Honeywell FocusPRO 5000 Thermostat Installation Guide

June 9, 2024
Honeywell

Honeywell FocusPRO 5000 Thermostat

INSTALLER SYSTEM TEST

FocusPRO® 5000 Series

  1. To begin, press and hold the buttons until the display changes.
  2. Press to turn system on/off
  3. Press NEXT to advance to next test.
  4. Press DONE to terminate system test.
  5. Proceed to Installer System Tests on page 8.

FocusPRO® 6000 Series

  1. To begin, press and hold the buttons until the display changes.Honeywell-FocusPRO-5000-Thermostat-fig-10
  2. Press to turn system on/off
  3. Press NEXT to advance to next test.
  4. Press DONE to terminate system test.
  5. Proceed to Installer System Tests on page 8.

Test the system’s heating, emergency heat, cooling, and fan.
Available tests vary by thermostat and system type.

Table 2. Installer System Test

System Test Number| Test Type| System Status Number and Description
10| Heating system| 0| Heat and fan off
| | 1| First stage heat
| | | on (Fan turns on if
| | | Setup Function 1 is
| | | set to 1, 5, 9, or 10
| | | OR setup Function
| | | 3 is set to 1)
| | 2| Second stage heat
| | | on
| | 3| Third stage heat
| | | on
20| Emergency heating system| 0

1

2

| Heat and fan off Heat and fan on Second stage heat (Aux. heat) turns on
30| Cooling system| 0| Compressor and
| | | fan off
| | 1| Compressor and
| | | fan on
| | 2| Second stage
| | | compressor on
40| Fan system| 0| Off
| | 1| On

caution

  • EQUIPMENT DAMAGE HAZARD.
  • Compressor protection is bypassed during testing.
  • To prevent equipment damage, avoid cycling the compressor quickly.

INSTALLER SETUP

FocusPRO® 5000 Series

  1. To begin, press and hold the and FAN buttons until the display changes.Honeywell-FocusPRO-5000-Thermostat-fig-7
  2. Press to change settingsHoneywell-FocusPRO-5000-Thermostat-fig-9
  3. Press NEXT to advance to the next function.
  4. Press DONE to exit and save settings.
  5. Proceed to Installer Setup Functions on page 4.

FocusPRO® 6000 Series

  1. To begin, press and hold the and FAN buttons until the display changes.
  2. Press to change settings
  3. Press NEXT to advance to the next function.
  4. Press DONE to exit and save settings.
  5. Proceed to Installer Setup Functions on page 4.

Available option and default settings vary by thermostat.

Table 1. Installer Setup

Setup functions| Setting & Options (factory default in bold)
1| System type| 0| 1 heat / 1 cool Conv.
| | 1| 1 heat / 1 cool heat
| | | pump (no Aux. heat)
| | 2| Heat only (2-wire, 3-wire
| | | zone valves [Series 20],
| | | and normally open zone
| | | valves)
| | 3| Heat only with fan
| | 4| Cool only
| | 5| 2 heat / 1 cool heat
| | | pump (with Aux. heat)
| | 6| 2 heat / 2 cool Conv.
| | 7| 2 heat / 1 cool Conv.
| | 8| 1 heat / 2 cool Conv.
| | 9| 2 heat / 2 cool heat pump
| | | (no Aux. heat)
| | 10| 3 heat / 2 cool heat
| | | pump (with Aux. heat)
2| Changeover valve| 0| Controls valve in cooling
| (O/B terminal)| 1| Controls valve in heating
3| Fan control (heating)| 0

1

| Gas/Oil heat (equipment controls heating fan) Electric furnace (thermo- stat controls heating fan)
5| First stage heat| 5| Gas or oil furnaces of
| cycle rate| | less than 90%
| | | efficiency
| | 1| Steam or gravity
| | 3| Hot water systems or fur-
| | | naces of 90%+ efficiency
| | 9| Electric furnaces
| | | [Other options: 1–12]
6| Second stage| 5| Gas or oil furnaces of
| heat/Aux heat| | less than 90% efficiency
| cycle rate| 1| Steam or gravity
| | 3| Hot water systems or fur-
| | | naces of 90%+ efficiency
| | 9| Electric furnaces
| | | [Other options: 1–12]
7| Auxiliary heat| 5| Gas or oil furnaces of
| cycle rate| | less than 90% efficiency
| | 1| Steam or gravity
| | 3| Hot water systems or fur-
| | | naces of 90%+ efficiency
| | 9| Electric furnaces
| | | [Other options: 1–12]
8| Emergency heat| 9| Electric emergency heat
---|---|---|---
| cycle rate| 1| Steam or gravity
| | 3| Hot water systems or fur-
| | | naces of 90%+ efficiency
| | 5| Gas or oil furnaces of
| | | less than 90% efficiency
| | | [Other options: 1–12]
9| First stage compressor cycle rate| 3| Recommended [Other options: 1–6]
10| Second stage compressor cycle rate| 3| Recommended [Other options: 1–6]
12| Manual/Auto| 0| Manual changeover
| changeover| | (Heat/Cool/Off)
| | 1| Auto changeover (Heat/
| | | Cool/Auto/Off)
| | 2| Auto changeover only
| | | (Auto)
13| Adaptive Intel-| 1| On
| ligent RecoveryTM| 0| Off
14| Temperature| 0| Fahrenheit
| display| 1| Celsius
15| Compressor protection| 5| 5-minute compressor off time [Other options: 0–4

minutes]

16| Schedule format| 0

1

| 5/2 (weekdays and weekends programmable) 5/1/1 (weekdays,

Saturday, and Sunday

programmable)

26| Auxiliary heat| 0| Comfort
| control| 1| Economy
27| Heat temperature range stops| 90| Max. heat temperature setting is 90°F (32°C) [Other options: 40–89°F (4.5°C to 32°C)]
28| Cool temperature range stop| 50| Min. cool temperature setting is 50°F (10°C) [Other options: 51–99°F (10.5°C to 37°C)]

ABOUT COMPANY

  • Automation and Control Solutions
  • Honeywell International Inc.
  • 1985 Douglas Drive North
  • Golden Valley, MN 55422
  • Honeywell Limited-Honeywell Limitée
  • 35 Dynamic Drive
  • Toronto, Ontario M1V 4Z9