SH24W-1530
SELECT-A-STROBE/HORN
COMBINATION
Owner’s Manual
SH24W-1530 Select-A-Strobe-Horn Combination
-
Meets or exceeds NFPA/ANSI Standards
-
UL Listed for wall mounting
-
Screw terminal capacity AWG #12
-
Universal mounting plate included
-
Polarized strobes with wide operating voltage range using fi ltered DC or unfi ltered FWR input voltage
-
Horn fi eld selectable tones:
3000 Hz interrupted or electro-mechanical
Temporal or Non-temporal
High or low dBA output -
Mounts to 4” square, single gang, double gang, or octagonal back box
-
Synchronization requires Sync Module (SMD10-3A)
-
Available in red or white housing
Amseco’s Select-A-Horn/Strobe Series is designed to comply with the Americans
with Disabilities Act (ADA) and meet UL Standard 1971 requirements for
emergency signaling devices for the hearing impaired.
The SH24W series features a unique candela intensity fi eld selector switch for
alternating the candela output 15cd to 30cd. The horn provides two different fi
eld selectable tones, and a high/low output setting that can be achieved with
the use of mini-jumpers located on the back of the unit. These appliances are
polarized for connecting to supervised fi re alarm circuits. The strobe is
designed with a xenon fl ash tube and provides a candela intensity fi eld
selector switch for maximum performance.
The SH24W-1530 can be synchronized by using the SMD10-3A Sync Module to comply
with NFPA recommendations concerning photosensitive epilepsy when installing
more than two visual appliances within the fi eld of view. The strobe signals
are listed for indoor use, wall mount, under UL 1971 Standard.
Ordering Information
Model Number| Stock Number| Housing Color| Input Voltage|
Operating Voltage Range| Selectable Strobe Output (cd)| Horn Sound Ouput|
Wiring Type| Mounting Type| Operating Temperature Range
---|---|---|---|---|---|---|---|---|---
SH24W-1530R| 4560006| Red| Regulated 24V DC/ FWR| 16-33 VDC
16-33 VFWR| 15 or 30| Selectable| **** Terminals| Wall Mount|
32°F – 120°F (0°C – 49°C)
SH24W-1530W| 4560007| White
Engineering Specifi cations
The audible and visual alarm indicating appliances shall be amseco model
SH24W-1530 or equivalent device. The strobe shall be listed under UL 1971
Standard for signaling devices for the hearing impaired and shall be approved
for fi re protective service. The candela output shall be fi eld selectable,
having a dual setting of 15cd or 30cd output. The horn shall provide two
different fi eld selectable, temporal, or steady tones, and a high/low fi eld
selectable sound ouput setting. The signaling strobe shall operate on 24V DC
from a non-coded, regulated, DC supply or full-wave rectifi ed, unfi ltered
supply. The horn may operate on 24V DC coded system. The strobe shall be
designed to produce one signal fl ash per second with continuously applied
minimum voltage. The strobe/horn shall have a universal back mounting plate,
capable of wall mounting
to a back box. When strobe synchronization is required, the strobe/horn shall
be compatible with the Amseco SMD10-3A (daisy chain) or other source of Amseco
sync protocol. Audible and visual signaling devices shall be installed in
accordance with current NFPA guidelines.
Dimensions: inches (mm)
UL Required Minimum Light Output
Degrees | Horizontal | Vertical |
---|---|---|
15cd | 30cd | 15cd |
5-25 | 13.50 | 27.00 |
30 | 11.25 | 22.50 |
35 | 11.25 | 22.50 |
40 | 11.25 | 22.50 |
45 | 11.25 | 22.50 |
50 | 8.25 | 16.50 |
55 | 6.75 | 13.50 |
60 | 6.00 | 12.00 |
65 | 5.25 | 10.50 |
70 | 5.25 | 10.50 |
75 | 4.50 | 9.00 |
80 | 4.50 | 9.00 |
85-90 | 3.75 | 7.50 |
Compound 45 | 3.60 | 7.20 |
Specifications
Tone Selection | PC3 Pattern | PC2 Tone | PC1 Volume |
---|---|---|---|
Jumper | Non- Temporal | Electro- Mechanical | |
Temporal | 3000Hz | Low |
Sound Output Dispersion ULC | Horizontal dB | Vertical dB |
---|---|---|
DEGREES | +90 | -6 |
+60 | -2 | -2 |
+30 | -1 | -1 |
0 | 0 | 0 |
-30 | -1 | -3 |
-60 | -2 | -5 |
-90 | -6 | -6 |
Wiring Diagram
Current Draw Table
| PC3: Pattern PC2: Tone PC1: Volume| Maximum RMS Operating Current (mA)|
Minimum Sound Output (dBA at 10ft per UL464)
---|---|---|---
PC3| PC2| PC1| Regulated 24V DC (Typical)| Regulated 24V FWR (Typical)|
Regulated 24V DC
Horn & Strobe 15cd| Non-Temporal| Electro Mecanical| HIGH| 1| 1| 1| 112 (99)|
145 (145)| 83
3000 Hz| LOW| 1| 1| 0| 109 (80)| 142 (120)| 74
Electro Mechanical| HIGH| 1| 0| 1| 118 (99)| 153 (145)| 84
3000 Hz| LOW| 1| 0| 0| 106 (80)| 139 (120)| 74
Temporal| Electro Mechanical| HIGH| 0| 1| 1| 112 (99)| 145 (145)| 79
LOW| 0| 1| 0| 109 (80)| 142 (120)| 69
3000 Hz
| HIGH| 0| 0| 1| 118 (99)| 153 (145)| 80
LOW| 0| 0| 0| 106 (80)| 139 (120)| 70
Horn & Strobe 30cd| Non-Temporal| Electro Mechanical| HIGH| 1| 1| 1| 158
(130)| 207 (185)| 83
LOW| 1| 1| 0| 155 (111)| 204 (160)| 74
3000 Hz
| HIGH| 1| 0| 1| 164 (130)| 215 (185)| 84
LOW| 1| 0| 0| 152 (111)| 201 (160)| 74
Temporal| Electro Mechanical| HIGH| 0| 1| 1| 158 (130)| 207 (185)| 79
LOW| 0| 1| 0| 155 (111)| 204 (160)| 69
3000 Hz
| HIGH| 0| 0| 1| 164 (130)| 215 (185)| 80
LOW| 0| 0| 0| 152 (111)| 201 (160)| 70
Horn Only| Non-Temporal| Electro Mechanical| HIGH| 1| 1| 1| 57| 91| 83
LOW| 1| 1| 0| 42| 44| 74
3000 Hz
| HIGH| 1| 0| 1| 70| 68| 84
LOW| 1| 0| 0| 36| 38| 74
Temporal| Electro Mechanical| HIGH| 0| 1| 1| 57| 91| 79
LOW| 0| 1| 0| 42| 44| 69
3000 Hz
| HIGH| 0| 0| 1| 70| 68| 80
LOW| 0| 0| 0| 36| 38| 70
Strobe Light Only| Max. RMS Operating Current (mA)
---|---
| Regulated 24V DC (Typical)| Regulated 24V FWR (Typical)
15cd| 88 (57)| 127 (95)
30cd| 134 (87)| 184 (135)
Under ULC 525/526| ULC Current @ 24V DC (mA)
---|---
| Low Volume| High Volume
15cd| 79| 92
30cd| 111| 124
Installation Options
WARNING
Strobes must be used only on circuits with continuously operating voltage. DO
NOT use strobe on coded or interrupted circuits in which the applied voltage
is interrupted ON and OFF as the strobe may fail to fl ash. The applied voltage
must be within its rated input voltage range. Fuse ratings on signaling
circuits must handle peak currents from all devices connected to those
circuits.
Potter Electric Signal Company
2081 Craig Road, St. Louis, MO, 63146-4161
Phone: 800-325-3936/Canada
888-882-1833
www.amseco-kai.com
PRINTED IN USA
MKT. #8850011 – REV G