LG ThermaV12 Air to Water Heat Pump Instruction Manual

June 9, 2024
LG

ThermaV12 Air to Water Heat Pump

ENGLISH ITALIANO PORTUGUÊS MAGYAR

ESPAÑOL

FRANÇAIS SRPSKI

INSTALLATION MANUAL
AIR-TO-WATER HEAT PUMP

DEUTSCH HRVATSKI

SLOVENSCINA

CESTINA DANSK

NEDERLANDS

POLSKI

Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Original instruction

MFL68026607 Rev.14_020922

www.lg.com
Copyright © 2018 – 2022 LG Electronics Inc. All Rights Reserved.

LIMBA ROMÂN

ENGLISH

2 TABLE OF CONTENTS
TABLE OF CONTENTS
5 PREFACE 6 SAFETY INSTRUCTIONS 14 INSTALLATION PART 15 GENERAL INFORMATION
15 Model Information 17 Model name and related information 18 Parts and Dimensions 24 Control Parts 26 Remote Controller 27 Typical Installation Example 33 Cycle Diagram 36 Water cycle
39 INSTALLATION
39 Transporting the Unit 40 Installation places 41 Seasonal Wind and Cautions in Winter 42 Foundation for Installation 43 Electrical Wiring 53 Wiring of main power supply and equipment capacity 54 Water Piping and Water Circuit Connection 56 Water Charging 56 Pipe Insulation 57 Water pump Capacity 57 Pressure Drop 58 Performance curve 59 Water Quality 59 Frost protection by antifreeze 60 Frost protection by antifreeze valve 62 Water Volume and Expansion Vessel Pressure
63 ACCESSORIES INSTALLATION
63 Accessories supported by LG Electronics 65 Accessories supported by 3rd party Companies 66 Before Installation 66 Thermostat 70 2nd Circuit 75 3rd Party Boiler 76 3rd Party Controller 77 Meter Interface 78 Central Controller 79 Remote Controller 82 DHW Tank 87 DHW Tank Kit 89 Solar Thermal Kit 91 Dry Contact 93 External Controller – Setting up programmable digital input operation 94 Remote Temperature Sensor 97 Solar pump 98 External pump 99 Wi-fi Modem 100 Energy State 101 Digital Input for energy saving (ESS, Smart Grid) 102 2Way Valve 104 3Way Valve(A) 105 3Way Valve(B)

106 Electric Heater 112 Final check
113 CONFIGURATION
113 DIP Switch Setting
123 SERVICE SETTING
123 How to enter service setting 123 Service setting 124 Service Contact 125 Model Information 126 RMC Version lnformation 127 Open Source License
128 INSTALLER SETTING
128 How to enter installer setting 129 Installer setting (For 3 Series) 131 3 Minutes Delay 132 Select Temperature Sensor 133 Dry Contact Mode 134 Central Control Address 135 Pump test run 136 Air cooling set temp 137 Water cooling set temp 138 Air heating set temp 139 Water heating set temp 140 DHW set temp 141 Screed drying 143 Heater on temperature 145 Water supply off temp. during cooling 147 Tank disinfection setting 1, 2 148 Tank setting 1 149 Tank setting 2 151 Heater priority 152 DHW time setting 153 TH on/off Variable, heating air 154 TH on/off Variable, heating water 155 TH on/off Variable, cooling air 156 TH on/off Variable, cooling water 157 Heating temp. setting 158 Cooling temp. setting 159 Pump setting in heating 160 Pump setting. in cooling 161 Forced operation 162 CN_CC 163 Pump Capacity 164 Seasonal auto temp 166 Modbus Address 167 CN_EXT 168 Anti-freezing Temperature 169 Add Zone 170 Use External Pump 171 3rd Party Boiler 172 Meter Interface 173 Pump Prerun/Overrun 174 Solar Thermal System 176 Energy state 177 Data logging 178 Password Initialization 179 Overview settings (For 3 Series) 181 Installer setting (For 4 Series) 184 Select Temperature Sensor 185 Use Heating Tank Heater

TABLE OF CONTENTS 3

ENGLISH

ENGLISH

4 TABLE OF CONTENTS
186 Mixing Circuit 187 Use External Pump 188 RMC master/slave 189 LG Therma V Configuration 190 Forced operation 191 Pump Prerun/Overrun 192 Water Flow Control 193 Energy Monitoring 194 Anti-Freezing Option 1 (For 4 Series) 195 Password Reset 196 Screed drying 198 Heater on temperature 200 Air heating set temp. 201 Water heating set temp. 202 Hysteresis Room Air(Heating) 203 Hysteresis Heating Water 204 Heating temp. setting 205 Pump setting in heating 206 Air cooling set temp. 207 Water cooling set temp. 208 Water supply off temp. during cooling 210 Hysteresis Room Air(Cooling) 211 Hysteresis Cooling Water 212 Cooling temp. setting 213 Pump setting in cooling 214 Seasonal auto temp. 217 Heater priority 218 DHW set temp. 219 Tank disinfection setting 1, 2 220 Tank setting 1 221 Tank setting 2 223 DHW time setting 224 Recirculation time 225 Solar Thermal System 227 Pump test run 228 Frost Protection Temp. 229 Dry Contact Mode 230 Central Control Address 231 CN_CC 232 LG Therma V Configuration 233 Pump frequency setting (RPM) 234 Smart Grid(SG) 235 Power Supply Blockage (Smart Grid) 236 Energy state 237 Thermostat control type 238 Pump operation time 239 IDU operation time 240 Modbus Address 241 Modbus gateway memory map 244 CN_EXT 245 3rd Party Boiler 246 Meter Interface 247 Current flow rate 248 Data logging 249 Overview settings (For 4 Series)
252 COMMISSIONING
252 Check List before Starting Operation 253 Starting Operation 254 Starting Operation flow chart 254 Airborne Noise Emission 255 Vacuum & Charge of Refrigerant 257 How to drain remaining water in the product 258 Troubleshooting

PREFACE 5

ENGLISH

PREFACE

This installation manual is to present information and guide about understanding, installing,

and checking

.

Your careful reading before installation is highly appreciated to make no mistake and to prevent

potential risks. The manual is divided into nine chapters. These chapters are classified according

to installation procedure. See the table below to get summarized information.

Chapters Chapter 1 Chapter 2 Chapter 3
Chapter 4
Chapter 5 Chapter 6 Chapter 7

Contents
· Warning and Caution concerned with safety. · This chapter is directly related with human safety. We strongly recommend reading
this chapter carefully.
· Items Inside product Box · Before starting installation, please make it sure that all parts are found inside the
product box.
· Fundamental knowledge about · Model identification, accessories information, refrigerant and water cycle diagram,
parts and dimensions, electrical wiring diagrams, etc. · This chapter is important to understand
· Installation about the unit. · Installation location, constraints on installation site, etc · Electrical wiring at the unit. · System set-up and configuration. · Information about water pump
· Information about supported accessories · Specification, Constraints, and wiring are described. · Before purchasing accessories, please find supported specification to buy proper
one.
· Information about DIP switch setting
· check and input service contact · information about model and open source license

Chapter 8

· Information on the installer setup mode that sets the detailed functions of the remote control
· Incorrectly setting the installer setup mode may result in product failure, personal injury, or property loss, so this chapter requires a deeper understanding

Chapter 9

· Check points before starting operation are explained. · Troubleshooting, maintenance, and error code list are presented to correct
problems

6 SAFETY INSTRUCTIONS

ENGLISH

SAFETY INSTRUCTIONS

Read the precautions in this manual carefully before operating the unit.
This symbol indicates that the Operation Manual should be read carefully.

This appliance is filled with flammable refrigerant (for R32)
This symbol indicates that a service personnel should be handling this equipment with reference to the Installation Manual.

The following safety guidelines are intended to prevent unforeseen risks or damage from unsafe or incorrect operation of the appliance. The guidelines are separated into WARNING’ andCAUTION’ as described below.

! This symbol is displayed to indicate matters and operations that can cause risk. Read the part with this symbol carefully and follow the instructions in order to avoid risk.
! WARNING
This indicates that the failure to follow the instructions can cause serious injury or death.
! CAUTION
This indicates that the failure to follow the instructions can cause the minor injury or damage to the product.

! WARNING
Installation
· Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit. – There is risk of fire or electric shock.
· For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center. – There is risk of fire or electric shock.

ENGLISH

SAFETY INSTRUCTIONS 7
· Always ground the unit. – There is risk of fire or electric shock.
· Install the panel and the cover of control box securely. – There is risk of fire or electric shock.
· Always install a dedicated circuit and breaker. – Improper wiring or installation may cause fire or electric shock
· Use the correctly rated breaker or fuse. – There is risk of fire or electric
· Do not modify or extend the power cable. – There is risk of fire or electric shock.
· Do not install, remove, or reinstall the unit by yourself (customer). – There is risk of fire, electric shock, explosion, or injury
· For antifreeze, always contact the dealer or an authorized service center. – Almost the antifreeze is a toxic product.
· For installation, always contact the dealer or an authorized Service Center. – There is risk of fire, electric shock, explosion, or injury.
· Do not install the unit on a defective installation stand. – It may cause injury, accident, or damage to the unit.
· Be sure the installation area does not deteriorate with age. – If the base collapses, the unit could fall with it, causing property damage, unit failure, and personal injury.
· Do not install the water pipe system as Open loop type. – It may cause failure of unit.
· Use a vacuum pump or inert (nitrogen) gas when doing leakage test or purging air. Do not compress air or oxygen and do not use flammable gases. – There is the risk of death, injury, fire or explosion.
· Make sure the connected condition of connector in product after maintenance. – Otherwise, it may cause product damage

ENGLISH

8 SAFETY INSTRUCTIONS
· Do not touch leaked refrigerant directly. – There is risk of frostbite.
· Compliance with national gas regulations shall be observed.
· Refrigerant tubing shall be protected or enclosed to avoid damage.
· The installation of pipe-work shall be kept to a minimum.
· A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts. A vacuum valve shall be provided to evacuate the interconnecting pipe and/or any uncharged refrigerating system part.
· Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification.
· Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is smaller than 1) The minimum floor area : 49.4 m2 2) The maximum refrigerant charge amount : 2.4 kg
· Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
· Do not pierce or burn.
· Be aware that refrigerants may not contain an odour.
· Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
· Ducts connected to an appliance shall not contain an ignition source.
· Copper in contact with refrigerants shall be oxygen-free or deoxidized, for example Cu-DHP as specified in EN 12735-1 and EN 12735-2.

ENGLISH

SAFETY INSTRUCTIONS 9
Operation
· Take care to ensure that power cable could not be pulled out or damaged during operation. – There is risk of fire or electric shock.
· Do not place anything on the power cable. – There is risk of fire or electric shock.
· Do not plug or unplug the power supply plug during operation. – There is risk of fire or electric shock.
· Do not touch (operate) the unit with wet hands. – There is risk of fire or electric shock.
· Do not place a heater or other appliances near the power cable. – There is risk of fire or electric shock.
· Do not allow water to run into electric parts. – There is risk of fire, failure of the unit, or electric shock.
· Do not store or use flammable gas or combustibles near the unit. – There is risk of fire or failure of unit.
· Do not use the unit in a tightly closed space for a long time. – It may cause damage to the unit.
· When flammable gas leaks, turn off the gas and open a window for ventilation before turning the unit on. – There is risk of explosion or fire.
· If strange sounds or smell or smoke comes from unit, turn the breaker off or disconnect the power supply cable. – There is risk of electric shock or fire.
· Stop operation and close the window in storm or hurricane. If possible, remove the unit from the window before the hurricane arrives. – There is risk of property damage, failure of unit, or electric shock.
· Do not open the front cover of the unit while operation. (Do not touch the electrostatic filter, if the unit is so equipped.) – There is risk of physical injury, electric shock, or unit failure.

ENGLISH

10 SAFETY INSTRUCTIONS
· Do not touch any electric part with wet hands. you should be power off before touching electric part. – There is risk of electric shock or fire.
· Do not touch refrigerant pipe and water pipe or any internal parts while the unit is operating or immediately after operation. – There is risk of burns or frostbite, personal injury.
· If you touch the pipe or internal parts, you should be wear protection or wait time to return to normal temperature. – Otherwise , it may cause burns or frostbite, personal injury.
· Turn the main power on 6 hours ago before the product starting operation. – Otherwise, it may cause compressor damage.
· Do not touch electric parts for 10 minutes after main power off. – There is risk of physical injury, electric shock.
· The inside heater of product may operate during stop mode. It is intended to protect the product.
· Be careful that some part of the control box are hot. – There is risk of physical injury or burns.
· When the unit is soaked (flooded or submerged), contact an Authorized Service Center. – There is risk of fire or electric shock.
· Be cautious that water could not be poured to the unit directly. – There is risk of fire, electric shock, or unit damage.
· Ventilate the unit from time to time when operating it together with a stove, etc. – There is risk of fire or electric shock.
· Turn the main power off when cleaning or maintaining the unit. – There is risk of electric shock.
· Take care to ensure that nobody could step on or fall onto the unit. – This could result in personal injury and unit damage.
· For installation, always contact the dealer or an Authorized Service Center. – There is risk of fire, electric shock, explosion, or injury.

ENGLISH

SAFETY INSTRUCTIONS 11
· If the unit is not used for long time, we strongly recommend not to switch off the power supply to the unit. – There is risk of water freezing.
· The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
· The appliance shall be stored in a room without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example an operating electric heater).
· The appliance shall be stored so as to prevent mechanical damage from occurring.
· Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
· When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re- fabricated.
· Be aware that refrigerants may not contain an odor. · Periodic(more than once/year) cleaning of the dust or salt
particles stuck on the heat exchangers by using water. · Keep any required ventilation openings clear of obstruction.
! CAUTION
Installation
· Always check for gas (refrigerant) leakage after installation or repair of unit. – Low refrigerant levels may cause failure of unit.
· Keep level even when installing the unit. – To avoid vibration or water leakage.
· Use two or more people to lift and transport the unit. – Avoid personal injury.
· Do not install the unit in potentially explosive atmospheres.

ENGLISH

12 SAFETY INSTRUCTIONS
· Connect the water for filling or refilling the heating system as specified by EN 1717/EN 61770 to avoid contamination of drinking water by return flow.
Operation
· Do not use the unit for special purposes, such as preserving foods, works of art, etc. – There is risk of damage or loss of property.
· Use a soft cloth to clean. Do not use harsh detergents, solvents, etc. – There is risk of fire, electric shock, or damage to the plastic parts of the unit.
· Do not step on or put anything on the unit. – There is risk of personal injury and failure of unit.
· Use a firm stool or ladder when cleaning or maintaining the unit. – Be careful and avoid personal injury.
· Do not turn on the breaker or power under condition that front panel cabinet, top cover, control box cover are removed or opened. – Otherwise it may cause fire, electric shock, explosion or death.
· The appliance shall be disconnected from its power source during service and when replacing parts.
· Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
· The Installation kit supplied with the appliance are to be used and that old Installation kit should not be reused.
· If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
· In order to avoid a hazard due to inadvertent resetting of the thermal cut- out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.

ENGLISH

SAFETY INSTRUCTIONS 13
· This equipment shall be provided with a supply conductor complying with the national regulation.
· The instructions for service to be done by specialized personnel, mandated by the manufacturer or the authorized representative may be supplied in only one Community language which the specialized personnel understand.
· This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

ENGLISH

14 INSTALLATION PART

INSTALLATION PART
Thank you for choosing LG Electronics Air-to-Water Heat Pump Before starting installation, please make it sure that all parts are found inside the product box.

Item

Image

Installation Manual

Outdoor Unit UN36A Chassis (Product heating capacity :
5, 7, 9 kW)
Outdoor Unit UN60A Chassis (Product heating capacity : 9, 12, 14, 16 kW)

Remote Controller

Remote Controller Cable Damper Drain Cap
Drain Nipple

GENERAL INFORMATION 15

ENGLISH

GENERAL INFORMATION

With advanced inverter technology,

is suitable for applications like under floor

heating, under floor cooling, and hot water generation. By Interfacing to various accessories user

can customize the range of the application.

In this chapter, general information of

is presented to identify the installation

procedure. Before beginning installation, read this chapter carefully and find helpful information

on installation.

Model Information

Factory Model Name

Model

No. 1234567

Monobloc ZH B W 09 6 A 0

No.

Signification

1 Air-to-Water-Heat Pump for R32

2

Classification – B : Monobloc

3

Model Type – W : Inverter Heat Pump

4

Heating Capacity – E.g) 9 kW ’09’

Electrical ratings 5 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz

6

Function – A : General heating heat pump

7 Series Number

Buyer Model Name

– For 3 Series

Refrigerant

No.

123457 8

R32 H M 09 1 M U3 3

No.

Signification

1 Air-to-Water-Heat Pump

2

Classification – M : Monobloc

3

Heating Capacity – E.g) 9 kW ’09’

Electrical ratings 4 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz

5

Leaving Water Combination – M : Middle Temperature

Chassis Name 6 – U3 : UN60A Chassis
– U4 : UN36A Chassis
7 Series Number

16 GENERAL INFORMATION

ENGLISH

– For 3 Series
Refrigerant 123
R32 H M 09

No. 456 1MR

789 S U3 3

No.

Signification

1 Air-to-Water-Heat Pump

2

Classification – M : Monobloc

3

Heating Capacity – E.g) 9 kW ’09’

Electrical ratings 4 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz

5

Leaving Water Combination – M : Middle Temperature

6

Refrigerant – R : R32

7

Function – S : Silent

Chassis Name 8 – U3 : UN60A Chassis
– U4 : UN36A Chassis

9 Series Number

– Additional Information : Serial number refers to the barcode on the product.
– Max allowable pressure High side : 4.32 MPa / Low side : 2.4 MPa
[Operating condition] – Maximum operating temperature of water : 65 °C – Minimum operating temperature of water : 15 °C – Maximum inlet water pressure : 0.3 MPa – Minimum inlet water pressure : 0.03 MPa

– For 4 Series

Refrigerant

No.

12345678

R32 H M 09 1 M R U3 4

No.

Signification

1 Air-to-Water-Heat Pump

2

Classification – M : Monobloc

3

Heating Capacity – E.g) 9 kW ’09’

Electrical ratings 4 – 6 : 1 phase 220-240 V~ 50 Hz
– 8 : 3 phase 380-415 V~ 50 Hz

5

Leaving Water Combination – M : Middle Temperature

6

Refrigerant – R : R32

Chassis Name 7 – U3 : UN60A Chassis
– U4 : UN36A Chassis

8 Series Number

Check the model information based on the buyer model series number.
(e.g., geometry, cycle, etc.)

GENERAL INFORMATION 17

ENGLISH

Model name and related information

Chassis UN36A
UN60A

Model Name Phase(Ø) 1
1
3

Capacity(kW) 5 7 9 9 12 14 16 12 14 16

Capacity (kW)

Heating1)

Cooling2)

5.5

5.5

7

7

9

9

9

9

12

12

14

14

16

16

12

12

14

14

16

16

Power Source (Unit)
220-240 V~ 50 Hz
380-415 V 3N~ 50 Hz

1 : tested under EN14511 (water temperature 30 °C ¡ 35 °C at outdoor ambient temperature 7 °C / 6 °C)
2 : tested under EN14511 (water temperature 23 °C ¡ 18 °C at outdoor ambient temperature 35 °C / 24 °C)
C All appliances were tested at atmospheric pressure.

ENGLISH

18 GENERAL INFORMATION
Parts and Dimensions
– For 3 Series
4

UN36A (5, 7, 9 kW)

5

4

5

9

2

6

7

8

10

3

1

C The shape may differ depending on the model.

Description

No

Name

1 Entering water pipe

2 Leaving water pipe

3 Strainer

4 Top cover

5 Control Box

6 Plate Heat Exchanger

7 Water Pump

8 Pressure Gage

9 Safety valve

10 compressor

Remarks Male PT 1 inch Male PT 1 inch Filtering and stacking particles inside circulating water PCB and terminal blocks Heat exchanger between refrigerant and water Circulating the water Indicates circulating water pressure Open at water pressure 3 bar –

ENGLISH

GENERAL INFORMATION 19 UN60A (9, 12, 14, 16 kW)
C The shape may differ depending on the model.

20 GENERAL INFORMATION

ENGLISH

Description

No

Name

Remarks

1 Entering water pipe

Male PT 1 inch

2 Leaving water pipe

Male PT 1 inch

3 Strainer

Filtering and stacking particles inside circulating water

4 Top cover

5 Front Panel

6 Side Panel

7 Signal A

Network Kit cables

8 Signal B

Network Kit cables

9 Signal C

10 Outdoor Entry Power Cable –

11 Water Pump

Circulating the water

12 Plate Heat Exchanger

Heat exchanger between refrigerant and water

13 Pressure Gage

Indicates circulating water pressure

14 Safety valve

Open at Water pressure 3 bar

15 Heater Control Box

Heater PCB and terminal blocks

16 Outdoor Control Box

Outdoor PCB and terminal blocks

ENGLISH

– For 4 Series

GENERAL INFORMATION 21 UN36A (5, 7, 9 kW)

C The shape may differ depending on the model.

ENGLISH

22 GENERAL INFORMATION

UN60A (12, 14, 16 kW)

C The shape may differ depending on the model.

Description

No

Name

1

Entering water pipe

2

Leaving water pipe

3

Strainer

4

Top cover

5

Front Panel

6

Side Panel

7

Low Voltage

8

UNIT Power

9

Water Pump

10

Plate Heat Exchanger

11

Compressor shield panel

12

Safety valve

13

Indoor Control Box

14

Outdoor Control Box

15

Flow sensor

16

Pressure Sensor

GENERAL INFORMATION 23
Remarks Male PT 1 Inch Male PT 1 Inch Filtering and stacking porticles inside circulating water
Communication Cable Hole Power Cable Hole Heat exchange between refrigerant and water Open at water pressure 3 bar PCB and terminal blocks PCB and terminal blocks SIKA VVX20 5-80 LPM SENSATA 2HMP3-05W 02-MPa

ENGLISH

ENGLISH

24 GENERAL INFORMATION

Control Parts

– For 3 Series
Control box before structural change (Until August, 2020)

UN36A (5, 7, 9 kW)

UN60A (9, 12, 14, 16 kW)

2 2

1 1
Control box after structural change (From September, 2020)
2

1
C The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual.

Description

No

Name

1 Terminal blocks

2 Main PCB

Remark The terminal blocks allow easy connection of field wiring
The main PCB(Printed Circuit Board) controls the functioning of the unit

ENGLISH

– For 4 Series
Control box

GENERAL INFORMATION 25

2 1

C The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual.

Description

No

Name

1 Terminal blocks

2 Main PCB

Remark The terminal blocks allow easy connection of field wiring
The main PCB(Printed Circuit Board) controls the functioning of the unit

ENGLISH

26 GENERAL INFORMATION
Remote Controller

Operation display window

Back button

OK

Up/Down/Left/Right Button

On/Off Button OK Button

Operation display window Back button Up/down/left/right button OK button On/Off button

Operation and Settings status display When you move to the previous stage from the menu’s setting stage When you change the menu’s setting value When you save the menu’s setting value When you turn ON/OFF the Unit

ENGLISH

GENERAL INFORMATION 27

Typical Installation Example

! CAUTION

If

is installed with pre-existing boiler, the boiler and

should not be

operated together. If entering water temperature of

is above 55 °C, the system

will stop operation to prevent mechanical damage of the product. For detailed electric wiring

and water piping, please contact authorized installer.

Some installation scenes are presented for example. As these scenes are conceptual

figures, installer should optimize the installation scene according to the installation

conditions. Note that buffer tank should be installed.

CASE 1: Connecting Heat Emitters for Heating and Cooling
(Under floor loop, Fan Coil Unit, and Radiator)
Outdoor Indoor

R T
M / F

Buffer Tank

NOTE

Fan coil unit Floor heating loop Radiator

· Room thermostat – Type of thermostat and specification should be complied with chapter 4 and chapter 7 of installation manual.

· 2way valve

– It is important to install 2way valve to prevent dew condensation on the floor and radiator

while cooling mode.

– Type of 2way control valve and specification should be complied with chapter 4 and

chapter 7 of

installation manual.

– 2way valve should be installed at the supply side of the collector.

· By-pass valve – To secure enough water flow rate, by-pass valve should be installed at the collector. – By-pass valve should guarantee minimum water flow rate in any case. Minimum water flow rate is described in water pump characteristics curve.

High Temperature Low Temperature M / F Magnetic Filter (Mandatory)

Room Thermostat (Field supply)
2way valve (Field supply)

Shut-off valve By-pass valve(Field supply) R Remote controller

ENGLISH

28 GENERAL INFORMATION
CASE 2: Connecting DHW Tank

Outdoor Indoor R T
M / F

Buffer Tank

Hot water

City water

DHW tank

Fan coil unit Floor heating loop Radiator

NOTE
· DHW tank – It should be equipped with internal electric heater to generate sufficient heat energy in very cold season. – DHW : Domestic Hot Water
· 3way valve – Type of 3way valve and specification should be complied with chapter 4 and chapter 7 of installation manual.

High Temperature Low Temperature Shut-off valve M / F Magnetic Filter (Mandatory)

Room Thermostat(Field supply)
2way valve (Field supply) By-pass valve(Field supply)

R Remote controller
3way valve (Field supply)

ENGLISH

CASE 3: Connecting Solar thermal system

Outdoor Indoor R T
M / F

Buffer Tank

GENERAL INFORMATION 29

Solar heat source

Hot water

DHW tank

Fan coil unit Floor heating loop Radiator

City water

NOTE
· DHW tank – It should be equipped with internal electric heater to generate sufficient heat energy in very cold season. – DHW : Domestic Hot Water
· Pump – Maximum power consumption of pump should be less than 0.25 kW.

High Temperature Low Temperature Shut-off valve M / F Magnetic Filter (Mandatory)

Room Thermostat(Field supply)
2way valve (Field supply) By-pass valve(Field supply)

R Remote controller
3way valve (Field supply) Pump(Field supply)

ENGLISH

30 GENERAL INFORMATION
CASE 4: Connecting 2nd Circuit

Outdoor Indoor
R T
M / F

Buffer Tank

[Room A] Main Zone zone (Low Temp.)

Mix

2nd circuit temp. sensor

Mix Kit

Floor heating loop Floor heating loop

[Room B] Additional zone (High Temp.)

Radiator

Radiator

NOTE
· Mix Kit – You can install it when you want to set the temperature of two rooms individually – When heating, Main Zone can not be higher than Add Zone. – When cooling, Main Zone can not be lower than Add Zone. – The types and specifications of the Mix Kit are to comply with Chapters 4 and 7 of the Installation Manual.

High Temperature
Low Temperature
Shut-off valve M / F Magnetic Filter (Mandatory)
Pressure Regulation valve (Field supply)

Room Thermostat (Field supply) 2way valve (Field supply)
By-pass valve(Field supply)
Air vent (Field supply)

3way valve (Field supply) Pump(Field supply)
Mix Kit (Field supply)

ENGLISH

CASE 5: Connecting 3rd Party

Outdoor Indoor
R T
M / F

3 Way V/V direction Boiler On : Boiler Off :

Buffer Tank

Boiler

GENERAL INFORMATION 31

Floor

Floor

Floor

heating loop heating loop heating loop

NOTE
· DHW tank – 3rd Party Boiler – You can control the boiler automatically and manually by comparing the outside temperature and the set temperature.
· 3way valve – It is a valve for DHW use. – Not installed when installing Buffer Tank – Type of 3way valve and specification should be complied with chapter 4 and chapter 7 of installation manual.

High Temperature Low Temperature Shut-off valve M / F Magnetic Filter (Mandatory) Reverse check valve

Room Thermostat(Field supply) 2way valve (Field supply) By-pass valve(Field supply) Air vent (Field supply)

3way valve (Field supply) Pump(Field supply)
Aquastat V/V

ENGLISH

32 GENERAL INFORMATION
CASE 6 : Connecting backup heater

Outdoor Indoor R T
M/F

Buffer Tank

Floor heating Floor heating Floor heating

loop

loop

loop

NOTE
· Backup heater(Accessory) – You can retain sufficient capacity even though ambient temperature will be decreased in winter.

High Temperature Low Temperature M / F Magnetic Filter (Mandatory)

Room Thermostat (Field supply) 3way valve (Field supply)
R Remote controller

Shut-off valve
By-pass valve (Field supply)

ENGLISH

Cycle Diagram
– For 3 Series UN60A (12, 14, 16 kW)

GENERAL INFORMATION 33

S6 S2

Pressure

Switch

S5

Muffler Accumulator

S4

S3

Inv. Comp

S8

EEV1

EEV2

EEV3 (Inj.EEV) IHEX

S7

High Pressure Sensor S1
S9

Air Vent

:: HCoeaotliinngg S13

S12

Relief

Water

valve

Out Pressure

Gage

Backup Heater Accessory Expansion Tank
Air Vent

S10 [PHE] Water Flow W/Pump Strainer S11 In Switch

UN36A (5, 7, 9 kW)

S6 S2

High

Pressure

Pressure

Sensor

S5

Switch Muffler

S1

Accumulator

S4 EEV1
S7
EEV3 S8 (Inj.EEV)

Inv. Comp

S3
S9 EEV2

: Cooling : Heating

Air Vent

S13

S12

Relief

Water

valve

Out Pressure

Gage

Backup Heater Accessory Expansion Tank Air Vent

IHEX

S10

[PHE]

Water In

Flow W/Pump Switch

Strainer S11

Inv. Comp ENGLISH

34 GENERAL INFORMATION

UN60A (1Ø : 9 kW)

: Cooling

S6

High Pressure

Air Vent

: Heating S13

S2

Pressure

Sensor

S5

Switch

Muffler S1

Accumulator

S12

Backup Heater Accessory

EEV1

S4

S3

Water

Relief valve

Expansion Tank

Out Pressure

EEV3

S9

Gage

Air Vent

(Inj.EEV)

S10

[PHE]WIanter

Flow W/Pump Strainer S11 Switch

Description

Category Symbol

Meaning

Indoor Unit
Water Side

S1 High pressure sensor S2 Condenser middle temperature sensor S3 Compressor- discharge pipe temperature sensor S4 Compressor-suction pipe temperature sensor S5 Condenser temperature sensor S6 Outdoor air temperature sensor S7 Inlet IHEX temperature sensor S8 Outlet IHEX temperature sensor S9 PHEX gas temp. sensor S10 PHEX liquid temp. sensor S11 Entering water temperature sensor S12 Leaving water temperature sensor S13 Electric backup heater outlet (Accessory kit)

-S9, S10, S5 : Description is expressed based on Cooling mode.

PCB Connector CN_H_PRESS CN_MID CN_DISCHA CN_SUCTION CN_C_PIPE
CN_AIR CN_VI_IN CN_VI_OUT CN_PIPE_OUT CN_PIPE_IN
CN_TH3

ENGLISH Inv. Comp

GENERAL INFORMATION 35

– For 4 Series
UN36A (5, 7, 9 kW) UN60A (12, 14, 16 kW)

S6 S2
S5
EEV1
EEV3 (Inj.EEV)

Pressure Switch

Accumulator

S4

S3

S7

Pressure Sensor

Air Vent

S13 Backup Heater Accessory

: Cooling : Heating

S10 [PHE]

Expansion Tank

Relief Water valve Out

S12 Air Vent

S11

Water In

A1

S17 Strainer S19

Flow Sensor

Pressure Sensor

Description

Category Symbol

Meaning

Refrigerant side

S1 S2 S3 S4 S5 S6 S7 EEV1 EEV2

PHEX liquid temperature sensor Outdoor-HEX middle temperature sensor Compressor-discharge pipe temperature sensor Compressor-suction pipe temperature sensor Outdoor-HEX temperature sensor Outdoor air temperature sensor Compressor-injection pipe temperature sensor Electronic Expansion Valve (Heating/Cooling) Electronic Expansion Valve (Injection)

S12 Outlet water temperature sensor

S11 Inlet water temperature sensor S13 Backup heater outlet sensor S17 Flow sensor Water Side S19 Water pressure sensor

A1 Main Water Pump

A8 Electric backup heater(1Ø, Optional accessory) A9 Electric backup heater(3Ø, Optional accessory)

PCB Connector
CN_PIPE_IN CN_MID
CN_DISCHARGE CN_SUCTION CN_C_PIPE CN_AIR CN_VI_IN CN_EEV1 CN_EEV_MAIN
CN_WATER_OUT CN_WATER_IN
CN_TH3 CN_F_SENSOR CN_H20_PRESS CN_PUMP_A1 CN_MOTOR1 CN_HEATER_PCB
HEATER1

ENGLISH

36 GENERAL INFORMATION
Water cycle
– For 3 Series

Remote Room Temp. Sensor
S14
3WAY V/V_1

Shower

B/HT
S15 City Water
DHW Tank

3WAY V/V_2

S16
Solar Thermal Componets

Solor Panel

W/PUMP_2

SOLAR THERMAL SYSTEM

Ref Out Ref In

S9 S10
Unit

F/S
2WAY V/V_1

S12

W/PUMP_1

EXP/TANK

S11 M/F

Fan Coil Unit
Underfloor Heating
Radiator

Indoor Unit (Hydro-Kit)

Magnetic Filter (Mandatory)

Basic installation

DHW Tank is Installed
(DHW tank is necessary)

Solar thermal system is connected
(Solar thermal kit is necessary)

– For 4 Series

Remote Room Temp. Sensor
S14
3WAY V/V_1

Shower

B/HT
S15 City Water
DHW Tank

3WAY V/V_2

S16
Solar Thermal Componets

Solor Panel

W/PUMP_2

SOLAR THERMAL SYSTEM

GENERAL INFORMATION 37

Ref Out Ref In
S10
Unit

F/S
2WAY V/V_1

S12

W/PUMP_1

EXP/TANK

S11 M/F

Fan Coil Unit
Underfloor Heating
Radiator

Indoor Unit (Hydro-Kit)

Magnetic Filter (Mandatory)

Basic installation

DHW Tank is Installed
(DHW tank is necessary)

Solar thermal system is connected
(Solar thermal kit is necessary)

ENGLISH

38 GENERAL INFORMATION

ENGLISH

Description

Category

Symbol S9 S10 S11 S12
F/S

Meaning Refrigerant temperature sensor (Gas side) Refrigerant temperature sensor (Liquid side) Water temperature sensor (Water In) Water temperature sensor (Water Out)
Flow Switch

E/HT Electric Heater
Unit W_PUMP1 Internal Water Pump EXP/TANK Expansion Tank S14 Remote Air temperature sensor CTR/PNL Remote Controller 2WAY V/V_1 To control water flow for Fan Coil Unit
M / F Magnetic Filter

W/TANK DHW Tank

B/HT Booster heater(in DHW tank)

Water Heating

– Flow control for water which is leaving from unit. 3WAY V/V_1 – Flow direction switching between underfloor and
water tank

CITY WATER

Water to be heated by Indoor unit and B/HT of W/TANK

SHOWER Water supplied to end-user

S15 W/TANK water temperature sensor

S16 Solar-heated water temperature sensor

3WAY V/V_2

– Flow control for water which is heated and circulated by SOLAR THERMAL SYSTEM. – Flow direction switching between SOLAR THERMAL SYSTEM and W/TANK

PCB Connector CN_PIPE_OUT CN_PIPE_IN
Water _IN Water _OUT CN_FLOW1
CN_E/HEAT(A) CN_E/HEAT(B)
CN_MOTOR1 (no connector)
CN_ROOM CN_REMO CN_2WAY(A)
(No connector)
(no connector)
CN_B/HEAT(A)
CN_3WAY(A)
(no connector) (no connector)
CN_TH4
CN_3WAY(B)

Remarks
– Meaning is expressed based on Cooling mode.
– Optional accessory (sold separately) – Model : HA**1A E1 – Heating capacity is divided into two level : partial capacity by E/HEAT(A) and full capacity by E/HEAT(A) + E/HEAT(B). – Operating power(220-240 V~ 50 Hz) of E/HEAT(A) and E/HEAT(B) are supplied by external power source via relay connector and ELB. – Water Pump is connected at CN_MOTOR1 – Absorb volume change of heated water, – Optional accessory (sold separately) – Model : PQRSTA0
– 3rd party accessory and Field installation (sold separately) – 2 wire NO or NC type 2way valve is supported. – 3rd party accessory and Field installation (sold separately) – It is Mandatory to install an additional filter on the heating water circuit. – 3rd party accessory and Field installation (sold separately) – Generating and storing DHW by AWHP or built-in electric heater – 3rd party accessory and Field installation (usually built-in at W/TANK) – Supplying additional water heating capacity. – 3rd party accessory and Field installation (sold separately) – SPDT type 3way valve is supported.
– Field installation
– Field installation – S15 and S16 are connected at 4 pin type connector CN_TH4. – S15 is a part of DHW tank kit.(Model : PHLTB) – S16 is a part of solar thermal kit (Model:PHLLA)
– 3rd party accessory and Field installation (sold separately) – SPDT type 3way valve is supported.

Solar Heating

W_PUMP/2 External Water Pump

CN_W/PUMP(B)

– 3rd party accessory and Field installation (sold separately) – If water pump of SOLAR THERMAL SYSTEM is incapable of circulation,external water pump can be used.

SOLAR THERMAL SYSTEM

– This system can include following components :

Solar panel, Sensors, Thermostats, Interim heat

exchanger, Water pump, etc.

(no connector)

– To utilized hot water heated by SOLAR THERMAL

SYSTEM, end-user must by LG AWHP Solar-Kit.

– 3rd party accessory and Field installation (sold separately)

ENGLISH

INSTALLATION 39
INSTALLATION
Transporting the Unit
· When carrying the suspended unit, pass the ropes between legs of base panel under the unit. · Always lift the unit with ropes attached at four points so that impact is not applied to the unit. · Attach the ropes to the unit at an angle of 40° or less. · Use only accessories and parts which are of the designated specification when installing. · Forklift trucks are not available without a palette. · Be careful not to damage the product when moving the forklift.
Sub line

40º or less

Air outlet grille

Corner Handle

Intake hole

Always hold the unit by the corners, as holding it by the side intake holes on the casing may cause them to deform.

Forklift

ENGLISH

40 INSTALLATION
Installation places
– If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
– Ensure that the spaces indicated by arrows around front, back and side of the unit. – Do not place animals and plants in the path of the warm air. – Take the Unit weight into account and select a place where noise and vibration are minimum. – Select a place so that the warm air and noise from the air conditioner do not disturb neighbors. – Place that can sufficiently endure the weight and vibration of the outdoor unit and where even
installation is possible – Place that has no direct influence of snow or rain – Place with no danger of snowfall or icicle drop – Place without weak floor or base such as decrepit part of the building or with a lot of snow
accumulation

More than 300

Awning

  • : Please secure the space to Maintain the shut-off valve and strainer.

oFbesntcaecloers

*Minimum 300

More than 600 More than 700

Unit : mm

! CAUTION
Be very careful while carrying the product.
· Do not have only one person carry product if it is more than 20 kg.
· PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
· Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
· Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
· When carrying in Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
· Use 2 belts of at least 8 m long.
· Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
· Hoist the unit making sure it is being lifted at its center of gravity.

ENGLISH

INSTALLATION 41
Installation at Seaside
! CAUTION
· Unit should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
· Do not install the unit where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the unit. Corrosion, particularly on the condenser and evaporator fins, could cause unit malfunc-tion or inefficient performance.
· If unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location
· If the unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the unit on the opposite side of the sea wind direction.

Sea wind

Sea wind

· In case, to install the unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak Sea wind

– It should be strong enough like concrete to prevent the sea wind from the sea.
– The height and width should be more than 150 % of the unit.
– It should be keep more than 700 mm of space between unit and the windbreak for easy air flow.

· Select a well-drained place.
– If you can’t meet above guide line in the seaside installation, please contact your supplier for the additional anticorrosion treatment.
– Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
Seasonal Wind and Cautions in Winter
· Sufficient measures are required in a snow area or severe cold area in winter so that unit can be operated well.
· Get ready for seasonal wind or snow in winter even in other areas. · Install a suction and discharge duct not to let in snow or rain. · Install the unit not to come in contact with snow directly. If snow piles up and freezes on the air
suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system. · Install the unit at the higher installation console by 500 mm than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall. · Where snow accumulated on the upper part of the unit by more than 100 mm, always remove snow for operation. – The height of H frame must be more than 2 times the snowfall and its width shall not exceed
the width of the unit. (If width of the frame is wider than that of the unit, snow may accumulate.) – Don’t install the suction hole and discharge hole of the unit facing the seasonal wind.

ENGLISH

42 INSTALLATION

Foundation for Installation
· Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation.
· Fix the unit securely by means of the foundation bolts. (Prepare 6sets of M12 foundation bolts, nuts and washers each which are available on the market.)
· It is best to screw in the foundation bolts until their length are 20 mm from the foundation surface.
· When installing the unit on the ground, install a separate pedestal with enough height to install the drain nipple.

620

293

100 75
200 75
200 361

Spring washer

Frame

Nut

H-Beam

Anti-vibration materials
Concrete base

Six bolt are required 3 thread ridges

Foundation bolt executing method

[Unit:mm]

! WARNING
· Be sure to remove the Pallet(Wood Support) of the bottom side of the unit Base Pan before fixing the bolt. It may cause the unstable state of the unit settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
· Be sure to remove the Pallet(Wood Support) of the bottom side of the unit before welding. Not removing Pallet(Wood Support) causes hazard of fire during welding.

Pallet(Wood Support) – Remove before Installation

ENGLISH

INSTALLATION 43
Electrical Wiring
· Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
! WARNING
· Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual. If power supply circuit has a lack of capacity or electric work deficiency, it may cause an electric shock or fire.
· Install the Unit transmission line away from the power source wiring so that it is not affected by electric noise from the power source. (Do not run it through the same conduit.)
· Be sure to provide designated grounding work to Unit.
! CAUTION
· Be sure to correct the unit to earth. Do not connect earth line to any gas pipe, liquid pipe, lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
· Give some allowance to wiring for electrical part box of Units, because the box is sometimes removed at the time of service work.
· Never connect the main power source to terminal block of transmission line. If connected, electrical parts will be burnt out.
· Only the transmission line specified should be connected to the terminal block for Unit transmission.
! CAUTION
· This product have reversed phase protection detector that only works when the power is turned on. If there exists black out or the power goes on and off which the product is operating, attach a reversed phase protection circuit locally. running the product in reversed phase may break the compressor and other parts.
· Use the 2-core shield cables for communication lines. Never use them together with power lines.
· The conductive shielding layer of cable should be grounded to the metal part of both units. · Never use multi-core cable · As this unit is equipped with an inverter, to install a phase leading capacitor not only will
deteriorate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading capacitor. · Make sure that the power unbalance ratio is not greater than 2 %. If it is greater, the unit’s lifespan will be reduced. · Introducing with a missing N-phase or with a mistaken N-phase will break the equipment

44 INSTALLATION

ENGLISH

! CAUTION
The power cable connected to the unit should be complied with IEC 60245 or HD 22.4 S4 (This equipment shall be provided with a cable set complying with the national regulation. Pipes and wires should be purchased separately for installation of the product.)
Select a circuit breaker and power cable suitable for the current specification.

Factory Model Name ZHBW056A0 ZHBW076A0 ZHBW096A0 ZHBW096S0 ZHBW126A0 ZHBW146A0 ZHBW166A0 ZHBW128A0 ZHBW148A0 ZHBW168A0 ZHBW056A1 ZHBW076A1 ZHBW096A1 ZHBW126A1 ZHBW146A1 ZHBW166A1 ZHBW128A1 ZHBW148A1 ZHBW168A1

Buyer Model Name HM051M U43 HM071M U43 HM091M U43
HM091MRS U33 HM121M U33 HM141M U33 HM161M U33 HM123M U33 HM143M U33 HM163M U33 HM051MR U44 HM071MR U44 HM091MR U44 HM121MR U34 HM141MR U34 HM161MR U34 HM123MR U34 HM143MR U34 HM163MR U34

Phase[Ø] 1 1 3 1 1 3

Capacity [kW] 5 7 9 9 12 14 16 12 14 16 5 7 9 12 14 16 12 14 16

ELCB 16 A 20 A 25 A 16 A 40 A 40 A 40 A 16 A 16 A 16 A 16 A 20 A 25 A 40 A 40 A 40 A 16 A 16 A 16 A

Power cable (Type : H07RNF)

Current [A] Area [mm2] [A] 0.2 Tinsel cord a

0.2< [A] 3

0.5 a

3< [A] 6

0.75

6< [A] 10 1.0 (0.75)b

10< [A] 16 1.5 (1.0)b

16< [A] 25

2.5

25< [A] 32

4

32< [A] 40

6

40< [A] 63

10

a These cords may only be used if their length does not exceed 2 m between the point where the cord or cord guard enters the appliance and the entry to the plug.
b Cords having the cross-sectional areas indicated in the parentheses may be used for portable appliances if their length does not exceed 2 m.

10±3 mm 35±5 mm

10±3 mm 35±5 mm

GN/YL 20 mm
For the 1-Phase

GN/YL 20 mm
For the 3-Phase

ENGLISH

INSTALLATION 45

Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.

Round pressure terminal

Power wire

When none are available, follow the instructions below. – Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.) – When connecting wiring which is the same thickness, do as shown in the figure below.

Connect same thickness wiring to both sides.

It is forbidden to connect two to one side.

It is forbidden to connect wiring of different thicknesses.

– For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
– Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and make proper tightening impossible.
– Over-tightening the terminal screws may break them.
! WARNING
· Make sure that the screws of the terminal are free from looseness.

ENGLISH

46 INSTALLATION
Point for attention regarding quality of the public electric power supply (For 3 Series)
– European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current 75 A.
– European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current 16 A of > 75 A per phase.
For 1 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents emission limits corresponding Rsce = 33.
– This equipment complies with reference impedance for IEC (EN) 61000-3-3.
For 3 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 provided that the short- circuit power Ssc is greater than or equal to 2067 kVA at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to 2067 kVA.
– This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (5,7, 9 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents emission limits corresponding Rsce = 33.
– This equipment complies with IEC (EN) 61000-3-3.

ENGLISH

INSTALLATION 47
Point for attention regarding quality of the public electric power supply (For 4 Series)
– European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current 75 A.
– European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current 16 A of > 75 A per phase.
For 1 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents emission limits corresponding Rsce = 33.
– This equipment complies with reference impedance for IEC (EN) 61000-3-11.
For 3 Phase (12, 14, 16 kW)
– This equipment complies with IEC (EN) 61000-3-12 provided that the short- circuit power Ssc is greater than or equal to 2672 kVA at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to 2672 kVA.
– This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (5,7 kW)
– This equipment complies with IEC (EN) 61000-3-2. – This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (9 kW)
– This equipment complies with IEC (EN) 61000-3-12 in harmonic currents emission limits corresponding Rsce = 33.
– This equipment complies with IEC (EN) 61000-3-3.

ENGLISH

48 INSTALLATION
Circuit Breaker Specification
Perform the electrical wiring work according to the electrical wiring connection. · All wiring must comply with local requirements. · Select a power source that is capable of supplying the current required by the appliance. · Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power source and the
unit. A disconnection device to adequately disconnect all supply lines must be fitted. · Model of circuit breaker recommended by authorized personnel Only. · Select a circuit breaker suitable for the current specification.

Unit

Backup

Live Signal for Backup Heater

Heater

(A+B)

CB

Live Signal for DHW Tank kit

CB ELCB

Switch Box

DHW Tank
CB DHW Tank kit
Power source Sensor Signal

CB : Circuit Breaker ELCB : Electric Leakage Circuit Breaker

ENGLISH

INSTALLATION 49
Wiring procedure for power cable
This cable is generally connected between external power source (such as main electric power distribution panel of user’s house) and the unit. Before starting wiring, check if wire specification is suitable and read following directions and cautions VERY carefully.
! CAUTION
After checking and confirming following conditions, start wiring work. · Secure dedicated power source for the Air-to-Water heat pump. The wiring diagram
(attached inside the control box of the unit) is presenting related information. · Provide a circuit breaker switch between power source and the outdoor unit. · Although it is very rare case, sometimes the screws used to fasten internal wires can be
loosen due to the vibration while product transportation. Check these screws and make it sure if they are all fastened tightly. If not tightened, burn-out of the wire can be occurred. · Check the specification of power source such as phase, voltage, frequency, etc. · Confirm that electrical capacity is sufficient. · Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. · Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) · Provide an ELB(electric leakage breaker) when the installation place is wet or moist. · The following troubles would be caused by abnormal voltage supply such as sudden voltage increasing or voltage drop-down. – Chattering of a magnetic switch (frequent on and off operation) – Physical damage of parts where magnetic switch is contacted – Break of fuse – Malfunction of overload protection parts or related control algorithms. – Failure of compressor start up – Ground wire to ground outdoor unit to prevent electrical shock.
Step 1. Disassemble side panel and front panel from the unit by loosing screws.
UN36A (5, 7, 9 kW)

UN60A(1Ø : 9, 12, 14, 16 kW)

UN60A (3Ø : 12, 14, 16 kW)

  • The feature may be vary according to the type of model.

ENGLISH

50 INSTALLATION
Step 2. Connect power cable to main power terminal See below figure for detailed information. When connecting earth cable, the diameter of cable should be refer to the below table. The earth cable is connected to the Control box case where earth symbol is marked.
Step 3. Use cable clamps (or cord clamps) to prevent unintended move of power cable. Step 4. Reassemble the side panel to the unit by fastening screws.

CODE CLAMP

UNIT POWER
UN36A (5, 7, 9 kW)
CODE CLAMP

CODE CLAMP

UNIT POWER
UN60A(1Ø : 9, 12, 14, 16 kW)

UNIT POWER
UN60A (3Ø : 12, 14, 16 kW)

Failure to do these instruction can result in fire, electric shock or death. · Make sure the power cable do not touch to copper tube. · Make sure to fix [cord clamp] firmly to sustain the connection of terminal. · Make sure to connect unit power & heater power separately.

  • The feature may be vary according to the type of model.

ENGLISH

INSTALLATION 51

Terminal Block Information
– For 3 Series Symbols used below pictures are as follows : – L, L1, L2 : Live (220-240 V~) – N : Neutral (220-240 V~) – BR : Brown, WH : White, BL : Blue, BK : Black

Case 1
Terminal Block 1
Energizing water pump for solar thermal system

1

2

3

L1 L2 N

MIXING VALVE

45 LN
MIX PUMP

67
LN
WATER PUMP
(B)

8 9 10 L L1 N
3WAY VALVE (B)

Power supply for 2nd heating kit

Water flow switching between using solar thermal heating and skipping solar thermal heating

Opening or closing water flow for FCU cooling

11 12 13
L L1 N
3WAY VALVE (B)

14 15 16 L L1 N
2WAY VALVE (A)

17 18 19 20 L N L1 L2
THERMOSTAT (Default : 230 V AC)

Water flow switching between under floor heating and DHW tank heating

Connection for thermostat (230 V AC)
Supporting type : Heating only or Heating/Cooling

Case 2
Terminal Block 1
Energizing water pump for solar thermal system

Water flow switching between under floor heating and DHW tank heating

1

2

3

L L1 N

3WAY VALVE (B)

45
LN
WATER PUMP
(B)

67
LN
WATER TANK HEATER

8 9 10 L L1 N
3WAY VALVE (A)

Water flow switching between using Turn on or off DHW

solar thermal heating and skipping

tank heater

solar thermal heating

Terminal Block 2
Power supply for 2nd heating kit

11 12 13 14

ABL N

3rd PARTY CONTROLLER

MIX PUMP

15 16 17 18 19 20 L1 L2 N L L1 N
MIXING VALVE 2WAY VALVE(A)

Connection for 3rd PARTY CONTROLLER

Opening or closing water flow for FCU cooling

Terminal Block 2 Terminal Block 3

21

22

L1

L2

WATER TANK HEATER

Turn on or off DHW tank heater

Turn on or off backup heater

23 24 LN
HEATER (B)

25 26 27 28 LNAB
HEATER 3rd PARTY (A) CONTROLLER

Connection for 3rd PARTY CONTROLLER

Terminal Block 4

Terminal Block 3

Connection for thermostat (230 V AC)
Supporting type : Heating only or Heating/Cooling

21 22 23 24 25 26 27 28 29 30

L N L N L N L1 L2

HEATER (A)

HEATER (B)

THERMOSTAT (Default : 230 V AC)

Turn on or off backup heater
Terminal Block 4

29

30

L1

L2

E/HEATER OUT SENSOR (5 V DC)

Connection for E/HEATER OUT SENSOR

31

32

L1

L2

E/HEATER OUT SENSOR (5 V DC)

Connection for E/HEATER OUT SENSOR

Terminal Terminal Block 1 Block 2

Terminal Terminal Block 3 Block 4
(Accessory)

Terminal Block 4

Terminal Terminal Terminal Block 1 Block 3 Block 2

(Accessory)

C Refer to Terminal Block Information according to the C/Box shape.

ENGLISH

52 INSTALLATION
– For 4 Series Symbols used below pictures are as follows : – L, L1, L2 : Live (220-240 V~) – N : Neutral (220-240 V~) – BR : Brown, WH : White, BL : Blue, BK : Black

Terminal Block 1

1

23

L L1 N

MIXING VALVE

45 6 L L1 N
2WAY VALVE (A)

7

89

L L1 N

3WAY VALVE (A)

Power supply for 2nd heating kit

Water flow switching between using solar thermal heating and skipping solar thermal heating

Energizing water pump for solar thermal system

10 11 12 13 14 L L1 N L N

3WAY VALVE WATER TANK

(B)

HEATER

15 16 LN
WATER PUMP(B)

17 18 LN
MIX PUMP

19 20 LN
WATER PUMP(C)

Water flow switching between under floor heating and DHW tank heating

Power supply for 2nd heating kit

Terminal Block 2 Terminal Block 3

21 22 23 24 25 26 27

L

N L1 L2 L3 A B

THERMOSTAT (Default : 230 V AC)

3rd PARTY CONTROLLER
(5V DC)

Connection for thermostat (230 V AC)
Supporting type : Heating only or Heating/Cooling

Connection for 3rd PARTY CONTROLLER

Terminal Block 1

Terminal Terminal Terminal Block 2 Block 3 Block 4
(Accessory)

Terminal Block 4

28

29

L1

L2

E/HEATER OUT SENSOR (5 V DC)

Connection for E/HEATER OUT SENSOR

C Refer to Terminal Block Information according to the C/Box shape.

ENGLISH

INSTALLATION 53
Wiring of main power supply and equipment capacity
1. Use a separate unit power and heater power. 2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when
proceeding with the wiring and connections. 3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1
rank thicker taking into account the line voltage drops. Make sure the power- supply voltage does not drop more than 10 %. 4. Specific wiring requirements should adhere to the wiring regulations of the region. 5. Power supply cords of parts of appliances for unit use should not be lighter than polychloroprene sheathed flexible cord. 6. Don’t install an individual switch or electrical outlet to disconnect each of unit separately from the power supply.
! WARNING
· Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
· Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
· Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
! CAUTION
· Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
· Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.

ENGLISH

54 INSTALLATION
Water Piping and Water Circuit Connection
! CAUTION
Followings are should be considered before beginning water circuit connection. · Service space should be secured. · Water pipes and connections should be cleaned using water. · Space for installing external water pump should be provided if internal water pump
capacity is not enough for installation field. · Never connect electric power while proceeding water charging.
Definition of terms are as follow : · Water piping : Installing pipes where water is flowing inside the pipe. · Water circuit connecting : Making connection between the unit and water pipes or between
pipes and pipes. Connecting valves or elbows are, for example, in this category.
Configuration of water circuit is shown in “Installation Scenes”. All connections should be complied with presented diagram.
While installing water pipes, followings should be considered : · While inserting or putting water pipes, close the end of the pipe with pipe cap to avoid dust
entering. · When cutting or welding the pipe, always be careful that inner section of the pipe should not be
defective. For example, no weldments or no burrs are found inside the pipe. · Drain piping should be provided in case of water discharge by the operation of the safety valve.
This situation can be happened when the internal pressure is over 3.0 bar and water inside the unit will be discharged to drain hose. · Pipe fittings (e.g. L-shape elbow, T-shape tee, diameter reducer, etc) should be tightened strongly to be free from water leakage. · Connected sections should be leakage-proof treatment by applying tefron tape, rubber bushing, sealant solution, etc. · Appropriate tools and tooling methods should be applied to prevent mechanical breakage of the connections. · Operation time of flow valve(e.g. 3way valve or 2way valve) should be less than 90 seconds. · While supplying water, pressure of supplying water should be 2.0 bar approximately. · Pipe is insulated to prevent heat loss to external environment and to prevent dew generation on the surface of the pipe in cooling operation. · Maximum allowable Torque at the water piping connection is 50 N·m

ENGLISH

INSTALLATION 55
When the water pipes are connected. It must be tightened the nut with two wrench. Otherwise pipes can be deformed.
Water Out
Union Water In

  • The feature may be vary according to the type of model.
    ! WARNING
    Installing shut-off valve · While assembling two shut-off valves, pop sound will be heard when valve is open or
    close by rotating handles. It is normal condition because the sound is due to leakage of charged nitrogen gas inside the valve. The nitrogen gas is applied to secure quality assurance. · Before starting water charging, these two shut- off valves should be assembled with water inlet and outlet pipe of the unit.
    Water condensation on the floor While cooling operation, it is very important to keep leaving water temperature higher than 16 °C. Otherwise, dew condensation can be occurred on the floor. If floor is in humid environment, do not set leaving water temperature below 18 °C.
    Water condensation on the radiator While cooling operation, cold water may not flow to the radiator. If cold water enters to the radiator, dew generation on the surface of the radiator can be occurred.
    Water Pipe Insulation Purpose of water pipe insulation is : To prevent heat loss to external environment. To prevent dew generation on the surface of the pipe in cooling operation. To prevent pipe breakage by freeze at winter season, Must be insulation at exterior water pipe between product and building.

ENGLISH

56 INSTALLATION
Water Charging
For water charging, please follow below procedures.
Step 1. Open all valves of whole water circuit. Supplied water should be charged not only inside the unit, but also in the under floor water circuit, DHW water tank circuit, FCU water circuit, and any other water circuits controlled by the product.
Step 2. Connect supply water into drain valve and fill valve located at the side of the shut-off valve.
! CAUTION
No water-leakage permitted at the drain and fill valve. Leakage-proof treatment which is described in previous section should be applied.
Step 3. Start to supply water. While supplying water, following should be kept. – Pressure of supplying water should be 2.0 bar approximately. – For supplying water pressure, time to be taken from 0 bar to 2.0 bar should be more than 1 minute. Sudden water supply can yield water drain through safety valve. – Fully open the cap of air vent to assure air purging. If air is exist inside the water circuit, then performance degrade, noise at the water pipe, mechanical damage at the surface of electric heater coil. – Open both the air vent in the water pipe and the air vent in the pump.
Step 4. Stop water supplying when the pressure gage located in front of the control panel indicates 2.0 bar.
Step 5. Close drain valve and fill valve. Then wait for 20~30 seconds to observe water pressure being stabilized.
Step 6. If following conditions are satisfactory, then go to Next process(Pipe Insulation). Otherwise, go to step 3. – Pressure gage indicates 2.0 bar. Note that sometimes pressure in decreased after step 5 due to water charging inside expansion vessel. – No air purging sound is heard or no water drop are popping out from air vent.
! CAUTION
Keep the air vent of the water pipe open and keep the air vent of the pump closed. Otherwise, the pump may make noise.
Pipe Insulation
Purpose of water pipe insulation is : · To prevent heat loss to external environment · To prevent dew generation on the surface of the pipe in cooling operation

ENGLISH

INSTALLATION 57
Water pump Capacity
The water pump us variable type which is capable to change flow rate, so it may be required to change default water pump capacity in case of noise by water flow. In most case, however, it is strongly recommended to set capacity as Maximum.
NOTE
· To secure enough water flow rate, do not set water pump capacity as Minimum. It can lead unexpected flow rate error CH14.

Pressure Drop

NOTE
When installing the product, install additional pump in consideration of the pressure loss and pump performance. If flow rate is low, overloading of product can occur

Capacity [kW] 16 14 12 9 7 5

Rated flow-rate [LPM(m3/h)]

Pump Head [m] (At rated flow rate)

Product pressure

drop [m] Serviceable Head

(Plate heat

[m]

exchanger)

46.0 (2.8)

9.0

1.4

7.6

40.25 (2.4)

9.3

1.1

8.2

34.5 (2.1)

9.8

0.8

9.0

25.87 (1.5)

6.1

0.4

5.7

20.12 (1.2)

7.3

0.3

7.0

14.37 (0.9)

7.5

0.2

7.3

ENGLISH

58 INSTALLATION
Performance curve
MGQ62321901 : UPML GEO 20 – 105 CHBL UN60A (12, 14, 16 kW)
MGQ62321902 : UPM3K GEO 20 – 75 CHBL UN36A (5, 7, 9 kW), UN60A (9 kW)
Performance test based on standard ISO 9906 with pre-pressure 2.0 bar and liquid temperature 20 °C.
! WARNING
· Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.

ENGLISH

INSTALLATION 59
Water Quality
Water quality should be complied with EN 98/83 EC Directives. Detailed water quality condition can be found in EN 98/83 EC Directives.
! CAUTION
· If the product is installed at existing hydraulic water loop, it is important to clean hydraulic pipes to remove sludge and scale.
· Installing sludge strainer in the water loop is very important to prevent performance degrade.
· Chemical treatment to prevent rust should be performed by installer. · It is strongly recommended to install an additional filter on the heating water circuit.
Especially to remove metallic particles from the heating piping, it is advised to use a magnetic or cyclone filter, which can remove small particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump system.

Frost protection by antifreeze
In areas of the country where entering water temperatures drop below 0 °C, the water pipe must be protected by using an approved antifreeze solution. Consult your AWHP unit supplier for locally approved solutions in your area. Calculate the approximate volume of water in the system. (Except the AWHP unit.) And add six liters to this total volume to allow for the water contained in AWHP unit.

Antifreeze type
Ethylene glycol Propylene glycol
Methanol

Antifreeze mixing ratio

0 °C

-5 °C

-10 °C -15 °C -20 °C -25 °C

0 %

12 %

20 %

30 %

0 %

17 %

25 %

33 %

0 %

6 %

12 %

16 %

24 %

30 %

If you use frost protection function, change DIP switch setting and input the temperature condition in Installation mode of remote controller. Refer to CONFIGURATION > DIP Switch Setting > DIP Switch Information > Option Switch 3 and INSTALLER SETTING > Antifreezing Temperature.

! CAUTION
· Use only one of the above antifreeze. · If a antifreeze is used, pressure drop and capability degradation of the system can be
occurred. · If one of antifreezes is used, corrosion can be occurred. So please add corrosion inhibitor. · Please check the concentration of the antifreeze periodically to keep same concentration. · When the antifreeze is used (for installation or operation), take care to ensure that
antifreeze must not be touched. · Ensure to respect all laws and norms of your country about Anti-freeze usage.

ENGLISH

60 INSTALLATION
Frost protection by antifreeze valve
About antifreeze valve This is a valve to prevent freeze in winter. When no antifreeze is added to the water, you can use antifreeze valves at all lowest points of the field piping to drain the water from the system before it can freeze
To install antifreeze valve To protect the field piping against freezing, install the following parts:
Outdoor Indoor
a C
b C

b

a Automatic air intake b Antifreeze valve (Optional ­ field supply) c Normally closed valves (recommended ­ field supply)

Part

Description

An automatic air intake (for air supply) should be installed at the highest point.

a

For example, an automatic air purge.

Protection for the field piping. The antifreeze valve must be installed:

· Vertically to allow water to flow out properly and free from obstructions.

b

· At all lowest points of the field piping.

· In the coldest part and away from heat sources.

Isolation of water inside the house when there is a power interruption.

Normally closed valves (located indoors near the piping entry/exit points) can

prevent that all water from indoor piping is drained when the antifreeze valve

open.

s

· When there is a power interruption: The normally closed valves close and

c

isolate the water inside the house. If the antifreeze valve open, only the

water outside the house is drained.

· In other circumstances (example: when there is a pump failure): The normally closed valves remain open. If the antifreeze valve open, the water from inside the house is also drained.

ENGLISH

INSTALLATION 61

NOTE
· Do not make any trap connections. If the shape of the connection pipe has the potential to create a trap effect, part of the pipe will not be able to drain and frost protection will no longer be guaranteed.
· Leave at least 15 cm clearance from the ground to prevent ice from blocking the water exit.
· Keep a distance of at least 10 cm between the antifreeze valves.
· The valve must be free of insulation for the system to work properly.
· When antifreeze valves are installed, do NOT select a minimum cooling setpoint lower than 7 °C. If lower, antifreeze valves can open during cooling operation.
· When installed outdoors, the antifreeze valve must be protected from rain, snow and direct sunlight.

Outdoor Indoor

10 cm

b b

15 cm

62 INSTALLATION

ENGLISH

Water Volume and Expansion Vessel Pressure
Inside expansion vessel is included which is 8 liter capacity with 1 bar pre- pressure. That means, according to the volume-pressure graph, total water volume of 230 liter is supported as default. If total water volume is changed because of installation condition, the pre-pressure should be adjusted to secure proper operation.
– Minimum total water volume is 20 liter. – Pre-pressure is adjusted by the total water volume. If the indoor is located at the highest
position of the water circuit, adjustment is not required. – To adjust pre- pressure, use nitrogen gas by certificated installer.
2.4

Pre-pressure in Expansion vessel (bar)

2.1

1.7

1.4

1.0

0.7

0.3

20

60

100 140

180 220 260 300 340

Maximum total water volume (liter)

Adjusting pre-pressure of expansion vessel is as following :
Step 1. Refer “Volume-Height” table. If installation scene is belong to Case A, go to Step 2. Otherwise, if it is Case B, do nothing. (pre-pressure adjustment is not required.) Otherwise, if it is Case C, go to Step 3.
Step 2. Adjust pre-pressure by following equation. Pre-pressure [bar] = (0.1 x H + 0.3) [bar] where H : difference between unit and the highest water pipe 0.3 : minimum water pressure to secure product operation
Step 3. Volume of expansion vessel is less than installation scene. Please install additional expansion vessel at the external water circuit.

Volume-Height Table

H < 7 m H7m

V < 230 liter V 230 liter

Case B

Case A

Case A

Case C

H : difference between unit and the highest water pipe V : total water volume of installation scene

ACCESSORIES INSTALLATION 63

ENGLISH

ACCESSORIES INSTALLATION

can interface to various accessories to extend its functionality and to improve user

convenience. In this chapter, specifications about supported 3rd party accessories and how to

connect to

is introduced.

It is noted that this chapter only deal with 3rd party accessories. For accessories supported by LG Electronics, please refer to installation manual of each accessories.

Accessories supported by LG Electronics

Item DHW Tank Install Kit Thermistor for DHW Tank Remote Temperature Sensor Dry Contact
Solar thermal Kit Meter Interface
Central Controller
Backup heater
Wi-Fi Modem Thermistor for 2nd Circuit Extension wire
PI485
ESS

Purpose
To operate with DHW tank
To control hot water temperature of DHW tank

PHLTB

Model

PHRSTA0

To control by air temperature

PQRSTA0

To receive on & off external signal Dry Contact For Thermostat

PDRYCB000 PDRYCB300

To operate with solar heating system

PHLLA(Limit temperature : 96 °C)

To measure production / consumption power

PENKTH000

Multiple installed products into one central control

AC EZ Touch (PACEZA000) AC Smart IV (PACS4B000) AC Smart 5 (PACS5A000) ACP 5 (PACP5A000) AC Manager 5 (PACM5A000)

To supplement insufficient capacity

HA031M E1 / HA061M E1 / HA063M E1

To enable remote system operation from smartphone

PWFMDD200

To interlock with 2nd circuit operation and control temperature of main zone.

PRSTAT5K10

To connect remote controller with Indoor PCB for communication

PZCWRC1

To communicate and control through For 3 Series: PMNFP14A1

the central controller

For 4 Series: PP485A00T

To control the operation mode according to the energy storage state

HOME 8 (PCS) : D008KE1N211 HOME10(PCS) : D010KE1N211 HB7H(Battery) : BLGRESU7H HB10H(Battery) : BLGRESU10H

64 ACCESSORIES INSTALLATION

ENGLISH

Item

Purpose

Model

DHW Tank

To generate and store hot water

OSHW-200F : 200 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-300F : 300 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-500F : 500 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-300F : 300 L, Double Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater

Cloud Gateway To use Becon cloud

PWFMDB200

Wi-Fi Modem

To enable remote system operation from smartphone

PWFMDD200

Extension cable for Wi-Fi Modem

To connect with Wi-Fi modem to the USB cable

PWYREW000

Thermistor for 2nd Circuit or E/Heater

To interlock with 2nd circuit

operation and control temperature

of main zone or To interlock with 3rd party E/Heater and control

PRSTAT5K10

temperature of water out 3rd

party E/Heater.

RS3 remote controller

To control unit with 2 remote controllers

PREMTW101

2-Remo Control Wire

The wire for 2 remo control

PZCWRC2

ACCESSORIES INSTALLATION 65

ENGLISH

Accessories supported by 3rd party Companies

Item Solar Heating System

Purpose
To generate auxiliary heating energy for water tank

Specification
· Solar collector · 3way valve(B)

Mix Kit 3rd Party Boiler 3rd Party Controller

To use 2nd Circuit
To use auxiliary boiler. To connect external controller using modbus protocol

· Mixing valve · Mix pump

Thermostat

To control by air temperature

Heating-Only type (230 V AC) Cooling/Heating type (230 V AC with Mode selection switch)

3way valve and actuator

(A) : To control water flow for hot water heating or floor heating / To control water flow when installing 3rd party boiler
(B) : To control close/open mode of solar circuit

3 wire, SPDT (Single Pole Double Throw) type, 230 V AC

To control water flow for Fan Coil 2way valve and actuator Unit / To serve as 3way valve when
installing backup heater

2 wire, SPST (Single Pole Sing Throw) type, 230 V AC

External Pump

To retain sufficient capacity using additional pump

Smart Grid

To control operation mode depending on input signal from provider

3rd Party ESS

To control the operation mode according to the energy storage state

(For 4 Series)

3rd party Backup heater To supplement in sufficient capacity (For 4 Series)

Antifreeze valve

To protect the pipes against freezing

DHW Recirculation Pump

To control the water flow of DHW recirculation pump

(For 4 Series)

ENGLISH

66 ACCESSORIES INSTALLATION
Before Installation
! WARNING
Followings should be kept before installation · Main power must be turned off during installing 3rd party accessories. · 3rd party accessories should be comply with supported specification. · Proper tools should be chosen for installation. · Never do installation with wet hands.
Thermostat
Thermostat is generally used to control the product by air temperature. When thermostat is connected to the product, the product operation is controlled by the thermostat.
Installation condition
! CAUTION
· USE 220-240 V~ Thermostat · Some electro-mechanical type thermostat has internal delay time to protect compressor. In
that case, mode change can takes time more than user’s expectation. Please read thermostat manual carefully if the unit does not response quickly. · Setting temperature range by thermostat can be different with that of the unit. The heating or cooling set temperature should be chosen within the setting temperature range of the unit. · It is highly recommended that the thermostat should be installed where space heating is mainly applied.
Following location should be avoid to secure proper operation : · Height from floor is approximately 1.5 m. · Thermostat can not be located where the area may be hidden when door is open. · Thermostat can not be located where external thermal influence may be applied. (such as
above heating radiator or open window)
Direct Sun ray contact area
yes
no
no
1.5 m
no

ENGLISH

ACCESSORIES INSTALLATION 67

General Information
The Heat Pump supports following thermostats.

Type Mechanical
(1)
Electrical (2)

Power 230 V~
230 V~

Operating Mode Heating Only (3) Heating / Cooling (4) Heating / Cooling / DHW Heating (5) Heating Only (3) Heating / Cooling (4) Heating / Cooling / DHW Heating (5)

Supported Yes Yes Yes Yes Yes Yes

(1) There is no electric circuit inside the thermostat and electric power supply to the thermostat is not required.
(2) Electric circuit such as display, LED, buzzer, etc is included in the thermostat and electric power supply is required.
(3) Thermostat generates “Heating ON or Heating OFF” signal according to user”s heating target temperature.
(4) Thermostat generates both “Heating ON or Heating OFF” and “Cooling ON or Cooling OFF” signal according to user”s heating and cooling target temperature.
(5) Thermostat generates “Heating ON or Heating OFF”, “Cooling ON or Cooling OFF”, “DHW Heating ON or DHW Heating OFF” signal according to user’s heating, cooling and DHW heating target temperature. (For Split Indoor unit 5 Series, For Hydrosplit)
! CAUTION
Choosing heating / cooling thermostat · Heating / cooling thermostat must have “Mode Selection” feature to distinguish operation
mode. · Heating / cooling thermostat must be able to assign heating target temperature and
cooling target temperature differently. · If above conditions are not kept, the unit can not operation properly. · Heating / cooling thermostat must send cooling or heating signal immediately when
temperature condition is satisfied. No delay time while sending cooling or heating signal is permitted.

68 ACCESSORIES INSTALLATION

ENGLISH

How to wire thermostat
Follow below procedures Step 1 ~ Step 5. Step 1. Uncover front cover of the unit and open the control box. Step 2. Identify the power specification of the thermostat. If it is 220-240 V~, go to Step 3. Step 3. If it is Heating only thermostat, go to step 4. Otherwise, if it is Heating / cooling
thermostat, go to step 5. Step 4. Find terminal block and connect wire as below.

27 28 29 30

L

N L1 L2

THERMOSTAT (Default : 230 V AC)

(L)

(N)

(H)

Thermostat

! WARNING
Mechanical type thermostat Do not connect wire (N) as mechanical type thermostat does not require electric power supply.
! CAUTION
Do not connect external electric loads. Wire (L) and (N) should be used only for operation electric type thermostat. Never connect external electric loads such as valves, fan coil units, etc. If connected, Main PCB (Heater) can be seriously damaged.

(L) : Live signal from PCB to thermostat (N) : Neutral signal from PCB to thermostat (H) : Heating signal from thermostat to PCB
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

Step 5. Find terminal block and connect wire as below.

27 28 29 30 L N L1 L2
THERMOSTAT (Default : 230 V AC)

! WARNING
Mechanical type thermostat Do not connect wire (N) as mechanical type thermostat does not require electric power supply.

(L) (N) (C) (H) Thermostat

! CAUTION
Do not connect external electric loads.
Wire (L) and (N) should be used only for operation Electric type thermostat.
Never connect external electric loads such as valves, fan coil units, etc. If connected, Main PCB (Heater) can be seriously damaged.

(L) : Live signal from PCB to thermostat (N) : Neutral signal from PCB to thermostat (C) : Cooling signal from thermostat to PCB (H) : Heating signal from thermostat to PCB

ENGLISH

ACCESSORIES INSTALLATION 69
How to wire Heating / Cooling / DHW Heating thermostat (For 4 Series)
Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the unit and open the control box. Step 2. Identify the power specification of the thermostat. If it is 220-240 V~, go to Step 3. Step 3. Find terminal block and connect wire as below.
23 24 25 26 27 L N L1 L2 L3
THERMOSTAT (Default : 230 V AC) (L) (N) (C) (H) (D)
Thermostat
! WARNING
Mechanical type thermostat. Do not connect wire (N) as mechanical type thermostat does not require electric power supply.
! CAUTION
Do not connect external electric loads. Wire (L) and (N) should be used only for operation electric type thermostat. Never connect external electric loads such as valves, fan coil units, etc. If connected, Main PCB (Heater) can be seriously damaged.
(L) : Live signal from PCB to thermostat (N) : Neutral signal from PCB to thermostat (C) : Cooling signal from thermostat to PCB (H) : Heating signal from thermostat to PCB (D) : DHW Heating signal from thermostat to PCB

ENGLISH

70 ACCESSORIES INSTALLATION

Final check
· DIP switch setting : Set DIP switch No. 8 to ON’. Otherwise, the unit can not recognize the thermostat. · Remote Controller : –Thermostat’ text is displayed on the remote controller. – Button input is prohibited. – In case of Heating / Cooling / DHW Heating thermostat, select `Heat&Cool / DHW’ as the Thermostat Control Type in the remote controller installer settings.

2nd Circuit
The 2nd circuit is generally used to control the temperature of 2 rooms differently. To use the 2nd Circuit, you need to prepare a separate Mix Kit. The mix kit must be installed in the main zone. – Main Zone : zone where the water temperature is lowest when heating. – Add. Zone : The other zone

– For 3 Series [Install Guide 2nd Circuit Heating]

Main Zone Add. Zone
Floor (35 °C)
Convector (FCU, 45 °C)
Radiator (45 °C) Radiator (55 °C)

Floor (35 °C)

Convector (FCU, 45 °C)
X

Radiator (45 °C)
X

Radiator (55 °C)
X X

[Install Guide 2nd Circuit Cooling]

Main Zone Add. Zone
Floor (18 °C)

Floor (18 °C)

Radiator(18 °C)

Convector (FCU, 5 °C)

X

Radiator(18 °C) X

Convector (FCU, 5 °C)
X
X

C To use a floor combination during cooling operation, the flow through the floor of the flow must be blocked by the 2 way valve.

ACCESSORIES INSTALLATION 71

ENGLISH

– For 4 Series [Install Guide 2nd Circuit Heating]

Circuit 2 Circuit 1
Floor (35 °C)
Convector (FCU, 45 °C)
Radiator (45 °C) Radiator (55 °C)

Floor (35°C)

Convector (FCU, 45 °C)

Radiator (45 °C)

Radiator (55 °C)

[Install Guide 2nd Circuit Cooling]

Circuit 2 Circuit 1
Floor (18 °C) Convector (FCU, 5 °C)

Floor (18 °C)

Convector (FCU, 5 °C)

C To use a floor combination during cooling operation, the flow through the floor of the flow must be blocked by the 2 way valve.

NOTE
Circuit 1 = Direct circuit : Zone where the water temperature is lowest when heating Circuit 2 = Mixing circuit : The other zone

ENGLISH

72 ACCESSORIES INSTALLATION

How to Wire 2nd Circuit
– For 3 Series Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below

13 14 15 16 17 L N L1 L2 N

MIX PUMP

MIXING VALVE

(L) (N) (L1) (L2) (N1)

(L) : Live signal from PCB to mix pump
(N) : Neutral signal from PCB to mix pump
(L1) : Live signal (for Normal* Closed type) from PCB to mixing valve
(L2) : Live signal (for Normal Open type) from PCB to mixing valve
(N1) : Neutral signal from PCB to mixing valve

MIX PUMP

MIXING VALVE

*Closed = NOT Mixed

C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

Step 3. Insert the temperature sensor to ‘CN_MIX_OUT’ (Brown) of the main PCB as shown below. The sensor should be mounted correctly to outlet pipe of mix kit water pump as shown below.

CN_MIX_OUT

Indoor PCB

Buffer Tank

[Room A] Main zone (Low Temp.)

Mix

2nd circuit temp. sensor

Mix Kit

Floor heating loop Floor heating loop

[Room B] Additional zone (High Temp.)

Radiator

Radiator

ENGLISH

ACCESSORIES INSTALLATION 73

How to Wire Mix Pump, Mixing Valve and Thermistor for 2nd Circuit

– For 4 Series
Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below

7 8 9 10 11 L N L1 L2 N

MIX PUMP

MIXING VALVE

(L) (N) (L1) (L2) (N1)

MIX PUMP

MIXING VALVE

(L) : Live signal from PCB to mix pump (N) : Neutral signal from PCB to mix pump (L1) : Live signal (for Normal Closed type)
from PCB to mixing valve (L2) : Live signal (for Normal Open type)
from PCB to mixing valve (N1) : Neutral signal from PCB to mixing valve
Closed = NOT Mixed

Step3. Insert the temperature sensor to ‘CN_MIX_OUT’ (Brown) of the main PCB as shown below. The sensor should be mounted correctly to outlet pipe of mix kit water pump as shown below.

CN_MIX_OUT

Indoor PCB

[Circuit 2] Mixing Circuit

Mix

2nd circuit temp. sensor

Buffer Tank

Hydronic separator

Mix Kit

Floor

Floor

heating loop heating loop

[Circuit 1] Direct Circuit

Radiator

Radiator

NOTE
Temperature sensor specification: Type : Thermistor,NTC Resistance at 25 °C : 5 k Minimum operating temperature range : -30 °C~100 °C

ENGLISH

74 ACCESSORIES INSTALLATION [Thermistor for 2nd circuit]

Sensor

Sensor Holder

Sensor Connector

Follow below procedures step 1 ~ step 4.
Step 1. Install sensor connector to outlet pipe of mix kit water pump. (Welding must be performed to connect the sensor connector to the pipe. )
Step 2. Check if the power of the unit is turned off.
Step 3. Fasten the sensor connector to the sensor holder as shown in the figure below.
Step 4. Insert harness into PCB(CN_TH4) fully and fix the thermal sensor into tube connector as shown below.

ENGLISH

ACCESSORIES INSTALLATION 75
3rd Party Boiler
The product can be used by connecting an Auxiliary boiler. You can control the boiler automatically and manually by comparing the outside temperature and the set temperature.
How to install 3rd party boiler
Follow below procedures step 1 ~ step 3. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and Distinguish terminal block in Indoor PCB. Step 3. Connect Power cable to terminal block (TB_BOILER) fully.

– For 3 Series

TB_BOILER

3rd party boiler (Voltage free)
– For 4 Series

Indoor PCB
EXT_BOILER

Indoor PCB

3rd party boiler (Voltage free)

ENGLISH

76 ACCESSORIES INSTALLATION

3rd Party Controller
The product can also be linked to 3rd party controller. You can connect external controllers using Modbus protocol except for LG controller. If 3rd party controller is used, LG controller is not applied to AWHP simultaneously.

How to install 3rd party controller
Follow below procedures step 1 ~ step 4.
Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish control box(Indoor) of
the unit. Step 3. Check if the harness(White) is inserted fully to the indoor unit
PCB (CN_COM). Step 4. Connect the 3rd party controller to terminal block 2(11/12)
completely. (including Meter interface module)

11

12

1(L) 2(N)

3rd PARTY CONTROLLER
(DC 5 V)

1(L) 2(N)

3rd PARTY CONTROOLER
or METER INTERFACE(LG)

– For 3 Series

CN_COM

– For 4 Series

Indoor PCB

CN_MODBUS

Indoor PCB

ENGLISH

ACCESSORIES INSTALLATION 77
Meter Interface
This product can be used by connecting the meter interface module supplied in the field. The meter interface module can communicate with the wired remote controller. The meter interface module lets you know the amount of power generated by the product.
How to install Meter Interface
[Parts of Meter interface]

Meter interface body
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and Distinguish control box(Indoor) of the unit. Step 3. Check if the harness(White) is inserted fully to the indoor unit PCB (CN_COM). Step 4. Connect the external pump to terminal block 2(11/12).

– For 3 Series

CN_COM

11

12 11 : Black

A

B 12 : White

3rd PARTY CONTROLLER

Indoor PCB

– For 4 Series

CN_MODBUS

Meter interface

Indoor PCB

ENGLISH

78 ACCESSORIES INSTALLATION
Central Controller
The product can communicate and control through the central controller. The following functions can be controlled in the central control linked state (Operation/Stop, Desired temperature, Hot water operation / stop, Warm water temperature, Full lock, Etc)
How to Install Central Controller
To use central controller, you need to establish an environment for mutual communication between central controller and the THERMA V and register the corresponding devices through the functions of central controller. To use central controller, it shall be installed in the following order. Step 1. Installation environment inspection and device address setting
Before installing central controller, check the network for any interfacing devices and assign non overlapping addresses to the connected devices. Step 2. PI485 setting Install PI485 and set the DIP switch accordingly. Step 3. Connections Connect PI485 and central controller through RS-485 cable. Step 4. Access and Device Registration Log in to central controller and register device with address set. Consult a qualified engineer/ technician for the installation of central controller. If you have any installation queries, contact the LG service center or LG Electronics.
How to Installation PI485 Fix the PI485 PCB as shown in below images. For detailed installation method refer to PI485 Installation Manual
UN60A (9, 12, 14, 16 kW)

UN36A (5, 7, 9 kW)

– For detailed installation instructions, refer to the manual included in the accessories. – The shape may differ depending on the model.

ENGLISH

ACCESSORIES INSTALLATION 79
Remote Controller
Installation of Remote Controller
· After fixing the remote controller installation plate on the desired location, fix it firmly with the provided screws. – If the installation plate is not flat on the surface, it may result in the controller being twisted and cause a defect. – If there is a mounting box, install the remote controller installation plate using the fixings holes which suit, as in the below diagrams. – Do not leave a gap with the wall or product loose after the installation.

· The wired remote controller cable can be installed in 3 directions. Install to the suitable direction according to the installation environment.
– Installation direction: Rear entry, top side, right side
– When you install the remote controller cable at the top side and right side, remove the remote controller cable guide hole before the installation. Use a long nose pliers to remove the guide hole.
· After removing the hole, trim the cut surface neatly.

Top side guide groove
Right side guide groove

Top side guide groove

Rear cable entry

Right side guide groove

· After fixing the remote controller top side on the installation plate attached to the wall as in the following figure, press the bottom side to combine with the installation plate.
– Do not leave a gap in the top, bottom, left, and right side of the remote controller and the installation plate after combining them.
– Before combining with the installation plate, arrange the cables to avoid interference with the circuit parts.

Wall

Wall

ENGLISH

80 ACCESSORIES INSTALLATION
· When you remove the remote controller from the installation plate, insert a small flat head screwdriver into the bottom side separation hole and turn clockwise to separate the remote controller. – There are 2 separation holes at the bottom part. Slowly separate one by one. – Be careful not to damage the internal parts during the removal.

Wall Side

· Use the connection cables to connect the indoor unit with the remote controller.

DC 12 V Red

Signal Yellow

GND Black

OK

Please check if connector is normally connected. Connecting cable

Unit side

· For the following cases, separately purchase and use the cables suitable for the situation.
– Do not install the cable over 50 m. (It may cause communication issues.)
– If the distance between the wired remote controller and the unit is 10 m or more : 10 m extension cable (model name: PZCWRC1)

NOTE
During the wired remote controller installation, do not bury it in the wall. (It may cause temperature sensor failure.) Do not install the cable over 50 m. (It may cause communication defect.) When you install the extension cable, carefully check the direction of the connectors on the remote controller side and the product side before the installation. Specification of extension cable: AWG 24, 3 conductor or above.

CN_REMO

Indoor PCB

ENGLISH

Wired controller

ACCESSORIES INSTALLATION 81

Extension Cable

Indoor MAIN PCB
Indoor terminal block RED(12V) YL(SIGNAL) BR(GND)

Check whether the connector is connected correctly.

Check whether the connector is connected correctly.

Cable connection method to use external device

  1. Wired remote controller-cable connection method. – In the wired remote controller, connect the part marked in the following figure (J02C, DOPort) to the cable. – According to the installation environment, there are 3 directions (Rear entry, top side, and right side) for the installation.
  2. Cable extension connection method – Among the cables connected to the wired remote controller, cut the remaining connectors on the other side, and then extend and connect the cables – Extension cable specification: 24~26 AWG.

! CAUTION
For the External device connection, use the cable insulated with sheath for the extension connection. Before combining with the installation plate, arrange the cables to avoid interference with the internal parts.

RMC DO-Port
2 3

30 cm
(GND_Black) (DC 12 V_Red)
Remote controller product composition

· Output specification – Voltage : DC 11~12 V – Current : 5 mA
Field connection

ENGLISH

82 ACCESSORIES INSTALLATION
DHW Tank
To establish DHW circuit, 3way valve and DHW tank kit is required. If solar thermal system is pre-installed at the installation field, solar thermal kit is required to interface solar thermal system ­ to ­ DHW tank ­ to ­
Installation condition
Installing DHW water tank requires following considerations : · DHW water tank should be located at the flat place. · Water quality should be complied with EN 98/83 EC directives. · As this water tank is DHW water tank (indirect heat exchange), do not use anti water-freezing
treatment like ethylene grycol. · It is highly recommend to wash out inside of the DHW water tank after installation. It ensures
generating clean hot water. · Near the DHW water tank there should be water supply and water drain to easy access and
maintenance. · Set the maximum value of the temperature control device of DHW tank.

Water Tank Sensor

Water Out

Water In

DHW Water Tank

General Information
supports following 3way valve.

Type

Power

SPDT1) 3-wire 230 V AC

Operating Mode
Selecting Flow A2) between Flow A and Flow B
Selecting Flow B3) between Flow A and Flow B

Supported Yes Yes

1. SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow A), Live 2 (for selecting Flow B), and Neutral (for common).
2. Flow A means water flow from the unit to under floor water circuit.
3. Flow B means water flow from the unit to DHW tank.

ENGLISH

ACCESSORIES INSTALLATION 83

Installing recirculation pump

– For 3 Series

When

is used with DHW tank, it is STRONGLY recommended to install recirculation

pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water

temperature inside DHW tank

– The recirculation pump should be operated when DHW demand is not required. Therefore, external time scheduler to determine when the recirculation pump should turn on and turn off is required.

– The operating duration time of the recirculation pump is calculated as follow : Duration time [minute] = k x V x R

k : 1.2 ~ 1.5 is recommended. (If distance between pump and tank is far, then choose high number)

V : Volume of DHW water tank [liter]

R : Water flow rate of pump [liter per minute], which is determined by pump performance curve

– The pump operating start time should be prior to the DHW water demand.

Water Tank Sensor

Hot water supply

Recirculation Pump

Shower (End of Hot water supply)

Water Out Water In

Check Valve

DHW

City water

Water Tank

External Time Scheduler

C Water In / Water Out installation scene may vary depending on the model.

ENGLISH

84 ACCESSORIES INSTALLATION

Installing recirculation pump

– For 4 Series

When

is used with DHW tank, it is STRONGLY recommended to install recirculation

pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water

temperature inside DHW tank

– The recirculation pump should be operated when DHW demand is not required. Therefore, external time scheduler to determine when the recirculation pump should turn on and turn off is required.

– The operating duration time of the recirculation pump is calculated as follow : Duration time [minute] = k x V x R

k : 1.2 ~ 1.5 is recommended. (If distance between pump and tank is far, then choose high number)

V : Volume of DHW tank [liter]

R : Water flow rate of pump [liter per minute], which is determined by pump performance curve.

– The pump operating start time should be prior to the DHW demand.

Hot water supply
Water Tank Sensor

Recirculation Pump

Shower (End of Hot water supply)

Water Out Water In

Check Valve

DHW

City water

Water Tank

Remote Controller

C Water In / Water Out installation scene may vary depending on the model.

NOTE
· For more information about recirculaton pump, Please refer chapter 8 and chapter 9 of installation manual and owners manual.

How to wire recirculation pump
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish
control box(Indoor) of the unit. Step 3. Check if the harness(Violet) is inserted fully to
the indoor unit PCB (CN_PUMP_A15). Step 4. Connect the DHW recirculation pump to
terminal block 1(3/4).

Indoor PCB

3

4

L

N

WATER PUMP(C)

Recirculation Pump AC 230 V

CN_PUMP_A15

ENGLISH

ACCESSORIES INSTALLATION 85

How to Wire Booster Heater
Step 1. Uncover heater cover of the DHW tank. It is located side of the tank. Step 2. Find terminal block and connect wires as below. Wires are field- supplied item. (L) : Live signal from PCB to Heater. (N) : Neutral signal from PCB to Heater.
! WARNING
Wire specification · Cross-sectional area of the wire should be 6 mm2.

Adjusting thermostat temperature
– To guarantee proper operation, it is recommended to set temperature of thermostat to maximum temperature (symbol at the picture).
– 1Ø Backup Heater Model and 3Ø Backup Heater Model are set by same method as below.

For 4 Series

1

2

L

N

WATER TANK HEATER

(L)

(N)

A

1(L) 2(N)
TO ELB FOR DHW TANK E/HEATER

ENGLISH

86 ACCESSORIES INSTALLATION
How to Wire DHW Tank Heater
Step 1. Uncover heater cover of the DHW tank. It is located side of the tank. Step 2. Find terminal block and connect wires as below. Wires are field- supplied item. (L) : Live signal from PCB to Heater (N) : Neutral signal from PCB to Heater
! WARNING
Wire specification · Cross-sectional area of the wire should be 6 mm2.
Adjusting thermostat temperature · To guarantee proper operation, it is recommended to set temperature of thermostat to
maximum temperature (symbol at the picture). · 1Ø Electric Heater Model and 3Ø Electric Heater Model are set by same method as below.
LN WATER TANK HEATER (L) (N)
A

ENGLISH

ACCESSORIES INSTALLATION 87

DHW Tank Kit
This product can be used by connecting the DHW tank kit in the field. It can be utilized hot water heated by booster heater in DHW tank.
How to install DHW tank kit
[Parts of DHW Tank Kit] 12 3 4 5 6

Tank kit body

Sensor

Multi harness

Temperature sensor for DHW tank is used to control hot water temperature of DHW tank. If sensor will be defective, you can purchase it separately.(Model name : PHRSTA0)
Follow below procedures step 1 ~ step 4.
Step 1. Uncover DHW tank kit and locate it on the wall.
Step 2. Connect Harness(Violet) of Main PCB assembly(TB1(6/7)) to ‘CN_B_Heat_A` of the Main PCB like following fig. 1.
Step 3. Insert DHW tank sensor to ‘CN_TH4′ (Red) of the Main PCB refer as below.
Step 4. Connect power supply to the DHW tank kit as shown fig. 1.
C The sensor should be mounted correctly to the sensor hole of DHW water tank like below fig. 2.

– For 3 Series

CN_TH4

DHW Tank

Signal

Sensor CN_B_HEAT_A

Indoor PCB

Multi harness
67
Fig. 1

12

34 5 6

Power supply 1Ø 220-240 V 50 Hz

67 LN DHW TANK HEATER
Heater power

Fig. 3

Insert sensor until the cable tie as shown below.

DHW Tank Temperature Sensor

Sensor holder

Inside DHW tank

DHW tank outer wall

Fig. 2

C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

ENGLISH

88 ACCESSORIES INSTALLATION

– For 4 Series

CN_TH4

Indoor PCB Fig. 1

CN_TANK_HEATER

1

2

L

N

DHW TANK HEATER

1(L) 2(N)
TO ELB FOR DHW TANK E/HEATER

ENGLISH

ACCESSORIES INSTALLATION 89
Solar Thermal Kit
This product can be used by connecting the solar thermal kit in the field. It can be utilized hot water heated by solar thermal system. End-user must be LG AWHP solar thermal kit.
How to Install Solar Thermal Kit
[Parts of Solar Thermal Kit]

Holder sensor

Tube Connector

Solar Thermal Sensor 12 m(1 EA)

Follow below procedures step 1 ~ step 4.
Step 1. Install tube connector(it is necessary to reduce or extend diameter of pipe.) the pipe and solar thermal kit.
Step 2. Check if the power of the unit is turned off.
Step 3. Disassemble front panels and distinguish control box(Indoor) of the unit.
Step 4. Insert harness into PCB(CN_TH4) fully and fix the thermal sensor into tube connector as shown below.
C If the DHW tank sensor is connected, disconnect the sensor from PCB first.

– For 3 Series

Solar thermal sensor

CN_TH4
– For 4 Series

Indoor PCB

Water Pipe
Tube connector

Indoor PCB

Solar
Solar thermal sensor
Water Pipe
Tube connector

90 ACCESSORIES INSTALLATION

ENGLISH

Solar Thermal Sensor
(less than 12 m) 3way valve (Field Supply)

Water Tank Sensor (less than 12 m)
Water In

Tube connecter
Pump (Field Supply)

Water In

Solar Thermal

System Water Out (Field Supply)

Water Out

Water Tank

C Water In / Water Out installation scene may vary depending on the model.

– Insert sensor until the cable tie as shown below.

Solar Collector (Field Supply)

! CAUTION
Sensor mounting Insert sensor into sensor socket and bolt it tightly.

ENGLISH

ACCESSORIES INSTALLATION 91
Dry Contact
Dry Contact is a solution for automatic control of HVAC system at the owner’s best. In simple words, it’s a switch which can be used to turn the unit On/Off after getting the signal from external sources.
How to install dry contact
[Parts of Dry contact]

Dry Contact body Cable(for connecting with IDU)
Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish terminal block in Indoor PCB. Step 3. Connect cable to the unit PCB(CN_CC) fully. Step 4. Then, Insert harness to the dry contact PCB(CN_INDOOR) firmly as shown below. – For 3 Series
CN_CC

Dry contact

CN_INDOOR
– For 4 Series

Indoor PCB
CN_CC

NOTE

Indoor PCB

Dry contact CN_INDOOR

· For more information about installing Dry Contact, Please refer installation manual provided with Dry Contact.
· For system set-up, please read chapter 8 (Accessory Installation) and chapter 9 (DIP Switch setting).

ENGLISH

92 ACCESSORIES INSTALLATION [Setting of Contact Signal Input] · For input contact closure only(No power input)
Notes
Do not input the voltage signal in “NON VOLT” setting mode. Otherwise it will cause serious damage. · For input contact voltage : DC 12 V, 24 V~
Connect separate External voltage of DC 12
V, 24 V~

COMM Themal Operation COMM FAN HEAT COOL LOW MIDDLE HIGH

COMM Themal Operation COMM FAN HEAT COOL LOW MIDDLE HIGH

Thermostat LG does not supply this section (Field supply)
Thermostat LG does not supply this section (Field supply)

ENGLISH

ACCESSORIES INSTALLATION 93
External Controller – Setting up programmable digital input operation
If you require to operate control depending on external digital input(ON/OFF), connect cable to indoor PCB(CN_EXT). Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish control box(Indoor) of the unit Step 3. Connect the external controller to PCB(CN_EXT) completely. Step 4. Connect the cable and field installation part.
– For 3 Series

CN_EXT
– For 4 Series

Indoor PCB

Adapter Cable

CN_EXT

Indoor PCB

Installation example #1

Indoor Unit PCB

0.5 m

Max 10 m

CN_EXT

SW

Supplied Part Field Installation Part

· SW : Single pole switch – Select a part with contacts for extremely low amperage – DC 5 V ~ 12 V is used at the contact point – Switch load is approximately 0.5 ~ 1 mA
· Control cable – Cable size : 22 to 26 AWG – Don’t extend the cable more than 10 meters

Adapter Cable

Installation example #2

Indoor Unit PCB

0.5 m Max 10 m

CN_EXT

Supplied Part

· X : Relay(a point of contact, fixed DC 0.5 ~ 1 mA)

· SW : Distance ON/OFF switch

· Control cable(Indoor unit to Relay Circuit)

– Cable size : 22 to 26 AWG

Relay Circuit – Don’t extend the cable more than 10 meters

XX

Power

SW

supply

of relay

Field Installation Part

Determining the purpose of CN_EXT Setting value: 0 ~ 5 step Indoor CN-EXT port setting – 0: default – 1: Simple operation on / off – 2: Dry contact (simple contact)

– 3: Emergency stop only for indoor unit – 4: Reattachment / absence – 5: Emergency stop of all indoor units (It can
be set only when indoor unit has emergency stop function)

ENGLISH

94 ACCESSORIES INSTALLATION
Remote Temperature Sensor
Remote temperature sensor can be installed any place a user wants to detect the temperature.
Installation condition
Role and constraint while installation of remote air temperature sensor is very similar to that of thermostat. · Distance between the unit and the remote air temperature sensor should be less than 15 m
due to length of the connection cable of remote air temperature sensor. · For other constraints, please refer to previous page where constraints about thermostat is
described

Direct Sun ray contact area
yes
no
no
5ft (1.5m)
no

Connection cable
(less than 15 m) no

Direct Sun ray contact area
yes
no
no 5 ft (1.5 m)

Thermostat

Remote Air Temperature Sensor

ENGLISH

ACCESSORIES INSTALLATION 95
How to Install Remote Temperature Sensor
[Parts of Remote Temperature Sensor]

Sensor

Screw(to fix remote sensor)

Follow below procedures step 1 ~ step 5.
Step 1. Decide where the remote temperature sensor is Installed. Then, Determine the location and height of the fixing screws in fig. 1 (Interval between the screws : 60 mm)
Step 2. Check if the power of the unit is turned off.
Step 3. Disassemble front panels and distinguish control box(Indoor) of the unit.
Step 4. Insert temperature sensor into PCB(CN_ROOM) and fix the sensor firmly in fig. 2.
Step 5. The Connection wire does not matter if you change the color of the wire because of nonpolar.

– For 3 Series

CN_ROOM

BK
Fixing screws 60 mm

[Fig. 1]

Indoor PCB [Fig. 2]

WH Sensor

– For 4 Series Fixing screws 60 mm
[Fig. 1]

CN_ROOM BK

Indoor PCB [Fig. 2]

WH Sensor

ENGLISH

96 ACCESSORIES INSTALLATION
Step 6. Integrate the remote temperature sensor with the screws as the order of arrows.

Fixing the Remote Sensor 1 2

! CAUTION
· Choose the place where the average temperature can be measured for the unit operates. · Avoid direct sunlight. · Choose the place where the cooling/heating devices do not affect the remote sensor. · Choose the place where the outlet of the cooling fan do not affect the remote sensor. · Choose the place where the remote sensor isn’t affected when door is open.
NOTE
· For more information about installing Remote Temperature Sensor, Please refer installation manual provided with Remote Temperature Sensor.
· For system set-up, please read chapter 8.(Especially function code No.3)

ENGLISH

ACCESSORIES INSTALLATION 97

Solar pump
Solar pump can be required to energize water flow when solar thermal system is installed.

How to install solar pump

Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish control box(Indoor) of the unit. Step 3. Check if the harness(Black) is inserted fully to the indoor unit PCB (CN_W_PUMP_B). Step 4. Connect the external pump to terminal block 1(4/5).

C It is possible to un-use solar pump depending on installation environment.

– For 3 Series

Indoor PCB

WATER PUMP (B)

4

5

BR BL

L

N

Solar pump AC 230 V

– For 4 Series

CN_W_PUMP_B
Indoor PCB

5

6

L

N

WATER PUMP (B)

Solar pump AC 230 V

CN_PUMP_A4
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

ENGLISH

98 ACCESSORIES INSTALLATION

External pump
External pump can be required when the room to take floor heating is too large or not wellinsulated.(potential free) Also, External pump is installed with buffer tank to retain sufficient capacity.

How to install external pump
Follow below procedures step 1 ~ step 3. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish terminal block in Indoor PCB. Step 3. Connect signal cable to terminal block (TB_W_PUMP_C) fully.

– For 3 Series

Indoor PCB

Power

External pump (Voltage free)

TB_W_PUMP_C

– For 4 Series

Indoor PCB

PUMP A2

External pump (Voltage free)

ENGLISH

ACCESSORIES INSTALLATION 99
Wi-fi Modem
Wi-fi modem enables remote system operation from smartphone. Available functions include selection of on/off, operation mode, DHW heating, temperature setup and weekly scheduling etc.
How to install Wi-fi Modem
[Parts of Wi-fi modem]

Wi-fi modem body

USB Cable

Extension Cable

Follow below procedures step 1 ~ step 5. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish control box(Indoor) of the unit. Step 3. Connect the USB cable to the indoor unit PCB (CN_WF ; Blue) until it clicks into place. Step 4. Connect the Wi-Fi modem to the USB cable fully. Step 5. Refer to the image below to install the Wi-Fi modem in the marked position.

– For 3 Series
CN_WF

Indoor PCB

– For 4 Series
CN_WF

USB Cable

Indoor PCB USB Cable
In case of using the extension wire (PWYREW000), fasten the core of extension wire to clamp of the indoor control box.

100 ACCESSORIES INSTALLATION

ENGLISH

Energy State
This product provides energy states that enable customers to use as much as possible of their own renewable energy. It can shift setpoints depending on input signal from Energy Storage System (ESS) or from any other third-party device using Modbus RTU or Digital 230V inputs.

Available Energy States
There are 8 energy states available. 4 fixed and 4 customizable – each with the possibility to enhance selfconsumption of renewable energy.

Energy state

Command

Battery State of charge

Operation (standard setting)

Heating

Cooling

Domestic Hot Water

Setting Range Setting Range Setting Range

1

Operation Off (Utility lock)

Low

Forced internal operation off

Fixed

Forced internal operation off

Fixed

Forced internal operation off

Fixed

2

Normal Operation

Maintain Normal operation
status status

Fixed

Maintain operation status

Fixed

Maintain operation status

Fixed

3

Operation On Recommend

High

Increase 2 °C from target temperature

Fixed

Maintain operation Status

Fixed

Increase 5 °C from target temperature

Fixed

4

Operation On Recommend

Very High

Maintain operation
status

Fixed

Maintain operation status

Fixed

DHW Target 80 °C

Fixed

5

Operation On Commend

Very High

Increase from target
temperature

0/+30 (Default : +5)

Decrease from target
temperature

0/-30 (Default : -5)

Increase from target
temperature

0/+50 (Default : +30)

6

Operation On Recommend

High

Increase from target
temperature

0/+30 (Default : +2)

Decrease from target
temperature

0/-30 (Default : -2)

Increase from target
temperature

0/+50 (Default : +10)

7

Operation Save

Low

Decrease from target
temperature

0/-30 (Default : -2)

Increase from target
temperature

0/+30 (Default : +2)

Decrease from Target
Temperature

0/-50 (Default : 0)

8

Operation Super Save

Very Low

Decrease from target
temperature

0/-30 (Default : -5)

Increase from target
temperature

0/+30 (Default : +5)

Decrease from Target
Temperature

0/-50 (Default : 0)

ENGLISH

ACCESSORIES INSTALLATION 101
Digital Input for energy saving (ESS, Smart Grid)
This product provides two digital inputs (TB_SG1 / TB_SG2) that can be used to switch between energy states when not using Modbus RTU (CN-COM).
Available Energy States
There are 8 energy states available in total. Four different states can be triggered using the 230V-inputs ­ by default Energy states 1-4. With the digital input assignment in the menue `Energy state/Digital input assignment of the control pane, different Energy states can be selected for Signals 0:1 and 1:1. 0:0 is always linked with ES2 (Normal operation) and 1:0 is always linked with ES1 (Operation off/Utility lock).
How to set Digital input signal
Follow below procedures step 1 ~ step 3. Step 1. Check if the power of the unit is turned off. Step 2. Disassemble front panels and distinguish terminal block in Indoor PCB. Step 3. Connect signal cable to terminal block in PCB (TB_SG2, TB_SG1) fully as shown below.
Indoor PCB

TB_SG2

TB_SG1

Energy state depending on input signal (TB_SG1/TB_SG2)

TB_SG1 0 1 0 1

Input Signal

TB_SG2 0 0 1 1

Output state

Default

Range

ES2 fixed
ES1

ES3 ES3-ES8
ES4

102 ACCESSORIES INSTALLATION

ENGLISH

2Way Valve
2way valve is required to control water flow while cooling operation. Role of 2way valve is to cut off water flow into under floor loop in cooling mode when fan coil unit is equipped for cooling operation.

General Information
supports following 2way valve.

Type NO 2-wire 1)
NC 2-wire 2)

Power 230 V AC 230 V AC

Operating Mode Closing water flow Opening water flow Closing water flow Opening water flow

Supported Yes Yes

1. Normal Open type. When electric power is NOT supplied, the valve is open. (When electric power is supplied, the valve is closed.)
2. Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric power is supplied, the valve is open.)

How to Wire 2Way Valve
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below.

– For 3 Series
18 19 20 L1 L2 N 2WAY VALVE
(A) (NO) (NC) (N)

– For 4 Series
15 16 17 L1 L2 N 2WAY VALVE
(A) (NO) (NC) (N)

2way valve

2way valve

! CAUTION
Dew Condensation · Wrong wiring can yield dew condensation on the floor. If radiator is connected at the
under floor water loop, dew condensation can be occurred on the surface of the radiator.
! WARNING
Wiring · Normal Open type should be connected to wire (NO) and wire (N) for valve opening in
cooling mode. · Normal closed type should be connected to wire (NC) and wire (N) for valve closing in
cooling mode.

ENGLISH

ACCESSORIES INSTALLATION 103
(NO) : Live signal (for Normal Open type) from PCB to 2way valve (NC) : Live signal (for Normal Closed type) from PCB to 2way valve (N) : Neutral signal from PCB to 2way valve
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.
Final Check
· Flow direction : – Water should not flow into under floor loop in cooling mode. – To verify the flow direction, check temperature at the water inlet of the under floor loop. – If correctly wired, this temperatures should not be approached to 6 °C in cooling mode.

104 ACCESSORIES INSTALLATION

ENGLISH

3Way Valve(A)
3Way Valve(A) is required to operate DHW water tank. Role of 3way valve is flow switching between under floor heating loop and water tank heating loop. Plus, it is required to operate 3rd party boiler.

General Information
supports following 3way valve.

Type

Power

SPDT 3-wire1)

220-240 V~

Operating Mode
Selecting Flow A2) between Flow A and Flow B
Selecting Flow B3) between Flow A and Flow B

Supported Yes Yes

1. SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow A), Live 2 (for selecting Flow B), and Neutral (for common).
2. Flow A means water flow from the unit to under floor water circuit.’ 3. Flow B meanswater flow from the unit to DHW water tank.’

How to wire 3way valve(A)
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below.

– For 3 Series
3WAY VALVE (A)
8 9 10 L L1 N BR BK BL (W) (U) (N)

– For 4 Series
12 13 14 L L1 N 3WAY VALVE
(A)
(W) (U) (N)

3way valve

3way valve

! WARNING
· 3way valve should select water tank loop when electric power is supplied to wire (W) and wire (N).
· 3way valve should select under floor loop when electric power is supplied to wire (U) and wire (N).
(W) : Live signal (Water tank heating) from PCB to 3way valve (U) : Live signal (Under floor heating) from PCB to 3way valve (N) : Neutral signal from PCB to 3way valve
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

ENGLISH

ACCESSORIES INSTALLATION 105

3Way Valve(B)
3way valve(B) is required to operate Solar thermal system. Role of 3way valve is flow switching between open and close mode of the solar circuit.

General Information
supports following 3way valve.

Type

Power

SPDT 3-wire1)

220-240 V~

Operating Mode
Selecting Flow A2) between Flow A and Flow B
Selecting Flow B3) between Flow A and Flow B

Supported Yes Yes

1. SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow A), Live 2(for selecting Flow B), and Neutral (for common).
2. Flow B means heat source toward solar panel repeatedly’. (close mode of circuit) 3\. Flow A meansheat source flow from solar panel to DHW tank in solar circuit’. (open mode of circuit)

How to wire 3way valve(B)
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below.

– For 3 Series

– For 4 Series

3WAY VALVE (B)

12

3

BR WH BL

L L1 N

(W) (U) (N)

28 29 30 L L1 N
3WAY VALVE (B)
(W) (U) (N)

3way valve

3way valve

! WARNING
· 3way valve should select “close solar circuit” when electric power is supplied to wire (W) and wire (N).
· 3way valve should select “open solar circuit” when electric power is supplied to wire (U) and wire (N).
(W) : Live signal (close solar circuit) from PCB to 3way valve (U) : Live signal (open solar circuit) from PCB to 3way valve (N) : Neutral signal from PCB to 3way valve
C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

ENGLISH

106 ACCESSORIES INSTALLATION
Electric Heater
How to Pipe Electric Heater
Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater accessory. Step 2. Check the diameter of pre-installed pipes of unit. Step 3. If the diameter of pre-installed pipes is different from diameter of electric heater
accessory kit, it is necessary to reduce or expand pipe’s diameter. Step 4. Connect the pipes. The inlet pipe of electric heater accessory must be connected to
outlet of the unit.
! WARNING
Followings should be kept before installation · The unit should be stop before the piping work. · Never connect electric power while piping electric heater. · Before the piping working, water in the part(or to heating loop) installed with electric heater
should be drained. After working, water should be charged.
! CAUTION
· Electric Heater should be installed with enough space for installation and service. · Water pipes and connections should be cleaned using water. · Methods to prevent leakage in plumbing connections must be applied. · Heater must not be impacted. · Do not let dirty particle be dropped inside tank to avoid possibility of degrade. · After installation, make it sure that no leakage is appeared in the connection.

ENGLISH

Terminal Block Information
Symbols used below pictures are as follows : – L, L1, L2 : Live (220-240 V~) – N : Neutral (220-240 V~) – BR : Brown, WH : White, BL : Blue, BK : Black
< 3 kW >

ACCESSORIES INSTALLATION 107 < 6 kW >

Terminal Block 1

Terminal Block 2

Terminal Block 1

Terminal Block 2

108 ACCESSORIES INSTALLATION

ENGLISH

How to Wire Electric Heater
– For 3 Series
Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater accessory. Step 2. Find the terminal block and connect wires. Refer to the installation manual of the electric
heater. (Wires are field-supplied item.) Step 3. Connect terminal block ports unit and electric heater accessory.
– HAETER(A) : Signal to activate 1st step – HEATER(B) : Signal to activate 2nd step

(3 kW) Terminal Block 2 (In Backup Heater)

1(L)

2(N)

3

4

5

6

L

N

Power Supply 50 Hz 220-240 V~

A(A1)

A(A2)

ELECTRIC HEATER A (SIGNAL)

23

24

BR

BL

L

N

HEATER (A)

Terminal Block 3 (In Unit)

25

26

BR

BL

L

N

HEATER (B)

(6 kW)

Terminal Block 2 (In Backup Heater)

1(L)

2(N)

3

4

5

6

L

N

Power Supply 50 Hz 220-240 V~

A(A1)

A(A2)

B(A1)

B(A2)

ELECTRIC HEATER A ELECTRIC HEATER B

(SIGNAL)

(SIGNAL)

23

24

BR

BL

L

N

HEATER (A)

Terminal Block 3 (In Unit)

25

26

BR

BL

L

N

HEATER (B)

Step 4. Connect power supply cable to terminal block 2.
When Tightening the power cable on terminal block, Be careful to prevent a shock or injury. (AC 220-240 V signal)

Terminal Block 2 (In Backup Heater) 1(L) 2(N)
Power Supply 50 Hz 220-240 V~

· For more information about installing Electric Heater, Please refer installation Manual provided with Electric Heater

C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

ENGLISH

ACCESSORIES INSTALLATION 109
– For 4 Series Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater accessory. Step 2. Find the terminal block and connect wires. (Wires are field-supplied item.) Step 3. Connect terminal block ports of unit and electric heater accessory.
Indoor PCB

COMMON 3PHASE HEATER 1 HEATER 2

(1Ø 3 kW)

Terminal Block 2 (In Backup Heater)

1(L)

2(N)

3

4

L

N

Power Supply 50 Hz 220-240 V~

L

Voltage Free Contact

N

A(A1)

A(A2)

ELECTRIC HEATER A (SIGNAL)

L

L

N

COMMON 3PHASE

5

6

L HEATER 1 HEATER 2

(1Ø 6 kW)

Terminal Block 2 (In Backup Heater)

1(L)

2(N)

3

4

L

N

Power Supply 50 Hz 220-240 V~

A(A1)

A(A2)

ELECTRIC HEATER A (SIGNAL)

L(1)

L(1)

L(1)

Voltage

L(2)

Free Contact N

COMMON 3PHASE

5

6

B(A1)

B(A2)

ELECTRIC HEATER B (SIGNAL)

L(2)

L(2)

L(1)

L(2)

HEATER 1 HEATER 2

ENGLISH

110 ACCESSORIES INSTALLATION

(3Ø 6 kW) Terminal Block 2 (In Backup Heater)

1(L)

2(N)

3(T)

R

S

T

Power Supply 3Ø 380-415 V, 50 HZ

L

Voltage Free Contact

N

N COMMON

4

5

A(A1)

A(A2)

ELECTRIC HEATER A (SIGNAL)

L

L

L

3PHASE HEATER 1 HEATER 2

Step 4. Connect power supply cable to terminal block 2.

1(L) 2(N)

1(R) 2(S) 2(T)

Power Supply 50 Hz 220-240 V~

Power Supply 3Ø 380-415 V, 50 HZ

ENGLISH

ACCESSORIES INSTALLATION 111

How to Install 3way Valve for Backup Heater Bypass
Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below. When Tightening the connect wire on terminal block, Be careful to prevent a shock or injury. (230 VAC)

2WAY VALVE (B)
18 19 20 BR WH BL L L1 N
(NO) (NC) (N)

! WARNING
· When type of 2way valve is NO type, 3way valve should select Flow A(bypass). Electric power is supplied to wire(NO) and wire(N).
· When type of 2way valve is NC type, 3way valve should select Flow B(heating In Backup heater). Electric power is supplied to wire(NC) and wire(N).

3way valve

! CAUTION
· 3way valve should be connected together with 2way valve in terminal block.
· Keep the distance between 3way valve and Backup Heater more than 0.5m.
· To prevent reverse flow, It is important to use one way valve(check valve) to Backup Heater water outlet.

How to Connect Backup Heater Sensor to Unit
Follow below procedures Step 1 ­ Step 5. Find backup heater terminal block Kit(Fig. 1). Assemble the terminal block kit using screw on unit. Plug it to `E/Heater Out’ (White Connector) of CN_TH3 in the Main PCB (Unit) as shown Fig.2. Connect harness between the unit and the Backup Heater until it clicks into place.(Fig. 3). Use the cord clamper to fix the cable through low voltage hole.

E/HEATER OUT SENSOR (5 V DC)

7

8

31

32

A

B

Fig.3

E/HEATER OUT SENSOR (5 V DC)

Fig.1

Fig.2

C The terminal block connection number may differ depending on the model. Refer to the “Wiring Diagram” in the SVC Manual.

112 ACCESSORIES INSTALLATION

ENGLISH

Final check

No.

Check point

1

Connection of Water Inlet/Outlet

2 Hydraulic pressure

Description
– Check if the shut-off valves should be assembled with Water inlet

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals