Overview

DDSU666 Single-phase electronic type guide rail mounting electric energy meter is designed for power monitoring and energy metering demand of the electric power system, communication industry, and construction industry.It is a new generation of intelligent instruments integrated into Communication and Measurement, mainly used as the measurement and display of voltage and current, power, frequency, power factor and active power in electrical circuits. It will realize the data network of external devices by RS485 communication. It uses a standard DIN35mm rail mounting structure, a modular design. It has the advantages of small size, easy installation, and easy networking. It is used widely as energy monitoring and assessment in industrial and mining enterprises, hotels, schools, and large public buildings.

Technical Parameters

General Specifications

Voltage| 230Vac
Specified operating voltage range| 0.9Un~1.1Un
Extended operating voltage range| 0.8Un~1.15Un
Base current(Ib)| 5A
---|---
Current range| 5~80A
Voltage line power consumption| ≤1W/8VA
Frequency| 50 Hz~60Hz
AC voltage withstand| 2KV /5mA for 1 minute
Impulse voltage withstand| 4KV-1.2/50uS wavform
Max. Reading| 999999. 99kWh
Accuracy
Voltage| 1% of range maximum
Current| 1% of nominal
Frequency| 1% of mid-frequency
Power factor| 1% of Unity
Active power| 1% of range maximum
Reactive power| 2% of range maximum
---|---
Enviroment
Rated temperature| -25℃~+55℃
Limit temperature| -35℃~+70℃
Relative humidity(average annual)| ≤75%
Atmosphere| 86kPa~106kPa
Installation category| CAT III
Degree of pollution| Conform to RoHS
Communication
Communication| RS485 output for Modbus RTU
Baud rate| 9600
Mechanics
Din rail dimensions| 36x98x65(WxHxD)
Mounting| DIN rail 35mm
---|---
Sealing| IP 51 (indoor)

Unpacking

Item Number Description
A 1 Single phase meter
B 1 RS485 cable(standard length 15m)
C 1 User Manual

Dimension unit mm

Growatt-DDSU666-Single-Phase-Meter-fig- \(2\)

Installation

Wire diagram:

The Ingress Protection rate is IP51, So the meter must be installed in the door. The whole installation chart shows below:Growatt-DDSU666-Single-Phase-
Meter-fig- \(4\)

Before screwing the cable. Please open the cover of the meter:

The standard communication cable between the meter and inverter is 5m, if it is not enough, Customers can be extended through the network cable.

Note:

  1. Be careful with the wire of input and output of L/N and the range of input voltage or current, if the data is outranged, it may destroy the meter.
  2. Be careful with the input and output of the meter line, if the lines are wrong, the system will work in the wrong way.

Display

When the energy meter is in normal working condition (on load state), the positive pulse indicator should be flashed. If long time for no flashing or light for the indicator, please check whether the wiring mode of the energy meter is right or not.

Symbol Meaning
V The unit of the voltage, the display data of indicating LCD is voltage
A The unit of the current, the display data of indicating LCD is current
W The unit of the active power, the display data of indicating LCD is active

power
var| The unit of the reactive power, the display data of indicating LCD is reactive power
Hz| The unit of the frequency, the display data of indicating LCD is frequency
Symbol| Meaning
---|---
kWh| The unit of the active energy, the display data of indicating LCD is active energy
T| When communicating, T flashes

The display time of the measurement data is five seconds and the information sample for every page of the measured information of measurement data (if not consistent with the instrument panel, please take the object as the standard.)

Light time of the background: 1 min.

Content Instruction
This means the current display voltage is U, the unit is “V”, and the left

picture is U=220.0V.
Growatt-DDSU666-Single-Phase-Meter-fig- \(8\)| This means the current display current is I, the unit is “A”, and the left picture is I=5.000A.
| This means the current display is the active power P, the unit is “kW”, and the left picture is P=1.100kW.
| This means the current display is the power factor Ft, and the left picture is Ft=1.000.

Content

|

Instruction

---|---
| This means the current display is frequency F, and the left picture is F=50.00Hz.
| This means the current positive active energy EImp, the unit is “kWh”, the left picture is EImp=1.20kWh.
| This means the current negative active energy EExp, the unit is “kWh”, the left picture is EExp=1.00kWh.
| Means the current combination active energy total ComEp, the unit is “kWh”, the left picture is ComEp=2.20kWh.
| Means the current communication protocol is Modbus.

| Represents 8 data bits, no effect bit and one stop bit of the current communication protocol.

Means the current communication address
is 011.
*Growatt SPM-C default address is 003.

Content

|

Instruction

---|---
| Means the current communication baud rate is 9600.

Service and contact

Shenzhen Growatt New Energy Co., Ltd
4-13/F, Building A, Sino-German(Europe) Industrial Park, Hangcheng Ave, Baoan District, Shenzhen, China.