_OUT’ (Brown) of the main PCB as shown below. The sensor should be mounted correctly to outlet pipe of mix kit water pump as shown below.
CN_MIX_OUT
Indoor PCB
Buffer Tank
[Room A] Main zone (Low Temp.)
Mix
2nd circuit temp. sensor
Mix Kit
Floor heating loop Floor heating loop
[Room B] Additional zone (High Temp.)
Radiator
Radiator
ENGLISH
ACCESSORIES INSTALLATION 73
How to Wire Mix Pump, Mixing Valve and Thermistor for 2nd Circuit
– For 4 Series
Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the
unit. Step 2. Find terminal block and connect wire as below
7 8 9 10 11 L N L1 L2 N
MIX PUMP
MIXING VALVE
(L) (N) (L1) (L2) (N1)
MIX PUMP
MIXING VALVE
(L) : Live signal from PCB to mix pump (N) : Neutral signal from PCB to mix
pump (L1) : Live signal (for Normal Closed type)
from PCB to mixing valve (L2) : Live signal (for Normal Open type)
from PCB to mixing valve (N1) : Neutral signal from PCB to mixing valve
Closed = NOT Mixed
Step3. Insert the temperature sensor to ‘CN_MIX_OUT’ (Brown) of the main PCB as shown below. The sensor should be mounted correctly to outlet pipe of mix kit water pump as shown below.
CN_MIX_OUT
Indoor PCB
[Circuit 2] Mixing Circuit
Mix
2nd circuit temp. sensor
Buffer Tank
Hydronic separator
Mix Kit
Floor
Floor
heating loop heating loop
[Circuit 1] Direct Circuit
Radiator
Radiator
NOTE
Temperature sensor specification: Type : Thermistor,NTC Resistance at 25 °C :
5 k Minimum operating temperature range : -30 °C~100 °C
ENGLISH
74 ACCESSORIES INSTALLATION [Thermistor for 2nd circuit]
Sensor
Sensor Holder
Sensor Connector
Follow below procedures step 1 ~ step 4.
Step 1. Install sensor connector to outlet pipe of mix kit water pump.
(Welding must be performed to connect the sensor connector to the pipe. )
Step 2. Check if the power of the unit is turned off.
Step 3. Fasten the sensor connector to the sensor holder as shown in the
figure below.
Step 4. Insert harness into PCB(CN_TH4) fully and fix the thermal sensor into
tube connector as shown below.
ENGLISH
ACCESSORIES INSTALLATION 75
3rd Party Boiler
The product can be used by connecting an Auxiliary boiler. You can control the
boiler automatically and manually by comparing the outside temperature and the
set temperature.
How to install 3rd party boiler
Follow below procedures step 1 ~ step 3. Step 1. Check if the power of the
unit is turned off. Step 2. Disassemble front panels and Distinguish terminal
block in Indoor PCB. Step 3. Connect Power cable to terminal block (TB_BOILER)
fully.
– For 3 Series
TB_BOILER
3rd party boiler (Voltage free)
– For 4 Series
Indoor PCB
EXT_BOILER
Indoor PCB
3rd party boiler (Voltage free)
ENGLISH
76 ACCESSORIES INSTALLATION
3rd Party Controller
The product can also be linked to 3rd party controller. You can connect
external controllers using Modbus protocol except for LG controller. If 3rd
party controller is used, LG controller is not applied to AWHP simultaneously.
How to install 3rd party controller
Follow below procedures step 1 ~ step 4.
Step 1. Check if the power of the unit is turned off. Step 2. Disassemble
front panels and distinguish control box(Indoor) of
the unit. Step 3. Check if the harness(White) is inserted fully to the indoor
unit
PCB (CN_COM). Step 4. Connect the 3rd party controller to terminal block
2(11/12)
completely. (including Meter interface module)
11
12
1(L) 2(N)
3rd PARTY CONTROLLER
(DC 5 V)
1(L) 2(N)
3rd PARTY CONTROOLER
or METER INTERFACE(LG)
– For 3 Series
CN_COM
– For 4 Series
Indoor PCB
CN_MODBUS
Indoor PCB
ENGLISH
ACCESSORIES INSTALLATION 77
Meter Interface
This product can be used by connecting the meter interface module supplied in
the field. The meter interface module can communicate with the wired remote
controller. The meter interface module lets you know the amount of power
generated by the product.
How to install Meter Interface
[Parts of Meter interface]
Meter interface body
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the
unit is turned off. Step 2. Disassemble front panels and Distinguish control
box(Indoor) of the unit. Step 3. Check if the harness(White) is inserted fully
to the indoor unit PCB (CN_COM). Step 4. Connect the external pump to terminal
block 2(11/12).
– For 3 Series
CN_COM
11
12 11 : Black
A
B 12 : White
3rd PARTY CONTROLLER
Indoor PCB
– For 4 Series
CN_MODBUS
Meter interface
Indoor PCB
ENGLISH
78 ACCESSORIES INSTALLATION
Central Controller
The product can communicate and control through the central controller. The
following functions can be controlled in the central control linked state
(Operation/Stop, Desired temperature, Hot water operation / stop, Warm water
temperature, Full lock, Etc)
How to Install Central Controller
To use central controller, you need to establish an environment for mutual
communication between central controller and the THERMA V and register the
corresponding devices through the functions of central controller. To use
central controller, it shall be installed in the following order. Step 1.
Installation environment inspection and device address setting
Before installing central controller, check the network for any interfacing
devices and assign non overlapping addresses to the connected devices. Step 2.
PI485 setting Install PI485 and set the DIP switch accordingly. Step 3.
Connections Connect PI485 and central controller through RS-485 cable. Step 4.
Access and Device Registration Log in to central controller and register
device with address set. Consult a qualified engineer/ technician for the
installation of central controller. If you have any installation queries,
contact the LG service center or LG Electronics.
How to Installation PI485 Fix the PI485 PCB as shown in below images. For
detailed installation method refer to PI485 Installation Manual
UN60A (9, 12, 14, 16 kW)
UN36A (5, 7, 9 kW)
– For detailed installation instructions, refer to the manual included in the accessories. – The shape may differ depending on the model.
ENGLISH
ACCESSORIES INSTALLATION 79
Remote Controller
Installation of Remote Controller
· After fixing the remote controller installation plate on the desired
location, fix it firmly with the provided screws. – If the installation plate
is not flat on the surface, it may result in the controller being twisted and
cause a defect. – If there is a mounting box, install the remote controller
installation plate using the fixings holes which suit, as in the below
diagrams. – Do not leave a gap with the wall or product loose after the
installation.
· The wired remote controller cable can be installed in 3 directions. Install
to the suitable direction according to the installation environment.
– Installation direction: Rear entry, top side, right side
– When you install the remote controller cable at the top side and right side,
remove the remote controller cable guide hole before the installation. Use a
long nose pliers to remove the guide hole.
· After removing the hole, trim the cut surface neatly.
Top side guide groove
Right side guide groove
Top side guide groove
Rear cable entry
Right side guide groove
· After fixing the remote controller top side on the installation plate
attached to the wall as in the following figure, press the bottom side to
combine with the installation plate.
– Do not leave a gap in the top, bottom, left, and right side of the remote
controller and the installation plate after combining them.
– Before combining with the installation plate, arrange the cables to avoid
interference with the circuit parts.
Wall
Wall
ENGLISH
80 ACCESSORIES INSTALLATION
· When you remove the remote controller from the installation plate, insert a
small flat head screwdriver into the bottom side separation hole and turn
clockwise to separate the remote controller. – There are 2 separation holes at
the bottom part. Slowly separate one by one. – Be careful not to damage the
internal parts during the removal.
Wall Side
· Use the connection cables to connect the indoor unit with the remote controller.
DC 12 V Red
Signal Yellow
GND Black
OK
Please check if connector is normally connected. Connecting cable
Unit side
· For the following cases, separately purchase and use the cables suitable for
the situation.
– Do not install the cable over 50 m. (It may cause communication issues.)
– If the distance between the wired remote controller and the unit is 10 m or
more : 10 m extension cable (model name: PZCWRC1)
NOTE
During the wired remote controller installation, do not bury it in the wall.
(It may cause temperature sensor failure.) Do not install the cable over 50 m.
(It may cause communication defect.) When you install the extension cable,
carefully check the direction of the connectors on the remote controller side
and the product side before the installation. Specification of extension
cable: AWG 24, 3 conductor or above.
CN_REMO
Indoor PCB
ENGLISH
Wired controller
ACCESSORIES INSTALLATION 81
Extension Cable
Indoor MAIN PCB
Indoor terminal block RED(12V) YL(SIGNAL) BR(GND)
Check whether the connector is connected correctly.
Check whether the connector is connected correctly.
Cable connection method to use external device
- Wired remote controller-cable connection method. – In the wired remote controller, connect the part marked in the following figure (J02C, DOPort) to the cable. – According to the installation environment, there are 3 directions (Rear entry, top side, and right side) for the installation.
- Cable extension connection method – Among the cables connected to the wired remote controller, cut the remaining connectors on the other side, and then extend and connect the cables – Extension cable specification: 24~26 AWG.
! CAUTION
For the External device connection, use the cable insulated with sheath for
the extension connection. Before combining with the installation plate,
arrange the cables to avoid interference with the internal parts.
RMC DO-Port
2 3
30 cm
(GND_Black) (DC 12 V_Red)
Remote controller product composition
· Output specification – Voltage : DC 11~12 V – Current : 5 mA
Field connection
ENGLISH
82 ACCESSORIES INSTALLATION
DHW Tank
To establish DHW circuit, 3way valve and DHW tank kit is required. If solar
thermal system is pre-installed at the installation field, solar thermal kit
is required to interface solar thermal system to DHW tank to
Installation condition
Installing DHW water tank requires following considerations : · DHW water tank
should be located at the flat place. · Water quality should be complied with
EN 98/83 EC directives. · As this water tank is DHW water tank (indirect heat
exchange), do not use anti water-freezing
treatment like ethylene grycol. · It is highly recommend to wash out inside of
the DHW water tank after installation. It ensures
generating clean hot water. · Near the DHW water tank there should be water
supply and water drain to easy access and
maintenance. · Set the maximum value of the temperature control device of DHW
tank.
Water Tank Sensor
Water Out
Water In
DHW Water Tank
General Information
supports following 3way valve.
Type
Power
SPDT1) 3-wire 230 V AC
Operating Mode
Selecting Flow A2) between Flow A and Flow B
Selecting Flow B3) between Flow A and Flow B
Supported Yes Yes
1. SPDT = Single Pole Double Throw. Three wires consist of Live1 (for
selecting Flow A), Live 2 (for selecting Flow B), and Neutral (for common).
2. Flow A means water flow from the unit to under floor water circuit.
3. Flow B means water flow from the unit to DHW tank.
ENGLISH
ACCESSORIES INSTALLATION 83
Installing recirculation pump
– For 3 Series
When
is used with DHW tank, it is STRONGLY recommended to install recirculation
pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water
temperature inside DHW tank
– The recirculation pump should be operated when DHW demand is not required. Therefore, external time scheduler to determine when the recirculation pump should turn on and turn off is required.
– The operating duration time of the recirculation pump is calculated as follow : Duration time [minute] = k x V x R
k : 1.2 ~ 1.5 is recommended. (If distance between pump and tank is far, then choose high number)
V : Volume of DHW water tank [liter]
R : Water flow rate of pump [liter per minute], which is determined by pump performance curve
– The pump operating start time should be prior to the DHW water demand.
Water Tank Sensor
Hot water supply
Recirculation Pump
Shower (End of Hot water supply)
Water Out Water In
Check Valve
DHW
City water
Water Tank
External Time Scheduler
C Water In / Water Out installation scene may vary depending on the model.
ENGLISH
84 ACCESSORIES INSTALLATION
Installing recirculation pump
– For 4 Series
When
is used with DHW tank, it is STRONGLY recommended to install recirculation
pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water
temperature inside DHW tank
– The recirculation pump should be operated when DHW demand is not required. Therefore, external time scheduler to determine when the recirculation pump should turn on and turn off is required.
– The operating duration time of the recirculation pump is calculated as follow : Duration time [minute] = k x V x R
k : 1.2 ~ 1.5 is recommended. (If distance between pump and tank is far, then choose high number)
V : Volume of DHW tank [liter]
R : Water flow rate of pump [liter per minute], which is determined by pump performance curve.
– The pump operating start time should be prior to the DHW demand.
Hot water supply
Water Tank Sensor
Recirculation Pump
Shower (End of Hot water supply)
Water Out Water In
Check Valve
DHW
City water
Water Tank
Remote Controller
C Water In / Water Out installation scene may vary depending on the model.
NOTE
· For more information about recirculaton pump, Please refer chapter 8 and
chapter 9 of installation manual and owners manual.
How to wire recirculation pump
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the
unit is turned off. Step 2. Disassemble front panels and distinguish
control box(Indoor) of the unit. Step 3. Check if the harness(Violet) is
inserted fully to
the indoor unit PCB (CN_PUMP_A15). Step 4. Connect the DHW recirculation pump
to
terminal block 1(3/4).
Indoor PCB
3
4
L
N
WATER PUMP(C)
Recirculation Pump AC 230 V
CN_PUMP_A15
ENGLISH
ACCESSORIES INSTALLATION 85
How to Wire Booster Heater
Step 1. Uncover heater cover of the DHW tank. It is located side of the tank.
Step 2. Find terminal block and connect wires as below. Wires are field-
supplied item. (L) : Live signal from PCB to Heater. (N) : Neutral signal from
PCB to Heater.
! WARNING
Wire specification · Cross-sectional area of the wire should be 6 mm2.
Adjusting thermostat temperature
– To guarantee proper operation, it is recommended to set temperature of
thermostat to maximum temperature (symbol at the picture).
– 1Ø Backup Heater Model and 3Ø Backup Heater Model are set by same method as
below.
For 4 Series
1
2
L
N
WATER TANK HEATER
(L)
(N)
A
1(L) 2(N)
TO ELB FOR DHW TANK E/HEATER
ENGLISH
86 ACCESSORIES INSTALLATION
How to Wire DHW Tank Heater
Step 1. Uncover heater cover of the DHW tank. It is located side of the tank.
Step 2. Find terminal block and connect wires as below. Wires are field-
supplied item. (L) : Live signal from PCB to Heater (N) : Neutral signal from
PCB to Heater
! WARNING
Wire specification · Cross-sectional area of the wire should be 6 mm2.
Adjusting thermostat temperature · To guarantee proper operation, it is
recommended to set temperature of thermostat to
maximum temperature (symbol at the picture). · 1Ø Electric Heater Model and 3Ø
Electric Heater Model are set by same method as below.
LN WATER TANK HEATER (L) (N)
A
ENGLISH
ACCESSORIES INSTALLATION 87
DHW Tank Kit
This product can be used by connecting the DHW tank kit in the field. It can
be utilized hot water heated by booster heater in DHW tank.
How to install DHW tank kit
[Parts of DHW Tank Kit] 12 3 4 5 6
Tank kit body
Sensor
Multi harness
Temperature sensor for DHW tank is used to control hot water temperature of
DHW tank. If sensor will be defective, you can purchase it separately.(Model
name : PHRSTA0)
Follow below procedures step 1 ~ step 4.
Step 1. Uncover DHW tank kit and locate it on the wall.
Step 2. Connect Harness(Violet) of Main PCB assembly(TB1(6/7)) to
‘CN_B_Heat_A` of the Main PCB like following fig. 1.
Step 3. Insert DHW tank sensor to ‘CN_TH4′ (Red) of the Main PCB refer as
below.
Step 4. Connect power supply to the DHW tank kit as shown fig. 1.
C The sensor should be mounted correctly to the sensor hole of DHW water tank
like below fig. 2.
– For 3 Series
CN_TH4
DHW Tank
Signal
Sensor CN_B_HEAT_A
Indoor PCB
Multi harness
67
Fig. 1
12
34 5 6
Power supply 1Ø 220-240 V 50 Hz
67 LN DHW TANK HEATER
Heater power
Fig. 3
Insert sensor until the cable tie as shown below.
DHW Tank Temperature Sensor
Sensor holder
Inside DHW tank
DHW tank outer wall
Fig. 2
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.
ENGLISH
88 ACCESSORIES INSTALLATION
– For 4 Series
CN_TH4
Indoor PCB Fig. 1
CN_TANK_HEATER
1
2
L
N
DHW TANK HEATER
1(L) 2(N)
TO ELB FOR DHW TANK E/HEATER
ENGLISH
ACCESSORIES INSTALLATION 89
Solar Thermal Kit
This product can be used by connecting the solar thermal kit in the field. It
can be utilized hot water heated by solar thermal system. End-user must be LG
AWHP solar thermal kit.
How to Install Solar Thermal Kit
[Parts of Solar Thermal Kit]
Holder sensor
Tube Connector
Solar Thermal Sensor 12 m(1 EA)
Follow below procedures step 1 ~ step 4.
Step 1. Install tube connector(it is necessary to reduce or extend diameter of
pipe.) the pipe and solar thermal kit.
Step 2. Check if the power of the unit is turned off.
Step 3. Disassemble front panels and distinguish control box(Indoor) of the
unit.
Step 4. Insert harness into PCB(CN_TH4) fully and fix the thermal sensor into
tube connector as shown below.
C If the DHW tank sensor is connected, disconnect the sensor from PCB first.
– For 3 Series
Solar thermal sensor
CN_TH4
– For 4 Series
Indoor PCB
Water Pipe
Tube connector
Indoor PCB
Solar
Solar thermal sensor
Water Pipe
Tube connector
90 ACCESSORIES INSTALLATION
ENGLISH
Solar Thermal Sensor
(less than 12 m) 3way valve (Field Supply)
Water Tank Sensor (less than 12 m)
Water In
Tube connecter
Pump (Field Supply)
Water In
Solar Thermal
System Water Out (Field Supply)
Water Out
Water Tank
C Water In / Water Out installation scene may vary depending on the model.
– Insert sensor until the cable tie as shown below.
Solar Collector (Field Supply)
! CAUTION
Sensor mounting Insert sensor into sensor socket and bolt it tightly.
ENGLISH
ACCESSORIES INSTALLATION 91
Dry Contact
Dry Contact is a solution for automatic control of HVAC system at the owner’s
best. In simple words, it’s a switch which can be used to turn the unit On/Off
after getting the signal from external sources.
How to install dry contact
[Parts of Dry contact]
Dry Contact body Cable(for connecting with IDU)
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the
unit is turned off. Step 2. Disassemble front panels and distinguish terminal
block in Indoor PCB. Step 3. Connect cable to the unit PCB(CN_CC) fully. Step
4. Then, Insert harness to the dry contact PCB(CN_INDOOR) firmly as shown
below. – For 3 Series
CN_CC
Dry contact
CN_INDOOR
– For 4 Series
Indoor PCB
CN_CC
NOTE
Indoor PCB
Dry contact CN_INDOOR
· For more information about installing Dry Contact, Please refer installation
manual provided with Dry Contact.
· For system set-up, please read chapter 8 (Accessory Installation) and
chapter 9 (DIP Switch setting).
ENGLISH
92 ACCESSORIES INSTALLATION [Setting of Contact Signal Input] · For input
contact closure only(No power input)
Notes
Do not input the voltage signal in “NON VOLT” setting mode. Otherwise it will
cause serious damage. · For input contact voltage : DC 12 V, 24 V~
Connect separate External voltage of DC 12
V, 24 V~
COMM Themal Operation COMM FAN HEAT COOL LOW MIDDLE HIGH
COMM Themal Operation COMM FAN HEAT COOL LOW MIDDLE HIGH
Thermostat LG does not supply this section (Field supply)
Thermostat LG does not supply this section (Field supply)
ENGLISH
ACCESSORIES INSTALLATION 93
External Controller – Setting up programmable digital input operation
If you require to operate control depending on external digital input(ON/OFF),
connect cable to indoor PCB(CN_EXT). Follow below procedures step 1 ~ step 4.
Step 1. Check if the power of the unit is turned off. Step 2. Disassemble
front panels and distinguish control box(Indoor) of the unit Step 3. Connect
the external controller to PCB(CN_EXT) completely. Step 4. Connect the cable
and field installation part.
– For 3 Series
CN_EXT
– For 4 Series
Indoor PCB
Adapter Cable
CN_EXT
Indoor PCB
Installation example #1
Indoor Unit PCB
0.5 m
Max 10 m
CN_EXT
SW
Supplied Part Field Installation Part
· SW : Single pole switch – Select a part with contacts for extremely low
amperage – DC 5 V ~ 12 V is used at the contact point – Switch load is
approximately 0.5 ~ 1 mA
· Control cable – Cable size : 22 to 26 AWG – Don’t extend the cable more than
10 meters
Adapter Cable
Installation example #2
Indoor Unit PCB
0.5 m Max 10 m
CN_EXT
Supplied Part
· X : Relay(a point of contact, fixed DC 0.5 ~ 1 mA)
· SW : Distance ON/OFF switch
· Control cable(Indoor unit to Relay Circuit)
– Cable size : 22 to 26 AWG
Relay Circuit – Don’t extend the cable more than 10 meters
XX
Power
SW
supply
of relay
Field Installation Part
Determining the purpose of CN_EXT Setting value: 0 ~ 5 step Indoor CN-EXT port setting – 0: default – 1: Simple operation on / off – 2: Dry contact (simple contact)
– 3: Emergency stop only for indoor unit – 4: Reattachment / absence – 5:
Emergency stop of all indoor units (It can
be set only when indoor unit has emergency stop function)
ENGLISH
94 ACCESSORIES INSTALLATION
Remote Temperature Sensor
Remote temperature sensor can be installed any place a user wants to detect
the temperature.
Installation condition
Role and constraint while installation of remote air temperature sensor is
very similar to that of thermostat. · Distance between the unit and the remote
air temperature sensor should be less than 15 m
due to length of the connection cable of remote air temperature sensor. · For
other constraints, please refer to previous page where constraints about
thermostat is
described
Direct Sun ray contact area
yes
no
no
5ft (1.5m)
no
Connection cable
(less than 15 m) no
Direct Sun ray contact area
yes
no
no 5 ft (1.5 m)
Thermostat
Remote Air Temperature Sensor
ENGLISH
ACCESSORIES INSTALLATION 95
How to Install Remote Temperature Sensor
[Parts of Remote Temperature Sensor]
Sensor
Screw(to fix remote sensor)
Follow below procedures step 1 ~ step 5.
Step 1. Decide where the remote temperature sensor is Installed. Then,
Determine the location and height of the fixing screws in fig. 1 (Interval
between the screws : 60 mm)
Step 2. Check if the power of the unit is turned off.
Step 3. Disassemble front panels and distinguish control box(Indoor) of the
unit.
Step 4. Insert temperature sensor into PCB(CN_ROOM) and fix the sensor firmly
in fig. 2.
Step 5. The Connection wire does not matter if you change the color of the
wire because of nonpolar.
– For 3 Series
CN_ROOM
BK
Fixing screws 60 mm
[Fig. 1]
Indoor PCB [Fig. 2]
WH Sensor
– For 4 Series Fixing screws 60 mm
[Fig. 1]
CN_ROOM BK
Indoor PCB [Fig. 2]
WH Sensor
ENGLISH
96 ACCESSORIES INSTALLATION
Step 6. Integrate the remote temperature sensor with the screws as the order
of arrows.
Fixing the Remote Sensor 1 2
! CAUTION
· Choose the place where the average temperature can be measured for the unit
operates. · Avoid direct sunlight. · Choose the place where the
cooling/heating devices do not affect the remote sensor. · Choose the place
where the outlet of the cooling fan do not affect the remote sensor. · Choose
the place where the remote sensor isn’t affected when door is open.
NOTE
· For more information about installing Remote Temperature Sensor, Please
refer installation manual provided with Remote Temperature Sensor.
· For system set-up, please read chapter 8.(Especially function code No.3)
ENGLISH
ACCESSORIES INSTALLATION 97
Solar pump
Solar pump can be required to energize water flow when solar thermal system is
installed.
How to install solar pump
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish control box(Indoor) of the unit. Step 3. Check if the harness(Black) is inserted fully to the indoor unit PCB (CN_W_PUMP_B). Step 4. Connect the external pump to terminal block 1(4/5).
C It is possible to un-use solar pump depending on installation environment.
– For 3 Series
Indoor PCB
WATER PUMP (B)
4
5
BR BL
L
N
Solar pump AC 230 V
– For 4 Series
CN_W_PUMP_B
Indoor PCB
5
6
L
N
WATER PUMP (B)
Solar pump AC 230 V
CN_PUMP_A4
C The terminal block connection number may differ depending on the model.
Refer to the “Wiring Diagram” in the SVC Manual.
ENGLISH
98 ACCESSORIES INSTALLATION
External pump
External pump can be required when the room to take floor heating is too large
or not wellinsulated.(potential free) Also, External pump is installed with
buffer tank to retain sufficient capacity.
How to install external pump
Follow below procedures step 1 ~ step 3. Step 1. Check if the power of the
unit is turned off. Step 2. Disassemble front panels and distinguish terminal
block in Indoor PCB. Step 3. Connect signal cable to terminal block
(TB_W_PUMP_C) fully.
– For 3 Series
Indoor PCB
Power
External pump (Voltage free)
TB_W_PUMP_C
– For 4 Series
Indoor PCB
PUMP A2
External pump (Voltage free)
ENGLISH
ACCESSORIES INSTALLATION 99
Wi-fi Modem
Wi-fi modem enables remote system operation from smartphone. Available
functions include selection of on/off, operation mode, DHW heating,
temperature setup and weekly scheduling etc.
How to install Wi-fi Modem
[Parts of Wi-fi modem]
Wi-fi modem body
USB Cable
Extension Cable
Follow below procedures step 1 ~ step 5. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish control box(Indoor) of the unit. Step 3. Connect the USB cable to the indoor unit PCB (CN_WF ; Blue) until it clicks into place. Step 4. Connect the Wi-Fi modem to the USB cable fully. Step 5. Refer to the image below to install the Wi-Fi modem in the marked position.
– For 3 Series
CN_WF
Indoor PCB
– For 4 Series
CN_WF
USB Cable
Indoor PCB USB Cable
In case of using the extension wire (PWYREW000), fasten the core of extension
wire to clamp of the indoor control box.
100 ACCESSORIES INSTALLATION
ENGLISH
Energy State
This product provides energy states that enable customers to use as much as
possible of their own renewable energy. It can shift setpoints depending on
input signal from Energy Storage System (ESS) or from any other third-party
device using Modbus RTU or Digital 230V inputs.
Available Energy States
There are 8 energy states available. 4 fixed and 4 customizable – each with
the possibility to enhance selfconsumption of renewable energy.
Energy state
Command
Battery State of charge
Operation (standard setting)
Heating
Cooling
Domestic Hot Water
Setting Range Setting Range Setting Range
1
Operation Off (Utility lock)
Low
Forced internal operation off
Fixed
Forced internal operation off
Fixed
Forced internal operation off
Fixed
2
Normal Operation
Maintain Normal operation
status status
Fixed
Maintain operation status
Fixed
Maintain operation status
Fixed
3
Operation On Recommend
High
Increase 2 °C from target temperature
Fixed
Maintain operation Status
Fixed
Increase 5 °C from target temperature
Fixed
4
Operation On Recommend
Very High
Maintain operation
status
Fixed
Maintain operation status
Fixed
DHW Target 80 °C
Fixed
5
Operation On Commend
Very High
Increase from target
temperature
0/+30 (Default : +5)
Decrease from target
temperature
0/-30 (Default : -5)
Increase from target
temperature
0/+50 (Default : +30)
6
Operation On Recommend
High
Increase from target
temperature
0/+30 (Default : +2)
Decrease from target
temperature
0/-30 (Default : -2)
Increase from target
temperature
0/+50 (Default : +10)
7
Operation Save
Low
Decrease from target
temperature
0/-30 (Default : -2)
Increase from target
temperature
0/+30 (Default : +2)
Decrease from Target
Temperature
0/-50 (Default : 0)
8
Operation Super Save
Very Low
Decrease from target
temperature
0/-30 (Default : -5)
Increase from target
temperature
0/+30 (Default : +5)
Decrease from Target
Temperature
0/-50 (Default : 0)
ENGLISH
ACCESSORIES INSTALLATION 101
Digital Input for energy saving (ESS, Smart Grid)
This product provides two digital inputs (TB_SG1 / TB_SG2) that can be used to
switch between energy states when not using Modbus RTU (CN-COM).
Available Energy States
There are 8 energy states available in total. Four different states can be
triggered using the 230V-inputs by default Energy states 1-4. With the
digital input assignment in the menue `Energy state/Digital input assignment
of the control pane, different Energy states can be selected for Signals 0:1
and 1:1. 0:0 is always linked with ES2 (Normal operation) and 1:0 is always
linked with ES1 (Operation off/Utility lock).
How to set Digital input signal
Follow below procedures step 1 ~ step 3. Step 1. Check if the power of the
unit is turned off. Step 2. Disassemble front panels and distinguish terminal
block in Indoor PCB. Step 3. Connect signal cable to terminal block in PCB
(TB_SG2, TB_SG1) fully as shown below.
Indoor PCB
TB_SG2
TB_SG1
Energy state depending on input signal (TB_SG1/TB_SG2)
TB_SG1 0 1 0 1
Input Signal
TB_SG2 0 0 1 1
Output state
Default
Range
ES2 fixed
ES1
ES3 ES3-ES8
ES4
102 ACCESSORIES INSTALLATION
ENGLISH
2Way Valve
2way valve is required to control water flow while cooling operation. Role of
2way valve is to cut off water flow into under floor loop in cooling mode when
fan coil unit is equipped for cooling operation.
General Information
supports following 2way valve.
Type NO 2-wire 1)
NC 2-wire 2)
Power 230 V AC 230 V AC
Operating Mode Closing water flow Opening water flow Closing water flow Opening water flow
Supported Yes Yes
1. Normal Open type. When electric power is NOT supplied, the valve is open.
(When electric power is supplied, the valve is closed.)
2. Normal Closed type. When electric power is NOT supplied, the valve is
closed. (When electric power is supplied, the valve is open.)
How to Wire 2Way Valve
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the
unit. Step 2. Find terminal block and connect wire as below.
– For 3 Series
18 19 20 L1 L2 N 2WAY VALVE
(A) (NO) (NC) (N)
– For 4 Series
15 16 17 L1 L2 N 2WAY VALVE
(A) (NO) (NC) (N)
2way valve
2way valve
! CAUTION
Dew Condensation · Wrong wiring can yield dew condensation on the floor. If
radiator is connected at the
under floor water loop, dew condensation can be occurred on the surface of the
radiator.
! WARNING
Wiring · Normal Open type should be connected to wire (NO) and wire (N) for
valve opening in
cooling mode. · Normal closed type should be connected to wire (NC) and wire
(N) for valve closing in
cooling mode.
ENGLISH
ACCESSORIES INSTALLATION 103
(NO) : Live signal (for Normal Open type) from PCB to 2way valve (NC) : Live
signal (for Normal Closed type) from PCB to 2way valve (N) : Neutral signal
from PCB to 2way valve
C The terminal block connection number may differ depending on the model.
Refer to the “Wiring Diagram” in the SVC Manual.
Final Check
· Flow direction : – Water should not flow into under floor loop in cooling
mode. – To verify the flow direction, check temperature at the water inlet of
the under floor loop. – If correctly wired, this temperatures should not be
approached to 6 °C in cooling mode.
104 ACCESSORIES INSTALLATION
ENGLISH
3Way Valve(A)
3Way Valve(A) is required to operate DHW water tank. Role of 3way valve is
flow switching between under floor heating loop and water tank heating loop.
Plus, it is required to operate 3rd party boiler.
General Information
supports following 3way valve.
Type
Power
SPDT 3-wire1)
220-240 V~
Operating Mode
Selecting Flow A2) between Flow A and Flow B
Selecting Flow B3) between Flow A and Flow B
Supported Yes Yes
1. SPDT = Single Pole Double Throw. Three wires consist of Live1 (for
selecting Flow A), Live 2 (for selecting Flow B), and Neutral (for common).
2. Flow A means water flow from the unit to under floor water circuit.’ 3. Flow B means
water flow from the unit to DHW water tank.’
How to wire 3way valve(A)
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the
unit. Step 2. Find terminal block and connect wire as below.
– For 3 Series
3WAY VALVE (A)
8 9 10 L L1 N BR BK BL (W) (U) (N)
– For 4 Series
12 13 14 L L1 N 3WAY VALVE
(A)
(W) (U) (N)
3way valve
3way valve
! WARNING
· 3way valve should select water tank loop when electric power is supplied to
wire (W) and wire (N).
· 3way valve should select under floor loop when electric power is supplied to
wire (U) and wire (N).
(W) : Live signal (Water tank heating) from PCB to 3way valve (U) : Live
signal (Under floor heating) from PCB to 3way valve (N) : Neutral signal from
PCB to 3way valve
C The terminal block connection number may differ depending on the model.
Refer to the “Wiring Diagram” in the SVC Manual.
ENGLISH
ACCESSORIES INSTALLATION 105
3Way Valve(B)
3way valve(B) is required to operate Solar thermal system. Role of 3way valve
is flow switching between open and close mode of the solar circuit.
General Information
supports following 3way valve.
Type
Power
SPDT 3-wire1)
220-240 V~
Operating Mode
Selecting Flow A2) between Flow A and Flow B
Selecting Flow B3) between Flow A and Flow B
Supported Yes Yes
1. SPDT = Single Pole Double Throw. Three wires consist of Live1 (for
selecting Flow A), Live 2(for selecting Flow B), and Neutral (for common).
2. Flow B means heat source toward solar panel repeatedly’. (close mode of circuit) 3\. Flow A means
heat source flow from solar panel to DHW tank in solar
circuit’. (open mode of circuit)
How to wire 3way valve(B)
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the
unit. Step 2. Find terminal block and connect wire as below.
– For 3 Series
– For 4 Series
3WAY VALVE (B)
12
3
BR WH BL
L L1 N
(W) (U) (N)
28 29 30 L L1 N
3WAY VALVE (B)
(W) (U) (N)
3way valve
3way valve
! WARNING
· 3way valve should select “close solar circuit” when electric power is
supplied to wire (W) and wire (N).
· 3way valve should select “open solar circuit” when electric power is
supplied to wire (U) and wire (N).
(W) : Live signal (close solar circuit) from PCB to 3way valve (U) : Live
signal (open solar circuit) from PCB to 3way valve (N) : Neutral signal from
PCB to 3way valve
C The terminal block connection number may differ depending on the model.
Refer to the “Wiring Diagram” in the SVC Manual.
ENGLISH
106 ACCESSORIES INSTALLATION
Electric Heater
How to Pipe Electric Heater
Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater
accessory. Step 2. Check the diameter of pre-installed pipes of unit. Step 3.
If the diameter of pre-installed pipes is different from diameter of electric
heater
accessory kit, it is necessary to reduce or expand pipe’s diameter. Step 4.
Connect the pipes. The inlet pipe of electric heater accessory must be
connected to
outlet of the unit.
! WARNING
Followings should be kept before installation · The unit should be stop before
the piping work. · Never connect electric power while piping electric heater.
· Before the piping working, water in the part(or to heating loop) installed
with electric heater
should be drained. After working, water should be charged.
! CAUTION
· Electric Heater should be installed with enough space for installation and
service. · Water pipes and connections should be cleaned using water. ·
Methods to prevent leakage in plumbing connections must be applied. · Heater
must not be impacted. · Do not let dirty particle be dropped inside tank to
avoid possibility of degrade. · After installation, make it sure that no
leakage is appeared in the connection.
ENGLISH
Terminal Block Information
Symbols used below pictures are as follows : – L, L1, L2 : Live (220-240 V~) –
N : Neutral (220-240 V~) – BR : Brown, WH : White, BL : Blue, BK : Black
< 3 kW >
ACCESSORIES INSTALLATION 107 < 6 kW >
Terminal Block 1
Terminal Block 2
Terminal Block 1
Terminal Block 2
108 ACCESSORIES INSTALLATION
ENGLISH
How to Wire Electric Heater
– For 3 Series
Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater
accessory. Step 2. Find the terminal block and connect wires. Refer to the
installation manual of the electric
heater. (Wires are field-supplied item.) Step 3. Connect terminal block ports
unit and electric heater accessory.
– HAETER(A) : Signal to activate 1st step – HEATER(B) : Signal to activate 2nd
step
(3 kW) Terminal Block 2 (In Backup Heater)
1(L)
2(N)
3
4
5
6
L
N
Power Supply 50 Hz 220-240 V~
A(A1)
A(A2)
ELECTRIC HEATER A (SIGNAL)
23
24
BR
BL
L
N
HEATER (A)
Terminal Block 3 (In Unit)
25
26
BR
BL
L
N
HEATER (B)
(6 kW)
Terminal Block 2 (In Backup Heater)
1(L)
2(N)
3
4
5
6
L
N
Power Supply 50 Hz 220-240 V~
A(A1)
A(A2)
B(A1)
B(A2)
ELECTRIC HEATER A ELECTRIC HEATER B
(SIGNAL)
(SIGNAL)
23
24
BR
BL
L
N
HEATER (A)
Terminal Block 3 (In Unit)
25
26
BR
BL
L
N
HEATER (B)
Step 4. Connect power supply cable to terminal block 2.
When Tightening the power cable on terminal block, Be careful to prevent a
shock or injury. (AC 220-240 V signal)
Terminal Block 2 (In Backup Heater) 1(L) 2(N)
Power Supply 50 Hz 220-240 V~
· For more information about installing Electric Heater, Please refer installation Manual provided with Electric Heater
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.
ENGLISH
ACCESSORIES INSTALLATION 109
– For 4 Series Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the
electric heater accessory. Step 2. Find the terminal block and connect wires.
(Wires are field-supplied item.) Step 3. Connect terminal block ports of unit
and electric heater accessory.
Indoor PCB
COMMON 3PHASE HEATER 1 HEATER 2
(1Ø 3 kW)
Terminal Block 2 (In Backup Heater)
1(L)
2(N)
3
4
L
N
Power Supply 50 Hz 220-240 V~
L
Voltage Free Contact
N
A(A1)
A(A2)
ELECTRIC HEATER A (SIGNAL)
L
L
N
COMMON 3PHASE
5
6
L HEATER 1 HEATER 2
(1Ø 6 kW)
Terminal Block 2 (In Backup Heater)
1(L)
2(N)
3
4
L
N
Power Supply 50 Hz 220-240 V~
A(A1)
A(A2)
ELECTRIC HEATER A (SIGNAL)
L(1)
L(1)
L(1)
Voltage
L(2)
Free Contact N
COMMON 3PHASE
5
6
B(A1)
B(A2)
ELECTRIC HEATER B (SIGNAL)
L(2)
L(2)
L(1)
L(2)
HEATER 1 HEATER 2
ENGLISH
110 ACCESSORIES INSTALLATION
(3Ø 6 kW) Terminal Block 2 (In Backup Heater)
1(L)
2(N)
3(T)
R
S
T
Power Supply 3Ø 380-415 V, 50 HZ
L
Voltage Free Contact
N
N COMMON
4
5
A(A1)
A(A2)
ELECTRIC HEATER A (SIGNAL)
L
L
L
3PHASE HEATER 1 HEATER 2
Step 4. Connect power supply cable to terminal block 2.
1(L) 2(N)
1(R) 2(S) 2(T)
Power Supply 50 Hz 220-240 V~
Power Supply 3Ø 380-415 V, 50 HZ
ENGLISH
ACCESSORIES INSTALLATION 111
How to Install 3way Valve for Backup Heater Bypass
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the
unit. Step 2. Find terminal block and connect wire as below. When Tightening
the connect wire on terminal block, Be careful to prevent a shock or injury.
(230 VAC)
2WAY VALVE (B)
18 19 20 BR WH BL L L1 N
(NO) (NC) (N)
! WARNING
· When type of 2way valve is NO type, 3way valve should select Flow A(bypass).
Electric power is supplied to wire(NO) and wire(N).
· When type of 2way valve is NC type, 3way valve should select Flow B(heating
In Backup heater). Electric power is supplied to wire(NC) and wire(N).
3way valve
! CAUTION
· 3way valve should be connected together with 2way valve in terminal block.
· Keep the distance between 3way valve and Backup Heater more than 0.5m.
· To prevent reverse flow, It is important to use one way valve(check valve)
to Backup Heater water outlet.
How to Connect Backup Heater Sensor to Unit
Follow below procedures Step 1 Step 5. Find backup heater terminal block
Kit(Fig. 1). Assemble the terminal block kit using screw on unit. Plug it to
`E/Heater Out’ (White Connector) of CN_TH3 in the Main PCB (Unit) as shown
Fig.2. Connect harness between the unit and the Backup Heater until it clicks
into place.(Fig. 3). Use the cord clamper to fix the cable through low voltage
hole.
E/HEATER OUT SENSOR (5 V DC)
7
8
31
32
A
B
Fig.3
E/HEATER OUT SENSOR (5 V DC)
Fig.1
Fig.2
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.
112 ACCESSORIES INSTALLATION
ENGLISH
Final check
No.
Check point
1
Connection of Water Inlet/Outlet
2 Hydraulic pressure
Description
– Check if the shut-off valves should be assembled with Water inlet
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>