Mircom MS-400AP Series Advanced Protocol Intelligent Manual Stations User Manual
- June 9, 2024
- Mircom
Table of Contents
Mircom MS-400AP Series Advanced Protocol Intelligent Manual
Description
Mircom’s MS-400AP Series are single action alarm manual stations that include
a permanently attached intelligent module. The intelligent manual station has
a pair of rotary decimal switches which allows for two digit address setting.
Pulling the handle initiates the operation of the intelligent module.
Resetting is accomplished by inserting a 1/8” screwdriver from the front. The
handle, once pulled will remain open and cannot be reset without utilizing the
screwdriver.
The MS-400AP Manual stations are constructed of durable aluminium and finished
in red. An abrasion resistant label with large, raised letters provides clear
legible instructions. The model MS-402AP (two stage) is similar to the MS-
401AP (single stage) except it contains an additional General Alarm (G.A.)
N.O. switch. For safety reasons, the G.A. switch is only accessible after the
handle has been pulled. A special key is supplied with each unit. All manual
stations can be easily converted from single action to double action station
by the addition of the MS-DA double action lever.
Mircom’s Advanced Protocol (AP) devices use a high speed communication
protocol that greatly increases the speed of communication between the
intelligent devices. Mircom’s Advanced Protocol uses a superior group polling
method as well as an interrupt feature that provide for a faster response to
an alarm condition. In addition, the Advanced Protocol allows for greater
system capacity with support for up to 318 devices per SLC circuit. The AP
devices are backwards compatible to operate in CLIP mode for legacy system
applications.
Features
- Durable Extruded Aluminium Construction
- Attractive, Low Profile Design
- Standard Single Gang Mount
- Converts to Double Action
- Glass Rod Optional
- Permanently attached intelligent addressable module. Two stage model is equipped with an intelligent module that provides two addresses for 1st and 2nd stage operation
- Rotary switches for direct-dial entry of address. Each unit can have address set for 01-159 for Advanced Protocol mode and 01-99 for CLIP mode
Operation
Pulling on the station’s handle will release the internal switch to trigger the intelligent addressable module. The MS-402AP (two stage version) also provides a key switch which is accessible after the handle has been pulled. Operation of the key switch will initiate the 2nd stage of a two stage alarm signalling system.
Engineer Specifications
The single action manual station shall be Mircom’s MS-400AP Series. Operating instructions shall be in raised English and French lettering and the unit shall be constructed of extruded aluminium, finished in red enamel paint to provide quick identification. Pulling the handle shall initiate immediate operation of the intelligent module. In addition, those stations installed in a two stage system shall come equipped with an internal key switch designed to operate the 2nd stage alarm initiating circuit. All manual fire alarm stations shall be installed as per the specific requirements outlined in the ULC codes, as well as all other applicable national or local codes.
Specifications
Specifications
Model| MS-401AP| MS-402AP
Dimensions| 4.55” H x 3.3” W x 2” D| 4.55” H x 3.3” W x 2.1” D
Nominal Operating Voltage| 15–32 VDC| 15–32 VDC
Maximum Alarm Current @ 24V| 600 μA| 5.4 mA
Average Operating Current @ 24V| 400 μA| 600 μA
Mounting Diagram
Wiring Diagram
Ordering Information
Ordering Information
Model| Description
MS-401AP| Advanced Protocol Intelligent Single Stage Manual Station
MS-402AP| Advanced Protocol Intelligent Two Stage Manual Station
MS-DA| Double Action Lever Kit (converts any of above to double action
stations)
NOT TO BE USED FOR INSTALLATION PURPOSES.
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655 Fax:
905-660-4113
www.mircom.com
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655 Fax Toll Free:
888-660-4113
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE
THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance,
installation, testing and certification, refer to technical literature. This
document contains intellectual property of Mircom. The information is subject
to change by Mircom without notice. Mircom does not represent or warrant
correctness or completeness.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>