TRIPP-LITE PDUMNH30AT2 2.9kW 120V Single-Phase ATS Monitored User Manual
- June 4, 2024
- Tripp Lite
Table of Contents
TRIPP-LITE PDUMNH30AT2 2.9kW 120V Single-Phase ATS Monitored
Highlights
- Built-in HTML5-based LX Platform interface allows you 24/7 remote access
- Enables redundant A/B power option for single-corded network devices
- Digital meter for real-time voltage, amp and load monitoring helps prevent overloads
- Dual 10 ft. cords with NEMA L5-30P inputs connect to separate power sources
- Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
Package Includes
- PDUMNH30AT2 2.9kW Single-Phase ATS/Monitored PDU
- Configuration cable, USB-A to USB Micro-B
- Rack-mounting hardware
- (4) Cord retention brackets
- (24) Cable ties
- Owner’s manual
ATS PDU allows real-time current metering and remote power monitoring to help prevent circuit overloads and ensure proper load balance.
Features
Single-Phase 30A ATS PDU Distributes and Monitors Network-Grade Power in
Real Time
This monitored PDU provides real-time remote monitoring of voltage, frequency
and load levels via its built-in network interface. Ideal for network IT
applications, small computer rooms and other equipment rack applications, the
PDUMNH30AT2 features 24 NEMA 5-15/20R 120V outlets and one NEMA L5-30R outlet,
which distribute AC power to rack equipment. Dual 10-foot (3.1-meter) power
cords with NEMA L5-30P inputs connect to separate primary and secondary mains
circuits, backup generators, UPS systems or utility power grids, including
out-of-phase sources.
Switches from Primary to Secondary Power Source in Milliseconds
Dynamic solid-state automatic transfer switching (ATS) allows the PDU to
switch to the secondary source within 1–5 milliseconds, should the primary
source fail or become unstable, to ensure your connected equipment operates
without interruption. An on-board ATS processor constantly evaluates the power
quality of both input sources. It prevents switching if the secondary source
is unavailable or of lower quality than the primary source.
Built-In LX Platform Network Management Card Allows Remote Access 24/7
The HTML5-based WEBCARDLX network interface enables full remote access for PDU
status monitoring and email notifications via secure web browser, SNMP, telnet
or SSH. The latest version of PowerAlert Device Manager (PADM20) provides
enhanced remote management capabilities, including customizable dashboard
graphs to fit user preferences. The PADM20 upgrade and Tripp Lite’s PowerAlert
Element Manager (PAEM) form a powerful tool for expanding maintenance
functions in large installations, including firmware update checks and backup
and restoration of device configurations.
Digital LED Display and Load Meter Helps Prevent Potentially Expensive
Overloads
A three-digit LED display shows measured or calculated amperage, kilowatt and
voltage values at a glance. Monitoring amperage helps ensure load levels
remain well below maximum capacity with no danger of overload that could lead
to costly downtime or damaged equipment. Maintaining proper load levels, even
while adding new equipment, can keep your TCO (total cost of ownership) low.
Monitoring current provides 1% billing grade accuracy.
Mounts into 2U of Rack Space or on a Wall
Use the included mounting hardware to install the all-metal housing into 2U
of space in an EIA-standard 19-inch rack. You may also use the mounting
brackets to secure the PDU to a wall or under a counter. Included cord
retention brackets help organize connected power cords and eliminate cable
clutter.
TAA-Compliant for GSA Schedule Purchases
The PDUMNH30AT2 is compliant with the Federal Trade Agreements Act (TAA),
which makes it eligible for GSA (General Services Administration) Schedule and
other federal procurement contracts.
Specifications
OVERVIEW
UPC Code| 037332261427
PDU Type| Auto-Transfer Switch; Monitored
INPUT
PDU Input Voltage| 120V
Recommended Electrical Service| 30A 120V
Maximum Input Amps| 30
Maximum Input Amps Details| Agency de-rated to 24A continuous
PDU Plug Type| (2) NEMA L5-30P
Input Phase| Single-Phase
Input Cord Details| Set of two inputs connect to separate PRIMARY and
SECONDARY power sources
Input Cord Length (ft.)| 10
Input Cord Length (m)| 3.05
OUTPUT
Output kW Capacity (kW)| 3.05
Output Capacity Details| 3.05kW (127V), 2.88kW (120V), 2.4kW (100V) / 30A
total capacity (Agency de-rated 24A); 24A max per L5-30R outlet; 20A max per
breakered load bank; 16A max per 5-15/20R outlet
Frequency Compatibility| 50 / 60 Hz
Output Receptacles| (24) 5-15/20R; (1) L5-30R
Output Nominal Voltage| 100; 120; 127
Overload Protection| 2x 20A output breakers protect 12 5-15/20R outlets each
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display| Digital display reports output amps and kW in 4
separately metered loading segments (BANK 1: 5-20R outlets #1- 12; BANK 2:
5-20R outlets #13-24; BANK 3: L5-30R outlet #25; BANK 4: Total PDU output),
whole-PDU output kW load level and input voltage on primary and secondary
input lines, and IP address assignment. Temperature and/or Humidity displayed
with optional Environsense2 modules
Front Panel LEDs| 2 LEDs for power status on Primary and Secondary input
connection and three additional LEDs to label the displayed numeric value as
Amps, kW or Voltage
Switches| ENTER and MODE switches toggle the digital display to show output
amps (Banks 1-4), total kW output and input voltage (primary, secondary)
---|---
SURGE / NOISE SUPPRESSION
Automatic Shut-Off| No
PHYSICAL
Material of Construction| Metal
Form Factors Supported| 2U rackmount
Minimum Required Rack Depth (cm)| 42.93
Minimum Required Rack Depth (inches)| ****
16.9
PDU Form Factor| Horizontal (2U)
Shipping Dimensions (hwd / in.)| 7.70 x 16.60 x 19.90
Shipping Weight (kg)| 8.16
Unit Dimensions (hwd / in.)| 3.41 x 17.32 x 11.89
Unit Dimensions (hwd / cm)| 8.66 x 44 x 30.2
Unit Weight (lbs.)| 13.71
Unit Weight (kg)| 6.22
ENVIRONMENTAL
Operating Temperature Range| 0C ~ 40C (32F ~ 104F)
Storage Temperature Range| -30°C to +50°C (-22°F to +122°F)
Relative Humidity| 5-95% noncondensing
Operating Elevation (ft.)| 0-10,000
Operating Elevation (m)| 0-3000
COMMUNICATIONS
PowerAlert Software| LX Platform Interface: PowerAlert Device Manager
Communications Cable| Micro-USB- to-USB A configuration/console Access cable
Network Monitoring Port| RJ45 Network port, Micro-USB Configuration port, USB
A port supports a variety of Envirosense2 environmental and control modules.
See Accessories>Management Hardware section for more information about these
modules.
SNMP Compatibility| n/a
Network Compatibility| 10 Mbps; 100 Mbps (Fast Ethernet)
FEATURES & SPECIFICATIONS
TVSS Grounding| Rear grounding lug
High Availability PDU Features| Auto-Transfer Switching
STANDARDS & COMPLIANCE
Certification & Compliance| UL 62368-1; CSA (Canada); FCC Part 15 Class A (USA); NOM (Mexico); RETIE (Colombia); RoHS
WARRANTY
Product Warranty Period (Worldwide)| ****
2-year limited warranty
© 2022 Tripp Lite. All rights reserved. All product and company names are
trademarks or registered trademarks of their respective holders. Use of them
does not imply any affiliation with or endorsement by them. Tripp Lite has a
policy of continuous improvement. Specifications are subject to change without
notice. Tripp Lite uses primary and third-party agencies to test its products
for compliance with standards. See a list of Tripp Lite’s testing agencies:
https://www.tripplite.com/products/product-certification-agencies