Terms | Description | Range |
---|---|---|
id | Plink address of the device | 1 – 31 |
p | Panel ID | 21 – 84 |
t | Target reporting account | UD-1000/UD-2000: 1-5IP: 1-64 |
Address | Point address | 1 – 127 |
user |
Report By Point
The following table identifies the reporting codes generated for specific panel events when reporting by point.
When using SIA reporting format with the MC-1000 module(s) to allow a single account for multiple panels, the events will have the “pi” modifier added to them to identify the specific panel the event pertains to.
Contact ID cannot be used to report by point when using MC-1000(s) to allow multiple panels to report using the same account
Report By Point | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
System Power Up | RR | |
AC Power Trouble | AT | 10+id |
AC Power Trouble Restore | AR | 10+id |
Earth Trouble | YP | 10 00 |
Earth Trouble Restore | YQ | 10 00 |
Battery Trouble | YT | 10+id |
Battery Trouble Restore | YR | 10+id |
Battery Charger Trouble | IA | 10+id |
Battery Charger Trouble Restore | IR | 10+id |
RA-6075 Trouble | ET | 03+id |
RA-6075 Trouble Restore | ER | 03+id |
UD-1000 Trouble | ET | 04+id |
UD-1000 Trouble Restore | ER | 04+id |
SLCE-127 Trouble | ET | 05+id |
SLCE-127 Trouble Restore | ER | 05+id |
CA-6075 Trouble | ET | 07 00 |
CA-6075 Trouble Restore | ER | 07 00 |
CA-6500 Trouble | ET | 08 00 |
CA-6500 Trouble Restore | ER | 08 00 |
RA-6500 Trouble | ET | 09+id |
RA-6500 Trouble Restore | ER | 09+id |
PSN-1000 Trouble | ET | 10+id |
PSN-1000 Trouble Restore | ER | 10+id |
Report By Point | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
DRV-50 Trouble | ET | 13+id |
DRV-50 Trouble Restore | ER | 13+id |
RLY-5 Trouble | ET | 14+id |
RLY-5 Trouble Restore | ER | 14+id |
LED-16 Trouble | ET | 15+id |
LED-16 Trouble Restore | ER | 15+id |
FCB-1000 Trouble | ET | 16+id |
FCB-1000 Trouble Restore | ER | 16+id |
SPG-1000 Trouble | ET | 17+id |
SPG-1000 Trouble Restore | ER | 17+id |
FIB-1000 Trouble | ET | 18+id |
FIB-1000 Trouble Restore | ER | 18+id |
PAD100-SLCE Trouble | ET | 20+id |
PAD100-SLCE Trouble Restore | ER | 20+id |
MC-1000 Host Trouble | ET | 21+id |
MC-1000 Host Trouble Restore | ER | 21+id |
MC-1000 Client Trouble | ET | 22+id |
MC-1000 Client Trouble Restore | ER | 22+id |
IP Reporting Ethernet Trouble | LT | 0 |
IP Reporting Ethernet Restore | LR | 0 |
DACT Line 1 Trouble | LT | 1 |
DACT Line 1 Restore | LR | 1 |
DACT Line 2 Trouble | LT | 2 |
DACT Line 2 Restore | LR | 2 |
DACT Communication Fail | YC | 0 |
DACT Communication Restore | YK | 0 |
DACT Com 1 Trouble | YS | 100 |
DACT Com 1 Restore | YK | 100 |
DACT Com 2 Trouble | YS | 200 |
DACT Com 2 Restore | YK | 200 |
DACT Primary Target Trouble | YS | t |
DACT Primary Target Restore | YK | t |
DACT Secondary Target Trouble | YS | t |
DACT Secondary Target Restore | YK | t |
IP Primary Target Trouble | YS | 100+t |
IP Primary Target Restore | YK | 100+t |
IP Secondary Target Trouble | YS | 200+t |
IP Secondary Target Restore | YK | 200+t |
Report By Point | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
Date Changed | JD | |
Time Changed | JT | |
Local Program Successful | LS | |
Remote Program Successful | RS | |
Remote Program Failed | RU | |
System Reset | OR | |
System Manual Test | RX | |
Periodic Test – Normal | RP | |
Periodic Test – Off Normal | RY | |
Fire Drill Begin | FI | |
Fire Drill End | FK | |
Printer Off-Line Trouble | VZ | 17+id |
Printer Off-Line Trouble Restore | VY | 17+id |
Printer Out of Paper Trouble | VO | 17+id |
Printer Out of Paper Restore | VI | 17+id |
PC Connect Supervision Trouble | NC | user |
PC Connect Supervision Restore | NC | user |
Disable Events
Waterflow Disable| SB| id + Address| 1| 571| id| Address| NA| NA
Aux Input Disable| UB| id + Address| 1| 571| id| Address| NA| NA
Supervisory Disable| SB| id + Address| 1| 571| id| Address| NA| NA
CO Disable| GB| id + Address| 1| 571| id| Address| NA| NA
Medical Alert Disable| MB| id + Address| 1| 571| id| Address| NA| NA
Tornado Alert Disable| PB| id + Address| 1| 571| id| Address| NA| NA
Process Alert Disable| QB| id + Address| 1| 571| id| Address| NA| NA
Security Alert Disable| BB| id + Address| 1| 571| id| Address| NA| NA
All Other Disables| FB| id + Address| 1| 571| id| Address| NA| NA
Enable Events
Waterflow Enable| SU| id + Address| 3| 571| id| Address| NA| NA
Aux Input Enable| UU| id + Address| 3| 571| id| Address| NA| NA
Supervisory Enable| SU| id + Address| 3| 571| id| Address| NA| NA
CO Enable| GU| id + Address| 3| 571| id| Address| NA| NA
Medical Alert Disable| MU| id + Address| 3| 571| id| Address| NA| NA
Tornado Alert Disable| PU| id + Address| 3| 571| id| Address| NA| NA
Process Alert Disable| QU| id + Address| 3| 571| id| Address| NA| NA
Security Alert Disable| BU| id + Address| 3| 571| id| Address| NA| NA
All Other Enables| FU| id + Address| 3| 571| id| Address| NA| NA
Report By Point | SIA Format | Contact ID Format |
---|
Description
| Event Code|
Parameter
|
Qualifier
|
Event
| Single Panel Accounts| Multiple Panel Accounts
Group| Zone| Group| Zone
Alarm Events
Manual Pull Station| FA| id + Address| 1| 115| id| Address| NA| NA
Water Flow| SA| id + Address| 1| 113| id| Address| NA| NA
Aux Contact Input| UA| id + Address| 1| 140| id| Address| NA| NA
CO Alarm| GA| id + Address| 1| 162| id| Address| NA| NA
All Other Alarms| FA| id + Address| 1| 110| id| Address| NA| NA
Alarm Restore Events
Manual Pull| FH| id + Address| 3| 115| id| Address| NA| NA
Water Flow| SH| id + Address| 3| 113| id| Address| NA| NA
Aux Contact Input| UH| id + Address| 3| 140| id| Address| NA| NA
CO Alarm| GH| id + Address| 3| 162| id| Address| NA| NA
All Other Alarms| FH| id + Address| 3| 110| id| Address| NA| NA
Alert Events
Medical Alert| MA| id + Address| 3| 100| id| Address| NA| NA
Tornado Alert| PA| id + Address| 3| 150| id| Address| NA| NA
Process Alert| QA| id + Address| 3| 160| id| Address| NA| NA
Security Alert| BA| id + Address| 3| 130| id| Address| NA| NA
Alert Restore Events
Medical Alert Restore| MH| id + Address| 3| 100| id| Address| NA| NA
Tornado Alert Restore| PH| id + Address| 3| 150| id| Address| NA| NA
Process Alert Restore| QH| id + Address| 3| 160| id| Address| NA| NA
Security Alert Restore| BH| id + Address| 3| 130| id| Address| NA| NA
Supervisory Events
Fire Supervisory| FS| id + Address| 1| 200| id| Address| NA| NA
Sprinkler Supervisory| SS| id + Address| 1| 200| id| Address| NA| NA
Tamper| SS| id + Address| 1| 203| id| Address| NA| NA
CO Supervisory| GS| id + Address| 1| 200| id| Address| NA| NA
Fire Supervisory Restore| FV| id + Address| 3| 200| id| Address| NA| NA
Sprinkler Supervisory Restore| SR| id + Address| 3| 200| id| Address| NA| NA
Tamper Restore| SR| id + Address| 3| 203| id| Address| NA| NA
CO Supervisory Restore| GR| id + Address| 3| 200| id| Address| NA| NA
Trouble Events
Manual Pull Trouble| FT| id + Address| 1| 373| id| Address| NA| NA
Waterflow Trouble| ST| id + Address| 1| 373| id| Address| NA| NA
Aux Trouble| UT| id + Address| 1| 373| id| Address| NA| NA
Supervisory Trouble| ST| id + Address| 1| 373| id| Address| NA| NA
CO Trouble| GT| id + Address| 1| 373| id| Address| NA| NA
All Other Troubles| FT| id + Address| 1| 373| id| Address| NA| NA
Report By Point | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
Trouble Restore Events
Manual Pull Trouble Restore| FJ| id + Address| 3| 373| id| Address| NA| NA
Waterflow Trouble Restore| SJ| id + Address| 3| 373| id| Address| NA| NA
Aux Trouble Restore| UJ| id + Address| 3| 373| id| Address| NA| NA
Supervisory Trouble Restore| SJ| id + Address| 3| 373| id| Address| NA| NA
CO Trouble Restore| GJ| id + Address| 3| 373| id| Address| NA| NA
All Other Trouble Restore| FJ| id + Address| 3| 373| id| Address| NA| NA
- see Identifying Points for address details
Report By Zone
The following table identifies the reporting codes generated for specific
panel events when reporting by zone. When using SIA reporting format and a
single account for multiple panels the events will have the “pi” modifier
added to them to identify the specific panel the event pertains to.
Report By Zone | SIA Format | Contact ID Format |
---|
Description
| Event Code|
Parameter
|
Qualifier
|
Event
| Single Panel Accounts| Multiple Panel Accounts
Group| Zone| Group| Zone
System Power Up| RR| | 1| 305| 00| 000| p| 000
AC Power Trouble| AT| 10+id| 1| 301| 10| id| p| 120+id
AC Power Trouble Restore| AR| 10+id| 3| 301| 10| id| p| 120+id
Earth Trouble| YP| 10 00| 1| 310| 10| id| p| 120+id
Earth Trouble Restore| YQ| 10 00| 3| 310| 10| id| p| 120+id
Battery Trouble| YT| 10+id| 1| 302| 10| id| p| 120+id
Battery Trouble Restore| YR| 10+id| 3| 302| 10| id| p| 120+id
Battery Charger Trouble| IA| 10+id| 1| 302| 10| id| p| 120+id
Battery Charger Trouble Restore| IR| 10+id| 3| 302| 10| id| p| 120+id
RA-6075 Trouble| ET| 03+id| 1| 333| 03| id| p| 0+id
RA-6075 Trouble Restore| ER| 03+id| 3| 333| 03| id| p| 0+id
UD-1000 Trouble| ET| 04+id| 1| 333| 04| id| p| 900
UD-1000 Trouble Restore| ER| 04+id| 3| 333| 04| id| p| 900
SLCE-127 Trouble| ET| 05+id| 1| 333| 05| id| p| 40+id
SLCE-127 Trouble Restore| ER| 05+id| 3| 333| 05| id| p| 40+id
CA-6075 Trouble| ET| 07 00| 1| 333| 07| 000| p| 900
CA-6075 Trouble Restore| ER| 07 00| 3| 333| 07| 000| p| 900
CA-6500 Trouble| ET| 08 00| 1| 333| 08| 000| p| 901
CA-6500 Trouble Restore| ER| 08 00| 3| 333| 08| 000| p| 901
RA-6500 Trouble| ET| 09+id| 1| 333| 09| id| p| 80+id
RA-6500 Trouble Restore| ER| 09+id| 3| 333| 09| id| p| 80+id
PSN-1000 Trouble| ET| 10+id| 1| 333| 10| id| p| 120+id
PSN-1000 Trouble Restore| ER| 10+id| 3| 333| 10| id| p| 120+id
DRV-50 Trouble| ET| 13+id| 1| 333| 13| id| p| 160+id
DRV-50 Trouble Restore| ER| 13+id| 3| 333| 13| id| p| 160+id
RLY-5 Trouble| ET| 14+id| 1| 333| 14| id| p| 200+id
RLY-5 Trouble Restore| ER| 14+id| 3| 333| 14| id| p| 200+id
LED-16 Trouble| ET| 15+id| 1| 333| 15| id| p| 240+id
LED-16 Trouble Restore| ER| 15+id| 3| 333| 15| id| p| 240+id
FCB-1000 Trouble| ET| 16+id| 1| 333| 16| id| p| 240+id
FCB-1000 Trouble Restore| ER| 16+id| 3| 333| 16| id| p| 280+id
SPG-1000 Trouble| ET| 17+id| 1| 333| 17| id| p| 320+id
SPG-1000 Trouble Restore| ER| 17+id| 3| 333| 17| id| p| 320+id
FIB-1000 Trouble| ET| 18+id| 1| 333| 18| id| p| 360+id
Report By Zone | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
FIB-1000 Trouble Restore | ER | 18+id |
PAD100-SLCE Trouble | ET | 20+id |
PAD100-SLCE Trouble Restore | ER | 20+id |
MC-1000 Host Trouble | ET | 21+id |
MC-1000 Host Trouble Restore | ER | 21+id |
MC-1000 Client Trouble | ET | 22+id |
MC-1000 Client Trouble Restore | ER | 22+id |
DACT Line 1 Trouble | LT | 1 |
DACT Line 1 Restore | LR | 1 |
DACT Line 2 Trouble | LT | 2 |
DACT Line 2 Restore | LR | 2 |
DACT Communication Fail | YC | 0 |
DACT Communication Restore | YK | 0 |
DACT Com 1 Trouble | YS | 100 |
DACT Com 1 Restore | YK | 100 |
DACT Com 2 Trouble | YS | 200 |
DACT Com 2 Restore | YK | 200 |
DACT Primary Target Trouble | YS | t |
DACT Primary Target Restore | YK | t |
DACT Secondary Target Trouble | YS | t |
DACT Secondary Target Restore | YK | t |
IP Primary Target Trouble | YS | 100+t |
IP Primary Target Restore | YK | 100+t |
IP Secondary Target Trouble | YS | 200+t |
IP Secondary Target Restore | YK | 200+t |
Date Changed | JD | |
Time Changed | JT | |
Local Program Successful | LS | |
Remote Program Successful | RS | |
Remote Program Failed | RU | |
System Reset | OR | |
System Manual Test | RX | |
Periodic Test – Normal | RP | |
Periodic Test – Off Normal | RY | |
Fire Drill Begin | FI | |
Fire Drill End | FK | |
Printer Off-Line Trouble | VZ | 17+id |
Printer Off-Line Trouble Restore | VY | 17+id |
Printer Out of Paper Trouble | VO | 17+id |
Report By Zone | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
Printer Out of Paper Restore | VI | 17+id |
PC Connect Supervision Trouble | NC | user |
PC Connect Supervision Restore | NC | user |
Disable Events
Waterflow Disable| SB| zone| 1| 571| 00| zone| p| zone
Aux Input Disable| UB| zone| 1| 571| 00| zone| p| zone
Supervisory Disable| SB| zone| 1| 571| 00| zone| p| zone
CO Disable| GB| zone| 1| 571| 00| zone| p| zone
Medical Disable| MB| zone| 1| 571| 00| zone| p| zone
Tornado Disable| PB| zone| 1| 571| 00| zone| p| zone
Process Disable| QB| zone| 1| 571| 00| zone| p| zone
Security Disable| BB| zone| 1| 571| 00| zone| p| zone
All Other Disables| FB| zone| 1| 571| 00| zone| p| zone
Enable Events
Waterflow Enable| SU| zone| 3| 571| 00| zone| p| zone
Aux Input Enable| UU| zone| 3| 571| 00| zone| p| zone
Supervisory Enable| SU| zone| 3| 571| 00| zone| p| zone
CO Enable| GU| zone| 3| 571| 00| zone| p| zone
Medical Enable| MU| zone| 3| 571| 00| zone| p| zone
Tornado Enable| PU| zone| 3| 571| 00| zone| p| zone
Process Enable| QU| zone| 3| 571| 00| zone| p| zone
Security Enable| BU| zone| 3| 571| 00| zone| p| zone
All Other Enables| FU| zone| 3| 571| 00| zone| p| zone
Zone Alarm Events
Fire Alarm| FA| zone| 1| 110| 00| zone| p| zone
Aux Alarm| UA| zone| 1| 140| 00| zone| p| zone
Waterflow Alarm| SA| zone| 1| 113| 00| zone| p| zone
CO Alarm| GA| zone| 1| 162| 00| zone| p| zone
Zone Alarm Restore Events
Fire Alarm Restore| FH| zone| 3| 110| 00| zone| p| zone
Aux Alarm Restore| UH| zone| 3| 140| 00| zone| p| zone
Waterflow Alarm Restore| SH| zone| 3| 113| 00| zone| p| zone
CO Alarm Restore| GH| zone| 3| 162| 00| zone| p| zone
Zone Alert Events
Medical| MA| zone| 1| 100| 00| zone| p| zone
Tornado| PA| zone| 1| 150| 00| zone| p| zone
Process| QA| zone| 1| 160| 00| zone| p| zone
Security| BA| zone| 1| 130| 00| zone| p| zone
Report By Zone | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
Zone Alert Restore Events
Medical| MH| zone| 3| 100| 00| zone| p| zone
Tornado| PH| zone| 3| 150| 00| zone| p| zone
Process| QH| zone| 3| 160| 00| zone| p| zone
Security| BH| zone| 3| 130| 00| zone| p| zone
Zone Supervisory Events
Supervisory| SS| zone| 1| 203| 00| zone| p| zone
CO Supervisory| SS| zone| 1| 203| 00| zone| p| zone
Zone Supervisory Restore
Supervisory Restore| SR| zone| 3| 203| 00| zone| p| zone
CO Supervisory Restore| SR| zone| 3| 203| 00| zone| p| zone
| | | | | | | |
Zone Trouble Events
Fire zone – Trouble| FT| zone| 1| 373| 00| zone| p| zone
Fire zone – Trouble Restore| FJ| zone| 3| 373| 00| zone| p| zone
Supervisory Zone – Trouble| ST| zone| 1| 373| 00| zone| p| zone
Supervisory Zone – Restore| SJ| zone| 3| 373| 00| zone| p| zone
Aux Zone – Trouble| UT| zone| 1| 373| 00| zone| p| zone
Aux Zone – Trouble Restore| UJ| zone| 3| 373| 00| zone| p| zone
Report By Panel
The following table identifies the reporting codes generated for specific
panel events when reporting by panel.
When using SIA reporting format and a single account for multipe panels the events will have the “pi” modifier added to them to identify the specific panel the event pertains to.
Report By System | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
Single Panel Accounts | Multiple Panel Accounts | |
Group | Zone | Group |
System Power Up | RR | |
Date Changed | JD | |
Time Changed | JT | |
System Reset | OR | |
System Manual Test | RX | |
Periodic Test – Normal | RP | |
Periodic Test – Off Normal | RY | |
Remote Program Success | RS | |
Local Program Success | LS | |
Remote Program Fail | RU | |
Fire Drill Begin | FI | |
Fire Drill End | FK | |
System Alarm | FA | |
System Alarm Restore | FH | |
System Supervisory | SS | |
System Supervisory Restore | SR | |
System Trouble | FT | |
System Trouble Restore | FJ |
Identifying Points
In order to uniquely identify points in all situations, points on specific
P-Link devices are assigned a distinct address reporting range as shown in the
table below: P-Link Device R
P-Link Device | Reported Address | Notes: |
---|---|---|
Built-in SLC, SLCE-127, and PAD100-SLCE | 1-127 | |
Built-in Power Supplies and PSN-1000/E | 301-310 | NAC1-6 reported as 301-306 |
I/O 1-4 reported as 307-310
DRV-50| 401-454| LED 1-50 reported as 401-450Inputs 1-4 reported as 451-454
LED-16| 501-548| LED 1-48 reported as 501-548
RLY-5| 601-605| Relay 1-5 reported as 601-605
MC-1000| Npi (Panel #)| Panel # based on Client ID number
Example: A trouble associated with address 1 on a SLCE-127 #2.
Format: As shown in Table Actual Reported Data
SIA: FT id+Address FT 02 001
Contact ID 373 id+Address 373 02 001
Example: A trouble associated with NAC 1 on PSN-1000 #2
Format: As shown in Table Actual Reported Data
SIA: FT id+Address FT 02 301
Contact ID 373 id+Address 373 02 301
Example: A trouble associated with LED 1 on DRV-50 #2
Format: As shown in Table Actual Reported Data
SIA: FT id+Address FT 02 401
Contact ID 373 id+Address 373 02 401
Reporting Multiple Panels with MC-1000
Events will have the “pi” modifier added to them to identify the specific
panels when using SIA format to report multiple panels using a single account
number.
Contact ID reporting format will not allow specific panel events to be identified when reporting by point with multiple panels reporting to a single account. All zone specific events limit the number of zones to 999.
Example: A trouble associated with address 3 on built in SLC Loop of Host
panel.
Format: As Shown in Table Actual Reported Data
SIA: Npi FT id+Address Npi01 FT 0003
Example: An alarm associated with address 12 on PAD100-SLCE #4 of Client #1
panel
Format: As Shown in Table Actual Reported Data
SIA: Npi FT id+Address Npi02 FA 04012
Example: A supervisory associated with I/O #3 of Client #2 panel
Format: As Shown in Table Actual Reported Data
SIA: Npi SS Id+Address Npi01 SS 00309
(Note: The Host panel reports as Npi01, Client 1 as Npi02 and Client 2 as Npi03, etc.)