TRANE Tracer VV550 Variable Air Volume Controller Instruction Manual
- June 9, 2024
- Trane
Table of Contents
- Introduction
- Automatic calibration
- Ventilation flexibility
- Flow tracking
- Ventilation flow control with tempering
- Local versus remote reheat flexibility
- Occupied and unoccupied operation
- Timed override
- Service pin from the Trane zone sensor
- Auto-commissioning sequence
- Manual test function
- Drive minimum and maximum from zone sensor
- Trane controller compatibility
- Interoperability
- Wiring diagram
- Wiring diagram for Tracer VV550/551 VAV controllers
- Network architecture
- Zone sensor options
- Dimensions and specifications
- Data lists
- Customer Support
- Documents / Resources
TRANE Tracer VV550 Variable Air Volume Controller
Introduction
Tracer VV550 and Tracer VV551 variable air volume (VAV) controllers provide single-duct digital control for VAV boxes. They support the following VAV control sequences:
- Space temperature control
- Flow tracking
- Ventilation flow control
The Tracer VV550 VAV controller is available factory-installed on Trane
VariTrane VAV boxes (Figure 1).
The Tracer VV551 VAV controller is available for field installation for a
variety of VAV applications (Figure 2).
Figure 1. Tracer VV550 controller
Figure 2. Tracer VV551 controller (uses same board as Tracer VV550)
Because the Tracer VV550 and Tracer VV551 VAV controllers use the same logic
controller, both offer the same wide range of application and control
flexibility. The Tracer VV551 VAV controller includes additional laborsaving
packaging features for field installed applications.
Tracer VV550/551 VAV controllers can operate as part of a Trane Integrated
Comfort™ system (ICS), as part of a building management system from another
manufacturer, or as a standalone device.
When it is part of a Trane ICS, a Tracer VV550/551 VAV controller enables the
building automation system (BAS) to perform functions such as scheduling,
trending, alarming, remote communications, and VAV air system (VAS)
coordination. The controller communicates with a Tracer Summit BAS over the
LonTalk® communications link. The controller can also communicate with other
building control systems that are compliant with the LonMark® Space Comfort
Controller (SCC) profile
Tracer VV550/551 VAV controllers can be configured using the Rover™ service
tool. They have the following inputs and outputs (Figure 3 on page 6):
Analog inputs:
- Space temperature (10 kΩ thermistor)
- Space setpoint (1 kΩ potentiometer)
- Primary/discharge air temperature (10 kΩ thermistor)
- Primary air flow Binary inputs:
- Occupancy or generic Binary outputs:
- Air valve close
- Air valve open
- Heat 1
- Heat 2
- Heat 3 or fan On/Off
™ ® The following are trademarks or registered trademarks of their respective companies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; Lon Mark, Lon Talk, and Lon Works of the Echelon Corporation.
Automatic calibration
Tracer VV550/551 VAV controllers automatically calibrate the flow transducer each time the box transitions to the unoccupied state. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which case the Tracer Summit building automation system can be used to initiate/schedule calibration.
Ventilation flexibility
Tracer VV550/551 VAV controllers can manage ventilation in the following ways:
- Fixed occupancy ventilation setpoint
- Scheduled (or otherwise calculated) ventilation setpoint
- Occupancy sensor to switch between normal and reduced ventilation
- CO2 sensor for demand-controlled ventilation
This flexibility gives owners and facility managers an option to simply select one of several effective solutions for managing ventilation.
Flow tracking
Tracer VV550/551 VAV controllers can easily be applied in flow tracking applications. In a flow tracking application, supply and exhaust boxes are paired together for the purpose of maintaining either positive or negative space static pressure. This feature allows the installer to quickly define the relationship of the supply and exhaust air boxes without the need for custom programming.
Ventilation flow control with tempering
Tracer VV550/551 VAV controllers have been designed for ventilation flow control applications. These applications pair a fresh air unit or self- contained unit with ventilation boxes to provide fresh (tempered) air to a floor/area. With this feature, the installer can quickly configure the flow control boxes and set up the system without the need for custom programming.
Local versus remote reheat flexibility
Tracer VV550/551 VAV controllers can be configured to have local and/or remote heat. This configuration flexibility enables the controllers to be applied across a broad range of VAV applications.
Occupied and unoccupied operation
The occupancy input on a Tracer VV550/ 551 VAV controller works with a motion (occupancy) sensor or a time clock to determine the occupancy mode. An occupancy request can also be communicated from a building automation system to determine the mode of the controller. Whether standalone or combined with a communicated occupancy request, a Tracer VV550/551 controller can be used with an occupancy sensor to save energy whenever a space is vacant.
Timed override
The timed override function for afterhours operation allows users to request unit operation by the touch of a button on the unit zone sensor. Additionally, users can press the CANCEL button at any time to place the unit back into unoccupied mode. This occupancy feature minimizes energy use by running the system only as scheduled or as demanded after hours.
Service pin from the Trane zone sensor
Certain installation scenarios require access to the SERVICE button on the controller. Access to this button typically requires a ladder or a lift. The Tracer VV550/551 VAV controller allows a technician to replicate pressing the SERVICE button by pressing the zone sensor ON button. This feature eliminates the need for accessing the SERVICE button, saving the technician time and energy.
Auto-commissioning sequence
Tracer VV550/551 VAV controllers provide an automatic commissioning sequence. With a discharge air temperature sensor installed, this feature exercises the air valve, fan, and heat in the box and records the discharge air temperature before and after the action. This allows the installer to easily checkout the operation of the box and commission by exception. The data from this test is retained in the controller for immediate reports or retrieval at a later date (for comparison purposes).
Manual test function
A Tracer VV550/551 VAV controller includes a manual test button, which enables a technician to easily exercise the outputs of the controller. On consecutive button presses, the controller steps through a predefined sequence that exercises all of the controller outputs.
Drive minimum and maximum from zone sensor
When applied with a Trane zone sensor module that includes a thumbwheel setpoint, a Tracer VAV VV550/551 controller can easily be overridden to minimum and maximum flow. By simply turning the thumbwheel to , the controller drives the air valve to the minimum cooling flow setpoint. Similarly, turning the thumbwheel to drives the air valve to the maximum cooling flow setpoint. This simple override feature is most useful during the checkout and balancing phases of a project.
Trane controller compatibility
Tracer VV550/551 VAV controllers are compatible with the latest generation of Trane control products. The controllers communicate over a LonTalk® communications link. This allows Tracer VV550/551 VAV controllers to exist on the same communication wire as other Trane controllers and to share data with them as required.
Interoperability
Tracer VV550/551 VAV controllers are designed with LonWorks® technology and are LonMark® certified. They follow the guidelines of the LonMark® Space Comfort Controller (SCC) profile. As such, the Tracer VV550/551 controllers enable control system integration flexibility.
Wiring diagram
See Figure 3 on page 6.
Wiring diagram for Tracer VV550/551 VAV controllers
Figure 3. Tracer VV550/551 wiring diagram
Network architecture
Tracer VV550/551 VAV controllers can operate on a Tracer Summit BAS, on a building management system from another manufacturer, on a peer-to-peer network, or as stand-alone devices. The Rover service tool can configure the controllers at any accessible location on the Lon Talk® communication link (Figure 4).
Figure 4. Network architecture with Tracer VV551 VAV controllers
Zone sensor options
Zone sensors are available in a variety of configurations. Table 1 describes
the features of the five Trane zone sensors that are available for use with
Tracer VV550/551 VAV controllers. The same five sensors are shown in Figure 5.
Contact your Trane sales office about other compatible zone sensors.
Table 1. Zone sensors for use with Tracer VV550/551
GCC order number
| Zone| Timed override buttons| LCD|
Comm jack
---|---|---|---|---
Setpoint thumbwheel
| Temperature sensor| ON|
CANCEL
4190 1087
| | x| | | | x
4190 1088| | x| x| x| |
x
4190 1090
| x| x| x| x| | x
4190 1094| x| x| | | |
x
4190 1120
| x| x| x| x| x|
x
Figure 5. Zone sensors for use with Tracer VV550/551
Dimensions and specifications
Power requirements
Supply: 18–32 Vac (24 Vac nominal) at 50/60 Hz
Operating environment
Temperature: 32 to 140°F (0 to 60°C)
Relative humidity: From 5 to 95% non-condensing
Storage environment
Temperature: -40 to 185°F (-40 to 85°C)
Relative humidity: From 5 to 95% non-condensing
Dimensions
(See Figure 6 on page 10.)
Board only
Height: 4.5 in. (11.4 cm)
Width: 5.5 in. (13.8 cm)
Depth: 2 in. (5.1 cm)
With enclosure (VV551)
Height: 7.5 in. (13.7 cm)
Width: 6.5 in. (16.7 cm)
Depth: 5.5 in. (14.0 cm)
Weight with enclosure (Tracer VV551)
With no actuator: 3.9 lb (1.77 kg)
With Belimo actuator: 5.0 lb (2.27 kg)
With Trane actuator: 5.2 lb (2.36 kg)
Analog inputs
Space temperature; thermistor:
10 kΩ@ 77°F (25°C) From 14 to 122°F (-10 to 50°C)
Space setpoint; potentiometer: 1 kΩ
From 50 to 90°F (-10 to 32.2°C) Primary/discharge air temperature; thermistor:
10 kΩ@ 77°F (25°C)
From -40 to 212°F (-40 to 100°C)
Primary air flow; pressure transducer: From 0 to 2 in. water (0 to 498 Pa)
Binary input
Occupancy or generic (dry contact)
Binary outputs
Air valve close: maximum output rating: 12 VA
Air valve open: maximum output rating: 12 VA
Heat stage 1: maximum output rating: 12 VA
Heat stage 2: maximum output rating: 12 VA
Heat stage 3/Fan on/off: maximum output rating: 12 VA
Agency listings/compliance
Tracer VV550:
UL 873 and CSA C22.2 No. 24-93: Temperature Indicating and Regulating
Equipment
Tracer VV551:
UL and C-UL 916, Energy management equipment
UL 94-5V (UL flammability rating for plenum use) FCC Part 15, Class A
Figure 6. Tracer VV551 dimensions
Data lists
Table 2 provides an input/output listing for Tracer VV550/551 VAV controllers.
Table 3 provides the configuration properties for the controller. The content
of the lists conforms to both the Lon Mark® SCC functional profile 8500 and
the Lon Mark® node object.
Table 2. Input/output listing
Input description | Input | SNVT type |
---|---|---|
Space temperature | nviSpaceTemp | SNVT_temp_p |
Setpoint | nviSetpoint | SNVT_temp_p |
Occupancy, schedule | nviOccSchedule | SNVT_tod_event |
Occupancy, manual command | nviOccManCmd | SNVT_occupancy |
Occupancy sensor | nviOccSensor | SNVT_occupancy |
Application mode | nviApplicMode | SNVT_hvac_mode |
Heat/cool mode input | nviHeatCool | SNVT_hvac_mode |
Fan speed command | nviFanSpeedCmd | SNVT_switch |
Auxiliary heat enable | nviAuxHeatEnable | SNVT_switch |
Valve override | nviValveOverride | SNVT_hvac_overid |
Flow override | nviFlowOverride | SNVT_hvac_overid |
Emergency override | nviEmergOverride | SNVT_hvac_emerg |
Source temperature | nviSourceTemp | SNVT_temp_p |
Space CO2 | nviSpaceCO2 | SNVT_ppm |
Clear alarms/ diagnostics | nviRequest* | SNVT_obj_request |
Air flow setpoint input | nviAirFlowSetpt | SNVT_flow |
Ventilation ratio limit | nviVentRatioLim | SNVT_temp_p |
Ventilation for the zone input | nviVentSetpt | SNVT_flow |
- Part of the node object.
Output description| Output| SNVT type
---|---|---
Space temperature| nvoSpaceTemp| SNVT_temp_p
Unit status, mode| nvoUnitStatus| SNVT_hvac_status
Effective setpoint| nvoEffectSetpt| SNVT_temp_p
Effective occupancy| nvoEffectOccup| SNVT_occupancy
Heat cool mode| nvoHeatCool| SNVT_hvac_mode
Setpoint| nvoSetpoint| SNVT_temp_p
Discharge air temperature| nvoDischAirTemp| SNVT_temp_p
Terminal load| nvoTerminalLoad| SNVT_lev_percent
Space CO2| nvoSpaceCO2| SNVT_ppm
Effective air flow setpoint| nvoEffectFlowSP| SNVT_flow
Air flow| nvoAirFlow| SNVT_flow
File table address| nvoFileDirectory| SNVT_address
Object status| nvoStatus| SNVT_obj_status
Alarm message| nvoAlarm Message| SNVT_str_asc - Part of the node object.
Table 3. Configuration properties
Configuration property description| Configuration property|
SNVT type| SCPT reference
---|---|---|---
Send heartbeat| nciSndHrtBt| SNVT_time_sec| SCPTmaxSendTime (49)
Occ temperature setpoints| nciSetpoints| SNVT_temp_setpt| SCPTsetPnts (60)
Minimum send time| nciMinOutTm| SNVT_time_sec| SCPTminSendTime (52)
Receive heartbeat| nciRecHrtBt| SNVT_time_sec| SCPTmaxRcvTime (48)
Location label| nciLocation| SNVT_str_asc| SCPT location (17)
Local bypass time| nciBypassTime| SNVT_time_min| SCPT bypass Time (34)
Manual override time| nciManualTime| SNVT_time_min| SCPT manOverTime (35)
Space CO2 limit| nciSpaceCO2Lim| SNVT_ppm| SCPTlimitCO2 (42)
Nominal air flow| nciNomFlow| SNVT_flow| SCPTnomAirFlow (57)
Air flow measurement gain| nciFlowGain| SNVT_multiplier| SCPTsensConstVAV (67)
Minimum air flow| nciMinFlow| SNVT_flow| SCPTminFlow (54)
Maximum air flow| nciMaxFlow| SNVT_flow| SCPTmaxFlow (51)
Minimum air flow for heat| nciMinFlowHeat| SNVT_flow| SCPTminFlowHeat (55)
Maximum air flow for heat| nciMaxFlowHeat| SNVT_flow| SCPTmaxFlowHeat (37)
Minimum flow for standby| nciMinFlowStdby| SNVT_flow| SCPTminFlowStby (56)
Firmware major version| nciDevMajVer| n/a| SCPTdevMajVer (165)
Firmware minor version| nciDevMinVer| n/a| SCPTdevMinVer (166)
Flow offset for tracking applications| nciFlowOffset| SNVT_flow_f|
SCPToffsetFlow (265)
Local heating minimum air flow| nciMinFlowUnitHt| SNVT_flow|
SCPTminFlowUnitHeat (270)
- Part of the node object.
Customer Support
Trane
A business of American Standard
Companieswww.trane.com
For more information, contact your local Trane office or e-mail us
atcomfort@trane.com
Trane has a policy of continuous product and product data improvement and
reserves the right to change design and specifications without notice.
firealarmresources.com
Documents / Resources
|
TRANE Tracer VV550 Variable Air Volume
Controller
[pdf] Instruction Manual
VV551, VV550, Tracer VV550 Variable Air Volume Controller, Tracer VV550,
Variable Air Volume Controller, Air Volume Controller, Controller
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>